Spirit Transfer Pump Isolation Procedure

GLO P4105

Document Number:

GLO P4105 Isolation


Dummy Not For Use!

Cadherent Limited
Riverside
North Esplanade West
Aberdeen, AB11 5RJ
Tel: +44 (0)1224 914850 Email: info@cadherent.com www.cadherent.com

QAF 58a 15/07/15


P 4105 Isolation

Contents:

Location ................................................................................................................................................. 3 
P&ID ........................................................................................................................................................ 4 
Procedure................................................................................................................................................ 4 

GLO P4105 Isolation 2


P 4105 Isolation

Location

Intermediate Spirit Receiver T4160

GLO P4105 Isolation 3


P 4105 Isolation

P&ID

Procedure

1. Locate Spirit Transfer Pump P4105.


2. Isolate pump electrical circuit breaker on main switch board and attach a notice.
3. Isolate local isolator ISL 4105.
4. Close valve CV 4161.
5. Close valve MV 4161.
6. Close valve MV 4163.
7. Close valve MV 4164.
8. Open valve MV 4161 and monitor any discharge to drain.
9. Close valve MV 4161.
10. Fully open and close valve MV4163.
11. Open valve MV 4161 and check that no spirit drains from valve.
12. Maintain Pump as per procedure.