You are on page 1of 24

Catalog HA 45.

31 · 2007

Switchgear Type 8DJ20


up to 24 kV, Gas-Insulated
Medium-Voltage Switchgear
Power Transmission and Distribution
Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Contents Application, Requirements

Page Features
8DJ20 switchgear is a factory- _ Option: Connection with
Application, Requirements assembled, type-tested, metal- conventional sealing ends
Features, typical uses 2 and 3 enclosed switchgear for indoor – For thermoplastic-insulated
installation. cables via elbow adapter
Technical Data AKE 20/630 (make Siemens)
Typical uses – For paper-insulated mass-im-
Electrical data, filling pressure, temperature 4 pregnated cables via commer-
8DJ20 switchgear is used for
Product Range power distribution in substations cially available adapter systems
– even under severe environmen- _ Easy installation
Equipment features 4
tal conditions, such as:
Product range overview, schemes 5
_ Industrial environments Personal safety
Design _ Safe-to-touch and hermetically-
_ Damp, sandy or dusty areas
Panel design 6 sealed primary enclosure
_ Simple outdoor substations
_ HV HRC fuses and cable sealing
Components ends are only accessible when
Main uses
Three-position switch-disconnector, outgoing feeders are earthed
operating mechanisms 7 _ Compact substations
_ Operation only possible when
HV HRC fuse assembly, secondary _ Compact transformer substations, enclosure is closed
equipment, pressure absorber system 8 e. g. for wind power stations
Cable connection 9 _ Logical mechanical interlocking
_ Garage and vault substations
_ Capacitive voltage detecting
Dimensions _ Underground and underfloor system to verify safe isolation
Switchgear 10 to 13 substations from supply
Floor openings, fixing points 14 and 15 _ Sidewalk substations, e.g. _ Feeder earthing by means of
Examples for cable connection 16 containing switchgear with a make-proof earthing switches
very small overall width – in
Shipping particular the basic versions Security of operation
Types of transport, transport data 17 of schemes 10, 32 and 71 –
in conurbations _ Hermetically-sealed primary
Designs, Special Designs enclosure independent of en-
_ Substations with control aisle vironmental effects such as
LV compartment, outdoor enclosures 18 to 20 pollution, humidity and small
Technology animals – sealed for life:
Standards, Notes
_ Switchgear design with up to – Welded switchgear vessel
Standards, specifications, 21 to 23 5 feeders – Welded-in bushings and
guidelines, classification operating mechanism
_ Maintenance-free
For further information, please refer to _ Operating mechanism parts
_ Climate-independent maintenance-free
_ Catalog HA 40.1: _ Partition class: PM (IEC 60 694/VDE 0670-1000)
Switchgear Types 8DJ and 8DH, General Part (partition of metal)
_ HA 45.31/41.11: _ Operating mechanisms of
Supplements to Switchgear Types 8DJ and 8DH _ Three-pole primary enclosure, switching devices located out-
metal-enclosed side the switchgear vessel
_ Insulating gas SF6 (primary enclosure)
_ Welded switchgear vessel with- _ Switchgear interlocking system
out seals, made of stainless with logical mechanical inter-
steel, with welded-in bushings locks
for electrical connections and
mechanical components Cost-efficiency
_ Three-position switch-discon- Extremely low “life-cycle costs”
nector with load-break and throughout the entire product
make-proof earthing function service life as a result of:
_ Cable connection for _ Maintenance-free concept
bushings with outside cone _ Climatic independence
_ Connection with cable plugs _ Minimum space requirements
– In ring-main feeders with _ Maximum availability
bolted contact (M16)
– In transformer feeders with Standards
The products and systems described in this catalog plug-in contact
see page 21
are manufactured and sold according to a certified
quality and environmental management system
(acc. to ISO 9001 and ISO 14001).
(DQS Certificate Reg. No. DQS 003473 QM UM).
The certificate is accepted in all IQNet countries.

© Siemens AG 2007

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Application

Typical uses
Our product range extends from
switchgear installed in a radial
transformer panel (individual
panel) to switchgear with 5

R-HA45-101c eps
R-HA45-099c eps

R-HA45-100b eps
feeders, consisting of
_ Ring-main feeders
_ Transformer feeders with
HV HRC fuse assemblies
_ Circuit-breaker feeders (for
the complete product range
see Supplements to Catalogs
HA 45.31/41.11 – 2006)
The switchgear is available in
three overall heights:
_ 1200 mm
(with low subframe)
_ 1400 mm and 1760 mm
Radial transformer Ring-main/ Ring-main/
(with high subframe) panel transformer block transformer block
These overall heights cover all 1 transformer feeder 2 ring-main feeders 3 ring-main feeders
areas of application, from com- 1 radial cable connection 1 transformer feeder 2 transformer feeders
pact substations to switchgear Scheme 01 Scheme 10 Scheme 82
rooms with control aisle.

Basic design
_ Manual operating mechanism
_ Transformer cable connection
at the front (standard)
_ With logical mechanical inter-
locks
_ With ready-for-service indicator
_ With capacitive voltage de-
tecting system at the ring-
main feeders

Options (others on request)


_ Capacitive voltage detecting
system at the transformer
feeders
_ Motor operating mechanisms
for the three-position switch-
disconnectors
_ Auxiliary switch for three-posi-
tion switch-disconnector and
make-proof earthing switch
_ Short-circuit indicator with
built-in housing
_ Surge arresters for ring-main
feeders
_ Shunt releases for transformer
feeders
_ Secondary equipment for
remote operation or remote
indication, e.g. with local-
remote switch in the case of
motor operating mechanisms
or ”tripped signal” in the case
of transformer feeders 8DJ20 switchgear in
R-HA45-086c eps

a compact substation
_ Locking devices
_ Closing lock-out
_ De-earthing lock-out
_ Cable clamps

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Technical Data, Product Range


Electrical data,
temperature, filling pressure Equipment features of panels

Rated voltage Ur kV 7.2 12 15 17.5 24 Equipment • Basic equipment


1
Rated insulation level ° Additional equipment e2 02
(option), further em e
Rated short-duration kV 20 28 1) 36 38 50 h em
c
additional equipment rs ch
power-frequency
on request fo rs
withstand voltage Ud (E) fo
K ) lK
x Not el ch ne
Rated lightning impulse kV 60 75 1) 95 95 125 applicable pan wit pa
s ,
withstand voltage Up n, g ion ch)
– Not avail- io in t 1
e ct rth ect swi s er e 0
Rated frequency fr 50/60 Hz a n g r
able n
n al e
on in ede e ed em
co c h f h
Rated normal current Ir e on le art fe er sc er
bl iti b e in rm T in orm s
for ring-main feeders 400 or 630 A ca add l ca out ma RK o 1
al a - l f
s l s er l T
f
di ith adi ith ing ane ran ane ran ed ane
for transformer feeders 200 A Ra (w R (w R p T p T fe p
depending on the
HV HRC fuse link Manual operating mechanism for
three-position switch-disconnector:
for schemes 01 and 21 200 A
– As spring-operated mechanism • x • – –
depending on the
– As spring-operat./stored-energy mech. – x – • •
HV HRC fuse link
Rated short-time Motor operating mechanism for
– x
withstand current Ik three-position switch-disconnector ° ° °
at 1 s kA – – – 16 16
Interlock for cable compartment
kA 20 20 20 20 20 • – • • •
cover
kA 25 25 25 25 –
at 3 s (option) kA 20 20 20 20 20 Cable compartment cover locked
in place/screwed on – • – – –
Rated peak kA – – – 40 40
withstand current IP kA 50 50 50 50 50 Cable bracket 2) in ring-main and cable
kA 63 63 63 63 – feeders, cable routing downwards • • • • x
Rated short-circuit
making current Ima Cable bracket in transformer feeder:
For cable routing
for transformer feeders kA 25 25 25 25 25
– Downwards (standard), f. cable elb. plugs x x x x •
for ring-main feeders kA – – – 40 40 or
kA 50 50 50 50 50 – Downwards, for straight cable plugs x x x • •
kA 63 63 63 63 – or
– To the rear, for cable elbow plugs x x x without without
Ambient air temperature T 3) 3)
(operating conditions acc. to
IEC 62 271-200/Clause 2 or Low-voltage terminals in the
IEC 60 694) operating mechanism • – • • •
– Without secondary equipment - 40 to + 70 °C 5) (option for secondary equipment)
– With secondary equipment,
Shunt release – – –
class “Minus 5 indoor” - 5 to 55 °C 5) ° °
Pressure values at 20 °C Auxiliary switch for
for the insulation: – Switch-disconnector
x
Rated filling level pre 1500 hPa (absolute) CLOSED/OPEN: 1NO + 2NC
– EARTHING CLOSED/OPEN:
° ° ° °
x
Minimum functional level pme 1300 hPA (absolute) 1NO + 1NC ° ° ° °
Locking device for
x
three-position switch-disconnector ° ° ° °
Short-circuit or earth-fault indicator
1) According to some national requirements, higher values of the – Wiring at the indicator – –
rated short-duration power-frequency withstand voltage (standard) ° ° °
available for Ik = 20 kA with: – Wiring to terminal (option) – –
– 42 kV for phase-to-phase, phase-to-earth and open contact ° ° °
gap as well as De-earthing lock-out for
– 48 kV across the isolating distance make-proof earthing switch
in transformer feeder x x x 4)
Higher values of the rated lightning impulse withstand voltage:
– 95 kV for phase-to-phase, phase-to-earth and open contact
° °
Closing lock-out for
gap as well as
three-position switch-disconnector – x – –
– 110 kV across the isolating distance °
2) For overall height of switchgear 1200 mm: Double cable connection for
Cable bracket below the feeder – Overall height of switchgear 1200 mm x x
3) Cable fixing by customer – Overall height of switchgear 1400 mm ° ° ° x x
(the switchgear is supplied without cable bracket) – Overall height of switchgear 1760 mm ° ° ° x x
4) In case of scheme 01 the cable compartment cover is bolted.
° ° °
The transformer connection is effected via the bushings Surge arrester for
arranged underneath the switchgear vessel. The transformer – Overall height of switchgear 1200 mm – – o. r. 6) x x
feeder is earthed by the three-position switch – Overall height of switchgear 1400 mm x x
– Overall height of switchgear 1760 mm ° ° ° x x
5) Temperature range, reduced normal currents at ambient air
temperatures > + 40 °C
° ° °
Cable clamps for cable fixing
6) Surge arrester type RDA with RICS (Tyco Electronics) not
– Supplied separately
possible for a height of 1200 mm
– Preassembled (option) ° ° ° °
– °
o. r. = on request ° ° ° °
Siemens HA 45.31 · 2007
Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Product Range

Product range overview, schemes

Scheme Overall dimensions Net 1) Scheme Overall dimensions Net 1)


weight weight
Components shown in dotted Width Depth Height approx. Components shown in dotted Width Depth Height approx.
lines can be used optionally. 2)3) lines can be used optionally. 2)3)
mm mm mm kg mm mm mm kg

Radial transformer panels


Scheme 01 * 1 transformer feeder, Scheme 21 1 radial cable connection,
K Radial cable 1 radial cable connection K(E) Radial cable 1 transformer feeder
HA45-2294d eps

HA45-2299c eps
connection as (Abbreviation 1T) connection, K as (Abbreviations 1K(E)+1T)
infeed K(E) with make-proof
510 775 1200 140 earthing switch 710 775 1200 200
1400 160 1400 210
1760 200 1760 250
K T K(E) T

Radial panel
Scheme 02 1 ring-main feeder with
radial cable connection
HA45-2295c eps

(Abbreviation 1RK)
710 775 1200 150
1400 170
RK K 1760 210

Block versions, consisting of ring-main and transformer feeders (with HV HRC fuse assembly)

Scheme 10 * 2 ring-main feeders, Scheme 20 1 ring-main feeder,


1 transformer feeder 1 transformer feeder
HA45-2298c eps
HA45-2296c eps

(Abbreviations 2RK+1T) (Abbreviations 1RK+1T)


1060 775 1200 280 710 775 1200 200
1400 300 1400 210
1760 340 1760 250
RK RK T RK T
Scheme 71 * 3 ring-main feeders, Scheme 72 4 ring-main feeders,
1 transformer feeder 1 transformer feeder
HA45-2302c eps

HA45-2303c eps

(Abbreviations 3RK+1T) (Abbreviations 4RK+1T)


1410 775 1200 340 1760 775 1200 420
1400 360 1400 440
1760 400 1760 480
RK RK RK T RK RK RK RK T
Scheme 81 * 2 ring-main feeders, Scheme 82 3 ring-main feeders,
2 transformer feeders 2 transformer feeders
HA45-2304c eps

HA45-2305c eps

(Abbreviations 2RK+2T) (Abbreviations 3RK+2T)


1410 775 1200 400 1760 775 1200 470
1400 420 1400 500
1760 460 1760 540
T RK RK T T RK RK RK T

Block versions, consisting of ring-main feeders (without HV HRC fuse assembly)

Scheme 11 2 ring-main feeders Scheme 32 * 3 ring-main feeders


(Abbreviation 2RK) (Abbreviation 3RK)
HA45-2300c eps
HA45-2297c eps

710 775 1200 160 1060 775 1200 210


1400 170 1400 230
1760 210 1760 270
RK RK RK RK RK
Scheme 70 * 4 ring-main feeders Scheme 84 5 ring-main feeders
(Abbreviation 4RK) (Abbreviation 5RK)
HA45-2301c eps

HA45-2306c eps

1410 775 1200 280 1760 775 1200 350


1400 300 1400 380
1760 340 1760 420
RK RK RK RK RK RK RK RK RK

1) Depending on the relevant equipment, e.g. motor operating mechanism Abbreviations:


2) Additional wall distance required: W 15 mm RK = Ring-main feeder K = Cable feeder T = Transformer feeder
3) For cable routing of transformer cables downwards K(E) = Cable feeder for radial cable connection with make-proof earthing switch
* Scheme is also suitable for outdoor enclosure (see pages 18 and 19)

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Design

Panel design (example)

Ring-main/transformer block Transformer feeder Ring-main feeder


Section A-A Section B-B
B
38 A 38

1 11
2 12
25
3 13 26
4 14
27 27
5
15
28 33
6 16
10
7 17
19 10
8 L1 L2 L3 18
20
9 19 29 34
10 20 30 35
21 31 31
22 22 36
23
23
HA45-2337d eps

24
24

32
B A Standard Cable connection with bolted contact (M16):
Cable connection for cable elbow plugs – For cable T-plug or cable elbow plug
Scheme 10 (option: for cable T-plugs), – For conventional cable sealing ends via
cable routing downwards elbow adapter AKE 20/630

1 Niche for customer-side low-voltage equipment 17 Manual operation for the mechanism of
HA45-2308e eps

the earthing function


2 Feeder designation label
18 Manual operation for the mechanism of
Switch position indicators
the load-break function
in the ring-main feeder:
3 Load-break function ”CLOSED – OPEN” 19 Switchgear vessel, filled with gas
4 Earthing function ”OPEN – EARTHED” 24 31 20 Connecting bar to cable connection
5 Rating and type plate
30 21 Arrangement of cable connections
6 Ready-for-service indicator
22 Cable compartment
7 Mimic diagram 29
23 Cable bracket
8 Short-circuit/earth-fault indicator (option)
22 32 24 Cable (not included in the scope of supply)
9 Sockets for voltage detecting system
25 Cover of the HV HRC fuse compartment
10 Interlock of the cable compartment cover Option 26 Connecting bar to the bushings
11 HV HRC fuse assembly, cover removed Cable connection for cable elbow for the HV HRC fuse
plugs, cable routing to the rear
12 Handle for replacing the HV HRC fuse link (cable fixing by customer) 27 Three-position switch-disconnector
13 Interlock for HV HRC fuse assembly 28 Spring-operated/stored-energy mechanism
Switch position indicators 29 Bushing as interface type “A“ for cable
HA45-2309e eps

in the transformer feeder: plug with plug-in contact


14 Earthing function ”OPEN – EARTHED”
30 Option: Cable elbow plug with
15 Load-break function ”CLOSED – OPEN”
plug-in contact
with ”HV HRC fuse tripped” or ”shunt release
tripped”, where applicable 31 Cable compartment cover
16 Locking device 29 31 32 M12 earthing connection
(option for three-position switch-disconnector)
33 Spring-operated mechanism
37
34 Bushing as interface type “C“ for cable
22 plug with bolted contact (M16)

23
35 Option: Cable T-plug with bolted contact
32 36 Pressure relief device
24
37 Option: Straight cable plug with
Option plug-in contact
Cable connection for 38 Option: Low-voltage compartment
Personal safety straight cable plugs,
All feeder-related covers can only be cable routing downwards
opened if the associated three-position
switch-disconnector has been switched to
the “EARTHED” position.

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Components

Three-position switch-disconnector, operating mechanisms


Three-position
switch-disconnector Three-position switch-disconnector
The switching device used
Switchgear vessel of a

R-HA45-102 eps
is the proven three-position ring-main/transformer
switch-disconnector 1 block, scheme 10
(rear view)
Functions 1 Three-position switch-
disconnector in the
_ Load-break function
transformer feeder
_ Earthing function with 2 Three-position switch-
short-circuit making capacity 2 disconnector in the
ring-main feeders
_ Switch positions
CLOSED – OPEN – EARTHED 3 Pressure relief device
3
Operating mechanisms
The three-position switch-
disconnector is operated from
the switchgear front via

Detachable lever mechanism Operating mechanisms


(standard)
R-HA45-103a eps

Control board for detach-


• Spring-operated mechanism able lever mechanisms
– With ”spring-operated 4 (standard)
CLOSED” and ”spring-oper- Example:
ated OPEN” for installation 5 Ring-main/transformer block,
in ring-main feeders scheme 10
6 4 Locking device (option)
_ Spring-operated/stored- for the detachable lever
energy mechanism mechanism
– With ”spring-operated 5 Detachable lever
CLOSED” and ”spring-oper- operation for the
ated OPEN” for installation earthing function
R-HA45-105 eps
R-HA45-104 eps

in transformer feeders 6 Detachable lever


– With an additional energy operation for the
load-break function
store for the function ”stored-
energy OPEN” after tripping 7 Detachable lever
mechanism for the
by the HV HRC fuse (striker ring-main feeder
pin tripping) or by the shunt
8 Detachable lever
release 7 8
mechanism for the
transformer feeder
Options
_ Motor operating mechanism
for switch-disconnector
_ Rotary operating mechanism
_ Locking devices Control board for rotary
R-HA45-106a eps

operating mechanisms
_ Auxiliary contacts for three- (option)
position switch-disconnector
Example: Ring-main feeder
and make-proof earthing
9 9 Symbols for the actuating
switch
direction of the rotary
_ Shunt release for transformer operating mechanism
feeders 10 Locking device for the ro-
10
tary operating mechanism
_ Closing lock-out for ring-
main feeders
11 Rotary operating
R-HA45-107 eps

_ De-earthing lock-out for


mechanism (option)
transformer feeders
_ Different operating levers 1) for
the operating mechanisms of
the switch-disconnector and of
the make-proof earthing switch
11
1) According to VDN */ VDEW **
recommendation
* Association of German Network
Operators VDN e.V. at the VDEW in
Germany (as of 2003)
** Association of German
Power Stations – VDEW e. V.

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Components

HV HRC fuse assembly, secondary equipment, pressure absorber system


HV HRC fuse assembly
The HV HRC fuse boxes are HV HRC fuse compartment
single-phase insulated and lo-
cated above the transformer
feeder outside the switchgear HV HRC fuse compartment
vessel. with cable compartment
cover removed
Standards (see page 21) Phase L1:
HV HRC fuse box with
HV HRC fuse links with striker HV HRC fuse slide removed
pin in “medium” version Phase L2:
according to HV HRC fuse box closed
_ IEC 60 282-1 Phase L3:
Replacement of HV HRC fuses
_ VDE 0670 Parts 4 and 402
R-HA45-108 eps

_ DIN 43 625 main dimensions

Features
_ Requirements fulfilled as HV
alternating current switch-
fuse combination Secondary equipment (option)
_ Selection of HV HRC fuses for Auxiliary switch, motor
operating mechanism and
transformers 1 shunt release
_ For further features Example: Transformer feeder
see Catalog HA 40.1 1 Wiring duct
2 2 Terminal strip
Secondary equipment (option) 6
3 Auxiliary switch at spring-
_ Auxiliary switches, motor 3 operated mechanism of a
operating mechanisms or ring-main feeder
shunt releases wired to a 4 Auxiliary contactors
terminal strip 4 (standard for motor
operating mechanism)
_ Location of the terminal strip
5 Motor operating mechanism
next to the operating mecha- at spring-operated/
nism module of the feeder stored-energy mechanism
concerned 7 6 Locking device
5
_ Customer-side cable routing (standard for motor
to the terminal strip from the operating mechanism)
side or rear 7 Shunt release at spring-
R-HA45-133 eps

operated/stored-energy
mechanism
Pressure absorber system
(option)
_ Maintenance-free
_ For all schemes (except radial Pressure absorber system
transformer panel, scheme 01) (option) Sectional views of the
_ For rated short-time with- pressure absorber system
HA45-2363 eps

stand current Ik w 16 kA, 1 Wall distance


with IAC (internal arc 2 Pressure absorber system
classification, see page 22) with rear pressure relief
HA45-2364 eps

duct directed upwards


_ With 105 mm deep pressure
absorber duct for pressure 3 Cable bushing
relief upwards 4 Divided floor plate for
~1762

cable entry for on-site


_ For overall height of switch- ~560 installation
1400

gear: 5 Floor opening for the


– Standard: 1400 mm 2 cable feeder
– Option: 1760 mm 3
~560
4
_ For wall-standing arrangement
2
_ Transformer cable routing:
3
– Standard: Downwards 4
~2

– Option: To the rear for


schemes 10, 71 and 72 5 5
1 435 240 1 435 240
_ Weight approx. 110 kg 775 775
³15 880 ³15 880

Standard: Overall height 1400 mm Option: Overall height 1760 mm

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Components

Cable connection
_ Bushings according to
EN 50 181/DIN EN 50 181 1) Cable connection (examples)
with outside cone
_ Cable connection at one level L1 L2 L3 L1 L2 L3
Cable connections
_ Access to the cable compart- in ring-main feeder
ment only if the feeder has
2 1 Prepared for cable plugs with
been isolated and earthed 1 bolted contact (M16)
3 2 Phase L1:
Ring-main cable connection Make: Euromold
_ With bolted contact (M16) as 4 type K400 LB
interface type ”C” according as cable elbow plug
to EN 50 181/ DIN EN 50 181 3 Phase L2:
Make: Euromold
_ For thermoplastic-insulated type K400 TB
cables as cable T-plug
_ For paper-insulated mass- 4 Phase L3:
Make: Euromold
R-HA45-111 eps

R-HA40-128 eps
impregnated cables with type AGT 20/630
adapter systems as cable T-plug
_ For conventional cable sealing Option:
ends via elbow adapters Cable compartment, Cable plugs with Mounted cable clamps
AKE 20/630 (make Siemens) as delivered bolted contact (M16)

_ For cable T-plugs or cable


elbow plugs with bolted
L1 L2 L3 L1 L2 L3
contact (M16)
Cable connections
_ For connection cross-sections in transformer feeder
up to 300 mm2 (standard) 6 5 Prepared for cable elbow plugs
_ Cable routing downwards, 5 with plug-in contact
cable connection at front 7 6 Phase L1:
Make: Euromold
_ For rated normal currents of 8 type K158 LR
400/630 A 7 Phase L2:
Make: nkt cables
Options type EASW 20/250
_ Suitable for the connection of 8 Phase L3:
surge arresters Make: Cooper
type DE 250-R-C
_ Short-circuit/earth-fault
R-HA45-113 eps

R-HA45-114 eps

Option:
indicator Mounted cable clamps
_ Mounted cable clamps
_ Double cable connection with Cable compartment, Cable elbow plugs with
corresponding cable plugs as delivered plug-in contact

Transformer cable connection Transformer cable connection for cable plugs


_ With plug-in contact as inter- Standard: With plug-in contact as interface type “A”
face type “A” according to Option: With bolted contact (M16) as interface type “C”
EN 50 181/ DIN EN 50 181 Arrangement of Cable routing Cable plug
connections version
_ For cable elbow plugs
(standard) or straight cable For all schemes (except scheme 01)
plugs with plug-in contact
At the front Downwards Cable elbow plug with plug-in contact
_ For thermoplastic-insulated (standard) Option: Cable plug with bolted contact (M16)
cables At the bottom To the rear 2) Cable elbow plug with plug-in contact
_ For connection cross-sections (option) Downwards Straight cable plug with plug-in contact
up to 120 mm2 Option: Straight cable plug with bolted contact (M16)

_ For rated normal currents


Only for scheme 01 (radial transformer panel 1T)
of 200 A
At the bottom To the rear 2) (standard) Cable elbow plug with plug-in contact
(standard)
Options Downwards (option) Straight cable plug with plug-in contact
Option: Straight cable plug with bolted contact (M16)
_ With bolted contact (M16) as
interface type “C” according
to EN 50 181/ DIN EN 50 181
_ Mounted cable clamps 1) Standard EN 50 181/DIN EN 50 181: 2) For cable routing of the trans- Cable plugs, cable
“Plug-in bushings above 1 kV up to former feeder to the rear: sealing ends and cable
_ Cable routing to the rear 36 kV and from 250 A to 1.25 kA for Cable fixing by customer clamps are not included
(for cable elbow plugs) equipment other than liquid-filled
transformers.”
in the scope of supply.

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Dimensions

Switchgear (for floor openings and fixing points refer to page 14)

Radial transformer panels · optionally in 3 overall heights

510 Section B-B Section B-B


B
Transformer Transformer
HA45-2345e eps

feeder T feeder T
Cable routing Cable routing
of feeder of feeder
to the rear downwards
with cable with straight
1200 /1400

elbow plugs cable plugs


515 515
(on request)

1 1
1760

4 2

375/575**
375/575**
T 3
220/420**

935

935
a

a
Dimension a
780

– 40 mm for
M12 M12 overall height 1400 mm
– 130 mm for
overall height 1200 mm
B ~520*, ~560* 240
500
*** 750 ~520*, ~560*
775 *** 750
Scheme 01
(with radial cable 775
connection as infeed)

1 Bushing at the front for cable routing downwards (infeed) * Dimension depending on the bushing size and make/type of cable plug
Standard: For cable elbow plugs with plug-in contact
Option: For cable T-plugs with bolted contact (M16) ** Dimensions depending on the overall heights of switchgear 1200 and 1400 mm
2 Bushing at the bottom for cable routing to the rear (feeder T) *** For cable routing to the rear, the depth dimensions are 10 mm deeper
3 Bushing at the bottom for cable routing downwards (feeder T) BB Dimension for bushing as interface type “A” with plug-in contact

4 Bolted joint of cable compartment cover (only for scheme 01)

710 Section A-A Section B-B


A B
Radial cable Transformer
HA45-2312h eps

connection K(E) feeder T


with make-proof
earthing switch
1200/1400

553 515
1
1760

2
375/575**
375/575**

K (E) T
220/420**
935

935
a
a

Dimension a
780

– 40 mm for
M12 overall height 1400 mm
– 130 mm for
overall height 1200 mm
A B ~560 367
350 350 750 ~520*, ~560*
775 *** 750
Scheme 21
775

1 Bushing at the front (standard) for cable routing downwards * Dimension depending on the bushing size and make/type of cable plug
2 Bushing at the bottom (option) for cable routing to the rear or ** Dimensions depending on the overall heights of switchgear 1200 and 1400 mm
downwards *** For cable routing to the rear, the depth dimensions are 10 mm deeper
B Dimension for bushing as interface type “C” with bolted contact (M16)
BB Dimension for bushing as interface type “A” with plug-in contact

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Dimensions

Switchgear (for floor openings and fixing points refer to page 14)

Block versions, consisting of ring-main feeders · optionally in 3 overall heights

1760 Section A-A


A
Ring-main
HA45-2319f eps

feeder RK

1200 /1400 553


1760

375/575**
RK RK RK RK RK

935
a
Dimension a
– 40 mm for
overall height 1400 mm
– 130 mm for
overall height 1200 mm
A ~560
350 350 350 350 350
750

Scheme 84 775

** Dimensions depending on the overall heights of switchgear 1200 and 1400 mm


B Dimension for bushing as interface type “C” with bolted contact (M16)

Further scheme types (side views, section A-A, see scheme 84)

710 710 1060 1410


A A A A
HA45-2315f eps

1200/1400
1760

RK RK RK RK RK RK RK RK RK RK

A A A A
350 350 350 350 350 350 350 350 350 350 350

Scheme 02 (1RK with Scheme 11 Scheme 32 Scheme 70


radial cable connection)

4 Bolted joint of cable compartment cover

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Dimensions

Switchgear (for floor openings and fixing points refer to page 15)

Block versions, consisting of ring-main feeders and 1 transformer feeder · optionally in 3 overall heights

1760 Section A-A Section B-B


A B
Ring-main Trans-
HA45-2324f eps

feeder RK former
feeder
T

1200 /1400 553 515


1760 1
2

375/575**
375/575**
RK RK RK RK T

220/420**
935

935
a
a

780
M12

A B ~560 367
350 350 350 350 350 ~520*, ~560*
750
775 *** 750
Scheme 72
775

1 Bushing at the front (standard) for cable routing downwards


* Dimension depending on the bushing size and make/type of cable plug
2 Bushing at the bottom (option) for cable routing to the rear or
downwards ** Dimensions depending on the overall heights of switchgear 1200 and 1400 mm
Dimension a *** For cable routing to the rear, the depth dimensions are 10 mm deeper
– 40 mm for overall height 1400 mm B Dimension for bushing as interface type “C” with bolted contact (M16)
– 130 mm for overall height 1200 mm BB Dimension for bushing as interface type “A” with plug-in contact

Further scheme types (for side views, sections A-A and B-B, see scheme 72)

710 1060 1410


A B A B A B
HA45-2321e eps

1200/1400
1760

RK T RK RK T RK RK RK T

A B A B A B
350 350 350 350 350 350 350 350 350

Scheme 20 Scheme 10 Scheme 71

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Dimensions

Switchgear (for floor openings and fixing points refer to page 15)

Block versions, consisting of ring-main feeders and 2 transformer feeders · optionally in 3 overall heights

1760 Section A-A Section B-B


A B
Ring-main Trans-
HA45-2326f eps

feeder RK former
feeder
T

1200 /1400 553 515


1760 1
2

375/575**
375/575**
T RK RK RK T

220/420**
935

935
a
a

780
M12

A B ~560 367
350 350 350 350 350 750 ~520*, ~560*
775 *** 750
Scheme 82
775

1 Bushing at the front (standard) for cable routing downwards


* Dimension depending on the bushing size and make/type of cable plug
2 Bushing at the bottom (option) for cable routing to the rear or
downwards ** Dimensions depending on the overall heights of switchgear 1200 and 1400 mm
Dimension a *** For cable routing to the rear, the depth dimensions are 10 mm deeper
– 40 mm for overall height 1400 mm B Dimension for bushing as interface type “C” with bolted contact (M16)
– 130 mm for overall height 1200 mm BB Dimension for bushing as interface type “A” with plug-in contact

Further scheme type (for side views, sections A-A and B-B, see scheme 82)

1410
A B
HA45-2325e eps

1200 /1400
1760

T RK RK T

A B
350 350 350 350

Scheme 81

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Dimensions

Floor openings (dimensions 1) in red) and fixing points

For transformer panels For block versions, consisting of ring-main feeders

1750
500 19 350 350 350 350 312
14 x 28 2
250 175 350
10 10
31

55

63
³15

³ 15
31

55

63
147 44

147 44
9 350 350 350 350 9
1 1
4 35

437
233

233
623
713
610

100 150 150

623
713
610
65 110 110 110 110 110 110 110 110 110 110
5
47 197

47 197
35

125
3
11
HA45-2365 eps

11
19 106 125 125 19 106 100
28 x 14 2 28 x 14

HA45-2367a eps
40 420 350 350 350 350 14 x 28 2
40 1670
Scheme 01
15 1720
700
Scheme 84
19 350 312
9
175 350 700 1050
10
³ 15
31

55

63
147 44

350 8
1
125 85 125 227

35 12
233

713

713
623
713
610

65 110 110 110 110


HA45-2368a eps

HA45-2369a eps
6
7
47 197

11
11
19 106 100 40 620 40 970
28 x 14
HA45-2366a eps

350 14 x 28 2 15 670 15 1020


40 620 Scheme 02 * and 11 * Scheme 32 *
15 670
Scheme 21 1400

1 Wall distance
2 Fixing points
3 Position of the incoming cables for the incoming feeder
713
HA45-2370a eps

4 Position of the incoming cables for the outgoing feeder


5 Position of the incoming cables in the ring-main feeder
6 Position of the incoming cables in the cable feeder
7 Position of the incoming cables in the transformer feeder 40 1320
8 Position of the incoming cables in the transformer feeder (option) 15 1370
9 Floor opening for HV cables (and, if applicable, control cables) Scheme 70 *
10 Fixing frame (base) of the switchgear
11 Cutouts for an overall height of switchgear of 1200 mm 1) Depending on additional options (e.g. surge arrester, 2nd cable, cable-type
12 Cutouts for an overall height of switchgear of 1200 mm only when current transformer) the corresponding floor openings have to be provided as
connecting the transformer cables to the bushing via straight cable standard (see also page 16)
plugs * Complete dimensions see top figure on the right

Position of the floor openings for switchgear with pressure absorber system (for overall heights 1400 and 1760 mm)
700 700 1 Wall distance
³ 15

³ 15
105

105

13 Pressure relief duct

1 13 1 13
435

435
713

713
HA45-2371b eps

HA45-2372b eps

Pressure absorber Pressure absorber


system for system for
240

240

schemes all other


02, 11, 20 and 21 schemes
40 620 40 970, 1320, 1670

Further _ For double cable connection _ For surge arrester – Standard


connection on request possible for the following – 25 mm deeper
combinations: cable compartment covers: – 150 mm deeper

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Dimensions

Floor openings (dimensions 1) in red) and fixing points

For block versions, consisting of ring-main feeders For block versions, consisting of ring-main feeders
and 1 transformer feeder and 2 transformer feeders
1750 1750
19 350 350 350 350 312 19 350 350 350 350 312
9 9
175 350 175 350
10 10

³ 15
31

55

63
³ 15
31
HA45-2373a eps

55

63

147 44
147 44

350 350 350 350 8 1 35 350 350 350 350 8


1

85 125 227
125 85 125 227
35 12 12 12

233
233

623
713
610
623 65 110 110 110 110 110 110 110 110 110 110
713
610
65 110 110 110 110 110 110 110 110 110 110
5 7
7 5

47 197
47 197

125
11 11
11 11
19 106 100 19 106 100
28 x 14 28 x 14

HA45-2377a eps
350 350 350 350 2 350 350 350 350 14 x 28 2
14 x 28
40 1670 40 1670
15 1720 15 1720
Scheme 72 Scheme 82

700 1050 1400


713

713

713
HA45-2375a eps
HA45-2374a eps

HA45-2378a eps

40 620 40 970 40 1320


15 670 15 1020 15 1370
Scheme 20 * Scheme 10 * Scheme 81 *

1400

1 Wall distance
2 Fixing points
5 Position of the incoming cables in the ring-main feeder
713

7 Position of the incoming cables in the transformer feeder


HA45-2376a eps

8 Position of the incoming cables in the transformer feeder (option)


9 Floor opening for HV cables (and, if applicable, control cables)
40 1320 10 Fixing frame (base) of the switchgear
15 1370 11 Cutouts for an overall height of switchgear of 1200 mm
Scheme 71 * 12 Cutouts for an overall height of switchgear of 1200 mm only when
connecting the transformer cables to the bushing via straight cable
plugs
1) Depending on additional options (e.g. surge arrester,
2nd cable, cable-type current transformer) other floor
openings have to be provided as standard accordingly
(see also page 16) * Complete dimensions see top figures on the right and left

Position of the floor openings and fixing points for double cable connection in ring-main feeders
1050
Note:
HA45-2379c eps

31

63
³ 15

Double cable connection in ring-main feeders


147 44

only possible for switchgear with an overall


height of 1400 mm
(900*** / 715****)
233

713

610

RK RK T
1013

Abbreviations
65 150 132 197
~245**

RK = Ring-main feeder
T = Transformer feeder
Scheme 10 * * Complete dimensions see top figure on the left
(example)
** Depending on the cable plug used (see also page 16)
40 620 350
19 662
*** 300 mm deeper cable compartment cover version
700 **** 105 mm deeper cable compartment cover version

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Dimensions
Examples for cable connection in ring-main feeders
(non-binding examples; further examples see Catalog HA 40.1)

Cable connection (examples for overall height 1400 mm)

HA45-2342e eps
HA45-2341e eps

1 Elbow adapter, make Siemens, 3 Cable T-plug, make nkt cables,


type AKE 20/630 with conventional type CB 24-630 and
cable sealing end, make CC 24-630
Lovink Enertech, type IAE 20 4 Cable T-plug, make Südkabel,
2 Cable T-plug, make Euromold, type SET (12/24) and SET (12/24)
type (K)400 TB/G with coupling insert KU 23.2

553 553
1 2 3 4

290,5*

575
575
575

575
~560 ~560 ~560 101 ~560 ~190
63 610** 610** 63 635** 715**
750 750 750 852
775 775 775 880

Standard cable compartment cover Cable compartment cover for double cable connection

Cable connection with surge arresters (examples for overall height 1400 mm)
Combination on request
HA45-2327h eps

HA45-2340f eps

Overall height of switchgear: 1400 mm 7 Elbow adapter,


5 Cable plug, make Siemens,
make Tyco Electronics, type AKE 20/630
type RICS 5139 with conventional cable
sealing end,
6 Surge arrester, make Lovink Enertech,
make Tyco Electronics, type IAE 20
up to type RDA21 and
553 type RDA24 553 On request:
5 7 8 Surge arrester,
make Siemens
Dimension a
– 610 mm up to type RDA21
575

575

– 635 mm for type RDA24

Overall height of switchgear: 1200 mm


Numbers 5 and 6 not possible
~560 ~560
6 8
63 a** 63 610**
750 750
Standard Standard
775 cable compartment cover 775 cable compartment cover
HA45-2328h eps

HA45-2329f eps

9 Cable plug, 11 Cable plug,


make Südkabel, make Südkabel,
type SET (12/24) type SEHDT (13/23)
10 Surge arrester, 12 Surge arrester,
make Südkabel, make Südkabel,
type MUT (13/23) type MUW (12/22)

553 553 or
9 11
11 Cable plug,
make Euromold,
type (K)400 TB/G
12 Surge arrester,
575

575

e.g. make Euromold,


type 400 Pb
or similar types of
construction
~560 ~560
10 12
63 610** 63 610**
772 897
25 mm deeper cable 150 mm deeper cable
800 compartment cover 925 compartment cover

B Dimension for bushing with bolted contact (M16) * Max. mounting space for cable and/or surge arrester
** Depth of floor opening

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Shipping
Types of
transport Transport data
8DJ20 switchgear is Sche- Version Switch- Transport Vol- Gross 2) Sche- Version Switch- Transport Vol- Gross 2)
delivered as complete me (abbre- gear dimensions 1) ume weight me (abbre- gear dimensions 1) ume weight
transport unit. no. viations) height no. viations) height
(with- Width Height Depth (with- Width Height Depth
The following must be out 1) LV out 1) LV
compart- compart-
noted: ment) approx. ment) approx.
_ Transport facilities on mm m m m m3 kg mm m m m m3 kg
site
Transport in Europe by rail, truck, container Transport overseas by seafreight
_ Transport dimensions Packing with PE protective foil and wooden base Packing with PE protective foil and seaworthy crate
and weights 01 1T 1200 1.10 1.4 1.10 1.69 170 01 1T 1200 1.10 2.0 1.15 2.53 230
_ Size of door open- 1400 1.10 1.6 1.10 1.94 180 1400 1.10 2.0 1.15 2.53 250
ings in building 1760 1.10 1.96 1.10 2.37 210 1760 1.10 2.0 1.15 2.53 270
_ Switchgear with LV 02 1RK 1200 1.10 1.4 1.10 1.69 210 02 1RK 1200 1.10 2.0 1.15 2.53 270
compartment:
1400 1.10 1.6 1.10 1.94 230 1400 1.10 2.0 1.15 2.53 290
Please take other
transport dimensions 1760 1.10 1.96 1.10 2.37 260 1760 1.10 2.0 1.15 2.53 320
and weights into
10 2RK+1T 1200 1.45 1.4 1.10 2.23 370 10 2RK+1T 1200 1.45 2.0 1.15 3.34 450
account
1400 1.45 1.6 1.10 2.55 400 1400 1.45 2.0 1.15 3.34 470
Packing 1760 1.45 1.96 1.10 3.13 440 1760 1.45 2.0 1.15 3.34 510

Place of destination in- 11 2RK 1200 1.10 1.4 1.10 1.69 210 11 2RK 1200 1.10 2.0 1.15 2.53 280
side Germany or other 1400 1.10 1.6 1.10 1.94 230 1400 1.10 2.0 1.15 2.53 290
European countries
1760 1.45 1.96 1.10 3.13 260 1760 1.10 2.0 1.15 2.53 320
_ Means of transport:
Rail and truck 20 1RK+1T 1200 1.10 1.4 1.10 1.69 260 20 1RK+1T 1200 1.10 2.0 1.15 2.53 320
_ Type of packing: 1400 1.10 1.6 1.10 1.94 280 1400 1.10 2.0 1.15 2.53 340
– Panels on open 1760 1.10 1.96 1.10 2.37 310 1760 1.10 2.0 1.15 2.53 370
pallets
– Covered with PE 21 1K(E)+1T 1200 1.10 1.4 1.10 1.69 260 21 1K(E)+1T 1200 1.10 2.0 1.15 2.53 310
protective foil 1400 1.10 1.6 1.10 1.94 280 1400 1.10 2.0 1.15 2.53 340

Place of destination 1760 1.10 1.96 1.10 2.37 310 1760 1.10 2.0 1.15 2.53 370
overseas 32 3RK 1200 1.45 1.4 1.10 2.23 300 32 3RK 1200 1.45 2.0 1.15 3.34 380
_ Means of transport: 1400 1.45 1.6 1.10 2.55 330 1400 1.45 2.0 1.15 3.34 400
Ship 1760 1.45 1.96 1.10 3.13 370 1760 1.45 2.0 1.15 3.34 440
_ Type of packing:
– Panels on open 70 4RK 1200 1.80 1.4 1.10 2.77 380 70 4RK 1200 1.80 2.0 1.15 4.14 470
pallets 1400 1.80 1.6 1.10 3.17 420 1400 1.80 2.0 1.15 4.14 500
– In closed crates with 1760 1.80 1.96 1.10 3.88 470 1760 1.80 2.0 1.15 4.14 550
sealed PE protective
foil 71 3RK+1T 1200 1.80 1.4 1.10 2.77 440 71 3RK+1T 1200 1.80 2.0 1.15 4.14 530
– With desiccant bags 1400 1.80 1.6 1.10 3.17 480 1400 1.80 2.0 1.15 4.14 560
– With sealed wooden 1760 1.80 1.96 1.10 3.88 530 1760 1.80 2.0 1.15 4.14 610
base
– Max. storage time: 72 4RK+1T 1200 2.05 1.4 1.10 3.16 510 72 4RK+1T 1200 2.05 2.0 1.15 4.72 640
6 months 1400 2.05 1.6 1.10 3.61 560 1400 2.05 2.0 1.15 4.72 670
1760 2.05 1.96 1.10 4.42 620 1760 2.05 2.0 1.15 4.72 730

81 2RK+2T 1200 1.80 1.4 1.10 2.77 500 81 2RK+2T 1200 1.80 2.0 1.15 4.14 590
1400 1.80 1.6 1.10 3.17 540 1400 1.80 2.0 1.15 4.14 620
1760 1.80 1.96 1.10 3.88 590 1760 1.80 2.0 1.15 4.14 670

82 3RK+2T 1200 2.05 1.4 1.10 3.16 570 82 3RK+2T 1200 2.05 2.0 1.15 4.72 700
1400 2.05 1.6 1.10 3.61 620 1400 2.05 2.0 1.15 4.72 730
1760 2.05 1.96 1.10 4.42 680 1760 2.05 2.0 1.15 4.72 790

84 5RK 1200 2.05 1.4 1.10 3.16 450 84 5RK 1200 2.05 2.0 1.15 4.72 580
1400 2.05 1.6 1.10 3.61 500 1400 2.05 2.0 1.15 4.72 610
1760 2.05 1.96 1.10 4.42 560 1760 2.05 2.0 1.15 4.72 670

1) With LV compartment: 2) Depending on Abbre- RK = Ring-main feeder


Other transport the relevant viations: T = Transformer feeder
dimensions and equipment, e.g. K(E) = Cable feeder for radial cable connection
weights motor operating with make-proof earthing switch
mechanism

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Designs

Switchgear with low-voltage compartment, switchgear installation


Option low-voltage
compartment

HA45-2423 eps
_ Overall height

HA45-2424 eps
HA45-2422 eps
– Standard: 400 mm
– Option: 600 or 900 mm
– Option: Cover
_ Installation on the switchgear
– Possible per feeder
– Customer-specific
configuration
– Separate cable duct on the

2300
switchgear next to the

2160
2100

2000
low-voltage compartment

1800
1800

1760
1600
Shipping and transport data

1400
RK LST
If the switchgear is delivered
1200

with low-voltage compartment,


other transport dimensions and
RK LST
weights have to be taken into
account.
RK LST

Switchgear height
1200 mm 1400 mm 1760 mm

Combinations with low-voltage compartment


Dimensions e.g. for scheme 20

Switchgear installation
Wall-standing arrangement
HA45-2432a eps
HA45-2384c eps

Direction of
7 1 Switchgear
pressure relief 7
1
2 Floor opening into cable duct
Overall height 1200 mm 1 3 Expanded metal
3 (not included in the scope
Downwards
700 ´ 700

of supply)
4
Overall height 1400 mm 5 4 Direction of pressure relief
Downwards 2 5 Cable
Option: to the rear 8 5 6 Partition (e.g. of sheet-
6 metal, not included in the
3
Overall height 1760 mm scope of supply)
700

4 5
Downwards 7 Wall distance
Option: to the rear 5 8 Rear cutout in the
700 switchgear (size approx.
350 mm x 615 mm, not
Free-standing arrangement Pressure relief downwards Option: Pressure relief to for scheme 01/ = 1T)
(on request) (all overall heights) the rear, overall height of
switchgear 1400 or 1760 mm
(Switchgear installation only for (only for transformer cable
pressure relief downwards) connection downwards)

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Special Designs

Outdoor enclosures with 8DJ20 switchgear


Application
8DJ20 switchgear in outdoor For 3-panel switchgear For 4-panel switchgear
enclosures is used where the
network structure requires this,

R-HA45-115c eps

R-HA45-117c eps
but without transformers and
low-voltage distribution
boards.

Features
_ Two sizes
– For switchgear with 3 feeders
– For switchgear with 4 feeders
_ Degree of protection IP 44
_ 8DJ20 switchgear installed in
outdoor enclosure
_ Cable compartment parti-
tioned off adjacent feeders
_ With lockable door
_ Complete interlocking
functions
Outdoor enclosure
Outdoor enclosure with 2-wing door
Cable connection with 2-wing door
Overall width 1500 mm
See pages 9 and 16. Overall width 1150 mm

_ Cable entry from below


R-HA45-116d eps

R-HA45-118d eps

_ Floor cover
– Divided and bolted
– Removable for inserting the
cables
_ Cable bracket movable
upwards or to the rear to suit
cable sealing ends
_ Cables fixed by cable clamps
(option) on C-rails of cable
bracket
_ Option:
Cable clamps

Schemes
_ For 3-panel outdoor
enclosure:
– Scheme 10 As above,
– Scheme 32 As above,
however with
however with doors removed
_ For 4-panel outdoor doors removed, some cable
compartment covers removed
enclosure:
– Scheme 70
HA45-2296c eps

HA45-2301c eps

– Scheme 71
– Scheme 81

Scheme Scheme
RK RK T 10 ** RK RK RK RK 70 **
HA45-2300c eps

HA45-2302c eps

Scheme Scheme
RK RK RK 32 ** RK RK RK T 71 **
** Option: Surge arrester
HA45-2304c eps

Only such surge arresters can


be used which are suitable for a
cable compartment cover flush
with the operating front,
e.g. make Tyco Electronics, Scheme
type RDA. T RK RK T 81 **

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Special Designs

Outdoor enclosures with 8DJ20 switchgear

Dimensions
1160 890
HA45-2343e eps

2005
9

6
1
7

1140
10
³ 200
M12

200
2
1110* 150* 150*
4 x Æ14*
1150 ~540
Outdoor enclosure 852
with 2-wing door
for 3-panel switchgear Sectional view of transformer feeder

1510 890

1 Door of outdoor enclosure


HA45-2344e eps

2 Floor fixing 4 x ;14 mm


3 HV HRC fuse assembly
4 Operating mechanism
5 Switchgear vessel
6 Bushing for cable connection
4
7 Cable elbow plug with plug-in contact
5 8 Cable T-plug with bolted contact (M16)
9 Pressure relief device
2005

9 10 Wall distance W 200 mm


6 * Floor fixing dimension
1
8
1140

10
³ 200
200

For position of incoming cables


2
1460* see pages 14 and 15
4 x Æ14* 150* 150*
1500 ~580 For cable connections with
Outdoor enclosure 852 surge arresters see page 16
with 2-wing door
for 4-panel switchgear Sectional view of ring-main feeder

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Standards

Standards, specifications, guidelines


Overview of standards (June 2007)

IEC standard VDE standard EN standard


Switchgear 8DJ20 IEC 60 694 VDE 0670-1000 EN 60 694
IEC 62 271-200 VDE 0671-200 EN 62 271-200
Switching devices Circuit-breaker IEC 62 271-100 VDE 0671-100 EN 62 271-100
Disconnector and IEC 62 271-102 VDE 0671-102 EN 62 271-102
earthing switch
Switch-disconnector IEC 60 265-1 VDE 0670-301 EN 60 265-1
Switch-disconnector / IEC 62 271-105 VDE 0671-105 EN 62 271-105
fuse combination
HV HRC fuses IEC 60 282-1 VDE 0670-4 EN 60 282
Voltage detecting systems IEC 61 243-5 VDE 0682-415 EN 61 243-5
Degree of protection – IEC 60 529 VDE 0470-1 EN 60 529
Insulation – IEC 60 071 VDE 0111 EN 60 071
Instrument transformers Current transformers IEC 60 044-1 VDE 0414-1 EN 60 044-1
Voltage transformers IEC 60 044-2 VDE 0414-2 EN 60 044-2
Combined transformers 1) IEC 60 044-3 VDE 0414-5 EN 60 044-3
Installation – IEC 61 936-1 VDE 0101 –
1) Only for switchgear type 8DH10

Standards Type of service location Internal arc classification Climate and ambient
The 8DJ20 switchgear 8DJ20 switchgear can be (option) conditions
complies with the relevant used as indoor installations in The possibility of arc faults in 8DJ20 switchgear is completely
standards and specifications accordance with IEC 61 936 gas-insulated switchgear type enclosed and insensitive to
applicable at the time of (Power installations exceeding 8DJ20 is improbable and a climatic influences.
type tests. 1 kV AC) and VDE 0101: mere fraction of that typical of _ Climatic tests fulfilled in
In accordance with the _ Outside lockable electrical earlier switchgear types, due accordance with IEC 60 932
harmonization agreement service locations at places to: (report)
reached by the countries of the which are not accessible to _ Use of gas-filled switchgear _ All medium-voltage devices
European Community, their the public. Enclosures of compartments (except for HV HRC fuses)
national specifications switchgear can only be _ Use of suitable switching are installed in a gas-tight,
conform to the IEC standard. removed with tools. devices such as three- welded stainless-steel
_ Inside lockable electrical position switches with make- switchgear vessel which is
Dielectric strength service locations. A lockable proof earthing switch filled with SF6 gas
See also Catalog HA 40.1 electrical service location is a _ Logical mechanical interlocks _ Live parts outside the switch-
“Standards”. place outdoors or indoors that gear vessel are provided with
is reserved exclusively for _ Use of ring-core current trans-
formers (option) single-pole enclosure
Terms housing electrical equipment
and which is kept under lock Optionally, switchgear type _ At no point can creepage
“Make-proof earthing switches” currents flow from high-
are earthing switches with and key. Access is restricted 8DJ20 can be designed with
to authorized personnel and internal arc classification: voltage potentials to earth
short-circuit making capacity
according to IEC 62 271-102/ persons who have been prop- _ Operating mechanism parts
erly instructed in electrical _ Internal arc classification IAC
VDE 0671-102. which are functionally impor-
engineering. Untrained or _ Type of accessibility A tant are made of corrosion-
unskilled persons may only (for authorized personnel proof materials
enter under the supervision of only)
authorized personnel or prop- _ Bearings in operating mech-
_ Accessible sides anisms are designed as dry-
erly instructed persons. – Side F (front) type bearings and do not
– Side L (lateral) require lubrication
– On request: Side R (rear)
_ Suitable instrument trans-
_ Arc test current former designs
up to 21 kA /1 s

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Standards

Classification
Classification of 8DJ20 switchgear according to IEC 62 271-200

Design and construction


Partition class PM (partition of metal)
Loss of service continuity category 1)
Switchgear
– With HV HRC fuses LSC 2A
– Without HV HRC fuses (RK, T, LST) LSC 2B
Accessibility to compartments Access option
(enclosure)
– Busbar compartment – Non-accessible
– Switching-device compartment – Non-accessible
– Low-voltage compartment (option) – Tool-based
– Cable compartment
– Switchgear with HV HRC fuses (T…) – Interlock-controlled
– Switchgear without HV HRC fuses – Interlock-controlled
– Switchgear scheme 01 (1 T) – Tool-based

Internal arc classification (option)


Designation of Rated voltage 7.2 kV to 24 kV
internal arc classification IAC
IAC for
– Wall-standing arrangement (standard) IAC A FL 21 kA, 1 s
Type of accessibility A Switchgear in closed electrical service location,
access “for authorized personnel only“ (acc. to IEC 62 271-200)
–F Front
–L Lateral
Arc test current 2) Up to 21 kA
Test duration 1s

1) The loss of service continuity category 2) 8DJ20 switchgear with pressure


is always referred to the complete absorber:
switchgear, i.e. the panel with the Arc test current up to 16 kA,
lowest category defines the loss of for overall height of switchgear
service continuity category of the 1400 and 1760 mm.
complete switchgear.

Siemens HA 45.31 · 2007


Switchgear Type 8DJ20 up to 24 kV, Gas-Insulated

Notes

If not stated otherwise on


the individual pages of this
catalog, we reserve the right
to include modifications, espe-
cially regarding the stated val-
ues, dimensions and weights.
Drawings are not binding.
All product designations used
are trademarks or product
names of Siemens AG or other
suppliers.
If not stated otherwise, all
dimensions in this catalog are
given in mm.

Responsible for

Technical contents:
Christoph Maul
Siemens AG, Dept. PTD M 2 PPM
Erlangen

General editing:
Gabriele Pollok
Siemens AG, Dept. PTD CC M
Erlangen

Siemens HA 45.31 · 2007


Siemens AG For questions concerning Subject to change without notice
Power Transmission and Distribution Power Transmission and Distribution: Order No.:
Medium Voltage Division You can contact our Customer Support Printed in Germany
Dispo 31606
Postfach 32 40 Center 24 hours a day, 365 days a year.
KG 07.07 0.0 24 En
91050 Erlangen Tel.: +49 180/524 70 00 102618 6101/2831
Germany Fax: +49 180/524 24 71
(Calls charged: e.g.14 ct/min)
www.siemens.com/ E-Mail: support.energy@siemens.com
medium-voltage-switchgear www.siemens.com/energy-support

The information in this document contains general descriptions of the technical options available, which do not always have to be present in individual cases.
The required features should therefore be specified in each individual case at the time of closing the contract.