Product Specifications
PSS 2B-2A3 B
Model E69F
Current-to-Pneumatic Signal Converter
Field-Mounted
BOLTED
COVER
THREADED
COVER
WITH GAUGES
Required item
Relay (31-07-009)
The E69F Field-Mounted Current-to-Pneumatic Signal Converter accepts a standard direct current input
signal and converts it to a proportional pneumatic output signal for use with other pneumatic instruments or
control valves. As symbolized by the “CE” Logo marking on the product, this product conforms to the
applicable European Union Directives.
COMPACT AND EASILY MOUNTED particles do not hinder operation of the mechanism,
as sometimes happens with voice coil type
The E69F Converter is a small, compactly designed
instruments.
device which is very simply connected to both
electrical and pneumatic interfaces. It can be easily
mounted to a surface, a valve yoke, or to a nominal
APPLICATION VERSATILITY
DN 50 or 2 in vertical pipe. Choice of input and output signals, split input
ranges, as well as direct or reverse action, makes
MINIMAL EFFECTS FROM AMBIENT this converter easily adaptable for a wide range of
ATMOSPHERIC CONDITIONS applications. Output signals are available to make
this converter particularly suitable for use in valve
The design of the galvanometric motor in the E69F
applications.
Converter provides for generous clearances
between coil and housing. Normal atmospheric
changes which may cause corrosion and dust
MI 018-430 – June 2005
Procedure
NOTE
Any adjustment to the span will interact with the zero adjustment and will change
the initial zero setting. Therefore, any adjustment made to the span must be
followed by readjustment of zero.
Required item
Relay (31-07-009)
Figure 8.
4. Loosen 5/16-inch bellows locknut. Note reference line on bellows. Rotate bellows1 so
that reference line moves toward motor to decrease span or away from motor to
increase span until the error is within ±2%. Tighten bellows locknut.
Repeat Steps 2 and 3.
5. See Figure 9. Loosen the 5/16-inch span locknut and turn the 5/16-inch span
adjustment nut a proportional amount (noted in Step 3) based on the following: 1/6
of a turn (point to point on the hexagonal nut) corrects the error by 0.5%.
7
MI 018-430 – June 2005
8. Apply 20 mA (100%) input and check output for 100 kPa or 15 psi (100%). If
output is not correct, repeat Steps 5 through 7.
9. Apply 4 mA (0%) and check output for 20 kPa or 3 psi (0%). If necessary, readjust
zero screw for correct output.
10. Apply 100% input and check output. If output is not correct, repeat Steps 5 and 8
until both 0% and 100% outputs are correct.
Maintenance
Relay Maintenance
To Remove Relay
Remove the two large screws and pry off relay. See Figure 11. A gasket is supplied with each
replacement relay.
For maintenance details, see Instruction MI 011-493 (Model 40G) or MI 011-491 (Model 40D).
! CAUTION
If converter is equipped with explosionproof cover, three flame arresters are present.
Arresters must remain in place for explosionproof protection.
Required item
Relay (31-07-009)
Figure 11.
To Clean Restrictor
Remove relay. See “To Remove Relay” procedure.
Clean by inserting a 0.1 mm (0.005 in) diameter wire (or Foxboro cleaning wire, Part 0042527)
through orifice.
9
PL 008-645
Page 3
1 2 4 6 8 9 10 30 11 12 13 14 15 16 17 18 19
3 5 7
18
25
26 22
46 44 42 34 41 38 38 35
50 45 43 33 35 40 39 37 34 33
23 24
32
48 47 29 27
31 28
38 B0136EP 2 Strap
39 X0104CY 1 Nut, 0.164-32
40 B0130XG 1 Clamp
41 B0136FN 1 Spacer Washer
42 B0130WS 1 Bracket
43 B0130UG 1 Nozzle Assembly
45 B0130XA 1 Bracket
46 X0166KR 1 Retaining Ring
47 Below 1 Split Range Spring
B0130WU Model Code Output Signal 2 and 3
B0130XQ Model Code Output Signal 7 and 8
Number of Parts
Recommended for
Figure Item Part 1 5 20
Number Number Number Part Name Inst. Inst. Inst.
1 10 Below Tubing, 0.3 m (1 ft) Length 0 1 2
C0138NZ Nozzle Tubing
R0128AA Bellows Tubing
12 Below Galvo Motor Assembly 0 1 2
D0124ZY 10 to 50 mA Input Signal
D0124ZZ 4 to 20 mA Input Signal
14 C0123AX O-Ring, 9.3 mm (0.36 in) I.D. 0 1 3
18 U0103FP Screen 2 2 4
25 B0130VM Gasket 0 1 3
26 B0130VL Plate Assembly 0 1 3
28 F0108FA Relay Model 40K 0 1 3
29 C0100EM Gasket (used with kit above) 0 1 3
31 Below Feedback Assembly 0 0 1
B0130UP Output Signal 2
B0130UQ Output Signal 3
B0130UB Output Signal 7
B0130UC Output Signal 8
2 5 B0130YK Gasket 0 1 2
11 C0123AS O-Ring, 4.5 mm (0.18 in) I.D. 0 1 3
3 11 C0123AS O-Ring, 4.5 mm (0.18 in) I.D. 0 1 3
15 X0144QE O-Ring, 104 mm (4.1 in) I.D. 0 1 2
5 33 D0179EG O-Ring, Cover 0 1 2