1811P01

QAC...
Outside Sensors FW-T1G
Passive sensors for acquiring the outside temperature and – to a lesser
degree – solar radiation, the wind effect and the temperature of the wall.
Range of use -40/50…+70 °C / 5…95 % r. F.

Use

The QAC… outside sensors are for use in heating, ventilation and air conditioning
plants as:
Reference sensors for weather-compensated control
Measuring sensors, e.g. for optimization, measured value indication, or for connec-
tion to a building automation and control system

Type summary

Type reference Sensing element Range of use Time constant Approval


QAC22 LG-Ni 1000 50... 70 °C ca. 14 min
QAC32 NTC 575 50... 70 °C ca. 12 min
(linearized)
QAC2010 Pt 100 50... 70 °C ca. 14 min UL, class 2
QAC2012 Pt 1000 50... 70 °C ca. 14 min UL, class 2
QAC2030 NTC10k 40... 70 °C ca. 14 min UL, class 2
*)
FW-T1G T1 (PTC) 50... 70 °C ca. 14 min
*) No longer available

Ordering and delivery

When ordering, please give name and type reference, e.g.:


Outside sensor QAC22.

CE1N1811E
2017-12-01 Building Technologies
Equipment combinations

The outside sensors are suited for use with all types of controllers capable of acquiring
and handling the sensor’s measured value.

Function

The outside sensor acquires the outside temperature and to a lesser degree solar
radiation, the wind effect and the temperature of the wall. The sensing element
changes its resistance value as a function of the temperature.

Sensing elements Characteristic: Accuracy:

LG-Ni 1000 R[ ]
[K]

1811D01
1400 2.0

1811D02
1200 1.0

1000 0.0

800 1.0

600 2.0
50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C] 50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C]

NTC 575 R[ ] [K]


700
3.0
1811D03

1811D04
650 2.0

1.0
600

0.0
550
1.0

500
2.0

450 3.0
50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C] 50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C]

R[ ]
Pt 100 (class B)
[K]
1811D05

140
0.8 1811D06

120
0.4

100 0.0

0.4
80

0.8
60
50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C] 50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C]

Pt 1000 (class B) R[ ]
[K]
1811D07

1400
1811D06

0.8

1200
0.4

1000 0.0

0.4
800

0.8
600
50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C] 50 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C]

2/6

Siemens Outside sensors QAC... CE1N1811E


Building Technologies 2017-12-01
R[ ]
NTC 10k [K]
1000000

1811D09
1.20

1811D08
1.00
0.80
0.60
100000
0.40
0.20
0.00
-0.20
10000 -0.40
-0.60
-0.80
-1.00
1000 -1.20
-40 -30 -20 -10 0 10 20 30 40 50 60 70 80 [°C] -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 [°C]

R[ ]
T1 (PTC)
3200
[K]

1819D01
3000 5.0

1819D02
2800 4.0
3.0
2600
2.0
2400 1.0
2200 0.0
2000 1.0
2.0
1800
3.0
1600 4.0
1400 5.0
40 30 20 10 0 10 20 30 40 50 60 70 80 [°C] 40 30 20 10 0 10 20 30 40 50 60 70 80 [°C]

Legend R Resistance in Ohm


Temperature in degrees Celsius
Temperature differential in Kelvin

Mechanical design

The sensor has a plastic housing with a removable cover.


The connection terminals can be accessed after removal of the cover.
Cable entry is either from the rear (concealed wiring) or from below (surface-run wires).
A cable entry gland can be screwed into the bottom of the housing.

Engineering notes

The permissible cable lengths depend on the type of controller with which the sensor is
used. They are specified in the Data Sheet of the relevant controller.

Mounting notes

Depending on use, the outside sensor must be located as follows:


Mounting location For control:
On the wall of the house or building that has the windows of the occupied rooms, but
the sensor must not be exposed to the morning sun. In case of doubt, it should be
mounted on the wall facing north or north-west
For optimization:
Always on the coldest wall of the house or building (normally the wall facing north).
The sensor must never be exposed to the morning sun
Mounting height Preferably in the middle of the house or building or heating zone, but at least 2.5 m
above the ground.
The sensor must not be fitted at the following locations:
Above windows, doors, air extracts or other heat sources
Below balconies or the eave of the roof
To prevent measuring errors due to air circulation, the cable conduit at the sensor
should be sealed.
The sensor may not be painted over.
Mounting Instructions are printed on the packaging.
3/6

Siemens Outside sensors QAC... CE1N1811E


Building Technologies 2017-12-01
Disposal

The device is considered electrical and electronic equipment for disposal in terms of the
applicable European Directive and may not be disposed of as domestic garbage.
Dispose of the device via the channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.

Technical data

Functional data Range of use refer to "Type summary"


Sensing element refer to "Type summary"
Time constant refer to "Type summary"
Accuracy refer to "Function"
Type of measurement and output passive
Degree of protection Protection class III according to EN 60730
Protection degree of housing IP54 according to EN 60529
2 2
Electrical connections Screw terminals for 2 x 1.5 mm or 1 x 2.5 mm
Cable entry for cable gland (e.g. M 16 x 1.5)
Perm. cable length refer to "Engineering notes"
Environmental conditions Operation
Climatic conditions
Temperature 40...+ 70 °C
Humidity 0 . . . 1 0 0 % r. h.
Storage / transport to IEC 721-3-2
Climatic conditions class 2K3
Temperature 25...+ 65 °C
Humidity < 95 % r. h.
Mechanical conditions class 2M2
Directives and Standards Product standard EN 60730-1
Automatic electrical controls for house-
hold and similar use
EU conformity (CE) 8000073890 *)
UL UL873 http://ul.com/database
Environmental compatibility *)
The product environmental declaration CE1E1701 contains data on environmentally compatible prod-
uct design and assessments (RoHS compliance, materials composition, packaging, environmental
benefit, disposal).
Materials and colors Base plastic (ASA)
Cover plastic (ASA), RAL9003
Packaging cardboard
Weight Incl. packaging approx. 0.093 kg
*) The documents can be downloaded from http://siemens.com/bt/download.

Internal diagram
1811G01

B M

The internal diagram is identical for all types of outside sensors covered by this Data
Sheet.
The connecting wires are interchangeable.

4/6

Siemens Outside sensors QAC... CE1N1811E


Building Technologies 2017-12-01
Dimensions

5,5 3

92

5,5
20,7
4

6
80 50 Ø 16

25 24,5

1811M03
49,5

Drilling plan
Dimension in mm

5/6

Siemens Outside sensors QAC... CE1N1811E


Building Technologies 2017-12-01
Published by:
Siemens Switzerland Ltd.
Building Technologies Division
International Headquarters
Gubelstrasse 22
6301 Zug
Switzerland
Tel. +41 58-724 24 24 © Siemens Switzerland Ltd 2014
www.siemens.com/buildingtechnologies Delivery and technical specifications subject to change

6/6

Siemens Outside sensors QAC... CE1N1811E