Arc Fault Containment – Special
Tests
© BU 3101 Low Voltage Systems
July 23, 2014 | Slide 1
1TGC900018N0201 BU 3101 Low Voltage Systems Arc Fault Containment
Special Tests
MNS & MNS iS
IEC 61641 Asta Test Report 2267
Test
conducted
originally
was
Special test: Doors of cable
1025, however the compartment open.
arc extinguished
before the duration Compartment above ignited
300mS, therefore
the test was module not equipped.
repeated with 1026.
Arc initiated on 24E, as below.
This test report details how MNS & MNS iS exceed the requirements
defined in IEC 61641, and demonstrates that personal and plant
protection is still maintained when:
§ Doors are open
§ Modules are completely removed
§ Modules are located in the isolated position
ABB utilises IPH-Berlin as the primary source for ASTA certification. The IPH
laboratory is ‘ASTA Recognized’ which means that in addition to its national
accreditation, the laboratory is rigorously audited by Intertek every year to
demonstrate technical competence and capability for the scope of work
registered.
As part of the ASTA certification scheme, tests are witnessed by an ‘ASTA
Observer’ supervised from the ASTA Certification Body in the United Kingdom,
on successful completion of which ASTA certificates are issued. These
certificates provide authoritative objective evidence that ABB equipment is
compliant to relevant safety standards and statutory regulatory specifications.