Professional Documents
Culture Documents
hyder
On
11/08/2015
press
maximum positive pressure coefficient, Cp e, to a value static methods of the type given in BS 6399: Part 2.
of +1.0. As the wind is deflected around the sides and
2
406
'0 ' .
c ' .
order of scale: tornado damage, background damage 0' .
....J : :
and storm damage (see box below). Each category is .. .. .. .~: : ...... ,.
If) 70 1J ' ' 1j
associated with a distinct meteorological phenomenon. Q)
u
c
Q)
Q) , .
Q)
Q)
a.' . a.
[I! 00 : : If)
:; 1J
c '0
U
.. .. c
The threshold gust wind speed at which damage starts u
0
60 '~
" .;
'~
e (ij : :
.S:;! , .
Iii
u
genera l maintenance, deterioration of older buildings Q)
a.'
>-, .. 'a'
Licensed copy from CIS: hyder, Hyder Consulting, 11/08/2015, Uncontrolled Copy.
a. >-
Q) I-- I--
and design or construction fa ults in new buildings. .~ 40 ., " ... ..',
m
~
"
'S
E
::J
Most wind damage is of a relatively minor nature, such ()
30 -- ',"
as the loss of a few tiles or slates or damage to cladding
and glazing. Major structural fai lures, particularly of
engineered structures, are rare. However, the wind can 20 . '" .. ,.,
search out weaknesses in a building, so regular - :Souttiern England and Wales
inspection and maintenance should be carried out and Northern England and Scotland
damaged or missing cladding or fixings replaced as 10 "
Tornado damage
Highly localised damage that occurs along a narrow tract,
typically 50 m wide and 200 m long, and continuing intermittently
over distances of up to 20 km as the tornado 'skips' over the
ground. On average, 10 cases of tornado damage are reported
annually in the UK.
Background damage
This occurs during wind storms of low-to-medium severity at
wind speeds below design values. Background damage is
distributed throughout the UK as many isolated events, and
occurs at a consistent level of about 125 000 cases each year.
Storm damage
This occurs during severe gales or storms where the wind speed
approaches or even exceeds design values. The damage is
widespread over the area covered by the storm and includes all
classes and ages of buildings. The severe gales of October 1987
and January 1990 were events of this kind.
3
406
where: Vs
Vb
Ve = VsSb m/s
is the
is the
site mean windspeed = Vb Sa SdSsSp
basic wind speed
l
understood to allow wind pressures or distributions to be Sb is the terrain and building factor
calculated directly. For this reason , the general procedure Sa is the altitude factor
Licensed copy from CIS: hyder, Hyder Consulting, 11/08/2015, Uncontrolled Copy.
used in most modern wind codes is to treat the calculation Sd is the direction factor
of wind speed in a fully probabilistic manner whilst S5 is the seasonal factor
retaining deterministic values of pressure coefficients. Sp is the probability factor
This is the approach of BS 6399: Part 2, which offers a
choice of methods for calculating wind loads: The reference dynamic pressure, q5 is then calculated
• a standard method similar to that used in the qs= kV/
previous wind code, CP 3: Chapter V: Part 2
where: k = 0.613 kg/m3
• a directional method which gives a more precise and multiplied by pressure coefficients, loaded areas,
assessment of critical wind loads for individual wind dynamic magnification factor (if appropriate), reduction
directions. factors and partial safety factors to give the wind load for
Table 1 shows the main differences between the codes. each element of the structure and each of the limit states.
Table 1 Major differe nces between CP3: Chapte r V: Pa rt 2: 1972 a nd BS 6399: Part 2: 1995
Areas of difference CP 3: Chapter V: Part 2: 1972 BS 6399: Part 2: 1994 Comments on BS 6399: Part 2
Methods Single method Standard method and Standard method is quick and conservative:
directional method directional method is slow but more precise
Calculation of Basic wind speed (three-second gust), V Basic wind speed (hourly mean). Vb A move towards European harmonisation;
wind speed required for dynamic analysis
Topography factor, 5 I Topography factor. 5 1t Method is the same as CP3 but factors are
applied differently - see Altitllde factor
Roughness. size, height factor, 52 Terrain and building factor, 5 b Adjusts mean wind speed to gust wind
derived from: speed of appropriate duration
• Fetch factors , 5 c T c
• Thrbulence factors. 51 T,
Statistical factor, 53
•Probability factor, 5
Gust peak factor, gl
p Now based on q rather than V
Seasonal factor, 55 New, for seasonal exposure of temporary
structures
Directional factor, 54 Direction factor. 5 d
Altitude factor, 5a
Similar to CP3
New; allows adjustment for altitude effects
\
and allows for topography in standard
method
Design wind speed, V5 Effective wind speed, V e Given as gust speeds. duration dependent
on loaded area
Terrain categories 1 Open country Country, town Simplifies selection of terrain category; now
2 Open country with scattered includes effect of distance from coast and
windbreaks from edge of town
3 Small towns, suburbs
4 City centres
DYllllmic stnlClUI'a Not covered Satisfied by use of a dynamic Applies only to mildly dynamic structures
magnification factor
4
406
• Using hip or mansard roofs instead -0.5 - 1.0 - 1.5 - 2.0 - 2.5 - 3.0
of conventional duo-pitch and fl a t
Flat roof
roofs
• Minimising roof overhangs
Low parapet
• Avoiding shallow mono-pitch roofs
Flat roof with parapet edium parape
• Minimising the use of right-angled
corners on eaves and walls High parapet
• Where possible, arranging buildings
in a way that maximises the
Steep chamf r
benefits of shelter and avoids large
variations in height between Mansard roof edium chamfe
adjacent buildings.
Shallow cha fer
6
406
I OTHER CONSIDERATIONS
kitchens, car parks, etc so that they are not drawn back Service considerations for dominant openings
into the building through the air-conditioning system. If a dominant opening is considered closed in the
ultimate load conditions, it should also be considered
Wind tunnel testing can be a useful tool for assessing the to be open under service conditions. The service
environmental aspects of wind flow around buildings. conditions may control the design - see BS 6399: Part 2.
BS 6399: Part 2 provides minimum requirements for WIND DAMAGE DURING CONSTRUCTION
both static and dynamic wind tunnel testing. Wind Many structures are most vulnerable to wind damage
tunnel testing provides a tailored assessment of wind when they are under construction. This is because
loads by accurately simulating both the model and its partially completed structures very often do not provide
immediate surroundings as well as the local wind the same level of resistance to wind loads as completed
conditions. In some cases, this is the only way the ones. Structures vulnerable in this way include:
designer can assure adequate structural performance
and improve economy of design. • Freestanding walls without support from floor or
roof beams
Wind tunnel testing should be considered for any of the • Precast units before permanent connections are made
foUowing:
• Structural frames and roofs before lateral bracing is
• Tall, flexible or wind-sensitive structures such as masts, installed
towers, chimneys, suspension bridges and other cable-
stayed structures (see also p8) • Tanks and silos before the roof is fitted.
• Structures with unusual or innovative external forms Careful planning of the erection sequence and provision
• Structures in locations with complex wind conditions of temporary bracing can help to minimise these dangers
(such as city centres) or close to tall buildings - see box on page 8.
• Any structure where a more accurate assessment of the
wind loads is required.
7
406
AIR-SUPPORTED STRUCTURES
Planning the erection sequence
Air-supported structures rely on maintaining a small
• Build up walls at the same rate wherever possible; do internal overpressure. In strong winds the internal
not build freestanding walls more than about 3 m high.
pressure must be increased in proportion to the increase
• Start construction at the windward edge of the in the external wind pressure. Ideally the blower should
development to take advantage of shelter provided by
completed structures. be linked to anemometers to allow automatic pressure
compensation. Emergency back-up should be provided
• Try to synchronise fixing of cladding and glazing; tbis
will maintain equal porosity on all external walls by in case the blower or electricity supply fails.
avoiding dominant openings. If this is not possible,
construct the windward face first as this will reduce the RELOCATABLE BUILDINGS
likelihood of high positive internal pressures and These structures are generally used for short-term
minimise the loads on tbe other walls and the roof. accommodation (often as temporary school classrooms).
Providing temporary bracing They are demountable, using prefabricated panels and
Reduced wind loads can often be taken when designing components which are assembled on-site, and can be
temporary works or for specific phases of the construction dismantled, relocated and reassembled many times
sequence where tbe duration is for sub-annual periods. For during their lifetime.
example, if it is known that the structural frame will be
erected during a particular month, the appropriate seasonal
factor can be used in the design of the temporary bracing to The severe storms in 1987 and 1990 caused considerable
account for the lower probability of strong winds occurring damage to structures of this type , particularly to older
Licensed copy from CIS: hyder, Hyder Consulting, 11/08/2015, Uncontrolled Copy.
during that month. However, this approach requires careful units and those which had been moved and re-erected.
and realistic scheduling to ensure that each phase is These units should be regularly inspected for structural
completed in the time allotted and that contingency plans, adequacy and deterioration, with particular attention
such as provision of additional temporary bracing, are in
place in case of over-runs. given to exposed timbers, the connections between
panels, and signs of movement between panels or at
the foundations. The frequency of inspection will
SCAFFOLDING FAILURE
depend on the building's location and on its age, use,
There are two main causes of scaffolding failure:
condition and the number of times it has been moved .
• Inadequate tyi ng-back to the main structure F urther information is given in Digest 374.
• Failure to design for the appropriate wind load (this
includes fai lures ca used by sheeting on the scaffold
where no allowance is made for the increased loads). FURTHER READING
Building Research Establishment
Precautions against scaffolding failure Buller, P S J. The gales of January and February 1990: damage to
Sheeting the roof for weather protection or using safety buildings and structures. BRE Report. Garston, CRC, 1993.
netting on the faces transfers the wind load to the Buller, P S J. The October gale of 1987: damage to buildings and
scaffolding. If sheeting is to be used, this should be taken structures in the south east of England. BRE Report. Garston,
into account at the design stage by treating the scaffold as a CRC,1988.
clad or partially clad structure. If netting is used, the increase Buller, P S J. Gale damage to buildings in the UK: an illustrated
in wind loading depends on the porosity of the netting. review. BRE Report. Garston, CRC, 1986
Cook, N J. The designer's guide to wind loading of building structures.
Part 1: Background, damage survey, wind data and structural
WIND-SENSITIVE STRUCTURES classification. Part 2: Static structures. London, Butterworths, 1985.
These can range from simple lamp standards, masts and Flint and Neill Partnership. Investigation into tbe structural
chimneys to tall office blocks. Special aerodynamic adequacy of relocatable buildings under wind loading.
BRE Report. Garston, CRC, 1990.
devices, such as strakes and baffles, can be used on
circular structures to suppress dynamic excitation; tuned Other BRE Digests
mass dampers can be used on a wide range of structures 346 The assessment of wind loads
to absorb wind energy and minimise deflections. For Part 1: Background and method
Part 2: Classification of structures
structures susceptible to dynamic instabilities such as Part 3: Wind climate in the UK
vortex shedding, the maximum dynamic response could Part 4: Terrain and building factors and gust peak factors
occur at wind speeds lower than the design value if the Part 5: Assessment of wind speed over topograpby
Part 6: Loading coefficients for typical buildings
shedding frequency coincides with a natural frequency Part 7: Wind speeds for serviceability and fatigue assessments
of the structure. Where guying systems are used on Part 8: Internal pressures
masts, attention must be given to the design of the guy 374 Relocatable buildings: structural design, construction and
maintenance
ropes to prevent undue vibration effects. 390 Wind around tall buildings
391 Damage to roofs from aircraft wake vortices
Mildly dynamic structures can be identified using the
British Standards Institution
assessment method given in BS 6399: Part 2. T hey can
BS 6399:- Loadi ng for buildings
be designed with quasi-static methods using an Part 2:1994 Code of practice for wind loading
appropriate dynamic magnification factor.
Printed in the UK a nd published by Construction Rese arch Communications Ltd . Avai lable by subscription . Curre nt prices fro m:
Construction Research Communications Ltd , 33 - 39 Bowling Green Lane, London EC1 R ODA. Tel: 01923 664444 Fax: 01923 664400
Full detai ls of a ll rece nt issue s of BRE publications are give n in BRE News sent free to s ubscribe rs.
Published by permission of the Controller of HMSO and the Building Research Establishment. Crown copyright 1995