Professional Documents
Culture Documents
fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
1
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
2
vi Rf Lf RC LC
are based on communication links, which two of them are Micro
Source
DC
AC
presented in [5]: Single master and Multi master operation. In il Cf
both approaches, VSI inverters act as masters by tracking the Vi* vb
demand and changing their output power based on a droop ilq
Abc/dq
vo io
Current Controller ild
characteristics. The secondary control is then obtained by n vn
Of VSI Inverter
changing the nominal set-point of VSI inverters. The Single Voq Vod
ild * ilq *
master operation is shown in Fig. 1. As the communication Abc/dq
links make the system more expensive and less reliable, in this Power Controller
Of VSI Inverter
Voltage Controller
Of VSI Inverter
Abc/dq
paper, DG’s communications are limited. In fact, the Voq Vod ioq iod ioq iod
secondary control for VSI inverters is decentralized without Control Section
any communication for VSI’s coordination. However, having Fig. 2. Block diagram of VSI inverter
PQ inverters in MG necessitates some links between VSIs and
1. Power Controller:
PQs to send them the P-Q set-point signal. These links can be
The underlying idea behind the droop control is to simulate
optimally chosen to have as little communication as possible.
P&Q setting
the governor of a rotating machine. In a conventional power
Droop setting
P&Q setting MGCC system, rotating machines share any increase in the demand by
Decide about the P&Q set point for
inverter based sources decreasing the frequency based on their governor droops. This
V,I
VSI Control
principle is implemented in inverters by decreasing the
Prime
reference frequency, ωi, when there is an increase in the load.
DC/AC
Mover
DC/AC
Prime Instantaneous active and reactive power components, p and
Electrical Mover
Micro Grid
q, can be calculated from the measured output voltage and
Prime
DC/AC
current, vod, voq, iod, ioq, using (2,3) where s is Laplace variable;
Mover
afterward, by passing them through low-pass filters (cut-off
frequency of ωco), the fundamental components, P and Q, are
Fig. 1. Control Scheme for Single Master Operation obtained. Finally, small power variation, ΔP and ΔQ, from the
This paper’s modeling approach decomposes the system operating point, P and Q, can be calculated as in (4,5).
into four modules; VSI inverters, PQ inverters, network, and Δvod, Δvoq, Δiod, and Δioq are small variations of output
loads. Each VSI is modeled on its own reference frame and its voltage and current with respect to the operating point (All
frequency is set by the local power sharing controller. The operating point values are provided in the simulation section).
VSI model includes the dynamics of current, voltage and The real power sharing between VSIs is attained by using
power controller, output filter and coupling inductor. While an artificial droop for frequency as in (6). In the following ωni
PQs only model the dynamics of current controller and RL and ωi are the nominal frequency set-point and the reference
filter. Network dynamics are usually neglected in conventional frequency of ith inverter, respectively; in which, ωi, is set
power systems due to their relatively small time constant; but, according to the droop gain mi. This will provide artificial
MGs have inverter-based DERs whose response times are inertia and subsequently a degree of negative feedback.
small so network dynamics can impact system stability [18]. p vod iod voqioq P (co / s co ) p (2)
Here, state equations are presented on the reference frame
q vod ioq voqiod Q (co / s co )q (3)
of one of the inverters, which is considered as the common
reference frame. All other inverters are translated to this frame P co P co vod iod co voq ioq (4)
using transformation technique given by (1) in which, δi is the
Q co Q co vod ioq co voq iod (5)
angle of ith inverter with respect to the common reference
frame. (D-Q) is the common reference frame rotating at ωcom, i ni mi Pi i ni mi Pi (6,7)
whereas (d-q)i is reference frame of ith inverter rotating at ωi. To share the reactive power among the VSIs, a droop is
The modeling of all modules is discussed in detail. also introduced in the voltage magnitude as in (8). Here, v*odi
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
3
and vni stand for the reference and the nominal set point of d- Voltage Controller Current Controller
axis output voltage and li defines the voltage droop gain of ith iod F ilq L
inverter. The control strategy is chosen such that the output Vod*
PI Controller
ild*
PI Controller Vid*
voltage magnitude is associated with the d-axis of VSI, and
the q-axis reference is set to zero. Voq C
Vod ioq
F
ild ild L
(10). Note that δi is the angle between VSIi reference frame Fig. 3. Current and voltage controller of VSI inverters
and the common reference frame (here, reference frame of φdq and γdq are auxiliary variables which measure the
VSI1 is considered as the common reference frame, ωcom=ω1) variation of voltage and current (vodq , ildq) from the reference
i (i com ) i i com (10,11) values (v*odq ––provided by power controller, i*ldq ––provided by voltage
controller). vi and il are the voltage and current of inverter, vo is
Now based on (11, 7), i can be calculated for all VSIs. the voltage measured after LC filter and io is the current of
Equations (12-14) show this variable for each VSI of a MG. In coupling inductance. These variables are depicted in Fig. 2.
this paper, the understudied microgrid has three VSIs and m1, 3. Output LC Filter and Coupling Inductance:
m2 and m3 are considered to be identical for them. The state space model for output filter and coupling
1 1 com 0 (12) inductance is given in (20). Details are given in the Appendix.
2 2 com (n 2 m2 P2 ) com (13) ildq ildq
vodq Al vodq Bl1 vidq Bl 2 vbdq (20)
i i com (ni mi Pi ) com (14) iodq iodq
By changing nominal set-point of each VSI inverter, ωni, Bl 3 com Bl 3 ncom
and considering its variations, Δωni, a proper tool for
ncom n1 com 1 (21)
implementing secondary frequency control will be obtained.
For example, for the understudied microgrid, Δωn1, Δωn2 and 4. Complete Model of VSI Inverters:
Δωn3 are used for the secondary frequency control. The state In order to connect the VSI inverters to a microgrid, all
space model of the power controller is obtained by linearizing output currents and voltages need to be expressed in a
equations (4, 5, and 14) and it is given in (16,17). The power common reference frame. So here the Δiodq will be converted
controller outputs are the variations of output reference to the ΔioDQ by use of the transformation technique given in
voltage Δυ*odq and the frequency of ith inverter Δωi. Δildq, Δvodq, (1). Finally, after merging all previous state equations, the
Δiodq are the state variables of LC filter and coupling model of one VSI inverter is given by (23) in which ΔxVSIi is
inductance represented in a compact notation by Δxf,CI in (15). the state variable vector of the ith inverter and is shown in (22).
In the following equations, relation x=X+Δx exists between After obtaining the state space model for each inverter, they
x, X and Δx. In which, x is the instantaneous value of the can be combined to form a unit model for all the VSI
variable, Δx is a small change from the operating point, and X inverters. Since, the understudied microgrid of this paper has
represents the operating point. By knowing the operating point three VSIs, the final VSI state space model, shown in (24-26),
value, and calculating the small signal variation through the is obtained. ΔxVSI is the state variable vector of all the VSI
modeling, we can easily calculate the instantaneous values. inverters in the microgrid. In this model, Bl3-i is the Bl3 matrix
(e.g. vod=Vod+Δvod; All operating point values are provided in for the ith inverter formed above in section 3.
the simulation section.) T
xVSIi i Pi Qi dq dq ildq vodq iodq (22)
T
x f ,CI ildq vodq iodq (15)
xVSIi AVSIi xVSIi BVSIi vbDQ Bicom com (23)
i i
P A P B x ni ncom
i i i i1 com Bi 2 ni (16)
f ,CI i Bi 2
0
Qi Qi
Bl 3i ncom
1
i Ci i T
* Pi 0 ni (17) xVSI xVSI 1T xVSI 2T xVSI 3T (24)
v odqi iv Qi 0
C
xVSI AVSI xINV BVSI vbDQ Bcom com Bn ni
2. Voltage and Current Controllers:
Voltage and current controllers of VSI inverters are ioDQ CVSI xVSI (25)
responsible for providing reference output current, i*ldq, and T
ni n1 n 2 n3 (26)
reference input voltage, v*idq, , respectively. In Fig. 3 the block
diagram of voltage and current controllers [21], are shown. B. Modeling of PQ or Current Source Inverters (CSIs)
The state equations for the voltage and current controllers are CSI (PQ) inverters are those inverters who receive a
given in (18) and (19) respectively. State space model matrix specific set-point about active and reactive power usually from
derivation is fully presented in the Appendix. a central controller, however here in this paper, these set-
dq v*odq vodq dq i*ldq ildq (18,19) points are sent through one of the neighboring VSIs. In fact,
each PQ inverter is communicating to one of the VSIs, and the
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
4
VSI will increase the set-points of PQ whenever it is reaching xLoad AL xLoad B1L vbDQ (37)
to its own maximum power production range. This strategy is B2 Ld com B2 L ncom
used to design a distributed secondary frequency controller.
As it was discussed PQs are not directly responsible for the D. Microgrid Model
frequency regulation, so their state space model has only four The microgrid model is obtained by combining the models
state variables because of the only one current controller of above 4 modules given by equations (25), (35), (36) and
instead of three current, voltage, and power controllers. These (37). It is given in the below form:
four state variables are shown in (27). γd and γq are the xVSI xVSI
auxiliary variables used for controlling the error of PQ
xPQ A xPQ B P
currents (ild , ilq) from the reference values (i*ld , i*lq). x Micro 1Micro n B2 Micro (38)
T Net grid x Net grid grid Q
xPQ d q ild ilq (27) xLoad xLoad
Fig. 4 shows the block diagram related to the current Amicrogrid, B1Microgrid and B2Microgrid matrices can completely
controller of a PQ inverter which adjusts the d-q terms of describe the microgrid. The obtained model has appropriate
output current, il. The term α in this figure is defined such that input term which allows working on the secondary frequency
the quadrature term of output voltage reaches zero. Two state control and power management of the microgrid. It can be
variables of PQ inverters are related to the dynamics of current seen that ΔVbDQ vector is needed for all four equations (25, 35,
controller block which is described in (28). 36, 37) because it is the input for the subsystems. This voltage
Power Component vector is defined by considering a virtual resistor between
vi Rf Lf vb each node and ground. The resistance is chosen sufficiently
Micro DC
Source AC large so it would have minimum influence on the dynamic
il stability of the system [18].
Vi*
vbDQ RN ( MVSI ioDQ M PQ iPQoDQ (39)
Control Section Abc/dq
M N iLineDQ M L iLoadDQ )
Current Controller α
Of PQ Inverter
Abc/dq
MVSI, MPQ, MN and ML are defined based on the system
configuration. They are also called mapping matrices which
ild* ilq* α map the connection points on to the network nodes. Furthure
Fig. 4: Current controller of PQ inverters description on how to calculate the mapping matrices can be
dq i*ldq ildq (28) found in [18]. Eventually, the MG matrices are as (40-42).
BV RN MVSI Cc
Equation (2, 3) calculates the active and reactive power. As BV RN M PQC BV RN M N BV RN M L
it was mentioned previously α is set such that vbq becomes AVSI
B R M C B11RN M PQC
zero [22], so P and Q equations will be decoupled and 11 N VSI c B11RN M N B11RN M L
simplified as (29, 30). The other two state variables of the PQ B C A
AMicro 3 (40)
inverter are related to the dynamics of RL filter. The change of grid B1N RN M VSI Cc B1N RN M N
B C B1N RN M PQC
AN
B1N RN M L
output d-q current which is fed to the microgrid through the 2N
RL filter forms these remaining state variables and can be B1L RN MVSI Cc B1L RN M L
B1L RN M PQC B1L RN M N
rewritten to shape the state space form (31-34). This procedure B2 LC AL
of PQ state space model derivation is described in details in Bn 0
Appendix. By transforming the variable to the reference B
B 0 0
frame, the final model is obtained as in (35). B1Micro 3 ,B
2 Micro
2 (41, 42)
grid B2 N 0 0 grid 0
P vbd ild vbqilq P vbd ild
2 L
B 0 0 0
As vbq 0 Q v i (29,30)
Q vbqild vbd ilq
bd lq
III. SECONDARY LOAD FREQUENCY CONTROL
i*ld P s / vbd
i* P V 1 0
* A , A
d bd (31 34) In an islanded microgrid a coordinated active and reactive
i q Q 0 Vbd 1
* s
i lq Q / vbd power regulation is essential for having power management.
PIn The focus of this paper is active power regulation and
xPQ A xPQ B11 vbDQ B2 frequency control, however as it was shown previously the
QIn
voltage control has the same droop characteristics and can be
B3 com B3 ncom (35)
implemented in the same way as the frequency control [21],
i
oDQ C xPQ
[22]. In order to ensure robustness of microgrid in case of any
communication link’s failure, an autonomous power sharing
C. Modeling of Network and Load strategy is needed for the primary control. Droop control
Considering typical RL loads and lines modeled by their strategy seems to be an acceptable solution to this requisite.
series impedances, state equations for the network and loads However, an important point is that the coordinated active
are shown in (36, 37). In [18], more detail about the small power control strategy should consider the status of all
signal state-space models of loads and lines are discussed. microgrid’s elements, DG’s available power as well as the
xNet AN xNet B1N vbDQ (36) state of charge of storage devices. MGs have different kinds of
DGs with their own particular functionalities in frequency
B2 N com B2 N ncom
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
5
control. Based on their participation in primary control, they IV. SIMULATION RESULT
are divided into two categories of VSI or PQ inverters. During Using the procedure discussed in section II, the state space
the primary control loop, The VSI inverters are those which matrices can be formed for any microgrid with different
act like a rotating machine and control the voltage and number of VSI and PQ inverters along with the loads and the
frequency while the PQ inverters are only producing a certain network. However, to have the numerical values of the
amount of power. The PQ inverters will just act in secondary matrices, the system parameters along with the steady state
control loop by changing their set-points and providing values of the operating point is required. So, first of all, a load
additional power for the microgrid. The VSI inverters consist flow analysis is performed, (using MATLAB software in this
of two different categories, i.e. generating units and storage study) to obtain the required values. Then, the obtained state
devices. Both of them are helpful in primary control but space model can be used for both stability analysis and small
storage devices do not have any role in the secondary control. signal transient analysis. The eigenvalues of A matrix are used
The reason behind that is the limited power they can produce for investigating the stability issues. It should be noticed that
in long term. Table I shows how DG’s are categorized based for different cases (with different operating points), the A
on their contribution in primary and secondary control: matrix differs and the eigenvalues will lie in different
TABLE I: locations which are going to be discussed in more detail in
DG TYPES AND THEIR CONTRIBUTION IN COORDINATED CONTROL stability analysis section. Fig. 6 shows the steps of these
DG TYPE Primary Control Secondary Control investigation procedures in which MATLAB environment is
VSI Generating units × × being used to conduct it. For small signal transient analysis, a
inverters Energy Storage Devices × state space block model is used in Simulink. The calculated A
and B matrices along with C and D are provided for the
CSI (PQ) inverters × mentioned block. Three inputs are defined for the microgrid
As it was discussed earlier, controlling the frequency of a where the first one is related to the nominal set-points of
microgrid has two levels: primary and secondary control. In frequency, second one provides the P-Q set-points of PQ
the primary control, the nominal frequency set-point, ωni , is inverters and finally the last one provides a proper input to
fixed and any change in the load will cause a change in ωi of simulate the load change as a disturbance for the system. The
the inverter, based on the defined droop for power controller. input related to VSI inverters (Δωni) is formed by receiving
Then in secondary control, if the inverter is connected to a the feedback from the outputs (ωi), comparing it with 60Hz
generating unit, ωni will be changed in a way that the and giving the error to a PI controller at the end to set the Δωni
frequency error is brought back to zero and if it is connected for all three VSIs. This procedure is also shown in Fig. 7.
to a storage device, ωni will remain fixed as before. The reason
is that these elements only participate in primary frequency
control (because their inverters are working as VSI inverters)
and since they should not be considered as a long term power
producer, they cannot contribute to secondary control like
other VSI inverters. Fig. 5 shows how these two categories of
VSI inverters act during the two levels of frequency control.
Primary Frequency Control Primary Frequency Control
Secondary Frequency Control Secondary Frequency Control
Fig. 6. Steps of simulation and analysis procedure along with the
ωn2
implementation environments
ωn1 ω1= ωn1 ωi
ω1 ω2
60 Hz
ω2
PI Δωni Instantaneous
Values
Controller
P2 Inputs ΔP, ΔQ dx/dt = Ax + Bu Output
P1 P2 P1=0
Energy Storage Devices y = Cx + Du Variables
Generating Units
Fig. 5. Frequency control of VSI - generating units and storage devices Operation
From Fig. 5 it can be seen that ωni will be changed for all Load Change (Disturbance)
State Space Model Points
VSI inverters except those who are connected to the storage Fig. 7. Secondary control implementation in MATLAB/Simulink
devices. These devices should come back to the nominal Here in this paper, an isolated MG with three VSIs and one
frequency (60Hz) without a change in the ωni of their curves. PQ inverter is used to demonstrate the validity of secondary
Usually, the droop defined in primary control is related to frequency control and the effect of different parameters such
the rating of each DG, but in secondary control, the droop can as PQ inverter contribution on the stability margin of
be changed to consider other parameters in steady state. In microgrid. Fig. 8 depicts the single-line diagram of the case
other words, each DG has a participating factor which can be a study. The nominal voltage and frequency are 380 V and 60
function of any criteria such as the speed of response or cost Hz. The microgrid parameters are summarized in Table II. All
of producing power or it can remain as primary droop. MGs inverters are assumed to have the same rating, consequently
also have PQ inverters which do not have droop curves. They all of them have similar droop gain. The operating point
measure the frequency using Phase Locked Loop (PLL) and parameters in different cases are outlined in Tables III to VII.
the ω for the inverter is calculated based on the measured Table III and IV show the load flow results when the PQ
frequency. These elements should receive PQ set-points which inverter is not connected to the microgrid and the other three
are usually provided by one of the neighboring VSI inverters. tables show the operating point values when PQ is attached.
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
6
A. Stability Analysis
The eigenvalues of the state space model are depicted in
Fig. 9 with and without PQ inverter’s involvement in
supplying the demand. The green crosses show the system’s
Fig. 11. Eigenvalue’s relocation trend by increasing the reactive load at bus 11
eigenvalues when the PQ inverter is not attached to bus 1 and
the blue crosses show the eigenvalues when it is connected to Finally, it is also important to notice the PQ inverters
the microgrid providing 25% of the total load. The loading condition as well. As it was discussed earlier, adding
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
7
PQ inverters to the microgrid can improve the stability of the can be seen that the ∆ωni for third inverter (inverter connected
system. But it is also important to see how different to ESS) is equal to zero.
participation factors, defined for PQ inverter, can influence the Primary Frequency Control m1=m2=m3
Secondary Frequency Control
stability dynamics. Fig. 12 shows where the eigenvalues lie
ωn2 ωn2
when the participation factor is changing from 10% to 20% of ωn2
Δωn
Δωn Δωn
the total demand. As it could be expected, the figure is ωn1 ωn1 ωn1
ω1 ω1
denoting that having a higher participation factor will bring ω1
P1 P1 P1 P2
P2 P2
Fig. 13. Case 1-Secondary control for VSI 1, 2 and 3 (There is no ESS)
Primary Frequency Control m1=m2=m3
Secondary Frequency Control
ω2 ω2 ω2
P1 P1 P1 P2
P2 P2
Fig. 14. Case 2- Secondary control for VSI 1,2 and 3 (VSI 3 is ESS)
TABLE VIII: DG TYPES AND THEIR PARTICIPATION
FACTOR DURING COORDINATED CONTROL IN SECOND CASE
Participation factor
DG Type
Fig. 12. Eigenvalue’s relocation trend by increasing the PQ inverter’s Primary Control Secondary Control
participation factor
DG 1 Generating Unit 0.33 0.5
B. Small Signal Transient Analysis DG 2 Generating Unit 0.33 0.5
DG 3 Energy Storage 0.33 0
The simulation results are presented for three different
scenarios. In the first and second cases, there is no PQ The results of simulation for cases 1 and 2 are depicted in
inverter. The PQ inverter will be added to the microgrid for Fig. 15-18. Fig. 15 compares the output power of inverters in
the third scenario. The only difference between first and cases 1 and 2. The dashed lines are the output power of
second cases is in the VSI inverter used inside the microgrid. inverters related to case 1 and the solid lines are associated
In the first case, all three inverters of the microgrid are with case 2. Note that inverter 3 (red curve) supports the
generating unit VSI which means they all participate in both system exclusively in primary control and not in secondary.
primary and secondary frequency control but in the second 1
Output Power of inverters
DG 1
case, one of the generating units is substituted by a storage 0.8 DG 2
device to see how the frequency control strategy would be DG 3
0.6
affected. In all cases, it has been assumed that there is a
sudden load change in bus 11. 0.4
1) Case 1 0.2
In the first case, all DG’s will act the same and they will 0
change their ωni similarly because the mi’s are equal for all 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
Time (sec)
three DGs. In other words, they will act in primary and Fig. 15. Output power (Dashed lines: Case1, Solid lines: Case2)
secondary control with same participation factor which is 0.33 Fig. 16 shows the change in nominal frequency set-point
(one-third of load). Fig. 13 can completely show the way that for both cases. It clarifies that in second case, the generating
secondary control is traced on all three inverters. At first, units need to increase their nominal frequency set-point more
before the load changes, the microgrid frequency is ω1 which than in the first case, because more participation is required.
is considered as nominal frequency, and then it is reduced to
ω2 because of load increase. Finally, by changing ωni set-
points, frequency is brought back to ω1 and VSI output power
has changed from P1 to P2.
2) Case 2
In the second scenario, two VSIs are connected to Case 1
generating units and the third one is an ESS. This means that Case 2
the participation factor in primary control is 0.33 but in
secondary control, this value will change and it is shown in Fig. 16. Change in frequency set-point (Dashed line: Case1, Solid line: Case2)
table VIII. In fact, after primary control, the ESS will change 3) Case 3
its participation factor to zero and subsequently, the other In the third case, a PQ inverter is added to bus 1, producing
VSIs will increase their participation to compensate for the power based on the set-point it receives through the
ESS’s portion. The secondary control for two generating-unit communication link from VSI1. The participation factor for
VSI and one storage-device VSI are illustrated in Fig. 14. It PQ inverter is chosen to be 25% of the total load change. Fig.
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
8
19 shows the frequency error of VSI inverter when the The stability results presented at the end indicate that the
participation factor is 0 and 25%. In fact, solid lines modeling method can be used to analyze the stability of the
demonstrate frequency error when the PQ does not participate microgrid primary control. In addition, the simulation results
in load change and the dashed lines show frequency error show the secondary controller successfully coordinates the
when PQ participation factor is equal to 25%. Finally, Fig. 20 multiple source types under challenging load conditions while
depicts the contribution of DGs in producing the demand managing their individual constraints.
power when the participation is 0% and 25%. REFERENCES
-5
x 10
0 [1] Y. A. R. I. Mohamed and E. F. El-Saadany, "Adaptive Decentralized
Frequency Error (Hz)
5
x 10 “Novel Load Frequency Control Approach Based on Virtual Area Error
DG 1 in a Microgrid including PV and Battery Energy”, IEEE PES General
0 DG 2 Meeting, Washington, D.C., July 26-29, 2014.
DG 3 [5] A.P. Lopes, C. L. Moreira, A. G. Madureira, “Defining control strategies
-5
for MicroGrids islanded operation”, IEEE Transactions on Power
Delta
-10
Systems, vol.21 , no.2, May 2006.
[6] J. M. Guerrero, J. C.Vasquez, J. Matas, L.de Vicua “Hierarchical control
-15 of droop-controlled AC and DC microgrids: A general approach toward
standardization,” IEEE Trans. on Industrial Electronics, Jan. 2011.
-20
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 [7] A. G. Tsikalakis and N. D. Hatziargyriou, “Centralized control for
Fig. 18. Change of delta (Dashed
Time lines:
(sec) Case1, Solid lines: Case2) optimizing microgrids operation,” IEEE Trans. on Energy Conversion,
x 10
-5
Frequency Deviation of Inverters with and without PQ inverter vol. 23, no. 1, pp. 241–248, Mar. 2008.
2
VSI 1
[8] S. Ahn, J.Choi, “Power Sharing and Frequency Control of an
0
VSI 2 Autonomous Microgrid Considering the Dynamic Characteristics of
Frequency Error (Hz)
VSI
VSI
3
1
Distributed Generations”, Journal of International Council on Electrical
-2 VSI 2 Engineering, vol. 2, no. 1, pp. 39~44, 2012.
VSI 3
[9] T. Ota, K. Yukita, H. Nakano, Y. Goto, K. Ichiyanagi, “Study of load
-4 frequency control for a microgrid”, Australasian Universities Power
Engineering Conference, AUPEC 2007, pp. 1-6, Dec. 2007.
-6
[10] K. Sedghisigarchi, A. Feliachi, “Impact of fuel cells on load-frequency
-8
control in power distribution systems”, IEEE Trans on Energy
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8
Conversion, vol. 21, no. 1, March 2006.
Fig. 19. Frequency error of VSI’s
Timewith and without PQ participation .
(sec)
[11] W.Gu, W. Liu, Z.Wu, B. Zhao, W. Chen “Cooperative Control to
a) Without PQ inverters Enhance the Frequency Stability of Islanded Microgrid with DFIG-
Output Power of Inverters
1
VSI1 SMES ” Journal Energies, April 2013.
0.8 VSI2 [12] A. Dimeas and N. D. Hatziagyriou, "A multiagent system for
VSI3
0.6 microgrids, ". IEEE PES General Meeting, Denver, CO , Jun. 2004.
0.4
[13] A. Dimeas and N. D. Hatziagyriou, "A MAS architecture for microgrids
control,".2005, 13th Int. Conf. on Intel. Sys. Application, pp. 402-405.
0.2 [14] A. Dimeas and N. D. Hatziargyriou, "Operation of a multiagent system
0
for microgrid control", IEEE Trans on Power System, no. 3, Aug. 2005.
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 [15] A. Dimeas and N. D. Hatziagyriou, "Agent based control for
b) With PQ inverter
microgrids,"2007, IEEE Power Engineering Society General Meeting.
Output Power of Inverters
1
VSI1 [16] P. Massioni and M. Verhaegen, “Distributed control for identical
0.8 VSI2
VSI3
dynamically coupled systems: A decomposition approach, IEEE Trans.
0.6
PQ On Automatic Control, vol. 54, no. 1, pp. 124–135, Jan. 2009.
0.4
[17] W. Liu, W. Gu, “Decentralized Multi-Agent system-Based cooperative
Frequency Control for Autonomous Microgrids with Communication
0.2 Constraints” IEEE Transaction on Sustainable Energy, April 2014.
0 [18] N. Pogaku, M. Prodanovic T. C. Green, “Modeling, Analysis and
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8
Testing of Autonomous Operation of an Inverter-based Microgrid” IEEE
Time (sec)
Transaction on Power Electronics, March 2007.
Fig. 20. Output power of inverters with and without PQ Participation
[19] G. D´ýaz, C. Mor´an, J. Aleixandre and A. Diez, “Complex-valued state
V. CONCLUSION matrices for simple representation of large autonomous microgrids
supplied by PQ and Vf generation,” IEEE Trans. Power Systems, 2009.
In this paper, a comprehensive state space model of a [20] F. Katiraei, M. R. Iravani, and P. W. Lehn, “Small-signal dynamic
microgrid consisting of PQ and VSI inverters is presented. model of a micro-grid including conventional and electronically
The effects of changing the nominal frequency set-point for interfaced distributed resources,” IET Gen., Transm., Distrib, 2007.
[21] A. Bidram, A. Davoudi, F. L. Lewis, J. M.Guerrero, “Distributed
VSI inverters and active and reactive power set-points for PQ Cooperative Secondary Control of Microgrids Using Feedback
inverters are taken into account all through the modeling Linearization” IEEE Transaction on Power system, August 2013.
which is then used to investigate the small signal stability and [22] A. Bidram, A. Davoudi, F. L. Lewis, J. M.Guerrero, “A Multiobjective
the effect of proposed secondary control. An 11 bus microgrid Distributed Control Framework for Islanded AC Microgrid” IEEE
Transaction on Industrial Informatics, August 2013.
is used to illustrate the effectiveness of the proposed approach.
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
9
APPENDIX dild r f 1 1
ild ilq vid vod
VSI inverter - Power Controller dt Lf Lf Lf
The state space matrices of the power controller model dilq r f 1 1
ilq ild viq voq
obtained in (16,17) are described here. dt Lf Lf Lf
v* ild vod iod dvod
v*odq
od 1 1
voq ild
* ldq ilq odq voq odq ioq
,i ,v ,i iod
dt Cf Cf
v oq
dvoq 1 1
0 m 0 0 1 vod ilq ioq
0 0 0 0 0
dt Cf Cf
Ai 0 c 0 , Bi1 0 0 c Iod c Ioq cVod cVoq , Bi 2 0
diod r
c 1 1
0 0 0 0 c I oq c Iod cVoq cVod 0 c iod ioq vod vbd
dt Lc Lc Lc
0 0 l dioq rc 1 1
Ci 0 m 0 , Civ ioq iod voq vbq
0 0 0 dt Lc Lc Lc
VSI inverter - Voltage Controllers The state space matrices of the output LC filter and coupling
State space equations of the VSI voltage controller: inductance model obtained in (20) are described here.
dq v*odq vodq r f 1
0 0 0 0
Lf Lf
Output equations of the VSI voltage controller:
r f
1 1 0 0
i*ld Fiod nC f voq K pv (v*od vod ) Kivd 0 0 0 0 0
Lf Lf Lf 0 0
1 0
i*lq Fioq nC f vod K pv (v*oq voq ) Kivq 0 0 0
1
0 0
1
0
C Cf Lf 0 0
Al f
l1
B , Bl 2
State space model of the VSI voltage controller: 0 0 1
1
0
1 0
* 0 0 0 0 0 Lc
dq [0] dq Bv1 v odq Bv 2 x f ,CI Cf Cf
0 0 0 1
1 rc
i* C D v* 0 0 0 0 Lc
odq Dv 2 x f ,CI Cf Lc 0 0
ldq v dq v1
1 rc
d 0 0 0 0
dq , x f ,CI ildq vodq iodq T
Lc Lc
q
11 0 0
1 0 0 0 1 0 0 0
Bv1 , Bv 2 Ilq
0 1 0 0 0 1 0 0 Bl 31 0 0
Ild
K 0 K pv 0 0 0 K pv nC f F 0 V n1 1 1 0
Cv iv , D , Dv 2
Bl 3 Bn
oq
0 Kiv v1 0
K pv
0 0 nC f K pv 0 F
V
, ni n 2 ,
od n3 Bl 3 2 0 0
where kpv and kiv are the PI parameters of voltage controller. Rf I oq
1 0 1
,Cf and Lf are LC filter parameters. I od
Bl 33 0 0
VSI inverter - Current Controllers PQ inverter
State space equations of the VSI current controller: Output equations of the PQ current controller:
dq i*ldq ildq v*id vod n L f ilq K pc (i*ld ild ) Kic d
Output equations of the VSI current controller: v*iq vod n L f ild K pc (i*lq ilq ) Kic q
v*id n L f ilq K pc (i*ld ild ) Kic d
State space representation of the PQ current controller:
v*iq n L f ild K pc (i*lq ilq ) Kic q
dq [0] dq B1 i*ldq B2 ildq
State space model of the VSI current controller:
v *
C D1 i ldq D2 ildq D3 vodq
*
dq [0] dq Bc1 i*ldq Bc 2 x f ,CI idq 1 dq
The state equations and the state space model related to the
v
idq Cc dq Dc1 i ldq Dc 2 x f ,CI
* *
two state variables of RL filter dynamics.
d dild r f 1 1
dq , x f ,CI ildq vodq iodq T
ild com ilq vid vod
q dt Lf Lf Lf
1 0 1 0 0 0 0 0 dilq r f 1 1
Bc1 , Bc 2 ilq com ild viq voq
0 1 0 1 0 0 0 0 dt Lf Lf Lf
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TEC.2017.2757012, IEEE
Transactions on Energy Conversion
10
0885-8969 (c) 2017 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.