TPSi
Inform service; Only at compact power sources, Unbalance in intermediate circuit; Error occurs at switching on power source: measure transistors, if they are ok, change firt pc-
board ELCSSS and then BPSXXX Servicedienst verständigen; Fehler tritt beim beim Einschalten der Sromquelle auf: Transistoren messen - wenn in Ordnung Print ELCSSS
und Print BPSXXX in der angegebenen Reihenfolge tauschen Fehler tritt beim Einschalten des Leistungsteil auf: Kontaktierung des Flachbandkabel überprüfen,
Trafoanschlüse auf richtige Reihenfolge überprüfen, Print SMB2700/5000, Print ELCXXX, Print BPSXXX in der angegebenen Reihenfolge tauschen Error occurs at switching
6514 Unbalance in intermediate circuit Unsymetrie im Zwischenkreis on power unit: check contacting of flat cables, check, if trafo connectors are in correct order, change pc-board SMB2700/5000 first, then ELCXXX and at last pc-board BPSXXX
Check main fuse, power cable and power plug; Check main fuse, power cable and power plug, check / repair lines between power supply terminal and RP5000 , if they are ok,
6515 Phase failure replace pc-board RP5000 or netfilter (TPSiC)
6517 Interruption at connection between pc-boards SMB5000/2700 and BPSXXX (ribbon cable) Check / replace ribbon cable between pc-board SMB5000/2700 and BPS XXX, if it is ok, change first pc-board SMB5000/2700 and then BPS XXX
6527 +17V supply on pc-board BPS XXX defective or missing check lines of +17V supply between NT241 and BPS; Check LEDs on the pc-boards, replace NT241
6577 Main switch is turned off Error is triggered when main switch ist turned off. If Error occurs while main switch ist turned on, replace the RP-pc oboard or netfilter. Check main switch
6641 Main switch is turned off Error is triggered when main switch ist turned off. If Error occurs while main switch ist turned on, replace the RP-pc oboard or netfilter. Check main switch
6710 Artual value of intermediate circuit voltage of BPS XXX to SMB5000/2700 is not transferred. Check ribbon cable; replace pc-board BPS XXX
6714 Overvoltage of the primary intermediate circuit detected. Operate power source in allowed voltage range
6715 Undervoltage of the primary intermediate circuit detected Operate power source in allowed voltage range
6774 Actual value of intermediate circuit voltage of BPS XXX to SMB5000/2700 is not transferred. Check ribbon cable; replace pc-board BPS XXX
6778 Overvoltage of the primary intermediate circuit detected. Operate power source in allowed voltage range
6779 Undervoltage of the primary intermediate circuit detected Operate power source in allowed voltage range
6838 Actual value of intermediate circuit voltage of BPS XXX to SMB5000/2700 is not transferred. Check ribbon cable; replace pc-board BPS XXX
6842 mains over voltage detected. Operate power source in allowed voltage range
6843 mains under voltage detected Operate power source in allowed voltage range
6902 Actual value of intermediate circuit voltage of BPS XXX to SMB5000/2700 is not transferred. Check ribbon cable; replace pc-board BPS XXX
6906 Overvoltage of the primary intermediate circuit detected. Operate power source in allowed voltage range
6907 Undervoltage of the primary intermediate circuit detected Operate power source in allowed voltage range
6966 Actual value of intermediate circuit voltage of BPS XXX to SMB5000/2700 is not transferred. Check ribbon cable; replace pc-board BPS XXX
6970 Overvoltage of the primary intermediate circuit detected. Operate power source in allowed voltage range
6971 Undervoltage of the primary intermediate circuit detected Operate power source in allowed voltage range
7030 Actual value of intermediate circuit voltage of BPS XXX to SMB5000/2700 is not transferred. Check ribbon cable; replace pc-board BPS XXX
7034 mains over voltage detected. Operate power source in allowed voltage range
7035 mains under voltage detected Operate power source in allowed voltage range
7093 Interruption at lines / plugs between booster and SMB Booster was logged on, but communication was lost. Check leads, change SMB / Booster
7095 Ready signal of booster not available BLT5000 (Booster) not connected (RS485 at plug X3 or supply at plug X1) Print BLT damaged check AC-Voltage, a loos cable on the net-filter can cause this error as well
7096 Interruption at lines / plugs between booster and SMB replace BLT pc-board
7156 Earth current detected Eliminate earth connection, …
7284 Welding current towards wire spool detected Connection between wire spool and ground
7355 Output voltage of power supply on SMB too low replace SMB
7415 After switching the machine on error 7415 appears Check main voltage, if a phase is missing the BPS does not get initialized correctly and the system does not start up properly
7479 Phase missing at startup of the system. The BPS ready signal is watched by the SMB in this case. Since the signal is not high the error shows up. Check phases
After firmware update it is possible that other components inside the system e.g. BPS or in case of MV the BOOSTER need to be updated - during this time periode the
7560 error is showing up on the screen 7560. This "error" should be disappear by itself without acknowledge.
7596 Power module initialization failed. Check led, replace UPS
7597 Grid does not supply enough power, Power source can't compensate the power loss; PFC defective, PFC choke brocken Check input voltage (Generator..); check PFC choke! (Core broken, windings short); replace UPS
7598 Operation on a Generator, Other huge Components let the Grid supply voltage go higher. check input voltage.
7599 Grid does not supply enough power, Power source can't compensate the power loss check input voltage
7600 Intermediat circuit detected a over current replace UPS
7607 update in progress Do not turn off power source, wait until update is finnished
7608 UPS not working Check led, replace UPS
9017 Synergic line is incomplete (z.B. no corrections or working points) choose different synergic line
9081 Emergency stop is activated or jumper plug on SMB (X13) is missing Acknowledge emergency stop, connect jumper plug
9113 Welding blocked, start originated from wrong source Start welding from external plc
9145 Message is thrown when communication between Spider and MCU is interrupted for more than 2 seconds. Update Firmware, check connection between SMB and MCU
9649 Arc break detected Increase Arc-break watchdog filtertime in PowerSource settings
9702 Short between wire and workpiece during welding has been detected Optimize welding process (z.B. increase welding power)
16703 Invalid configuration of Device ID and drive unit Check Motor harness, replace motor; (e.g. Device ID of a 3 phase motor --> one phase missing --> system identifies a 1-pase motor --> Error Device ID 3 phase - motor 1 phase
16704 Conntected motor is unknown update firmware, replace motor
16705 Motor alignemt has failed Cycle power on power source, dis- and reconnect torch, check encoder leads; possibillity of a jamed Motor
16706 encodersignal loss, possibillity of dirt in the encoder box, broken encoder glas replace motor
16707 Interruption on system bus between welding torch and motor regulator during welding Dis- and reconnect torch, check system bus between torch and motor controller / replace system bus leads. Check used port (POE)
16708 The alignment without load could not be executed. Retry alignment! Make sure wire is disengaged!
16709 Load alignment of wire feeding line could not be executed. Check if driver rolls on the front drive unit are engaged. Retry alignment.
16710 Load alignment of wire feeding line could not be executed. Check if driver rolls are engaged. Retry alignment.
16711 Motor does not reach nominal speed check pressure rolls for correct settings
16712 Check wire feed hoses, inner liner, wire spool, wire drum,... Wire should be easy to feed. Check wire feed hoses, inner liner, wire spool, wire drum,... Wire should be easy to feed.
16713
16748 Overtemperatur on motor regulator SR63/SMB2700 Cool down wire feeder, use it only at allowed ambient temperature. Replace SR63
16749 Wire feeder unknown or not supported update firmware
16750 EPROM defect. replace motor controller
16751 EPROM defect. replace motor controller
16752 Data packages on process bus are lost within a certain time. (10 pakages in 500ms) Datenpakete am Prozessbus gehen innerhalb einer bestimmten Zeit verloren check system bus lines / connections
16753 Supply voltage on pc-board SR63 is out of tolerance Check lines / connections, change pc-board NT241
16754 Device XML of motor controller not found. update firmware! Contact support!
16755 Smart ID not connected or unknown Slave jumper not plugged in and no Smart ID connected on motor controller Check harness, connect slave jumper or Smart ID
16757 not programmed Smart ID (SC2) on wire feeder replace SC2 (empty or damaged)
16758 Firmware update on Smart ID failed replace Smart ID (SC2)
16759 SR63 was replaced but not paird with SC2 yet Use Dongle to pair the devices
16760 lost process bus packages Hintereinander verlorene Processbus Pakete Change welding torch, if this is not successful,check system bus lines of torch, change welding torch
16761 Smart ID not ready Only possible in production facility
16762 Error while pairing the 2nd motor controller Check slave jumper on the 2nd motor controller. Replace SR63 pc-board
16763 R&D Smart ID on an official pc-board connected replace Smart ID to the correct one
16764 Unknown system configuration (e.g. to many wire feeders) check system configuration, perform firmware update, check system configuration
16765 Old SR 63A in use replace SR63 to SR63B
16766 Missing processbus packets check / replace system bus harness (pins) replace SR63
16767 dropped ethernet/processbus packets check / replace system bus harness (pins) replace SR63