Professional Documents
Culture Documents
D
AUTOMATIC TRANSFER SWITCH
User Manual
1.Introduction........................................................................................................................................ Page 4
1.1 General Specifications................................................................................................................ Page 4
1.2 Warranty...................................................................................................................................... Page 4
1.3 Maintenance .............................................................................................................................. Page 4
1.4 Order Information....................................................................................................................... Page 4
2.Installation.......................................................................................................................................... Page 5
2.1 Unit Configuration....................................................................................................................... Page 5
2.2 Panel Mounting........................................................................................................................... Page 5
Figure 2.1 Front View................................................................................................................. Page 5
Figure 2.2 Panel Cut-Out........................................................................................................... Page 5
2.3 Electrical Connection.................................................................................................................. Page 6
5.Specifications..................................................................................................................................... Page 53
2
EU DECLARATION OF CONFORMITY
3
1.Introduction
The unit is extensively programmable through the front panel, with password protection on
two levels. Operational parameters can also be monitored and controlled from a PC via a
built-in USB port.
The unit monitors both sources and gives warning of any faults that are detected.
If a fault is detected, the unit shuts down the engine(if generator application selected), transfers
load to the other source and shows the failure message on the LCD display.
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
4
2.Installation
Ýçindekiler
A visual inspection of this product for possible damage occured during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit , power off
the system and seperate the electrical connection of the device from the system.
Keep the power off until all of the wiring is completed so that electric shock and trouble with
the unit can be prevented.
The unit can be programmed using the buttons and LCD display on the front panel or PC
Software.
The unit is designed for panel mounting. Fixing is by two screw fixings.
1- Insert the unit in the panel cut-out from the front.
2- Insert the fixings in the slotted at the corners of the unit and tighten the fixing screws to secure
the unit against the panel.
! During the equipment is putted in hole on the metal panel while mechanical
installation some metal burrs can cause injury on hands, you must be careful.
ATS.D
ü
152mm
135mm
S1 S2
182mm
229mm
5
2.3 Electrical Connection
TRANS-ATS.D three phase connections schematic
43 44 45
BATTERY -
(Optional)
22 21
RS-485
USB
A(+) B(-)
! 1
FUSE-7
BATTERY +
LOAD
N
L1
L2
L3
! 2
13 14 15 16
N
L1
L2
L3
BATTERY -
S2: (GENERATOR)
Max. 300VV
5
FUSE-6
Emergency Stop or
4
35 34 33 32 31 30 29 28
FUSE-5
Configurable Input-1
Configurable Input-2
3
FUSE-4
Configurable Input-3
2
Configurable Input-4
8A
Configurable Input-5
1
Configurable Input-7
BATTERY +
Electrical interlock
Source 2 Ready or
Configurable Input-8
BATTERY +
Mechanical interlock
S1
Source 1
TRANSISTOR OUTPUTS
Relay
Configurable Output-2
10
8A
Configurable Output-3
MAX. 1 A
FUSE-3
Configurable Output-4
9
Max. 300VV
FUSE-2
8
FUSE-8 BATTERY +
42 41 40
FUSE-1
S1: (MAINS)
5A
7
Remote Start 1 or
Configurable Output-5
6
5A
Remote Start 2 or
Configurable Output-6
L1
L2
L3
N
1- Connect the unit as shown in the appropriate diagram. Be sure to connect the battery
! supply the right way round and battery negative should be grounded.
2- Current transformers secondary should be grounded.
6
3. Front Panel Description And Accessing To The Parameters
ATS.D 14 15 16
1 4
17 20
2 18
ü19
3 21
22 23 24
6 7
5
S1 S2
25 26 8
9 10 11 12 13
27 28 29 30 31 32
Number Comment
1 This LED indicates that a "Shutdown" alarm was detected.
2 This LED indicates that a "Warning" alarm was detected
3 This LED indicates that a "Maintenance" alarm was detected
4 This LCD display is used for displaying the electrical measurements during normal operation,
and editing/inspecting programming parameters in program mode.
5 This LED indicates that Source 1 voltage and frequency is within limits and is ready to take over
the load.
6 This LED shows that the load is supplied from the Source 1.
7 This LED shows that the load is supplied from the Source 2.
8 This LED indicates that Source 2 voltage and frequency is within limits and is ready to take over
the load.
9 This LED shows that the unit is in the AUTO mode.
10 This LED shows that the unit is in the TEST mode.
11 This LED shows that the unit is in the MANUAL mode.
12 In the MAN, AUTO and TEST modes, this LED indicates that the engine is starting up or is
running.
13 This LED shows that the unit is in the STOP mode.
7
Number Comment
14 Warning and Alarm messages shortcut button.
15 Event Logs shortcut button.
16 The LAMP TEST button illuminates all LED indicators.
17 In Programming mode, it operates as an Up button (changing cursor position) or Increment
button (increase parameter value).
18 This button is used for showing previous page in normal operation. In Programming mode, it
operates as an Left button (changing cursor position).
19 This button is used for entering parameter edit section and saving parameter value in
programming mode.
20 This button is used for showing next page in normal operation. In Programming mode, it
operates as an Right button (changing cursor position).
21 In Programming mode, it operates as an Down button (changing cursor position) or
Decrement button (decrease parameter value).
22 The Escape button is used for exit previous section in programming mode.
23 When this button is pressed, the unit goes into its PROGRAMMING Mode.
24 This button will silence the alarm horn after a failure has been detected.
25 This button opens or closes the S1 contactor, only operative when manual mode is selected.
26 This button opens or closes the S2 contactor, only operative when manual mode is selected.
27 This button will reset the controller after a failure has been detected.
28 The AUTO button is used for changing operating mode of the unit to the AUTO Mode.
29 The TEST button is used for changing operating mode of the unit to the TEST Mode.
30 The MAN button is used for changing operating mode of the unit to the MANUAL Mode.
31 The START button is used for starting the engine when the unit is in the Manual Mode.
32 The STOP button is used for changing operating mode of the unit to the STOP Mode.
The generator is stopped.
Measurement values
S1: MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V ü
V31: 380V V3: 220V
Source 1 okay
Engine Status or Error Messages
Use the Next and Previous buttons to select which Data display page (screen) is to be displayed.
When the Alarm (!) shortcut button is pressed, the Warning & Alarm display page is displayed.
When the Event log (LOG) shortcut button is pressed, the Event Log display page is displayed.
8
Data display pages on the LCD display;
Source 1 Page1:
V12: Source 1 voltage L1-L2
S1: MAINS V23: Source 1 voltage L2-L3
V12: 380V V1: 220V V31: Source 1 voltage L3-L1
V1: Source 1 voltage L1-N
V23: 380V V2: 220V V2: Source 1 voltage L2-N
V31: 380V V3: 220V V3: Source 1 voltage L3-N
S2 on load
Source 1 Page2:
Fq: Source 1 frequency
S1: MAINS Phase Seq.: Source 1 phase sequence
Fq:50.0Hz Dual time: Dual working time left for source 1
Phase seq.: L1 L2 L3
Dual time: 0:00
S2 on load
Source 2 Page1:
V12: Source 2 voltage L1-L2
S2: GENERATOR V23: Source 2 voltage L2-L3
V12: 380V V1: 220V V31: Source 2 voltage L3-L1
V1: Source 2 voltage L1-N
V23: 380V V2: 220V V2: Source 2 voltage L2-N
V31: 380V V3: 220V V3: Source 2 voltage L3-N
S2 on load
Source 2 Page2:
Fq: Source 2 frequency
S2: GENERATOR Phase Seq.: Source 2 phase sequence
Fq:50.0Hz Dual time: Dual working time left for source 2
Phase seq.: L1 L2 L3
Dual time: 2:00
S2 on load
Load Page1:
I1: Load Current L1
LOAD I2: Load Current L2
I1: 26A PF1: 0.84 I3: Load Current L3
PF1: Load power factor L1
I2: 23A PF2: 0.80 PF2: Load power factor L2
I3: 25A PF3: 0.82 PF3: Load power factor L3
S2 on load
Load Page2:
P1: Load active power L1
LOAD P2: Load active power L2
P1: 170kW P3: Load active power L3
P2: 170kW
P3: 170kW
S2 on load
9
Load Page3:
Q1: Load reactive power L1
LOAD Q2: Load reactive power L2
Q1: 40kVAr Q3: Load reactive power L3
Q2: 40kVAr
Q3: 40kVAr
S2 on load
Load Page4:
S1: Load apparent power L1
LOAD S2: Load apparent power L2
S1: 210kVA S3: Load apparent power L3
S2: 210kVA
S3: 210kVA
S2 on load
Load Page5:
SP: Load total active power
LOAD SQ: Load total reactive power
SP: 510kW SS: Load total apparent power
SQ: 120kVAr
SS: 630kVA
S2 on load
Load Page6:
kWh: Source active energy
LOAD KVArh: Source reactive energy
kWh : 30600
kVArh: 7200
S2 on load
S2 on load
10
Exp. Input & Output Status Page:
Inputs: Exp. input status information. If an input is active, related
digit is displayed as "1" else it is displayed as "0".
EXP. INPUT & OUTPUT 1: Exp. conf. in-1, 2: Exp. conf. in-2, 3: Exp. conf. in-3,
1 4 5 8 4: Exp. conf. in-4, 5: Exp. conf. in-5, 6: Exp. conf. in-6,
Inputs : 0000 0000 7: Exp. conf. in-7, 8: Exp. conf. in-8.
Outputs: 0000 0000 Outputs: Exp. output status information. If an output is active,
related digit is displayed as "1" else it is displayed as "0".
S2 on load 1: Exp. conf. out-1, 2: Exp. conf. out-2, 3: Exp. conf. out-3,
4: Exp. conf. out-4, 5: Exp. conf. out-5, 6: Exp. conf. out-6,
7: Exp. conf. out-7, 8: Exp. conf. out-8.
Date & Time Page:
Date: Day, Month, Year.
DATE & TIME Time: Hour, minute, second.
15/02/2011
13:32:28
11
Example-1: Displaying all Data display pages.
S1: MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Source 1 okay
12
Example-3: Displaying all Event Log display pages
S1: MAINS
V12: 380V V1: 220V
V23: 380V V2: 220V
V31: 380V V3: 220V
Source 1 okay
S1: GENERATOR
V12: 0V V1: 0V
V23: 0V V2: 0V ü
V31: 0V V3: 0V
S1 start active
LCD DISPLAY
Language
ENGLISH ü
13
3.2 Changing And Saving Parameters Values
Operation Screen
S1: MAINS PROGRAM
V12: 380V V1: 220V Operator setting Press the Up or
V23: 380V V2: 220V ü Technician setting ü Down buttons to
V31: 380V V3: 220V Factory adjustment
Source 1 okay select the section
you wish to
view/change.
When the Prog button is
pressed, the parameters
section is asked for
accessing to parameters.
14
4. Parameters
4.1 Operator Parameters
4.1.1 Source 1 (Mains)
SOURCE 1 VOLT LEVEL (Source 1->Volt level) Min Max Default Unit
Under volt trip Source 1 Under Voltage 60 600 320 VV
Under volt reset Source 1 Under Voltage Reset 60 600 340 VV
Over volt trip Source 1 Over Voltage 60 600 440 VV
Over volt reset Source 1 Over Voltage Reset 60 600 420 VV
SOURCE 1 FREQ. LEVEL (Source 1->Frequency level) Min Max Default Unit
Under freq trip Source 1 Under Frequency 20.0 75.0 45.0 Hz
Under freq reset Source 1 Under Frequency Reset 20.0 75.0 48.0 Hz
Over freq trip Source 1 Over Frequency 20.0 75.0 55.0 Hz
Over freq reset Source 1 Over Frequency Reset 20.0 75.0 52.0 Hz
SOURCE 2 VOLT LEVEL (Source 2->Volt level) Min Max Default Unit
Under volt trip Source 2 Under Voltage 60 600 320 VV
Under volt reset Source 2 Under Voltage Reset 60 600 340 VV
Over volt trip Source 2 Over Voltage 60 600 440 VV
Over volt reset Source 2 Over Voltage Reset 60 600 420 VV
SOURCE 2 FREQ. LEVEL (Source 2->Frequency level) Min Max Default Unit
Under freq trip Source 2 Under Frequency 20.0 75.0 45.0 Hz
Under freq reset Source 2 Under Frequency Reset 20.0 75.0 48.0 Hz
Over freq trip Source 2 Over Frequency 20.0 75.0 55.0 Hz
Over freq reset Source 2 Over Frequency Reset 20.0 75.0 52.0 Hz
CT ratio
Load current transformer’s transfer ratio(Primary current/Secondary current) value must be entered to
this parameter.
Example:
If Current Transformer Primary=500A and Current Transformer Secondary=5A, Current Transformer
Ratio should be entered CT Primary/CT Secondary=100.
PT ratio
Defines the scaling factor applied to voltage readout and associated fault conditions.
This PT ratio is for additional voltage transformers mounted the unit.
Type of AC System
This parameter is used to detail the type of AC system to which the unit is connected:
1 phase 2 wire, 3 phase 4 wire, 2 phase 3 wire L1-L2, 2 phase 3 wire L1-L3.
Phase Sequence
DISABLE: The Source 1 and the Source 2 phase sequence checking disabled.
L123 or L321: if the any of the source's phase sequence is faulty, the "S1/S2 phase sequence wrong"
warning is given and the source's contactor is deenergized. If the source with the faulty phase
sequence is configured as generator, then the generator will be stopped.
Operation type
This parameter is used to select the operation type of the system.
-Duty-standby: In this operation type, the source with the higher priorty supplies the load. If the
source with higher priorty fails then the source with the lower priority supplies the load.
-Dual:Each source supplies the load in turn. Each source supplies the load during Source dual timer.
If the source that supplies the load fails, then the other source supplies the load. When the dual time
expired, if the other source is failed, then source that is working supplies the load for one more
period.
Source priority
This parameter is used to select source working priority.
17
Example: If Hardware Breaker Selection parameter is selected as 0;
For closing For opening
S2 Shalter S2 Shalter
S2 Closed Out.
(NO) t[s]
S2 Closed Out.
(NC) t[s]
1- User Configured: S1 and S2 breakers have only close drives, when want to breaker close, close
breaker output on and after 1 sec. open breaker output on and after breaker close pulse time open
breaker output will off. When want to breaker open close breaker output and open breaker output will
off.
Parameters; S2 CLOSE BREAKER CONTACT TYPE, S2 CLOSE TIMER(if S2 closed input selected),
S2 OPEN TIMER(if S2 closed input selected), S1 CLOSE BREAKER CONTACT TYPE, S1 CLOSE
TIMER(if S1 closed input selected), S1 OPEN TIMER(if S1 closed input selected),BREAKER CLOSE
PULSE TIME, TRANSFER TIME.
Example: If Hardware Breaker Selection parameter is selected as 1;
For closing For opening
S2 Shalter S2 Shalter
Breaker close
pulse time
S2 Closed Out.
(NO) t[s]
S2 Closed Out.
(NC) t[s]
1s
S2 Open Out.
(NO) t[s]
S2 Open Out.
(NC) t[s]
18
rtNB
brCP brCP brCP brCP brCP brCP brCP brCP brCP brCP
S2CB close sPLD sPLD sPLD
command
t[s]
brOP S2bCt S2bCt brOP S2bCt brOP S2bCt S2bCt S2bCt S2bCt
1s 1s 1s
S2CB open
command
t[s]
Feedback
input
t[s]
S2CB fail to
close alarm
t[s]
S2CB close
command
t[s]
S2bOt S2bOt
S2CB open brOP
command
t[s]
Feedback
input
t[s]
S2CB fail to
open alarm
t[s]
S2 Close Timer
This is used to monitor the closure of the Source 2 contactor or breaker. It will only operate if an
auxiliary input is configured as ‘Source 2 Closed Auxiliary’ and connected to the auxiliary on the source
2 contactor or breaker. Once a source 2 closed signal is issued the ‘S2 close timer’ is initiated. Should
the ‘Source 2 Closed Auxiliary’ input become active the timer the ‘S2 close timer’ is cancelled. If the
timer expires and the ‘Source 2 Closed Auxiliary’ has not become active the module will issue a
‘Source 2 failed to close’ alarm.
S2 Open Timer
This is used to monitor the opening of the Source 2 contactor or breaker. It will only operate if an
auxiliary input is configured as ‘Source 2 Closed Auxiliary’ and connected to the auxiliary on the
Source 2 contactor or breaker. Once a Source 2 open signal is issued the ‘S2 open timer’ is initiated.
Should the ‘Source 2 Closed Auxiliary’ input become in-active the timer ‘S2 open timer’ is cancelled. If
the timer expires and the ‘Source 2 Closed Auxiliary’ has not become in-active the module will issue a
‘Source 2 failed to open’ alarm.
19
Source 1 Open Timer
This is used to monitor the opening of the Source 1 contactor or breaker. It will only operate if an
auxiliary input is configured as ‘Source 1 Closed Auxiliary’ and connected to the auxiliary on the
Source 1 contactor or breaker. Once a Source 1 open signal is issued the ‘Source 1 open timer’ is
initiated. Should the ‘Source 1 Closed Auxiliary’ input become in-active the timer the ‘Source 1 open
timer’ is cancelled. If the timer expires and the ‘Source 1 closed auxiliary’ has not become in-active the
module will issue a ‘Source 1 failed to open’ alarm.
Language Selection
Language selection: English or Chinese.
Digital Contrast
It is used to change contrast of LCD Display.
Auto Backlight Off
ENABL: If any button is not pressed during 120 secs, LCD backlight is automatically changed power
safety mode.
DISBL: LCD backlight is on continuously.
Auto Scroll Time
The scroll time between all data display pages.
Auto Scroll Number
The number of data display pages that will be scrolled.
Scroll Time For Error Messages
Error messages are displayed the last line of LCD Display. If more than one error condition is present,
each of them is displayed during time defined by Auto Scroll Timer parameter.
DATE & TIME SET (System->Date & time set) Min Max Default Unit
Year Year 0 99
Month Month 1 12
Day Date 1 31
Week Day of week 1 7
Hour Hour 0 23
Minute Minute 0 59
Second Second 0 59
Day of week 1=Monday,2=Tuesday,3=Wednesday,4=Thursday,5=Friday,6=Saturday,7=Sunday
SOURCE 1 FREQ. LEVEL (Source 1->Frequency level) Min Max Default Unit
S1 Under freq trip Source 1 Under Frequency 20.0 75.0 45.0 Hz
S1 Under freq reset Source 1 Under Frequency Reset 20.0 75.0 48.0 Hz
S1 Over freq trip Source 1 Over Frequency 20.0 75.0 55.0 Hz
S1 Over freq reset Source 1 Over Frequency Reset 20.0 75.0 52.0 Hz
SOURCE 1 ACTIONS (Source 1->Actions) Min Max Default Unit
S1 fail.stop mode Look Source 1 Failure at Stop Mode En/Dis ENABL/DISBL ENABL
S1 always return delay Always Look Source 1 Return Delay ENABL/DISBL DISBL
S1 return delay Source 1 return delay 0 99 2 sec
S1 fail delay Source 1 fail delay 0 99 2 sec
Look Source 1 Failure at Stop Mode En/Dis
(This parameter is only used if Source 1 is selected as `Mains` supply)
ENABLE: As soon as the module detects a source 1 failure the source 1 contactor or breaker relay will
be opened to remove the supply from the load. This is to prevent damage to the load in case of single-
phase failure.
DISABLE: In the event of a source 1 failure the unit will attempt to maintain the supply to the load for
the incoming AC source 1 supply until the source 2 is available to go on load. In the event of a
source 2 failure the module will default back to the incoming AC Source 1 supply.
Always Look Source 1 Return Delay
(This parameter is only used if Source 1 is selected as `Mains` supply)
ENABLE: The module will always wait the Source 1 Return Delay parameter before transferring the
load back to source 1.
DISABLE: The module will wait the Source 1 Return Delay parameter while only the source 2 is
available to go on load before transferring the load back to source 1.
22
4.2.3 Source 2(Generator)
SOURCE 2 VOLT LEVEL (Source 2->Volt level) Min Max Default Unit
S2 Under volt trip Source 2 Under Voltage 60 600 320 VV
S2 Under volt reset Source 2 Under Voltage Reset 60 600 340 VV
S2 Over volt trip Source 2 Over Voltage 60 600 440 VV
S2 Over volt reset Source 2 Over Voltage Reset 60 600 420 VV
SOURCE 2 FREQ. LEVEL (Source 2->Frequency level) Min Max Default Unit
S2 Under freq trip Source 2 Under Frequency 20.0 75.0 45.0 Hz
S2 Under freq reset Source 2 Under Frequency Reset 20.0 75.0 48.0 Hz
S2 Over freq trip Source 2 Over Frequency 20.0 75.0 55.0 Hz
S2 Over freq reset Source 2 Over Frequency Reset 20.0 75.0 52.0 Hz
23
4.2.4 Load
LOAD CUR LEVEL & ACT (Load->Current level & act.) Min Max Default Unit
Under cur. set Load Under Current Set 0 9999 1 AV
Under cur. prealarm Load Under Current Pre-Alarm 0(dis) 9999 dis AV
Under cur. reset Load Under Current Pre-Alarm Reset 0 9999 5 AV
Under cur. act. Load Under Current Actions 0(dis) 3 dis
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Under act. delay time Load Under Current Actions Delay Time 0 99 2 Sec
Over cur. set Load Over Current Set 0 9999 9999 AV
Over cur. prealarm Load Over Current Pre-Alarm 0(dis) 9999 9990 AV
Over cur. reset Load Over Current Pre-Alarm Reset 0 9999 9980 AV
Over cur. act. Load Over Current Actions 0(dis) 3 dis
0 - Disable
1 - Warning (Alarm Only, No Shutdown)
2 - Electrical Trip (Alarm/Off Load Generator
Followed By Shutdown After Cooling)
3 - Shutdown (Alarm And Shutdown)
Over act. delay time Load Over Current Actions Delay Time 0 99 2 Sec
Short circuit cur. Load Short Circuit Current Set 0 9999 9999 AV
24
4.2.5 Power supply
4.2.6 Engine
Cranking Time (This parameter is only used if one of the outputs is selected as Crank)
This is the maximum amount of time that the module will energise the starter motor for during starting
attempts once the starter has engaged.
Crank Rest Time (This parameter is only used if one of the outputs is selected as Crank)
This is the amount of time the module will wait for between start attempts. This is to allow the starter
motor to cool and the starter batteries to recover.
CONF. EXP. INPUT-2 (Inputs->Conf. exp. input-2) Min Max Default Unit
Dis,user conf.or list The same as Expansion Config. Input-1 options 0(dis) 2 1
Hardware type The same as Expansion Config. Input-1 options 0 1 0
Polarity The same as Expansion Config. Input-1 options 0 1 0
Indication The same as Expansion Config. Input-1 options 0 4 0
Activation The same as Expansion Config. Input-1 options 0 2 2
Select from list The same as Expansion Config. Input-1 options 2 21 2
Active delay Input active delay 0 250 5 Sec
CONF. EXP. INPUT-3 (Inputs->Conf. exp. input-3) Min Max Default Unit
Dis,user conf.or list The same as Expansion Config. Input-1 options 0(dis) 2 1
Hardware type The same as Expansion Config. Input-1 options 0 1 0
Polarity The same as Expansion Config. Input-1 options 0 1 0
Indication The same as Expansion Config. Input-1 options 0 4 0
Activation The same as Expansion Config. Input-1 options 0 2 2
Select from list The same as Expansion Config. Input-1 options 2 21 2
Active delay Input active delay 0 250 5 Sec
35
CONF. EXP. INPUT-4 (Inputs->Conf. exp. input-4) Min Max Default Unit
Dis,user conf.or list The same as Expansion Config. Input-1 options 0(dis) 2 1
Hardware type The same as Expansion Config. Input-1 options 0 1 0
Polarity The same as Expansion Config. Input-1 options 0 1 0
Indication The same as Expansion Config. Input-1 options 0 4 0
Activation The same as Expansion Config. Input-1 options 0 2 2
Select from list The same as Expansion Config. Input-1 options 2 21 2
Active delay Input active delay 0 250 5 Sec
CONF. EXP. INPUT-5 (Inputs->Conf. exp. input-5) Min Max Default Unit
Dis,user conf.or list The same as Expansion Config. Input-1 options 0(dis) 2 1
Hardware type The same as Expansion Config. Input-1 options 0 1 0
Polarity The same as Expansion Config. Input-1 options 0 1 0
Indication The same as Expansion Config. Input-1 options 0 4 0
Activation The same as Expansion Config. Input-1 options 0 2 2
Select from list The same as Expansion Config. Input-1 options 2 21 2
Active delay Input active delay 0 250 5 Sec
CONF. EXP. INPUT-6 (Inputs->Conf. exp. input-6) Min Max Default Unit
Dis,user conf.or list The same as Expansion Config. Input-1 options 0(dis) 2 1
Hardware type The same as Expansion Config. Input-1 options 0 1 0
Polarity The same as Expansion Config. Input-1 options 0 1 0
Indication The same as Expansion Config. Input-1 options 0 4 0
Activation The same as Expansion Config. Input-1 options 0 2 2
Select from list The same as Expansion Config. Input-1 options 2 21 2
Active delay Input active delay 0 250 5 Sec
CONF. EXP. INPUT-7 (Inputs->Conf. exp. input-7) Min Max Default Unit
Dis,user conf.or list The same as Expansion Config. Input-1 options 0(dis) 2 1
Hardware type The same as Expansion Config. Input-1 options 0 1 0
Polarity The same as Expansion Config. Input-1 options 0 1 0
Indication The same as Expansion Config. Input-1 options 0 4 0
Activation The same as Expansion Config. Input-1 options 0 2 2
Select from list The same as Expansion Config. Input-1 options 2 21 2
Active delay Input active delay 0 250 5 Sec
CONF. EXP. INPUT-8 (Inputs->Conf. exp. input-8) Min Max Default Unit
Dis,user conf.or list The same as Expansion Config. Input-1 options 0(dis) 2 1
Hardware type The same as Expansion Config. Input-1 options 0 1 0
Polarity The same as Expansion Config. Input-1 options 0 1 0
Indication The same as Expansion Config. Input-1 options 0 4 0
Activation The same as Expansion Config. Input-1 options 0 2 2
Select from list The same as Expansion Config. Input-1 options 2 21 2
Active delay Input active delay 0 250 5 Sec
2 AUXILIARY S1 FAIL
The unit will monitor the incoming single or three phase supply for Over Voltage, Under Voltage, Over Frequency
or Under Frequency. It may be required to monitor a different source 1 supply or some aspect of the incoming
source 1 not monitored by the unit. If the devices providing this additional monitoring are connected to operate
this input, the unit will operate as if the incoming source 1 supply has fallen outside of limits, the source 2 will be
instructed to start and take load. Removal of the input signal will cause the unit to act if the source 1 has returned
to within limits.
3 AUXILIARY S2 FAIL
The unit will monitor the incoming single or three phase supply for Over Voltage, Under Voltage, Over Frequency
or Under Frequency. It may be required to monitor a different source 2 supply or some aspect of the incoming
source 2 not monitored by the unit. If the devices providing this additional monitoring are connected to operate
this input, the unit will operate as if the incoming source 2 supply has fallen outside of limits, the source 1 will be
instructed to start and take load. Removal of the input signal will cause the unit to act if the source 2 has returned
to within limits.
37
14 SOURCE 1 LOAD INHIBIT
This input is used to prevent the unit from loading the Source 1 supply. If the Source 1 supply is already on load,
activating this input will cause the unit to unload the Source 1 supply. Removing the input will allow the Source 1
to be loaded again. Note: This input only operates to control the Source 1-switching device if the unit load
switching logic is attempting to load the Source 1. It will not control the Source 1-switching device when the
Source 2 is on load.
15 AUTO RESTORE INHIBIT
When module in the AUTO mode. In the event of a remote start or soruce failure, the other source will be
instructed to start and take load. On removal of the remote start signal or source with the higher priority return,
the module will continue to supply the load until this AUTO RESTORE INHIBIT input is removed. Once the input
is removed the unit will transfer the load back to the source with the higher priority. This input allows the module
to be fitted as part of a system where the manual restoration to source is controlled remotely or by an automated
system.
16 AUTO START INHIBIT
This input is used to provide an over-ride function to prevent the unit from starting the generator in the event of a
remote start or source failure condition occurring. If this input is active and a remote start signal or source failure
occurs the unit will not give a start command to the generator. If this input signal is then removed, the unit will
operate as if a remote start or source failure has occurred, starting and loading the generator. This function can
be used to give an 'AND' function so that a generator will only be called to start if the source fails and another
condition exists whish requires the generator to run. If the 'Auto Start Inhibit' signal become active once more it
will be ignored until the unit has returned the source supply on load and shutdown.
17 PANEL LOCK
This input is used to provide security to the installation. If the panel lock input is active, the unit will not respond to
operation of the mode select or start buttons. This allows the unit to be placed into a spesific mode (such as
Auto) and than secured. The operation of the unit is not affected and the operator will still be able to view the
various instrumentation pages etc. Note: External control sources (i.e. Simulate Start Button) are not affected by
the panel lock input and will continue to operate normally.
18 SCHEDULED RUNS(EXERCISE) INHIBITED
This input is used to prevent the generator for starting in the event of a programmed scheduled (exercise) run
occurring. While the input is active no scheduled runs will occur. If the input is active when a schedule run is
called for, and is removed during the running period the gen-set will start and complete any remaining scheduled
running time.
19 RESERVED
20 TRANSFER SOURCE 1 TO SOURCE 2
This input is used to transfer the load to the source 2 when running in Manual mode.
21 TRANSFER SOURCE 2 TO SOURCE 1
This input is used to transfer the load to the source 1 when running in Manual mode.
22 REMOTE INHIBIT
In AUTO mode, if one of the configurable inputs are selected as 22 (Remote Inhibit) and this input is active, the
module will inhibit the generator for starting. In the other hand, if this input is active while the generator was
starting, the module will stop the generator.
23 AUXILIARY SOURCE 1 READY
Allows an Auto Start module to instruct the ATS unit that the system is available to take load. The ATS unit then
monitors the voltage and frequency to check they are within acceptable limits before performing the load transfer
function.
24 AUXILIARY SOURCE 2 READY
Allows an Auto Start module to instruct the ATS unit that the system is available to take load. The ATS unit then
monitors the voltage and frequency to check they are within acceptable limits before performing the load transfer
function.
25 SIMULATE SOURCE 1 AVAILABLE
Allows an Auto Start module to instruct the ATS unit that the system is available to take load. The ATS unit then
performs the load transfer function.
26 SIMULATE SOURCE 2 AVAILABLE
Allows an Auto Start module to instruct the ATS unit that the system is available to take load. The ATS unit then
performs the load transfer function.
27 EMERGENCY STOP (FOR CONFIGURABLE INPUT-1)
This input is used as the emergency stop input.
38
4.2.8 Outputs
CONF. OUTPUT-1 (Outputs->Conf. output-1) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function 0-NOT USED
1-AIR FLAP CONTROL 0 129 71
2-ALARM RESET
3-AUDIBLE ALARM
4-AUTO START INHIBIT
5-AUXILIARY SOURCE 1 FAILURE
6-BATTERY HIGH VOLTAGE
7-BATTERY LOW VOLTAGE
8-CALLING FOR SCHEDULED RUN(EXERCISE)
9-AUXILIARY SOURCE 2 FAILURE
10-RESERVED
11-RESERVED
12-COMMON ALARM
13-COMMON ELECTRICAL TRIP ALARM
14-COMMON SHUTDOWN ALARM
15-COMMON WARNING ALARM
16-RESERVED
17-RESERVED
18-RESERVED
19-SOURCE 1 CRANK RELAY ENERGISED (For generator application)
20-COOLING DOWN TIMER IN PROGRESS
21-SOURCE 2 CRANK RELAY ENERGISED (For generator application)
22-DELAYED ALARM ACTIVE
23-DIGITAL INPUT1 ACTIVE
24-DIGITAL INPUT2 ACTIVE
25-DIGITAL INPUT3 ACTIVE
26-DIGITAL INPUT4 ACTIVE
27-DIGITAL INPUT5 ACTIVE
28-DIGITAL INPUT6 ACTIVE
29-DIGITAL INPUT7 ACTIVE
30-EXPANSION INPUT1 ACTIVE
31-EXPANSION INPUT2 ACTIVE
32-EXPANSION INPUT3 ACTIVE
33-EXPANSION INPUT4 ACTIVE
34-EXPANSION INPUT5 ACTIVE
35-EXPANSION INPUT6 ACTIVE
36-EXPANSION INPUT7 ACTIVE
37-EXPANSION INPUT8 ACTIVE
38-DIGITAL INPUT8 ACTIVE
39-EMERGENCY STOP
40-FAILED TO START SOURCE 2 (For generator application)
41-FAILED TO STOP SOURCE 2(For generator application)
42-FAILED TO START SOURCE 1 (For generator application)
43-FAILED TO STOP SOURCE 1(For generator application)
44-RESERVED
45-SOURCE 2 AT REST(For generator application)
46-SOURCE 2 AVAILABLE
47-SOURCE 2 CLOSED AUXILIARY
48-SOURCE 2 FAIL TO CLOSE
49-SOURCE 2 FAIL TO OPEN
50-SOURCE 2 HIGH FREQUENCY
51-SOURCE 2 FAILURE
52-SOURCE 2 HIGH VOLTAGE
53-RESERVED
54-SOURCE 2 LOAD INHIBIT
55-SOURCE 2 LOW FREQUENCY
56-RESERVED
57-SOURCE 2 LOW VOLTAGE
58-RESERVED
59-SOURCE 2 STOPPING(For generator application)
60-SOURCE 2 OPEN BREAKER
61-HORN OUT LATCHED
62-HORN OUT PULSED
63-LAMP TEST
64-RESERVED
65-SOURCE 1 AVAILABLE
66-SOURCE 1 AT REST (For generator application)
67-SOURCE 1 STOPPING (For generator application)
68-SOURCE 1 CLOSED AUXILIARY
69-SOURCE 1 FAIL TO CLOSE
70-SOURCE 1 FAIL TO OPEN
71-SOURCE 1 FAILURE
72-SOURCE 1 HIGH FREQUENCY
73-SOURCE 1 HIGH VOLTAGE
74-SOURCE 1 LOAD INHIBIT
75-SOURCE 1 LOW FREQUENCY
76-SOURCE 1 LOW VOLTAGE
77-SOURCE 1 OPEN BREAKER
78-SOURCE 2 NO LOADING COMMAND
79-SOURCE 1 NO LOADING COMMAND
80-SOURCE 1 OVER CURRENT PREALARM
81-SOURCE 1 OVER CURRENT
82-SOURCE 1 OVER POWER PREALARM
83-SOURCE 2 OVER CURRENT PREALARM
84-SOURCE 2 OVER CURRENT
85-SOURCE 2 OVER POWER PREALARM
86-SOURCE 2 OVER POWER SHUTDOWN
87-SOURCE 1 OVER POWER SHUTDOWN
88-RESERVED
89-PANEL LOCK
90-RESERVED
91-RESERVED
92-RESERVED
93-REMOTE START SOURCE 1 (For generator application)
94-REMOTE START SOURCE 2 (For generator application)
95-SOURCE 1 SHORT CIRCUIT
96-SOURCE 2 SHORT CIRCUIT
97-RESERVED
98-SOURCE 1 STOP RELAY ENERGISED (For generator application)
99-STARTING ALARM ARMED
100-SOURCE 2 STOP RELAY ENERGISED (For generator application)
101-SYSTEM AUTO MODE
102-SYSTEM MANUAL MODE
103-SYSTEM STOP MODE
104-SYSTEM TEST MODE
105-SOURCE 2 UNDER CURRENT PREALARM
106-SOURCE 2 UNDER CURRENT
107-SOURCE 2 UNDER POWER PREALARM
108-SOURCE 2 UNDER POWER SHUTDOWN
109-RESERVED
110-WAITING FOR SOURCE 1 (For generator application)
111-WAITING FOR SOURCE 2 (For generator application)
112-RESERVED
113-LOAD SUPPLY SOURCE 2
114-LOAD SUPPLY SOURCE 1
115-SOURCE 1 UNDER CURRENT PREALARM
116-SOURCE 1 UNDER CURRENT
117-SOURCE 1 UNDER POWER PREALARM
118-SOURCE 1 UNDER POWER SHUTDOWN
119-RESERVED
120-RESERVED
121-RESERVED
122-REMOTE CONTROL ACTIVE
123-SOURCE 2 REVERSE POWER
124-SOURCE 1 REVERSE POWER
125-RESERVED
126-RESERVED
127-RESERVED
128-RESERVED
129-REMOTE OUTPUT
39
CONF. OUTPUT-2 (Outputs->Conf. output-2) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 51
CONF. EXP. OUTPUT-1 (Outputs->Conf. exp. output-1) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
CONF. EXP. OUTPUT-2 (Outputs->Conf. exp. output-2) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
CONF. EXP. OUTPUT-3 (Outputs->Conf. exp. output-3) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
CONF. EXP. OUTPUT-4 (Outputs->Conf. exp. output-4) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
CONF. EXP. OUTPUT-5 (Outputs->Conf. exp. output-5) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
CONF. EXP. OUTPUT-6 (Outputs->Conf. exp. output-6) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
40
CONF. EXP. OUTPUT-7 (Outputs->Conf. exp. output-7) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
CONF. EXP. OUTPUT-8 (Outputs->Conf. exp. output-8) Min Max Default Unit
Polarity 0- Normally Open (Close To Activate) 0 1 0
1- Normally Close (Open To Activate)
Function The same as Configurable Output-1 options 0 129 12
CONFIGURABLE OUTPUTS SELECTIONS
0 NOT USED
Output is not used
2 ALARM RESET
The output indicates that an alarm reset being performed. Once the alarm reset has been completed, the output
become inactive again. The output could be used to give an external reset signal to external systems.
3 AUDIBLE ALARM
The output indicates that the internal sounder is operating. It may be use for external sounder.
10 RESERVED
11 RESERVED
12 COMMON ALARM
This output indicates that a warning, electrical trip or shutdown alarm has been activated.
41
16 RESERVED
17 RESERVED
18 RESERVED
42
38 DIGITAL INPUT8 ALARM
This output indicates that digital input 8 alarm has occurred.
39 EMERGENCY STOP
This output indicates that an emergency stop alarm has occurred.
44 RESERVED
45 SOURCE 2 AT REST
The output indicates that the generator 2 is not running.
46 SOURCE 2 AVAILABLE
This output indicates when the generator 2 is ready to accept load, i.e. warm up timer has timed out.
51 SOURCE 2 FAILURE
This output indicates that the unit has sensed that a failure of the Source 2. This output will become active
whenever the Source 2 voltage or frequency goes out of limits, or if the auxiliary Source 2 failure input active (if
used) and the Source 2 fail timer has expired.
53 RESERVED
56 RESERVED
43
58 RESERVED
59 SOURCE 2 STOPPING
This output indicates that the engine 2 has been instructed to stop but has not come to rest.
63 LAMP TEST
This output indicates that the module is performing a lamp test. Once the lamp test completed, the output will
become inactive again. The output can be used to feed a lamp test on external modules or panel lamps.
64 RESERVED
65 SOURCE 1 AVAILABLE
This output indicates when the generator 1 is ready to accept load, i.e. warm up timer has timed out.
66 SOURCE 1 AT REST
The output indicates that the generator 1 is not running.
67 SOURCE 1 STOPPING
This output indicates that the engine 1 has been instructed to stop but has not come to rest.
71 SOURCE 1 FAILURE
This output indicates that the unit has sensed that a failure of the Source 1. This output will become active
whenever the Source 1 voltage or frequency goes out of limits, or if the auxiliary Source 1 failure input active (if
used) and the Source 1 fail timer has expired.
44
77 SOURCE 1 OPEN BREAKER
This output used to control the load switching device. For Details see: "BREAKERS Page" section.
88 RESERVED
89 PANEL LOCK
This output indicates that the unit ‘panel lock’ is active. If the panel lock input is active, the unit will not respond to
operation of the Mode select or start buttons. This allows the unit to be placed into a specific mode (such as
auto) and then secured.
90 RESERVED
91 RESERVED
92 RESERVED
97 RESERVED
45
98 SOURCE 1 STOP RELAY ENERGISED
The output mimics the operation of the stop relay for Source 1. Can be used to control external logic circuitry.
(This output is used if the device is used as a Auto Start device.)
109 RESERVED
112 RESERVED
46
119 RESERVED
120 RESERVED
121 RESERVED
125 RESERVED
126 RESERVED
127 RESERVED
128 RESERVED
47
4.2.9 Timers
START TIMERS (Timers->Start timers) Min Max Default Unit
Generator start dely Generator Start Delay 0 9999 0 Sec
Remote start delay Remote Start Delay 0 3600 4 Sec
Generator fail delay Generator fail delay 0 250 45 Sec
Warming up time Warmup Time 0 250 5 Sec
Horn duration Horn Duration 0 (dis) 999 60 Sec
Horn Duration
This timer dictates how long the external horn and the internal sounder will work after the last error
detected. Once after this timer ended unit will do the external horn and the internal sounder reset.
Cooling Timer
This is the time the generator is to run off-load once the load transfer signal has ceased. This gives the
engine time to cool down before shutdown.
DIAL-UP & ETHERNET (Expansion modules->Dial-up & Ethernet) Min Max Default Unit
Disable/enable select Expansion Dal-up&Ethernet Module Selection ENABL/DISBL DISBL
Call back selection Call Back Selection ENABL/DISBL DISBL
GPRS WEB MODULE (Expansion modules->GPRS Web) Min Max Default Unit
Disable/enable select GPRS-Web Module Selection ENABL/DISBL ENABL
SOURCE 2 VOLTAGE OFFSET (User adjustment->Source 2 voltage offset) Min Max Default Unit
Source 2 V1 offset Source 2 V1 Offset -20 20 0 VV
Source 2 V2 offset Source 2 V2 Offset -20 20 0 VV
Source 2 V3 offset Source 2 V3 Offset -20 20 0 VV
51
Event Messages And Explanations:
Battery high warning : Battery high error
Battery low warning : Battery low error
Can bus warning : Can bus error
Changed mode to auto : Changed mode to auto
Changed mode to man : Changed mode to manual
Changed mode to stop : Changed mode to off
Changed mode to test : Changed mode to test
Emergency stop : Emergency stop error
Exp.spare-1 alarm : Expansion module spare 1 error
Exp.spare-2 alarm : Expansion module spare 2 error
Exp.spare-3 alarm : Expansion module spare 3 error
Exp.spare-4 alarm : Expansion module spare 4 error
Exp.spare-5 alarm : Expansion module spare 5 error
Exp.spare-6 alarm : Expansion module spare 6 error
Exp.spare-7 alarm : Expansion module spare 7 error
Exp.spare-8 alarm : Expansion module spare 8 error
S1 fail to start alrm : Fail to start source 1 (for generator application)
S2 fail to start alrm : Fail to start source 2 (for generator application)
GPRS IP not found : Gprs no IP alarm
GPRS reset fail : Gprs reset fail
S1 stop fail : Source 2 stop error (for generator application)
S2 stop fail : Source 2 stop error (for generator application)
Modem response: error : Gprs error response alarm
No respons.from modem : Gprs no response alarm
S1 Over cur. prealr! : Over current pre-alarm for source 1
S1 Over current alarm : Over current alarm for source 1
S1 Over pow. alarm : Over power error for source 1
S1 Over pow. prealarm : Over power pre-alarm for source 1
S1 Reverse pow. alarm : Reverse power alarm for source 1
S1 Short circuit alrm : Short circuit alarm for source 1
S1 Under cur. alarm : Under current error for source 1
S1 Under cur. prealr : Under current pre-alarm for source 1
S1 Under pow. alarm : Under power error for source 1
S1 Under pow.prealarm : Under power pre-alarm for source 1
S1 break.close fail : Source 1 breaker not closed alarm
S1 breaker open fail : Source 1 breaker not opened alarm
S1 over frequency : Source 1 over frequency
S1 over voltage : Source 1 over voltage
S1 phase seq.wrong : Source 1 phase sequence wrong
S1 under frequency : Source 1 under frequency
S1 under voltage : Source 1 under voltage
S2 Over cur. prealr! : Over current pre-alarm for source 2
S2 Over current alarm : Over current alarm for source 2
S2 Over pow. alarm : Over power error for source 2
S2 Over pow. prealarm : Over power pre-alarm for source 2
S2 Reverse pow. alarm : Reverse power alarm for source 2
S2 Short circuit alrm : Short circuit alarm for source 2
S2 Under cur. alarm : Under current error for source 2
S2 Under cur. prealr : Under current pre-alarm for source 2
S2 Under pow. alarm : Under power error for source 2
S2 Under pow.prealarm : Under power pre-alarm for source 2
S2 break.close fail : Source 2 breaker not closed alarm
S2 breaker open fail : Source 2 breaker not opened alarm
S2 over frequency : Source 2 over frequency
S2 over voltage : Source 2 over voltage
S2 phase seq.wrong : Source 2 phase sequence wrong
S2 under frequency : Source 2 under frequency
S2 under voltage : Source 2 under voltage
SMS was not sent : Sms wasn't sent
SMS was sent : Sms was successfully sent
Source 1 OK : Source 1 OK
Source 1 fail : Source 1 error
Source 2 OK : Source 2 OK
Source 2 fail : Source 1 error
Spare-1 alarm : Spare 1 error
Spare-2 alarm : Spare 2 error
Spare-3 alarm : Spare 3 error
Spare-4 alarm : Spare 4 error
Spare-5 alarm : Spare 5 error
Spare-6 alarm : Spare 6 error
Spare-7 alarm : Spare 7 error
Spare-8 alarm : Spare 8 error
52
5. Specifications
Equipment use : Electrical control equipment for generating sets.
Housing & Mounting : 229 mm x 152 mm x 41 mm. (including connectors). Plastic
housing for panel mounting.
Panel Cut-Out : 182mm x 135mm.
Protection : IP65 at front panel.
Weight : Approximately 0,53 Kg.
Environmental rating : Standard, indoor at an altitude of less then 2000 meters
with non-condensing humidity.
Operating/Storage Temperature : -20°C to +70°C / -30°C to +80°C
Operating/Storage Humidity : 90 % max. (non-condensing)
Installation Over Volt. Category : II Appliances, portable equipment
Pollution Degree : II, Normal office or workplace, non conductive pollution
Mode of Operation : Continuous.
DC Battery Supply Voltage : 8 to 32 V Z. Max. operating current is 360 mA.
Cranking Dropouts : Battery voltage can be “0” VDC for max. 50 ms during
cranking (battery voltage should be at least nominal
voltage before cranking).
Battery Voltage Measurement : 8 to 32 V Z, accuracy: 1 % FS, resolution: 0,1 V
Source 1 Voltage Measurement : 3 to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
Resolution: 1 V.
Source 1 Frequency : 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
Source 2 Voltage Measurement : 3 to 300 VAC Ph-N, 5 to 99.9 Hz. Accuracy: 1 % FS,
Resolution: 1 V.
Source 2 Frequency : 5 to 99.9Hz (min. 20 VAC Ph-N) Accuracy: 0,25 % FS,
Resolution: 0,1 Hz.
CT secondary : 5A.
Communication interface : USB device, RS-485 (optional).
Optional Expansion I/O Module : Expansion I/O module including 8 inputs and 8 outputs.
Optional Comm. Modules : Ethernet/Dial-up, GSM/GPRS and Web Server modules.
Relay Outputs : Source 1 contactor relay output 8A@250VV
Source 2 contactor relay output 8A@250VV
Configurable output-5 5A@250VV
Configurable output-6 5A@250VV
Transistor Outputs : Configurable output-1 1A at DC supply voltage
Configurable output-2 1A at DC supply voltage
Configurable output-3 1A at DC supply voltage
Configurable output-4 1A at DC supply voltage
All transistor ouputs supplied from DC supply terminal 22
53
6. Other Informations
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Þ.
Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Thank you very much for your preference to use Emko Elektronik
Your Technology Partner Products.
www.emkoelektronik.com.tr
54