Inhalt / Contents Dokumenten-Nr. / No.

Vorwort
Preface 3132

Sicherheitshinweise
Note on safety 2126

Technische Daten
Technical data 114062.0T0

Schaltbild
Circuit diagram 95611.00E040A3

Klemmenplan
Terminal diagram 95611.00P040A3

Beschreibung - SLIMLINE CARRIER 4500


Description - SLIMLINE CARRIER 4500 4345

Beschreibung - SLIMLINE DISTRIBUTION 4500


Description - SLIMLINE DISTRIBUTION 4500 4356

Beschreibung - Montageanleitung
Description - Assembly instructions 4389

Baugruppen/Components

Kurzbeschreibung - Batterie
Short description - battery 3256

2/2 A019330206.XLS
Preface

Preface

These operating instructions provide information essential for correct operation of


the unit. To ensure its safe operation, these instructions must be read and under-
stood before the unit is switched on. All the information they contain must be ob-
served!

This avoids:

- danger during operation

- danger to operating personnel

- downtime, and

- increases the reliability and lifespan of the unit.

Keep these instructions in a safe place for future reference.

Service centre

For reasons of industrial safety and operational availability we recommend that


you service and maintain the equipment or systems regularly.

For more detailed information, please call our service centre.

Our help-desk team is also available for technical support 24 hours a day at

+49-2871/93-555.

BENNING Elektrotechnik und Elektronik GmbH & Co. KG


Münsterstraße 135 – 137
46397 Bocholt
Germany
Telefon +49-2871/93-0 - Telefax +49-2871/93-417

Date Name No. 3132 en


Issued: 30.10.97 COBS Page 1/2 pages
Revision 08.09.2011 COBS
Checked 09.09.2011 Obstfelder
C:\qtemp\pdfhandbuch\A0332636.DOC
Preface

BENNING worldwide
Austria Belgium Belarus (Weißrussland)
BENNING GmbH BENNING IOOO BENNING
Elektrotechnik und Elektronik Power Electronics ul. Belorusskaya 51-25
Eduard-Klinger-Str. 9 Z.2 Essenestraat 16 224025, Brest
3423 St. Andrä-Wördern 1740 Ternat
Tel. +43 2242/324 16-0 Tel. +32 2/582 878 5 Tel. +375 162 97 47 82
Fax +43 2242/324 23 Fax +32 2/582 876 9 Fax +375 162 29 33 77
E-Mail: info@benning.at E-Mail: Info@benning.be E-Mail: info@benning.brest.by
Croatia Czech Republic
BENNING Zagreb d.o.o. BENNING CR s.r.o.
Trnjanska 61 Zahradní ul. 894
10000 ZAGREB 29306 Kosmonosy
HRVATSKA
Tel. +385 1-6312280 Tel. +420 326/721 003
Fax +385 1-6312289 Fax +420 326/722 533
E-Mail.: info@benning.hr E-Mail: benning@benning.cz
France Great Britain Hungary
BENNING BENNING BENNING Kft.
Conversion d’énergie Power Electronics (UK) Ltd. Power Elektronics
43, avenue Winston Churchill Oakley House Rákóczi út 145
B.P. 418 Hogwood Lane 2541 Lábatlan
27404 Louviers Cedex Finchampstead
Berkshire RG 40 4 QW

Tel. +33 2/322 523 94 Tel. +44 118/973 150 6 Tel. +36 33/507 600
Fax +33 2/322 508 64 Fax +44 118/973 150 8 Fax +36 33/507 601
E-Mail: info@benning.fr E-Mail: info@benninguk.com E-Mail: benning@vnet.hu
Italy The Netherlands Poland
BENNING BENNING NL BENNING
Conversione di Energia S.r.L. Power Electronics Power Electronics Sp.z.o.o.
Via 2 Giugno 1946, 8/B Peppelkade 42 Korczunkowa 30
40033 Casalecchio di Reno (BO) 3992 AK Houten 05503 Glosków

Tel. +39 051/758 800 Tel. +31 30/634 601 0 Tel. +48 22/757 845 3
Fax +39 051/616 765 5 Fax +31 30/634 602 0 +48 22/757 366 870
E-Mail: info@benningitalia.com E-Mail: info@benning.nl Fax +48 22/757 845 2
E-Mail: biuro@benning.biz
P.R. of China Russia Slovakia
BENNING 000 BENNING BENNING
Power Electronics (Beijing) Co., Ltd. Power Electronics Slovensko, s.r.o.
Tongzhou Industrial Scholkovskoje Chaussee, 5 Kukuričná 17
Development Zone 105122 Moscow 83103 Bratislava
No. 1-B BeiEr Str.
Beijing 1011137
Tel. +86 10/615 685 88 Tel. +7 4 95/967 685 0 Tel. +421 2/444 599 42
Fax +86 10/615 062 00 Fax +7 4 95/967 685 1 Fax +421 2/444 550 05
E-Mail: info@benning.cn E-Mail: benning@benning.ru E-Mail: benning@benning.sk
South East Asia Spain Switzerland
BENNING BENNING BENNING
Power Electronics Pte Ltd Conversión de Energía S.A. Power Electronics GmbH
85, Defu Lane 10 C/Pico de Santa Catalina 2 Industriestrasse 6
# 05-00 Pol.Ind. Los Linares 8305 Dietlikon
Singapore 539218 28970 Humanes, Madrid

Tel. +65 6844/313 3 Tel. +34 91/604 811 0 Tel. +41 44/805 757 5
Fax +65 6844/327 9 Fax +34 91/604 840 2 Fax +41 44/805 758 0
E-Mail: sales@benning.com.sg E-Mail: benning@benning.es E-Mail: info@benning.ch
Sweden Ukraine USA
Benning Sweden AB BENNING Power Electronics Benning Power Electronics, Inc.
Box 990 3 Sim’yi Sosninykh str. 1220 Presidential Drive
Hovslagarev. 3B 03148 Kyiv, RICHARDSON, TEXAS 75081
19129 Sollentuna
Tel. +46 8/623 950 0 Tel. +38 044 501 40 45 Tel. +1 214/553 144 4
Fax +46 8/969 772 Fax +38 044 273 57 49 Fax +1 214/553 135 5
E-Mail: power@benning.se E-Mail: info@benning.ua E-Mail: sales@benning.us

08.09.2011 COBS 2/2 3132 en


Description

Safety Notes

Contents

1 Safety notes.............................................................................. 2

Date Name 2126 en


Issued: 18.01.93 TB-Enck/Bp pag. 1/2 pag.
Revision:
Checked: 27.10.97 Enck
C:\qtemp\pdfhandbuch\A0363661.DOC
Safety notes

Before starting the unit:

Please read the description, paying special attention to the safety


notes.

1 Safety notes
The device is an electrical unit with dangerous voltage and current levels. For this
reason, the following safety instructions must be observed:

1) Installation, operation, servicing and maintenance should be carried out only


in accordance with the instructions given in this document.

2) Ensure that only qualified and authorized personnel have access to the
equipment. No other persons should be able to open the door.

3) Even when the unit is completely switched off, certain interior components
remain lives as long as they are connected with the mains supply or the bat-
tery.

4) Integrated capacitors may still be charged even when the unit is completely volt-
age-free. These must be properly discharged by a qualified person before the con-
nections are touched.

5) When working on the unit, only properly insulated tools should be used.

6) All persons carrying out work on the unit must be acquainted with the first
aid measures to be taken in cases of accidents involving electricity.

7) Always observe the safety regulations of the local power supply company as
well as other safety regulations.

18.01.93 - TB-Enck/Bp 2/2 2126 en


SLIMLINE MODULAR SYSTEM

Order No.: 001-00177612

VP: 1

UP: 1

Editor: loe Discription: Number:

Date: 08.01.2013 Slimline Carrier 4500: 4345

Checked: J.Bu SLIMLINE DISTRIBUTION: 4356

Date: 08.01.2013 Assembly instruction: 4389

Quantity: Part no.: Component: Remark: Type:

1 583212 A1...A3 SLIMLINE CARRIER 4500


1 583207 A4.1 SLIMLINE CONTROL
2 10000404 19 Zoll 6mm Fastening angular
2 506084 19 Zoll Fastening
1 583279 A5 SLIMLINE DISTRIBUTION 4500
1 583277 A1.5 SLIMLINE MCU 4500/13500
1 702070 zu A1.5 Cable connecting
1 10005043 Cable connecting
1 749511 F1 10A
1 749511 F2 10A
1 749642 F3 16A
1 749642 F4 16A
1 749641 F5 32A
1 749641 F6 32A
1 751146 Temperature sensor
1 777812 X3.1 Variovacemodul
1 712741 zu SLIM. CONTROL - X3.1 Cable connecting
1 777812 X3.2 Variovacemodul
1 712742 zu SLIM. MCU - X3.2 Cable connecting

TB / Buchowski Seite1von5 08.01.2013 11:09


SLIMLINE MODULAR SYSTEM

Technical data

Art of grounding: plus grounded X

Float charging: 54,7 V X

Boost charging: 54,7 V X

Direct feeding 48 V

Power limit 100 %

Compensation of temperature:

Reference temperature 20 °C

Lower temperature limit: -20 °C

Upper temperature limit: 50 °C

Temperature correction factor: -4 mV/Z/K

Battery:

Cells number 24

Automatic battery test: not activ

Battery test voltage: 44 V

Break-of voltage: 45,6 V

Battery test duration: 00:45:00 hh:mm:ss

Battery test interval: 00:03:00 dd:mm:yy

Charging automatic: not activ

Recharging criterion: 0 V

Mains failure time: 00:05:00 hh:mm:ss

Main charging time: 04:00:00 hh:mm:ss

TB / Buchowski Seite2von5 08.01.2013 11:09


SLIMLINE MODULAR SYSTEM

Charging current limiting: max.

I-channel inverting not activ

Display indication: load current, bar voltage, bat. temp.

Internal digital inputs Potential free relais

load fuse tripped not urgent inverse K3

battery circuit fault urgent

mains error not urgent inverse K1 60 sec

bus fault

modem fault not urgent

battery test negative urgent

discharging battery

temperature sensor fault not urgent

rectifier XX fault urgent inverse K2 10 sec

urgent error group signal inverse K1/1 10 sec

non-urgent error group signal inverse K2/1 60 sec

mains error inverse K4/1 max X

TB / Buchowski Seite3von5 08.01.2013 11:09


SLIMLINE MODULAR SYSTEM

GSR Relais

busbar voltage<XX,2V

upper limit 100V urgent inverse K3/1

lower limit 43,2V

busbar voltage<XX,0V

upper limit 100V not urgent

lower limit 48,0V

battery temperature>XX°C

upper limit 35°C not urgent

lower limit -100°C

temperatur alarm room

upper limit 35°C not urgent

lower limit -100°C

upper limit

lower limit

upper limit

lower limit

TB / Buchowski Seite4von5 08.01.2013 11:09


SLIMLINE MODULAR SYSTEM

external digital inputs Potential free relais

ext. Signal 01 not urgent

ext. Signal 02 not urgent

ext. Signal 03 not urgent

ext. Signal 04 not urgent

ext. Signal 05 not urgent

ext. Signal 06 not urgent

ext. Signal 07 not urgent

ext. Signal 08 not urgent

TB / Buchowski Seite5von5 08.01.2013 11:09


Operating instructions

SLIMLINE CARRIER 4500

Date Designation No. 4345 en


Issued: 13.02.06 TB – J.Bu p. 1/27p.
Revision: 10.12.09 J.Bu/Obs Kocarek
Checked: 10.12.09 Buchowski
C:\qtemp\pdfhandbuch\A4120657.DOC
SLIMLINE MODULAR SYSTEM

Table of contents
1 Safety notes................................................................................................5

2 General.......................................................................................................6

3 The components.........................................................................................7

3.1 SLIMLINE CARRIER 4500 .....................................................................8

3.2 SLIMLINE RECTIFIER 1500 ................................................................10

3.3 SLIMLINE CONTROL...........................................................................14

4 Technical data ..........................................................................................16

5 Assembly and commissioning .................................................................19

5.1 Transport ..................................................................................................19

5.2 Installation ...............................................................................................19

5.3 Commissioning ........................................................................................21

6 Maintenance / repair ................................................................................22

7 Material and spare parts...........................................................................23

8 Description of function ............................................................................24

9 Block diagram..........................................................................................25

10.12.098 J.Bu/Obs 2/27 4345 en


SLIMLINE MODULAR SYSTEM

List of figures:
Figure 1: Front view of the power supply system.....................................................7

Figure 2: Dimension diagram of the SLIMLINE CARRIER (completely equipped)8

Figure 3: Rear view of the SLIMLINE CARRIER...................................................9

Figure 4: SLIMLINE RECTIFIER 1500 ................................................................10

Figure 5: Dimension diagram SLIMLINE RECTIFIER 1500................................11

Figure 6: Front view of the SLIMLINE RECTIFIER 1500....................................12

Figure 7: Rear view of the SLIMLINE RECTIFIER 1500.....................................13

Figure 8: Connector layout scheme.........................................................................14

Figure 9 Screw .......................................................................................................19

10.12.098 J.Bu/Obs 3/27 4345 en


SLIMLINE MODULAR SYSTEM

These operating instructions contain important instructions for installa-


tion, operation and maintenance of the SLIMLINE Carrier 4500 and its
components. The instructions must be retained and observed at all times!
Explanation of the symbols used in these operating instructions and on the components of
the power supply system:

Indicates safety instructions which must be followed to avoid dan-


ger to persons!
Indicates instructions which must be followed to avoid material
damage!
All specifications in these operating instructions must be observed
at all times!
Ready for operation/Operation

fault

10.12.098 J.Bu/Obs 4/27 4345 en


SLIMLINE MODULAR SYSTEM

1 Safety notes
The SLIMLINE CARRIER 4500 and its SLIMLINE RECTIFIER
are electronic appliances that carry voltages and currents danger-
ous to man.

For this reason, the following instructions must be followed at all times:

1. Installation, operation, maintenance and repair of the SLIMLINE CARRIER


4500 should be carried out in strict accordance with the instructions in this do-
cument.

2. Ensure that only fully trained and qualified personnel have access to the sys-
tem. Only qualified and authorised personnel should be able to open the units.

3. Even when the SLIMLINE CARRIER 4500 is completely switched off, some
of its interior components remain live as long as they are connected to the
mains supply or the battery.

4. Installed capacitors may be charged even when the system is disconnected.


These must be correctly discharged by a qualified electrician before the con-
nections or terminals are touched.

5. When working at the unit, use properly insulated tools at all times which are
suitable for the levels of voltage concerned.

6. All persons working with the unit must be familiar with the first-aid measures
to be adopted in cases of accidents involving electricity.

7. The regulations of the local power-supply companies and all other applicable
safety regulations must be observed at all times.

10.12.098 J.Bu/Obs 5/27 4345 en


SLIMLINE MODULAR SYSTEM

2 General
The SLIMLINE CARRIER 4500 and its SLIMLINE RECTIFIER are compact 48 V power
supply systems for applications in the field of telecommunication.

This system features small size and a large permitted temperature range.

The output power of the power supply system can be extended in steps of 1.500W by con-
necting up to 3 SLIMLINE RECTIFIERS 1500 for each SLIMLINE CARRIER 4500 and
the parallel connection of several SLIMLINE CARRIERS 4500.
Here, 3 SLIMLINE CARRIERS 4500 are controlled by one SLIMLINE CONTROL.

The functionality of the system is rounded off by the optional inclusion of an MCU remote
monitoring system which makes possible remote monitoring of the power supply system
via a modem or TCP/IP adapter.

10.12.098 J.Bu/Obs 6/27 4345 en


SLIMLINE MODULAR SYSTEM

3 The components
The layout of the individual components of the power supply system is fixed because of
the compact modular design.
Depending on requirements different configurations are possible.

The individual components are:

• 1 – 3 SLIMLINE CARRIER with integrated mains filter; can be equipped with:


1 – 3 SLIMLINE RECTIFIER 1500 ( HOT-PLUG )
• 1 SLIMLINE CONTROL ( HOT-PLUG )

Figure 1: Front view of the power supply system

10.12.098 J.Bu/Obs 7/27 4345 en


SLIMLINE MODULAR SYSTEM

3.1 SLIMLINE CARRIER 4500


The SLIMLINE CARRIER 4500 is intended for fitting into the following racking systems:
- 19" racking system
- ETSI racking system

The SLIMLINE CARRIER 4500 is prepared for the installation of the SLIMLINE REC-
TIFIER and the SLIMLINE CONTROL.

Figure 2: Dimension diagram of the SLIMLINE CARRIER (completely equipped)

10.12.098 J.Bu/Obs 8/27 4345 en


SLIMLINE MODULAR SYSTEM

PE, L3, N3, L2, N2, L1, N1 1

2 3 4

Figure 3: Rear view of the SLIMLINE CARRIER

1 Mains terminals (PE, L3, N3, L2, N2, L1, N1 ) for connecting the supplying mains

2 + pole; copper bar for connecting battery and load

3 − pole; copper bar for connecting battery and load

4 Earth stud

10.12.098 J.Bu/Obs 9/27 4345 en


SLIMLINE MODULAR SYSTEM

3.2 SLIMLINE RECTIFIER 1500


The 48V-SLIMLINE RECTIFIERS 1500 feed the connected DC loads and charge/boost
the connected lead accumulator batteries at the same time. The slide-in units are hot-plug
units, that means all electrical connections are made and disconnected automatically when
plugging and unplugging the SLIMLINE RECTIFIER 1500.

There are no components in the SLIMLINE RECTIFIER 1500 which need to be accessible
under normal operating conditions.

Figure 4: SLIMLINE RECTIFIER 1500

10.12.098 J.Bu/Obs 10/27 4345 en


SLIMLINE MODULAR SYSTEM

Figure 5: Dimension diagram SLIMLINE RECTIFIER 1500

10.12.098 J.Bu/Obs 11/27 4345 en


SLIMLINE MODULAR SYSTEM

All connectors, control elements and indicator elements of the SLIMLINE RECTIFIER
1500 are located on the front or rear side.

1 2

Figure 6: Front view of the SLIMLINE RECTIFIER 1500

1 LED "SLIMLINE RECTIFIER 1500 ready for operation/in operation".


( If it flashes, data are transmitted between the SLIMLINE RECTIFIER 1500 and
the SLIMLINE CONTROL )

2 LED "SLIMLINE RECTIFIER 1500 fault"

10.12.098 J.Bu/Obs 12/27 4345 en


SLIMLINE MODULAR SYSTEM

Figure 7: Rear view of the SLIMLINE RECTIFIER 1500

1 Connector (AC output, control signals, DC output )

10.12.098 J.Bu/Obs 13/27 4345 en


SLIMLINE MODULAR SYSTEM

3.3 SLIMLINE CONTROL


The SLIMLINE CONTROL controls the SLIMLINE RECTIFIER and the optionally con-
nected distribution. The SLIMLINE CONTROL organises the data flow between the
SLIMLINE RECTIFIER and the optionally insertable MCU.

Figure 8: Connector layout scheme

The SLIMLINE CONTROL can be freely programmed via the service software. The stan-
dard programming of the relays is as follows.

1 Connector X33

PIN assignments:

X33:1 - battery test failure


X33:2 potential free message 1 - overvoltage protection released
X33:3 delay 10 sec. - SLIMLINE RECTIFIER 1500 fault
- battery circuit fault

X33:4 - mains fault


X33:5 potential free message 2 - temperature too high
X33:6 delay 1 min. - temperature sensor interrupted
- fan fault
- load fuse tripped
- UDC < 48 V

10.12.098 J.Bu/Obs 14/27 4345 en


SLIMLINE MODULAR SYSTEM

2 Connector X34

PIN assignments:

X34:1 Battery temperature


X34:2 sensor

3 RJ-45 plug; data connector for the connection to an external remote monitoring system
MCU or an additional SLIMLINE CONTROL

10.12.098 J.Bu/Obs 15/27 4345 en


SLIMLINE MODULAR SYSTEM

4 Technical data
Dimensions (H x W x D): (44.45 x 483 x 340 ) mm / Carrier

Weight (completely equipped): 7.8 kg / Carrier

Weight SLIMLINE RECTIFIER 1.7kg

Altitude: max. 2000 m above sea level

Protective class: IP20

Permitted ambient temperature: -33°C to +55°C

Humidity class: F

Protective class: I (acc. to EN60950)

Input voltage: 173V-415V (147V... 457V) / (3~);


100V-240V (85V... 264V) / (1~)

Input voltage 100V-240V (85V... 264V)

Input current per 7.3A


SLIMLINE RECTIFIER 1500:

Permitted frequency range: 47Hz ... 63Hz

Output voltages:

Boost: 2.4V/Z (57.6V)


Float charge: 2.23V/Z (53.5V)
Direct feeding 2.0V/Z (48.0V)
Battery circuit test: 1.8V/Z (43.2V)

Voltage tolerance:

Static: ±1%
Dynamic (10-90-10)%; (dt<200µs): ±5%
Settling time: <5 ms

Output current: 28.0A-84.0A (32.6A-97.8A) (200V... 264V)


25.2A-75.6A (29.3A-87.9A) (185V... 200V)
20.6A-61.8A (24.0A-72.0A) (150V... 185V)
14.0A-42.0A (16.3A-48.9A) (105V... 150V)
11.2A-33.6A (12.5A-37.5A) (85V... 105V)

10.12.098 J.Bu/Obs 16/27 4345 en


SLIMLINE MODULAR SYSTEM

Output power: max. 4500W (200V... 264V)


max. 4050W (185V... 200V)
max. 3300W (150V... 185V)
max. 2250W (105V... 150V)
max. 1800W (85V... 105V)

Efficiency: 90% (240V)


87% (100V)

Characteristics:

Charging characteristic: IPU

Temperature-controlled characteristic: -4 m V/°C/cell (option for float charge)

Operation as mains unit: IU

Power factor: >0.95


Interference voltage: 2mV
Radio interference degree: Class B (acc. to EN55022)

Conductor cross-sections:

Mains terminals:
Capacity of the terminals: 0.2mm²-2.5mm²/AWG24-AWG12

Battery connection; load connection:


Connections 1x CARRIER: Copper bars / 5mm hole
Connections 2-3x CARRIER: Copper bars / 8mm bolt

Signal connecting terminals:


Capacity of the terminals: 0.2mm²-1.5mm²/AWG26-AWG16

Protections:

Mains input ( operator side ): Max. 16A s.b.

Potential-free signals: 2 relays; each with 1 x changeover contact


Contact rating: max. 0.5 A/60 V DC

10.12.098 J.Bu/Obs 17/27 4345 en


SLIMLINE MODULAR SYSTEM

Standards and regulations:


Safety:

EN60950 Safety of information-technology equipment


( Exception: Touch guard and inflammability; the SLIMLINE CARRIER
4500 has no fire enclosure )

Electromagnetic compatibility / ECM:

EN61000-6-3 Emitted interference - Residential, commercial and light industry


EN61000-6-2 Interference immunity - Industrial environment
EN55022 Radio interference – Limit values and measuring methods
EN61000-3-2 Limit values – Limit values for harmonic currents
( ≤ 16A per conductor)
EN61000-3-3 Limit values – Limitation of voltage level changes, voltage fluctuations
and flicker ( ≤ 16A per conductor)
EN300386 Telecommunication network equipment – Electromagnetic compatibility
requirements

Environment:

ETS300019-1-1 class 1.3 Storage applicable with respect to


ETS300019-1-2 class 2.3 Transport temperature and humidity
ETS300019-1-4 class 4.1 Operation

10.12.098 J.Bu/Obs 18/27 4345 en


SLIMLINE MODULAR SYSTEM

5 Assembly and commissioning


After assembly and commissioning of the power supply system, all components are unre-
servedly ready for operation. No additional settings and readjustments are necessary during
operation under all permitted operating conditions.

Attention!
The safety instructions must be observed at all times during as-
sembly, installation and commissioning!

When selecting the site, the environmental conditions specified in the section "Technical
data" must be complied with. Attention must be paid that the power supply system is not
exposed to aggressive substances and the passage of cooling air is not hampered.

All components have been set in the factory to suit the operating conditions specified by
the customer, or to default values. For normal operation it is not necessary to change the
settings.

5.1 Transport
For transport, the SLIMLINE system is provided with exactly fitting packaging.

The SLIMLINE RECTIFIERS are not transported within the SLIMLINE CARRIER. The
SLIMLINE RECTIFIERS are provided with a separate packaging.

5.2 Installation
The SLIMLINE CARRIER is provided with an overvoltage protection. The marked screw
must be removed when performing an insulation resistance measurement. After having
measured the insulation resistance, the screw must be remounted.

Figure 9 Screw

10.12.098 J.Bu/Obs 19/27 4345 en


SLIMLINE MODULAR SYSTEM

Before plugging the individual components into the SLIMLINE CARRIER and installing
the latter in the 19" racking system cabinet, attention must be paid to the following points:

Attention!
The entire power supply system must be disconnected from the
supply voltages. Neither the mains (AC) nor the batteries (DC)
may be connected and must be disconnected if they were con-
nected.

Plug the components of the power supply system successively into the corresponding loca-
tions in the SLIMLINE CARRIER.
All electrical connections are established when the components are firmly pushed into the
SLIMLINE CARRIER. The completely equipped SLIMLINE CARRIER must be inserted
firmly into the 19" racking system cabinet and fixed with screws.

Attention!
The frontplate must be bolted on after equipping the SLIMLINE
CARRIER 4500 with the SLIMLINE RECTIFIER 1500 and the
SLIMLINE CONTROL.

Attention!
The power-supply circuits (mains input cable, battery leads) must
be provided with a disconnecting device. The disconnecting de-
vices must be readily accessible in the vicinity of the racking sys-
tem.

If an external battery is connected, then the instructions concern-


ing the installation and maintenance given by the manufacturer of
the battery must be observed.

As protection against electric shock and lightning, etc., a potential equalisation line must
be connected, if the SLIMLINE CARRIER is not firmly fixed in a reliably earthed cabinet.
This connection must be made on the rear of the SLIMLINE CARRIER
at the earth stud (M6).

For grounding the plus terminal of the supply busbar the ground stud has to be connected
with the + terminal.

The mains terminals are located on the mains filter at the rear of the SLIMLINE CAR-
RIER. The mains input cable must be fuse protected in the user supply system.

Battery and loads are connected via the copper bars on the back of the SLIMLINE CAR-
RIER.

10.12.098 J.Bu/Obs 20/27 4345 en


SLIMLINE MODULAR SYSTEM

Attention!
Observe correct polarity! The battery connections must be short
circuit proof!

Provide adequate conductor cross section area to avoid excessive voltage drop on the bat-
tery input line!

The terminals for the alarm, measuring and signal lines have a maximum capacity
of 1.5 mm²/AWG16.

Attention!
The potential-free contacts have a current carrying capacity
of 0.5 A / 60 V DC.
Only a special type of temperature sensor may be fitted
(2kΩ/25C° KTY81-210). This temperature sensor is available rea-
dy for use with various line lengths.

5.3 Commissioning
Attention!
Commissioning may be carried out only by properly instructed
qualified personnel!

Attention!
Before connecting the AC and DC supplies, check the following
points:
• Have all components of the power supply system been ad-
justed, mounted and connected according to the specifica-
tions?
• Is the mains voltage within the tolerance range?
(voltage, frequency) See the Section "Technical data"
• Is the connected battery a 48 V lead accumulator battery?

Commissioning itself is carried out by:

1) Connecting the mains


2) Connecting the battery

After a few seconds, the system start-up is complete and the LED "SLIMLINE CARRIER
1500 ready for operation/operating" lights up.

10.12.098 J.Bu/Obs 21/27 4345 en


SLIMLINE MODULAR SYSTEM

6 Maintenance / repair
All the components of the power supply system have been developed for continuous opera-
tion and are according the maintenance clues to treat. To ensure correct functioning, it is
recommended that the flow of cooling air is checked periodically and dust is removed from
the units if necessary.

Attention!
If servicing is carried out, the components may be exchanged only
by instructed and qualified personnel!

The SLIMLINE CARRIERS 1500 may be removed and inserted during operation (hot-
plug). However, this must be done steadily to avoid unnecessary contact burning.
If there is only one SLIMLINE CARRIER 1500 in the power supply system and if no bat-
tery is connected, the SLIMLINE CARRIER 1500 may only be pulled after the load has
been switched off.

10.12.098 J.Bu/Obs 22/27 4345 en


SLIMLINE MODULAR SYSTEM

7 Material and spare parts


If it is intended to extend the power supply system or if it is necessary to replace defective
components, the individual components can be ordered, stating the number of parts re-
quired and their part numbers.

BENNING Designation Remark


part no.
583212 SLIMLINE CARRIER 4500 The mains filter is inte-
grated
120358 SLIMLINE RECTIFIER 1500 48V/30A
583207 SLIMLINE CONTROL
506086 Frontplate
506084 Mounting flanges 2HE For the mounting of 2
CARRIERS to one another
506085 Mounting flanges 3HE For the mounting of 3
CARRIERS to one another
506081 Mounting angle 1HE For the mounting of the po-
wer supply system in a 19“
or ETSI cabinet
506083 Mounting angle 2HE For the mounting of the po-
wer supply system in a 19“
or ETSI cabinet
506093 Mounting angle 3HE For the mounting of the po-
wer supply system in a 19“
or ETSI cabinet
751276 Temperature sensor 1.6m
751146 Temperature sensor 2.5m
751308 Temperature sensor 5m
751202 Temperature sensor 10m
734840 Data cable MCU-PC 3m

10.12.098 J.Bu/Obs 23/27 4345 en


SLIMLINE MODULAR SYSTEM

8 Description of function
The power supply system feeds the connected DC loads and at the same time, if present,
the 48 V lead accumulator battery circuits. Up to 3 SLIMLINE RECTIFIERS 1500 for
each SLIMLINE CARRIER 4500 and max. 3 SLIMLINE CARRIER 4500 are connected
in parallel within a system.

The connected AC voltage is applied via a mains filter to the SLIMLINE RECTIFIER
1500 inputs. The mains filter is provided chiefly for suppressing interference voltages pro-
duced inside the power supply system, which would otherwise be transmitted out into the
connected mains system. Various control loops in the SLIMLINE RECTIFIER 1500 keep
the output voltage constant and ensure that the current drain from the mains is sinusoidal.

The SLIMLINE CONTROL controls the SLIMLINE RECTIFIER and the optionally con-
nected distribution. The SLIMLINE CONTROL organises the data traffic between the
SLIMLINE RECTIFIER and the optionally insertable MCU. The potential-free error mes-
sages "Urgent Fault" and "Non-urgent fault" are issued by the SLIMLINE CONTROL
with a time delay.

The operating state "Ready for operation" or "Fault" of the SLIMLINE RECTIFIERS 1500
is signalled by two LEDs on the front panel.

If the minimum load is not at least 5% of the rated load, a fault is indicated.

In the absence of external intervention the system is normally in the "float charging" opera-
tion mode.
The value of the float charge voltage is adjusted according to the actual temperature
(-4 mV/°C/cell) when a battery temperature sensor is connected.

10.12.098 J.Bu/Obs 24/27 4345 en


10.12.098 J.Bu/Obs

9
Block diagram
Optional Optional

Mains
Rack Rack Signal fault
bot- top cable dist-
tom ribution
25/27

SLIMLINE CONTROL

X33
urgent
fault

SLIMLINE MODULAR SYSTEM


non-urgent
fault

X34
Batt.temp.+

Batt.temp.-

Control LVD (Distribution)


Control NPLD (Distribution)
Fault batt.circuit (Distribution)
Fault conn. circuit (Distribution)
Batt. current measuring (Distribu-
tion)
Rack I

Optional
4345 en

SLIMLINE DISTRIBUTION
10.12.098 J.Bu/Obs

Optional Optional

X28

Mains
Rack Rack Signal fault
bot- top cable dist-
tom ribution
26/27

SLIMLINE MODULAR SYSTEM


Optional
Rack II
4345 en
10.12.098 J.Bu/Obs

Optional

X28

Mains
Rack Rack Signal fault
bot- top cable dist-
tom ribution
27/27

SLIMLINE MODULAR SYSTEM


Optional
Rack III
4345 en
Operating instructions

SLIMLINE DISTRIBUTION 4500

Date Designation No 4356 en


Issued: 28.02.06 TB – J.Bu p. 1/18 p.
Revision: 18.05.07 J.Bu/Wegm/Obs Kocarek
Checked: 03.08.07 Buchowski
C:\qtemp\pdfhandbuch\A4120563.DOC
SLIMLINE MODULAR SYSTEM

Table of contents
1 Safety notes................................................................................................4

2 General.......................................................................................................5

3 Set-up .........................................................................................................6

4 Fuse monitoring .........................................................................................7

5 SLIMLINE MCU.....................................................................................10

6 Assembly and commissioning .................................................................14

6.1 System connection ...................................................................................14

6.2 Commissioning ........................................................................................15

7 Technical data (general) ..........................................................................16

8 Construction and design data...................................................................17

9 Block diagram..........................................................................................18

18.05.07 J.Bu/Wegm/Obs 2/18 4356 en


SLIMLINE MODULAR SYSTEM

This operating instructions contain important information for the installation, opera-
tion and maintenance of the SLIMLINE DISTRIBUTION 4500. The instructions
must be retained and observed at all times!
Explanation of the symbols used in these operating instructions and on the components of
the SLIMLINE DISTRIBUTION 4500:

Indicates safety instructions which must be followed to avoid dan-


ger to persons!
Indicates instructions which must be followed to avoid material
damage!
All specifications in these operating instructions must be observed
at all times!

18.05.07 J.Bu/Wegm/Obs 3/18 4356 en


SLIMLINE MODULAR SYSTEM

1 Safety notes
The SLIMLINE DISTRIBUTION 4500 is a piece of electronic
equipment carrying voltages and currents that are dangerous to
human beings.

For this reason, the following instructions must be followed at all times!

1. Installation, operation, maintenance and repair of the SLIMLINE DISTRIBU-


TION 4500 should be carried out in strict accordance with the instructions in
this document.

2. Ensure that only fully trained and qualified personnel have access to the sys-
tem. Only qualified and authorised personnel should be able to open the units.

3. Even when the SLIMLINE MODULAR SYSTEM is completely switched off,


some of its interior components remain live as long as they are connected to the
mains supply or the battery.

4. Installed capacitors may be charged even when the system is disconnected.


These must be correctly discharged by a qualified electrician before the con-
nections or terminals are touched.

5. When working at the unit, use properly insulated tools at all times which are
suitable for the levels of voltage concerned.

6. All persons working with the unit must be familiar with the first-aid measures
to be adopted in cases of accidents involving electricity.

7. The regulations of the local power-supply companies and all other applicable
safety regulations must be observed at all times.

18.05.07 J.Bu/Wegm/Obs 4/18 4356 en


SLIMLINE MODULAR SYSTEM

2 General
The SLIMLINE DISTRIBUTION 4500 is a distribution unit for applications within the te-
lecommunications area.

The SLIMLINE DISTRIBUTION 4500 - in combination with a SLIMLINE CARRIER -


becomes a SLIMLINE MODULAR SYSTEM.

The functionality of the system is rounded off by the optional inclusion of a SLIMLINE
MCU remote monitoring system which makes possible remote monitoring of the power
supply system via a modem or TCP/IP adapter.

This system features small size and a large permitted temperature range.

18.05.07 J.Bu/Wegm/Obs 5/18 4356 en


SLIMLINE MODULAR SYSTEM

3 Set-up
The SLIMLINE DISTRIBUTION 4500 comprises 2 battery outputs, each with a 100A bat-
tery m.c.b., an exhaustive discharge relay for the protection of the battery as well as 6 pos-
sible load m.c.b.. The load m.c.b. can be freely selected from 2A - 60A.
The load m.c.b. can be distributed across not more than one NPLD bar.
The control of the exhaustive discharge relay and the load relay is effected via the SLIM-
LINE CONTROL which is fitted in the SLIMLINE CARRIER.
The load and battery circuits are connected to the SLIMLINE DISTRIBUTION 4500. All
circuits are fuse protected and monitored individually. A display for indicating the bar vol-
tage, load current and battery temperature/battery current is incorporated.
The SLIMLINE DISTRIBUTION 4500 can be optionally fitted with a SLIMLINE MCU.

The distribution drawer unit contains:

• the printed circuit board with the exhaustive discharge relay and the load relay, the load
fuse monitoring, the cable connections to the load and battery fuses as well as the con-
nectors for the battery and loads.

• the battery fuses A and B

• the optionally selectable load m.c.b. F1-F6

• a display for indicating the bar voltage, load current and battery temperature/battery
current

• optional SLIMLINE MCU

18.05.07 J.Bu/Wegm/Obs 6/18 4356 en


SLIMLINE MODULAR SYSTEM

4 Fuse monitoring
In the event of a fuse failing, a potential-free message is effected via the SLIMLINE
CONTROL in the SLIMLINE CARRIER.

The load remains connected to the negative circuit with a resistance of approx. 20 kohm.
For an alarm the load must be connected and show an internal resistance of <100 kohm.

4 1 2 3

Figure 1: Front view of the SLIMLINE DISTRIBUTION 4500

1 Display for indicating the bar voltage, load current and battery temperature/battery cur-
rent

2 Battery outputs A, B with 100A m.c.b. each

3 Load m.c.b. F1-F6

4 Optional SLIMLINE MCU

18.05.07 J.Bu/Wegm/Obs 7/18 4356 en


SLIMLINE MODULAR SYSTEM

1 2 3 4 5

Figure 2: Rear view of the SLIMLINE DISTRIBUTION 4500

1 Connector for load fuses F6, F5, F4

2 + terminal; copper bar for connecting the SLIMLINE CARRIER

3 Connector for load fuses F3, F2, F1

4 - terminal; copper bar for connecting the SLIMLINE CARRIER

5 Connector for battery fuses B, A

18.05.07 J.Bu/Wegm/Obs 8/18 4356 en


SLIMLINE MODULAR SYSTEM

Figure 3: Dimension diagram of the SLIMLINE DISTRIBUTION 4500

18.05.07 J.Bu/Wegm/Obs 9/18 4356 en


SLIMLINE MODULAR SYSTEM

5 SLIMLINE MCU

1 3 4 5 6

Figure 4: SLIMLINE MCU

1 X131 PS/2 connector for connecting a modem, a TCP/IP adapter or a service PC.
(Serial interface RS232)

2 X2 RJ-45 plug; data connector for connection to a SLIMLINE CONTROL

3 Connector X130 potential-free relay

K3

K2

K1

18.05.07 J.Bu/Wegm/Obs 10/18 4356 en


SLIMLINE MODULAR SYSTEM

4 Connector X34

PIN assignment:

X34:1 Battery temperature


X34:2 sensor 2 kohm 25°C

5 Connector X100 programmable external digital inputs

6 Connector X3 supply modem 12V/350mA

PIN assignment:

X3:1 +12V
X3:2 GND

18.05.07 J.Bu/Wegm/Obs 11/18 4356 en


SLIMLINE MODULAR SYSTEM

Standard configuration of the SLIMLINE MCU

Float charging 53.5V


Boost 57.6V
Direct feeding 48V
Power limitation 100%

Reference temperature 20°C


Temp. com-

Bottom temperature limit -20°C


pensation

Upper temperature limit 50°C


Temperature correction factor -4mV

Number of cells 24
Automatic battery test Not active
Battery test voltage 44.0V
Abort voltage 45.6V
Battery

Duration of the battery test 00:45:00 hh:mm:SS


Battery test interval 00:03:00 dd:mm:yy

Automatic charging Not active


Recharge criterion 0.0 V/cell
Automatic
charging

Mains failure time 00:05:00 hh:mm:SS


Main charging time 04:00:00 hh:mm:SS

Charging current limitation max.


I-channel, inverted Not active
Indication on the display Bar voltage., load current
batt.temp.
Low bar voltage < 48.0V
Battery temperature too high > 35°C
Room temperature too high > 35°C
Exhaustive discharge relay drop < 43.2V

Delay times "urgent fault" 10 sec.


"non-urgent fault" 60 sec.
"common fault" 0 sec.

18.05.07 J.Bu/Wegm/Obs 12/18 4356 en


SLIMLINE MODULAR SYSTEM

Mains failure X130: 1,2,3


Potential-free signal-
Unit fault X130: 4,5,6
Load fuse blown X130: 7,8,9
Urgent fault SLIMLINE CONTROL X33:
ling relay

1,2,3
Non-urgent fault SLIMLINE CONTROL X33:
4,5,6

18.05.07 J.Bu/Wegm/Obs 13/18 4356 en


SLIMLINE MODULAR SYSTEM

6 Assembly and commissioning


After assembly and commissioning of the SLIMLINE DISTRIBUTION 4500, all
components are unreservedly ready for operation.

Attention!
The safety instructions must be observed at all times during
assembly, installation and commissioning!

When selecting the site, the environmental conditions specified in the section "Techni-
cal data" must be complied with. Attention must be paid that the SLIMLINE DISTRI-
BUTION 4500 is not exposed to aggressive substances and the passage of cooling air
is not hampered.

All components have been set in the factory to suit the operating conditions specified
by the customer, or to default values. For normal operation it is not necessary to
change the settings.

6.1 System connection


Attention!
The power-supply circuits (battery leads) must be provided with a
disconnecting device. The disconnecting devices must be arranged
easily accessible in the proximity of the cabinet system.

Due to the single-pole fused output circuit the system is to be used


exclusively in a TN-net or TT-net, in which the plus pole is
grounded.

If an external battery is connected, then the instructions concern-


ing the installation and maintenance given by the manufacturer of
the battery must be observed.

In order to protect against body contacts, strikes of lightning etc. the SLIMLINE DIS-
TRIBUTION 4500 must be permanently connected to a SLIMLINE CARRIER.

Battery and loads are connected via the terminals on the rear of the SLIMLINE DIS-
TRIBUTION.

Attention!
Observe correct polarity! The battery connections must be short
circuit proof!

Provide adequate conductor cross section area to avoid excessive voltage drop on the bat-
tery input line!

18.05.07 J.Bu/Wegm/Obs 14/18 4356 en


SLIMLINE MODULAR SYSTEM

6.2 Commissioning
Attention!
Commissioning may be carried out only by properly instructed
qualified personnel!

Attention!
Before connecting the DC supplies, check the following points:
• Have all components of the SLIMLINE DISTRIBUTION
4500 been adjusted, mounted and connected according to the
specifications?
• Is the connected battery a 48 V lead accumulator battery?

18.05.07 J.Bu/Wegm/Obs 15/18 4356 en


SLIMLINE MODULAR SYSTEM

7 Technical data (general)


DC input: 40 – 60 V DC

I Input: SLIMLINE RECTIFIER max. 33A each


in total max. 100A

Input ripple: 10% SS max. permissible

Load fuse: 6 x m.c.b. 2A-60A optional equipment

Battery Imax: 84A

Load Imax: 84A

NPLD Imax: 84A

Ambient temperature: -33 °C to + 55 °C

Altitude: max. 2000 m above sea level

Protective class: IP 20 DIN 40 050


Enclosure against mechanical and electrical hazards, no fire
protection enclosure, no contact protection according to
EN 60 950

Environment:

ETS300019-1-1 class 1.3 Storage applicable with respect to


ETS300019-1-2 class 2.3 Transport temperature and humidity
ETS300019-1-4 class 4.1 Operation

18.05.07 J.Bu/Wegm/Obs 16/18 4356 en


SLIMLINE MODULAR SYSTEM

8 Construction and design data


Dimensions (H X W X D): 44x 482.6 x 320.5 mm

Weight: max. 5 kg

Load connection: X4-X9 (plug-in terminal 16 mm²)


PC16/2-G1-10.16 (Phönix)

Battery connection: X30-X31(plug-in terminal 16 mm²)


PC16/2-G1-10.16 (Phönix)

Direct current infeed: + terminal; - terminal on copper bars, thread M5

18.05.07 J.Bu/Wegm/Obs 17/18 4356 en


18.05.07 J.Bu/Wegm/Obs

9
Block diagram
SLIMLINE CARRIER SLIMLINE CARRIER

* Optional
Signal
bridge for
cable
earthing the +
terminal

Optional

Fault message
18/18

Fault message

Fault message

SLIMLINE MODULAR SYSTEM


Temp + Load fuse
Batt. fuse
Temp - monitoring monitoring
24VDC

(ext. alarm 1)
(ext. alarm 2)
(ext. alarm 3)
(ext. alarm 4)
(ext. alarm 5)
(ext. alarm 6)

(ext. alarm 7)
(ext. alarm 8)
to

Battery A Battery B Load


4356 en
Assembly instructions

Assembly instructions for


SLIMLINE CARRIER and
SLIMLINE DISTRIBUTION

Date Designation 4389 en


Issued 18.07.06 TB-Fr. Page 1/9 pages
Revision 11.08.06 TB-Fr/Obs Kocarek
Checked 28.08.06 Frank
C:\qtemp\pdfhandbuch\A4341826.DOC
Assembly instructions SLIMLINE

Table of contents
1 Safety notes and markings...................................................................................3

2 General.................................................................................................................4

3 Installation requirements ......................................................................................4

4 Connection and commissioning ...........................................................................9

11.08.06 – TB-Fr/Obs 2/9 4389 en


Assembly instructions SLIMLINE

Before starting the system up:


Please read the corresponding instructions, paying special attention
to the safety notes.

1 Safety notes and markings


International electrical, display and operating symbols are marked on the unit.
They have the following meanings:

Caution! See documentation!

Caution! Dangerous electrical voltage!

Alternating current

Direct current

Earth

The unit is a piece of electrical equipment carrying voltages and currents that
are dangerous to human beings. For this reason, the following instructions must
be followed at all times:

1. Installation, operation, maintenance, and repair must always be carried


out in accordance with the accompanying documents.
2. Ensure that only fully trained and qualified personnel have access to the
system / unit. Only qualified and authorised personnel is authorised to
open the cabinet/the unit.
3. Even when the unit is completely switched off, some of its interior
components remain live as long as they are connected to the power sup-
ply or the battery.
4. Installed capacitors may be charged even when the system is discon-
nected. These must be correctly discharged by a qualified electrician be-
fore the connections or terminals are touched.
5. When working with the cabinet/unit, use only properly insulated tools.
6. All persons who have to work with the cabinet / unit must be familiar
with first-aid procedures for accidents involving electricity.
7. Always observe the regulations of the local power-supply company as
well as other safety regulations!
8. Rectifier openings that are not used must always be closed!

11.08.06 – TB-Fr/Obs 3/9 4389 en


Assembly instructions SLIMLINE

2 General
The power supply system consists of one or several parallel-connected
SLIMLINE CARRIERS (1 U, 19 inches).

One CARRIER can house up to 3 parallel-connected SLIMLINE


RECTIFIERS. To connect the battery and the load, there are pre-fabricated dis-
tributors provided, e.g.

 SLIMLINE DISTRIBUTION 4500 (1 U, 19 inches),

 SLIMLINE DISTRIBUTION 13500 (3 U, 19 inches) or

 discretely assembled distributors.

If SLIMLINE CARRIER and SLIMLINE DISTRIBUTION are ordered as a u-


nit, the components are delivered as assembled and wired unit. The battery and
the loads must be connected to the corresponding terminals by the customer. If
necessary, the +connection of the "supply bar" must be connected to the earth
as a functional earthing (telephone earth FPE).

Due to the high output power and the resulting power loss of the system, some
requirements and preconditions apply to the installation and ventilation.

3 Installation requirements
The installation of the power supply unit or of the power supply system in a 19
/ 23 inch cabinet must be done according to the following instructions:

 No apertures or foreign bodies must be present in the exhaust air duct


that could cause the air to escape uncontrolled or to obstruct the air flow
in the aspired and outgoing air. Furthermore, take care that the air intake
area is closed at the front to prevent that warmed-up intake air from the
cabinet is used for device cooling.

 The following figures / drawings show the critical air paths of a cabinet
as an example. Clearances in space, like the exhaust air duct above the
cabinet, are taken into account. If the free air flow is impeded in the cabi-
net top area due to head frames or the like, the air duct must be placed el-
sewhere.

11.08.06 – TB-Fr/Obs 4/9 4389 en


Assembly instructions SLIMLINE

Figure 1: Cabinet with exhaust air aperture on top

Figure 2: Cabinet with obstacle in the top area (head frame)

11.08.06 – TB-Fr/Obs 5/9 4389 en


Assembly instructions SLIMLINE

Explanations on the figures 1 and 2:

A= power supply 1; 2 or 3 x 1 U, e.g. SLIMLINE CARRIER 4500

Power loss with 1 fully equipped carrier (3 rectifiers) = 500 W

Power loss with 2 fully equipped carrier (6 rectifiers) = 1000 W

Power loss with 3 fully equipped carrier (9 rectifiers) = 1500 W

B= Distribution, e.g. 1 U SLIMLINE DISTRIBUTION 4500 or

3 U SLIMLINE DISTRIBUTION 13500

(1) = Bulkhead towards the lower housing space

(2) = Deflector (45° angle) to guide the exhaust air into the exhaust air duct1

(3) = Bulkhead towards the top installation space (as exhaust air duct, close
it up to the upper cover!2)

(4) = Deflector plate (45° angle) for the air guidance

1
Example for (2),

 Leg length of the deflector angle and the straight duct depend on the ca-
binet depth (T).

 In case of more than 3 carriers, adapt the cabinet depth.

 The profile dimensions at different cabinet depths must ensure an opti-


mum exhaust air guidance.
2
Example for (3),

 Bulkhead over the carrier covers all apertures.

 The cut-out of the bulkhead must be dimensioned according to the 1 U or


the 3 U distributor (DISTRIBUTION).

 A perforation in the rear wall or the side walls of the cabinet is not ad-
missible.

11.08.06 – TB-Fr/Obs 6/9 4389 en


Assembly instructions SLIMLINE

F= Clearance (distance between cabinet and room ceiling)

T= Cabinet depth

E= Dimension for closed front.


Space below and above the carrier without apertures in the front area
(shunt air flow is prohibited); also filters, door, detachable covers etc.
are not allowed!

Measure E = 30 mm for 1 carrier


Measure E = 45 mm for 2 carriers
Measure E = 72 mm for 3 carriers

Example: Cabinet depth 400 mm

 max. 3 carriers

 measure F = 750 mm,

 only grid meshes or diamond meshes are allowed on top in the exhaust
air duct, free aperture surface approx. 95%!

11.08.06 – TB-Fr/Obs 7/9 4389 en


Assembly instructions SLIMLINE

Example: Cabinet depth 450 mm

 max. x carrier(s)

 measure F = xxx mm, DRAFT

Example: Cabinet depth 520

 max. x carrier(s)

 measure F = xxx mm, DRAFT

11.08.06 – TB-Fr/Obs 8/9 4389 en


Assembly instructions SLIMLINE

4 Connection and commissioning


 Install the unit / system in a dry and dust-protected environment.

 The flow of cooling air must not be obstructed.

 On account of its heavy weight, the racking unit must be provided with
crossrails or runners on the right and left.

 The unit / system as delivered is ready for operation.

 Before connecting up, make sure that the specifications on the rating pla-
te and data sheet agree with the actual mains and battery voltages.

 The circuit diagram should be observed at all times!

 Make the mains connection only when the mains supply voltage is swit-
ched off!

 According to the VDE regulations an accessible mains disconnecting de-


vice must be installed in the vicinity of the unit / system.

 Install equipotential bondings with sufficient conductor cross-section


(e.g. 16 mm²) (wiring pin in the terminal area) to protect the device/the
unit against interference voltage (e.g. due to lightning strokes).

 If necessary, connect the +terminal of the "supply bar" with earth (tele-
phone earth FPE).

11.08.06 – TB-Fr/Obs 9/9 4389 en


Description

Battery

Contents
1 General............................................................................................................... 2

2 Safety prescriptions with regard to use batteries ............................................... 2

Date Name No. 3256 en


Issued: 03.06.98 TB-Obs Page 1/2 pages
Revision:
Checked: 03.06.98 Enck
C:\qtemp\pdfhandbuch\A0356009.DOC
Description - Battery

1 General
The documentation of the battery is attached to the battery. Please read this de-
scription, paying special attention.

2 Safety prescriptions with regard to use batteries


Batteries should be charged, maintained and changed only by personnel who
have been trained for this. These instructions and the prescriptions of the bat-
tery manufacturers have to be observed! Near to batteries it is prohibited to
smoke and use open fire. No inflammable materials or sparking equipment (e.g.
machine tool) may be in a distance of min. 2 m of the battery which is charged.
Working with tools with high surface temperature (e.g. soldering iron, hot-air
blower etc.) is prohibited.

During battery charging explosive gasses are generated. The


ventilation during the charging process and min. one hour after
end of the charging process has to be warranted.

The room must be ventilated. Before each charging process the function of a
present ventilating system has to be verified. Fire prophylactics have to be avai-
lable.

Parts which can be sucked via the ventilators may not be depos-
ited near the charger. Obstructed ventilation slots result in over-
heating and inflammability.

Do not use water to cool overheated chargers, but let them cool
down in switched-off state.

03.06.98 - TB- Obs 2/2 3256 en