Professional Documents
Culture Documents
and
Reducing Arc Flash Hazards
Balance:
Continuity Minimize
of Service Equipment
Damage
Electronic Trip Units
Many modern circuit breakers have
electronic trip units which make them
more “intelligent”
Hi!
Hello?
Zone A
Zone Selective Interlocking
Breakers in the same zone “talk” to their upstream buddy.
Hi!
Hello?
Zone A
Zone Selective Interlocking
Breakers in the same zone “talk” to their upstream buddy.
Hi!
Hello?
Zone A
Zone Selective Interlocking
When a fault occurs at point X...
I sense
trouble!
X Zone A
Zone Selective Interlocking
However, when a fault occurs at point XX...
I sense
trouble!
I sense trouble too! Hey
upstream buddy, hang in
All is OK here, All is OK here,
there, I’ve got it!
so I’m quiet. so I’m quiet.
Zone A
XX
Zone Selective Interlocking
Breakers further downstream can also “talk” to their
upstream buddy in their zone.
Hi!
Zone B
Hello?
Zone Selective Interlocking
Breakers further downstream can also “talk” to their
upstream buddy in their zone.
Hi!
Zone B
Hello?
Zone Selective Interlocking
So, when a fault occurs further downstream at point XX...
I sense
trouble!
Zone B
All is OK here, so
I’m quiet.
XX All is OK here,
so I’m quiet.
Zone Selective Interlocking
So, when a fault occurs downstream at point XX...
Without ZSI, I’d
wait for MY Short
Delay time, and
then open!
Zone B
XX
Practical example – without ZSI
When a fault occurs at point X...
M1
I have to wait my pre-set
SD= 0.5S Short Delay time to
0.5S give the downstream
devices a chance to clear
the fault.
F1 F2 X F3
B1 B2
SD= SD=
0.1S 0.1S
Practical example – WITH ZSI
When a fault occurs at point X...
M1
Since none of my downstream
buddies are telling me that they
SD= sense trouble, I over-ride my pre-set
0.5S
SD time and act as quickly as
possible, clearing in 0.08S!
All is OK here, All is OK here,
All is OK here,
so I’m quiet.
F1
so I’m quiet.
F2 X F3 so I’m quiet.
Zone A
SD= SD= SD=
0.3S 0.3S 0.3S
B1 B2
SD= SD=
0.1S 0.1S
ZSI with Ground Fault Protection
Provides the same benefit when a ground fault occurs (at point X).
M1
Since none of my downstream buddies
GF= are telling me that they sense trouble,
0.5S I over-ride my pre-set GF time and
act as quickly as possible, clearing in
0.08S!
All is OK here, All is OK here,
so I’m quiet.
F1
so I’m quiet.
F2 X F3
All is OK here,
so I’m quiet.
B1 B2
GF= GF=
No No
time time
delay. delay.
Zone Selective Interlocking
Must have a Coordinated System to start.
M1
SD=
0.5S
F1 F2 F3
B1 B2
SD= SD=
0.1S 0.1S
Zone Selective Interlocking
where
log is the log 10
I a is arcing current (kA)
K is - 0.153 for open configurations and - 0.097 for box configurations
I bf is bolted fault current for three-phase faults (symmetrical RMS)(kA)
V is system voltage (kV)
G is the gap between conductors, (mm)
and convert from log
I a = 10 log I a
IEEE 1584 Formulas
• Use arcing current to determine incident energy, E
This is the most accurate method, and preferred, for these certain types of low-
voltage fuses.
IEEE 1584 Issues
• What if the fuse is not one of the specific
ones stated?
X
If not one of those specifically stated, or when outside the
model’s tested bolted fault current range…
This is a secondary method, for use when the preferred fuse method is not possible.
IEEE 1584 Issues
Note: This approach causes concern because commonly published time/current curves
in the instantaneous region have not been a focus of circuit breaker manufacturers, and
are very conservative.
At the present time, this is the most accurate circuit breaker calculation method
included in the IEEE 1584 Guide, and the preferred method, for use when the
manufacturer’s information is available.
IEEE 1584 Issues
• When entering specific OCPD times (for both low-voltage
fuses and low-voltage circuit breakers) 2 different values are
used; one based upon the arcing current and a second based
upon a “reduced” arcing current.
If the arc current falls on the steep part of the time-current
curve, or falls near a step change, a small variation in arc
current could cause a significant change in OCPD tripping or
operating time.
A second calculation is performed based upon a “reduced” arcing fault current, 85% of
the originally calculated arcing current. The highest resulting energy (either based upon
arcing current and arcing operating time, or reduced arcing current and reduced current
operating time) is then automatically used.
Applicable to low-voltage arc currents (under 1 kV)
IEEE 1584 Issues
• What if the circuit breaker time/current information (opening
times) is not available?
For certain low-voltage circuit breakers within specific continuous current ranges and
within specific ranges of bolted fault currents input CB type and bolted fault current :
9 Molded Case Circuit Breaker, 100-400A
10 Molded Case Circuit Breaker, 600-1200A, Thermo-magnetic trip
11 Molded Case Circuit Breaker, 600-1200A, Electronic trip w/Long Delay
12 Molded Case or Insulated Case Circuit Breaker, 1600-600A
13 LV Power Breaker, 800-6300A, w/Instantaneous trip
14 LV Power Breaker, 800-6300A, w/o Instantaneous (Short Delay only)
(Device Type number 9-14 corresponds to Spreadsheet selection)
Also requires input of the circuit breaker’s instantaneous trip level. Calculation is based
upon interruption times for generic breaker-ratings. Typically worst-case; maximum-
duration times based upon the published time-current curves of many manufacturers.
This method is conservative and calculates high values of arc energy that may mandate
more protection than is necessary.
This is a secondary method, for use only when specific time/current curve information
is not available and the preferred circuit breaker method is not possible!
IEEE 1584 Issues
Difficult to create models to accurately predict incident energy created by an arc flash
in a system using OCPDs.
•The arc current duration is controlled by the actual time of interruption. As previously
stated, commonly published circuit breaker time/current curves in the instantaneous region
have not been a focus of circuit breaker manufacturers, and are very conservative. For the
purpose of calculating arc flash energy, using those instantaneous region conservative
operating times will produce unrealistically high arc flash energy values. Actual operating
times will enable more accurate calculations of arc flash energy.
The other major component to consider is the reduction of the arc current magnitude due to
the breaker’s dynamic impedance.
Initial MCCB current limiting tests
Calorimeters constructed to ASTM Standard.
Table values based upon 480V, MCC, 18” distance from arc, ungrounded system.
Initial MCCB current limiting test conclusions
MCCB current limiting significantly reduces the energy levels (when in the
instantaneous range).
The IEEE 1584 calculation methods are very conservative when compared with the actual
measurements associated with MCCBs. (Need to correct this situation).
Although the resultant arc energies are significantly lower, this methodology is
preliminary and still needs to be refined.
Use Of Other Existing Technologies to Reduce Arc
Flash Risk
Retro-fit Kits: Provide Zone Selective Interlocking-type performance for existing trip
units (available soon).
Ground Fault Detection: trips the circuit breaker during the early stages of fault
development and prior to "bolted fault" conditions.
Use “finger-safe” electrical components as much as possible. This can reduce the chance
that an arcing fault will occur.
Use insulated bus for equipment such as motor control centers, switchboards,
switchgear, etc. This will reduce the chance that an arc fault may occur. In addition, it
increases the probability that an arc fault will self-extinguish.
Use High Resistance Grounding Systems. This limits the amount of fault current.
Size the current-limiting branch circuit OCPD as low as possible. Typically, the lower
the ampere rating, the greater degree of current-limitation.
Use remote racking & sensing devices. This increases the distance between personnel
and the electrical equipment.
Protecting Electrical Systems
Balance More Issues:
Minimize
Equipment
Damage
Continuity +
of Service Lower
Arc Flash
Hazard
Summary
Use Zone Selective Interlocking to minimize fault stress on
equipment AND to reduce arc flash energies.