Cooling Only R410A(50/60Hz)

0CSL0-03A(Replace: 0CSL0-02A)

P/No. : MFL62069312
Introduction
Preface
New era brings the more sophisticated and advanced buildings which in turn demands for specialized and optimized direct
expansion air conditioning systems. Also energy efficiency, environment friendly, low noise and low maintenance cost are
the features which are essential for these systems.

As a part of vertical integration LG makes all the key components in house, which gives an edge to LG to make better and
latest technology products with best quality in optimized time.

systems with are equipped with DC inverter technology and R410A refrigerant which is perfect solution to various
installation locations.

This Engineering product data book incorporates information about the product itself, its installation and designing for
system.

The comprehensive study of this book will improve your knowledge about the system and its application in details.

LG Electronics Inc.
Air Conditioning & Energy Solution Company
General information
1. Model line up
2. Nomenclature
1. Model line up
Model Name
Category Type Chassis Capacity class, kBtu/h

General information
18 21 24 30 36 42 48 54
ATNQ18GPLE3
TP ATNQ21GPLE3 ATNQ24GPLE5 ATNQ36GPLE5
ATNQ18GPLE5

TN ATNQ24GNLE3
Ceiling
4way
cassette ATNQ48GMLE3 ATNQ54GMLE3
TM ATNQ24GMLE6 ATNQ30GMLE3 ATNQ36GMLE3 ATNQ42GMLE3
ATNQ48GMLE5 ATNQ54GMLE5

TQ ATNQ18GQLE5 ATNQ24GQLE5

AVNQ18GJLA0 AVNQ24GJLA0
VJ AVNQ21GJLA0
AVNQ18GJLA2 AVNQ24GJLA2
AVNQ36GKLA0
Ceiling suspended VK AVNQ30GKLA0
AVNQ36GKLA2
AVNQ48GLLA0 AVNQ54GLLA0
VL AVNQ42GLLA0
AVNQ48GLLA2 AVNQ54GLLA2

BH ABNQ18GHLA0 ABNQ21GHLA0
Middle
static
BG ABNQ24GGLA0 ABNQ30GGLA0 ABNQ36GGLA0
Pressure(1)

BR ABNQ42GRLA0 ABNQ48GRLA0 ABNQ54GRLA0

Ceiling M1 ABNQ18GM1A2 ABNQ24GM1A2


concealed Middle
duct static M2 ABNQ36GM2A2
Pressure(2)
M3 ABNQ48GM3A2 ABNQ54GM3A2

ABNQ18GL2A0
Low L2 ABNQ21GL2A0
ABNQ18GL2A1
static
pressure ABNQ24GL3A0
L3
ABNQ24GL3A1

APNQ36GRA1
PR4 APNQ30GRA1
APNQ36GRA2
Floor standing
APNQ48GTA1
PT2 APNQ42GTA1
APNQ48GTA2

Cooling Only R410A(50/60Hz) _ 1


2. Nomenclature
2.1 Indoor units(Global)
General information

A T N Q 24 G N L E 3

Serial Number
Functions
A : Basic
E : Elevation grille

Look : Basic

Chassis Name
Electrical Ratings
G : 220-240V, 1Ø, 50Hz / 220V, 1Ø, 60Hz
L : 380-415V, 3Ø, 50Hz / 380V, 3Ø, 60Hz
Capacity Code based on ‘kBtu/h’ units
Model Type
Q: Cooling Only
R410A Single A Indoor Unit
ATN : Ceiling cassette type indoor unit
AVN : Convertible, Ceiling suspended type indoor unit
ABN : Ceiling concealed duct type indoor unit
APN : Floor Standing type indoor unit

2 _ Cooling Only R410A(50/60Hz)


n Indoor units
1. Ceiling cassette 4-way
2. Ceiling suspended
3. Ceiling concealed duct - Middle static Pressure(1)
4. Ceiling concealed duct – Low static pressure
5. Floor standing
6. Ceiling concealed duct – Middle static Pressure(2)
1. Ceiling cassette 4-way
1.1 List of functions
1.2 Specifications
1.3 Dimensions
1.4 Piping diagrams
1.5 Wiring diagrams
1.6 Air flow and temperature distributions (Reference data)
1.7 Sound levels
1.8 Controller
1.9 Installation
1. Ceiling cassette 4-way
1.1 List of functions
ATNQ24GNLE3 / ATNQ30GMLE3
ATNQ18GPLE3 ATNQ36GMLE3 / ATNQ42GMLE3
Category Functions
ATNQ21GPLE3 ATNQ48GMLE3 / ATNQ54GMLE3
ATNQ24GMLE6
Air supply outlet 4 4
Airflow direction control(left & right) X X
Airflow direction control(up & down) Auto Auto
Auto swing(left & right) X X
Air flow Auto swing(up & down) O O
Airflow steps(fan/cool/heat) 4/5/- 4/5/-
Chaos wind(auto wind) O O
Jet cool O O
Swirl wind O O
Triple filter (Deodorizing) X X
Plasma air purifier PTPKM0 PTPKM0
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O

Indoor units
Drain pump O O
E.S.P. control X X
Installation Electric heater X X
High ceiling operation* O O
Auto Elevation Grille PTEGM0 PTEGM0
Hot start X X
Reliability Self diagnosis O O
Soft dry operation X X
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) O O
Auto restart O O
Child lock* O O
Convenience Forced operation O O
Group control* O O
Sleep mode O O
Timer(on/off) O O
Timer(weekly)* O O
Two thermistor control* O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller O(PQWRCQ0FDB) O(PQWRCQ0FDB)
General central controller (Non LGAP) X X
CAC
Network Soluation(LGAP) X O
Network
Dry contact X PQDSA(1) / PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor X X
Others
Group Control wire PZCWRCG3 PZCWRCG3

Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Cooling Only R410A(50/60Hz) _ 1


1. Ceiling cassette 4-way

ATNQ24GPLE5 / ATNQ24GQLE5
ATNQ18GPLE5
Category Functions ATNQ36GPLE5 / ATNQ48GMLE5
ATNQ18GQLE5
ATNQ54GMLE5
Air supply outlet 4 4
Airflow direction control(left & right) X X
Airflow direction control(up & down) Auto Auto
Auto swing(left & right) X X
Air flow Auto swing(up & down) O O
Airflow steps(fan/cool/heat) 4/5/- 4/5/-
Chaos wind(auto wind) O O
Jet cool O O
Swirl wind O O
Triple filter (Deodorizing) X X
Plasma air purifier PTPKM0 PTPKM0
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump O O
E.S.P. control X X
Indoor units

Installation Electric heater X X


High ceiling operation* O O
Auto Elevation Grille PTEGM0 PTEGM0
Hot start X X
Reliability Self diagnosis O O
Soft dry operation X X
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) O O
Auto restart O O
Child lock* O O
Convenience Forced operation O O
Group control* O O
Sleep mode O O
Timer(on/off) O O
Timer(weekly)* O O
Two thermistor control* O O
Wired remote controller PQRCVSL0QW/PQRCVSL0 PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller O O
General central controller (Non LGAP) X X
CAC
Network Soluation(LGAP) X O
Network
Dry contact X PQDSA(1)/PQDSB(1)
function
PI 485(for Indoor Unit) X ×
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others
Group Control wire PZCWRCG3 PZCWRCG3

Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

2 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
1.2 Specifications
Model Name ATNQ18GPLE3 ATNQ21GPLE3

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 840 × 204 × 840 840 × 204 × 840
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 33-1/16 x 8-1/32 x 33-1/16
Net Weight Body kg (lbs) 20.5 (45.2) 20.5 (45.2)
Heat (Row x Column x Fins per inch) x No. - (2 x 8 x 19) x 1 (2 x 8 x 19) x 1
Exchanger Face Area m2 0.35 0.35
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 17.0 / 15.0 / 13.0 20.0 / 18.0 / 16.0
Air Flow Rate

Indoor units
H/M/L ft3/min 600 / 530 / 459 706 / 636 / 565
Type - BLDC BLDC
Fan Motor
Output W x No. 40 x 1 40 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 32 40 / 38 / 36
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 3


1. Ceiling cassette 4-way

Model Name ATNQ24GNLE3 ATNQ30GMLE3

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 1.00
Casing Color - - -
WxHxD mm 840 × 246 × 840 840 × 288 × 840
Dimensions Body
WxHxD inch 33-1/16 x 9-11/16 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16
Net Weight Body kg (lbs) 22.0 (48.5) 24.6 (54.2)
Heat (Row x Column x Fins per inch) x No. - (2 x 10 x 19) x 1 (2 x 12 x 19) x 1
Exchanger Face Area m2 0.43 0.53
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 23.0 / 21.0 / 19.0 30.0 / 28.0 / 26.0
Air Flow Rate
H/M/L ft3/min 812 / 742 / 671 1,060 / 989 / 918
Type - BLDC BLDC
Indoor units

Fan Motor
Output W x No. 166.3 x 1 166.3 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 40 / 38 / 36 43 / 41 / 39
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

4 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way

Model Name ATNQ36GMLE3 ATNQ42GMLE3

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 1.00 1.00
Casing Color - - -
WxHxD mm 840 × 288 × 840 840 × 288 × 840
Dimensions Body
WxHxD inch 33-1/16 x 11-11/32 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16
Net Weight Body kg (lbs) 24.6 (54.2) 28.0 (61.7)
1# (Row x Column x Fins per inch) x No. - (2 x 12 x 19) x 1 (2 × 12 × 19) × 1
Heat
2# (Row x Column x Fins per inch) x No. - (1 × 10 × 19) × 1
Exchanger
Face Area m 2
0.53 0.53
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 30.0 / 28.0 / 26.0 32.0 / 30.0 / 28.0
Air Flow Rate
H/M/L ft3/min 1,060 / 989 / 918 1,130 / 1,060 / 989

Indoor units
Type - BLDC BLDC
Fan Motor
Output W x No. 166.3 x 1 135.8 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.4 (7.2)
Sound Pressure Level H/M/L dB(A) 43 / 41 / 39 44 / 42 / 40
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 5


1. Ceiling cassette 4-way

Model Name ATNQ48GMLE3 ATNQ54GMLE3 ATNQ24GMLE6

220-240, 1, 50 220-240, 1, 50 220-240, 1, 50


Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60 220, 1, 60
Power Input W - - -
Running Current A 1.00 1.00 1.00
Casing Color - - - -
WxHxD mm 840 × 288 × 840 840 × 288 × 840 840 × 288 × 840
Dimensions Body
WxHxD inch 33-1/16 x 11-11/32 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16
Net Weight Body kg (lbs) 28.0 (61.7) 28.0 (61.7) 28.0 (61.7)
1# (Row x Column x Fins per inch) x No. - (2 × 12 × 19) × 1 (2 x 12 x 19) x 1 (2 x 12 x 19) x 1
Heat
2# (Row x Column x Fins per inch) x No. (1 × 10 × 19) × 1 (1 × 10 × 19) × 1 (1 × 10 × 19) × 1
Exchanger
Face Area m2 0.53 0.53 0.53
Type - Turbo Fan Turbo Fan Turbo Fan
Fan H/M/L m3/min 32.0 / 30.0 / 28.0 32.0 / 30.0 / 28.0 23.0 / 21.0 / 19.0
Air Flow Rate
H/M/L ft3/min 1,130 / 1,060 / 989 1,130 / 1,060 / 989 812 / 742 / 671
Indoor units

Type - BLDC BLDC BLDC


Fan Motor
Output W x No. 135.8 x 1 135.8 x 1 135.8 x 1
Dehumidification Rate l / h (pts/h) 3.6 (7.7) 3.6 (7.7) 2.5 (5.3)
Sound Pressure Level H/M/L dB(A) 44 / 42 / 40 44 / 42 / 40 40 / 38 / 36
Sound Power Level Cooling dB(A) - - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 19.05 (3/4) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0 Ø 32.0 / 25.0
Safety Devices - Fuse Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75 (18) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0) 5.0 (11.0)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

6 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way

Model Name ATNQ18GPLE5 ATNQ18GQLE5

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 840 × 204 × 840 570 × 256 × 570
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 22-7/16 x 8-7/16 x 22-7/16
Net Weight Body kg (lbs) 19.6 (43.2) 15 (33)
Heat (Row x Column x Fins per inch) x No. - (2 x 8 x 21) x 1 (2 x 10x 18) x 1
Exchanger Face Area m2 0.33(3.55) 0.27(2.9)
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 17.0 / 15.0 / 13.0 13.0 / 12.0 / 11.0
Air Flow Rate
H/M/L ft3/min 600 / 530 / 459 459 / 424 / 388
Type - BLDC BLDC

Indoor units
Fan Motor
Output W x No. 50.3 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.1 (4.5)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 32 43 / 41 / 38
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UQC
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 700 × 22 ×700
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 27-9/16 x 7/8 x 27-9/16
Net weight kg (lbs) 5.0 (11.0) 3.0 (6.6)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 7


1. Ceiling cassette 4-way

Model Name ATNQ24GPLE5 ATNQ24GQLE5

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 840 × 204 × 840 570 × 256 × 570
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 22-7/16 x 8-7/16 x 22-7/16
Net Weight Body kg (lbs) 19.7 (43.4) 15 (33)
Heat (Row x Column x Fins per inch) x No. - (2 x 8 x 21) x 1 (2 x 10x 18) x 1
Exchanger Face Area m2 0.33(3.55) 0.27(2.9)
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 18.0 / 16.0 / 14.0 13.0 / 12.0 / 11.0
Air Flow Rate
H/M/L ft3/min 636 / 565 / 494 459 / 424 / 388
Type - BLDC BLDC
Indoor units

Fan Motor
Output W x No. 50.3 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.5 (5.3)
Sound Pressure Level H/M/L dB(A) 40 / 38 / 36 43 / 41 / 38
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UQC
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 700 × 22 ×700
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 27-9/16 x 7/8 x 27-9/16
Net weight kg (lbs) 5.0 (11.0) 3.0 (6.6)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

8 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way

Model Name ATNQ36GPLE5 ATNQ48GMLE5 ATNQ54GMLE5

220-240, 1, 50 220-240, 1, 50 220-240, 1, 50


Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60 220, 1, 60
Power Input W - - -
Running Current A 1.00 1.00 1.00
Casing Color - - - -
WxHxD mm 840 × 204 × 840 840 × 288 × 840 840 × 288 × 840
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16
Net Weight Body kg (lbs) 20.5 (45.2) 28.0 (61.7) 28.0 (61.7)
Heat (Row x Column x Fins per inch) x No. - (3 x 8 x 21) x 1 (3 x 12 x 21) x 1 (3 x 12 x 21) x 1
Exchanger Face Area m2 0.33(3.55) 0.49(5.27) 0.49(5.27)
Type - Turbo Fan Turbo Fan Turbo Fan
Fan H/M/L m3/min 19.0 / 17.0 / 15.0 32.0 / 30.0 / 28.0 32.0 / 30.0 / 28.0
Air Flow Rate
H/M/L ft3/min 671 / 600 / 530 1,130 / 1,060 / 989 1,130 / 1,060 / 989
Type - BLDC BLDC BLDC

Indoor units
Fan Motor
Output W x No. 50.3 x 1 135.8 x 1 135.8 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.6 (7.7) 3.6 (7.7)
Sound Pressure Level H/M/L dB(A) 43 / 41 / 39 46 / 44 / 42 46 / 44 / 42
Sound Power Level Cooling dB(A) - - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32)
Safety Devices - Fuse Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0) 5.0 (11.0)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 9


Indoor units

TP Chassis

ATNQ18GPLE3
ATNQ21GPLE3
ATNQ18GPLE5
ATNQ24GPLE5
ATNQ36GPLE5
1.3 Dimensions

10 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
1. Ceiling cassette 4-way

ATNQ24GNLE3
TN Chassis

Indoor units

Cooling Only R410A(50/60Hz) _ 11


Indoor units

TM Chassis

ATNQ30GMLE3
ATNQ36GMLE3
ATNQ42GMLE3
ATNQ48GMLE3
ATNQ54GMLE3
ATNQ24GMLE6
ATNQ48GMLE5
ATNQ54GMLE5

12 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
1. Ceiling cassette 4-way

ATNQ18GQLE5
ATNQ24GQLE5
TQ Chassis

Indoor units

Cooling Only R410A(50/60Hz) _ 13


1. Ceiling cassette 4-way
1.4 Piping diagrams
Gas pipe connection port
Heat exchanger
(flare connection)

Cooling Thermistor for


Turbo fan Evaporator
outlet temperature Thermistor for
M suction air
temperature

Thermistor for
Evaporator inlet
temperature

Liquid pipe connection port


Indoor units

(flare connection)

Description PCB Connector

Thermistor for suction air temperature CN-ROOM

Thermistor for evaporator inlet temperature CN-PIPE / IN

Thermistor for evaporator outlet temperature CN-PIPE / OUT

n Refrigerant pipe connection port diameters


[Unit : mm(inch)]

Model Gas Liquid

ATNQ18GPLE3 ATNQ18GPLE5
Ø12.7(1/2) Ø6.35(1/4)
ATNQ21GPLE3 ATNQ18GQLE5

ATNQ24GNLE3 ATNQ24GMLE6
ATNQ30GMLE3 ATNQ24GPLE5
ATNQ36GMLE3 ATNQ24GQLE5 Ø15.88(5/8) Ø9.52(3/8)
ATNQ42GMLE3 ATNQ36GPLE5
ATNQ48GMLE3 ATNQ48GMLE5

ATNQ54GMLE3 ATNQ54GMLE5 Ø19.05(3/4) Ø9.52(3/8)

14 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
1.5 Wiring diagrams
Models : ATNQ18GPLE3 / ATNQ21GPLE3 / ATNQ24GNLE3 / ATNQ30GMLE3 / ATNQ36GMLE3 /
ATNQ42GMLE3 / ATNQ48GMLE3 / ATNQ54GMLE3 / ATNQ24GMLE6

Indoor units
Models : ATNQ18GPLE5 / ATNQ24GPLE5 / ATNQ36GPLE5 / ATNQ48GMLE5 / ATNQ54GMLE5

Cooling Only R410A(50/60Hz) _ 15


1. Ceiling cassette 4-way

Models : ATNQ18GQLE5 / ATNQ24GQLE5


Indoor units

16 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
1.6 Air flow and temperature distributions (Reference data)
Model : ATNQ18GPLE3 / ATNQ18GPLE5
Cooling
Discharge angle: 30°

Air velocity [m/s]

2.7m
2.0 2.0
1.5 1.5 2m
0.5 0.5
1.0 1.0
1m

0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Indoor units
Temperature [°C]

2.7m
18 18
24 24 2m
20 20

22 22 1m

0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Model : ATNQ21GPLE3 / ATNQ24GPLE5


Cooling
Discharge angle: 30°

Air velocity [m/s]

2.7m
2.5 2.5
2.0 2.0
1.5 1.5 2m

1.0 1.0
1m
0.5 0.5

0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Temperature [°C]

2.7m
24 18 18 24
2m
20 20

22 1m
22

0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Cooling Only R410A(50/60Hz) _ 17


1. Ceiling cassette 4-way
Model : ATNQ24GNLE3 / ATNQ24GMLE6 / ATNQ36GPLE5
Cooling
Discharge angle: 30°

Air velocity [m/s]

2.7m
3.0 3.0
2.0 2.0 2m
1.5 1.5

1.0 1.0
1m
0.5 0.5

0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]
Indoor units

2.7m
18 18
2m
20 20
24 24

22 22 1m

0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Model : ATNQ30GMLE3 / ATNQ36GMLE3


Cooling
Discharge angle: 30°

Air velocity [m/s]

3.2m
4.0 4.0
3.0 3.0
2.0 2.0
1.5 1.5 2m

1.0 1.0
1m
0.5 0.5

0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]

3.2m

24 18 18 24

20 20
2m

22 1m
22

0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

18 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
Model : ATNQ42GMLE3 / ATNQ48GMLE3 / ATNQ54GMLE3 / ATNQ48GMLE5 / ATNQ54GMLE5
Cooling
Discharge angle: 30°

Air velocity [m/s]

3.2m
4.0 4.0
3.0 3.0

2.0 2.0
2m
1.5 1.5

1.0 1.0 1m
0.5 0.5

0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Temperature [°C]

Indoor units
3.2m
18 18 24
24
20 20
2m
22 22

1m

0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m

Model : ATNQ18GQLE5 / ATNQ24GQLE5


Cooling
Discharge angle: 40°

Air velocity [m/s]

2.7m

2.0 2.0 2m
1.5 1.5

1.0 1m
1.0

0.5 0.5
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Temperature [°C]

2.7m
18 18
20 20 2m

22 22
1m

24 24
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m

Cooling Only R410A(50/60Hz) _ 19


1. Ceiling cassette 4-way
1.7 Sound levels
Overall
Notes :
- Sound measured at 1.5m below the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operation condition
Ceiling - Reference accoustic pressure 0dB = 20μPa
1.5m - Sound level will vary depending on a range of factors such as the
construction(acoustic absorption coefficient) of particular room in
which the equipment is installed.
- The operating conditions are assumed to be standard.

Sound Level(H/M/L) [dB(A)] Sound Level(H/M/L) [dB(A)]


Model Model
H M L H M L
ATNQ18GPLE3 36 34 32 ATNQ18GPLE5 36 34 32
ATNQ21GPLE3 40 38 36 ATNQ18GQLE5 43 41 38
ATNQ24GNLE3 40 38 36 ATNQ24GPLE5 40 38 36
ATNQ30GMLE3 43 41 39 ATNQ24GQLE5 43 41 38
Indoor units

ATNQ36GMLE3 43 41 39 ATNQ36GPLE5 43 41 39
ATNQ42GMLE3 44 42 40 ATNQ48GMLE5 46 44 42
ATNQ48GMLE3 44 42 40 ATNQ54GMLE5 46 44 42
ATNQ54GMLE3 44 42 40
ATNQ24GMLE6 40 38 36

Sound pressure level


ATNH18GQLE2 ATNQ24GNLE3
ATNQ18GQLE5 ATNQ21GPLE3 ATNQ24GQLE5
80 80 80

n High n High n High


70 70 70
Octave Band Sound Pressure Level (0dB = 20µPa)
Octave Band Sound Pressure Level (0dB = 20µPa)

Octave Band Sound Pressure Level (0dB = 20µPa)

NC-65 NC -65 NC -65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

20 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
ATNQ30GMLE3 ATNQ42GMLE3 ATNQ24GMLE6
ATNQ36GMLE3 ATNQ48GMLE3
ATNQ54GMLE3
80 80 80

n High n High n High


70 70 70
Octave Band Sound Pressure Level (0dB = 20µPa)

Octave Band Sound Pressure Level (0dB = 20µPa)

Octave Band Sound Pressure Level (0dB = 20µPa)


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

Indoor units
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

ATNQ18GPLE5 ATNQ24GPLE5 ATNQ36GPLE5


80 80 80

n High n High n High


70 70 70
Octave Band Sound Pressure Level (0dB = 20µPa)

Octave Band Sound Pressure Level (0dB = 20µPa)

Octave Band Sound Pressure Level (0dB = 20µPa)


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

ATNQ48GMLE5 ATNQ54GMLE5
80 80

n High n High
70 70
Octave Band Sound Pressure Level (0dB = 20µPa)

Octave Band Sound Pressure Level (0dB = 20µPa)

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

Cooling Only R410A(50/60Hz) _ 21


1. Ceiling cassette 4-way
1.8 Controller
Wireless remote control
The controls will look like the following.

1. VANE ANGLE Button


Used to set each vane angle.
2. FUNCTION SETTING Button
Used to set or clear Auto Clean, Smart Clean, Electric
heater or Individual vane angle control.
3. ON/OFF Button
1 Used to turn on/off the unit.
2 10
4. JET COOL Button
11 Speed cooling operates super high fan speed.
3 12 5. LEFT/RIGHT AIRFLOW Button (OPTIONAL)
Used to set the desired left/right(horizontal) airflow direction.
Indoor units

4 13
6. UP/DOWN AIRFLOW Button
5 Used to stop or start louver movement and set the desired
6 14 up/down airflow direction.
7 7. ON TIMER Button
8 15
16 Used to set the time of starting operation.
8. SLEEP TIMER Button
9 17 Used to set the time of sleeping operation.
9. SET / CLEAR Button
Used to set/clear the timer.
Used to set the current time(if it input for 3sec.)
10. PLASMA Button (OPTIONAL)
Used to start or stop the plasma-purification function.
Operation Mode 11. ROOM TEMPERATURE SETTING Button
Used to select the room temperature.
Cooling Mode 12. OPERATION MODE SELECTION Button
Used to select the operation mode.
Auto Mode or Auto Changeover 13. INDOOR FAN SPEED SELECTION Button
Used to select fan speed in four steps low, medium, high
Dehumidification mode and chaos.
14. ROOM TEMPERATURE CHECKING Button
Heating Mode Used to check the room temperature.
15. OFF TIMER Button
Fan Mode Used to set the time of stopping operation.
16. TIMER SETTING(Up/Down)/LIGHT Button
• Cooling Model( ), Heat Pump Model( ) Used to set the timer.
Used to adjust the brightness.(if it is not time adjust mode)
17. RESET Button
Used to reset the remote controller.

22 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
1.9 Installation
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Long life filter


Air
return
Remote
Air supply

Indoor units
Controller

1.9.1 Accessories
Check whether the following accessories are included with your unit.

1) Standard accessories

Washer for Insulation for


Name Drain hose Clamp metal Clamp (Other)
hanging backet fitting

Quantity 1 EA 1 EA 8 EA 8 EA 1 SET

• Paper pattern for


installation
• Owner's manual
• Installation manual
Diagram for gas pipe

for liquid pipe

Cooling Only R410A(50/60Hz) _ 23


1. Ceiling cassette 4-way
1.9.2 Selection of the best location 1.9.3 Precautions regarding cassette
• There should not be any heat source or steam near the unit. indoor unit installation
• There should not be any obstacles to the air circulation.
• There should be provision of easy condensate drain.
1) Main points about the indoor installation
• Taking into accounting the noise prevention criteria, spot • In case of high height ceiling
the installation location. In general commercial places and offices though the
• Do not install the unit near the door way. height of the ceiling is 2.3~2.7m, the ceiling height can
• Keep proper distances, of the unit, from ceiling, fence, be 3.1~3.6m. In such cases because of the temperature
floor, walls and other obstacles as shown in figure. difference with the floor the heating effect can fall down.
• The indoor unit must have the maintenance space.

Discharge
Suction
more
10 or

Ceiling High elevation Hot air


Ceiling Board of the ceiling
Ceiling Board Outdoor
300 or less Cold air
side (Entering of air by
Indoor units

frequent opening
and closing of door)
or more

500 or 500 or
1000

more more
H

• Countermeasure method
Unit : mm
① Air conditioner must be able to operate in high ceiling
conditioner.
Floor
② Plan to install the circulator.
③ The air discharge port is made to give more airflow to the
NOTE down wood directions.
Above figure means minimum value. Please keep these ④ The gate or exit of the building is protected by dual door
value at least. system.
• High Ceiling mode selection 2) In case the floor or surfaces of the place
Capacity ≤ 9.0 kW >9.0kW Mode Selection to be air conditioned is in direct contact
H ≤ 2.3m H ≤ 2.7m Low Ceiling with the outdoor air
Ceiling 2.3m < H ≤ 2.7m 2.7m < H ≤ 3.2m Standard
• The floor of the heating room indirect contact with
Height 2.7m < H ≤ 3.1m 3.2m < H ≤ 3.6m High Ceiling
the storeroom, garage or the outside air receives
3.1m < H ≤ 3.6m 3.6m < H ≤ 4.2m Super High Ceiling
the cold air at the floor and the floor temperature
decrease will feel cold at the feet.

Indoor
1500 or more
1500 or more

Low temperature
of the floor

Outdoor side (50~100mm


1500 or more

Insulation required)
Outdoor side Garage

Outdoor side

1500 or more
In such places where the feet comes in direct contact
with floors will give a cold feeling to the floor.

24 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
• Countermeasure: • In case of the multi flow type, use the high humidity kit.
- Use the carpet on the floor (compared to the tiles the car- Otherwise the dew drops can be seen in the unit body.
pet over it will have a 3 degree rise in temperature) • Refrigerant piping: Increase the piping insulation
- Insulating the floor. thickness with thickness above 20 mm.

- Floor heating Refrigerant piping

CAUTION

• Case of cold air intake:


The duct surface will have the dew drops so a insulation
on the duct is a must.(Insulation material: a glass wool of
thickness 25 mm will be appropriate.)
• Others: Inside the ceiling near th air tight seal places
(no escape of the humidity)
3) In case of high temperature or high
humidity between the false ceiling and

Indoor units
ceiling slab(near by the sea, river, lake,
spa)
• In case of temperature of 30 degree and humidity
above 80%, the units body as well as the piping
insulation should be strengthened.
Refer to the picture given below.

Psychrometric chart Enhance additional Grill for ventilation


insulation required area

• In case of multiple indoor cassette units


(recommended)

Indoor unit Indoor unit


Relative humidity 30˚C Ventilator

Lighting

• Places having the temperature and humidity of the


Above 1500mm
surrounding and the
Above 2000mm
The surrounding water sources(sea, river etc.) Above 3000mm

In case the steam is generated between the false ceiling


and the ceiling slab
Due to some nearby by steam source.
- Indoor unit: Insulate the unit body with some insulation
like glass wool atleast 10 mm in thickness.

Additional insulation required

Cooling Only R410A(50/60Hz) _ 25


1. Ceiling cassette 4-way
1.9.4 Ceiling opening dimensions and 1) Install the suspension bolts.
hanging bolt location (Use either a W3/8” or M10 size bolt) Use a hole-in anchor
for existing ceilings, and a sunken insert, sunken anchor or
① The dimensions of the paper pattern for installation are other field supplied parts for new ceilings to reinforce the
the same as those of the ceiling opening dimensions. ceiling to bear the weight of the unit. Adjust clearance from
② Select and mark the position for fixing bolts and piping the ceiling before proceeding further.
hole.
③ Decide the position for fixing bolts slightly tilted to the Ceiling
drain direction after considering the direction of drain Anchor
hose. Long nut or turn-buckle
④ Drill the hole for anchor bolt on the wall. Suspension bolt

False ceiling
TP/TN/TM Series
875(Ceiling opening)
787(Hanging bolt) NOTE
Indoor units

All the above parts are field suppiled.


875(Ceiling opening)
684(Hanging bolt)
671

840 Unit size


840 Unit size

Unit:mm

TQ/TR Series
585~660
517
570

585~660
523

517

570
319

461 Unit:mm

26 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
1.9.5 Indoor unit installation <Ceiling work>

• Installing of the accessories (except for the decoration (2) Adjust the unit to the right position for installa-
panel) before installing the indoor unit is easier. tion.
(3) Assure that the unit is horizontal.
1) Install the indoor unit temporarily.
• The indoor unit is equipped with a built-in drain pump
• Attach the hanger bracket to the suspension bolt. Be sure and float switch. At each of the unit's 3 corners, verify
to fix it securely by using a nut and washer from the upper that it is level by using awater-level or a water-filled
and lower sides of the hanger bracket. vinyl tube. (Otherwise it will result in the malfunctioning
of unit and cause water to drip.)
Hanging bolt
(W3/8 or M10) (4) Remove the washer fixing plate used for
Nut
Flat washer for M10 preventing the washer from falling and tighten
(W3/8 or M10)
(accessory) the upper nut.
Spring washer
(M10) (5) Remove the paper pattern for installation
Flat washer for M10
(accessory)
3) For existing ceilings

Indoor units
(1) Adjust the height and position of the unit.
180mm(TR,Q Chassis)

Ceiling
150mm(TP Chassis)

Keep the length of the bolt (2) Perform steps 3 and 4 in "5.1 For new ceilings".
from the bracket to 40mm

Air Conditioner body


Ceiling board Ceiling board 1.9.6 Connecting pipes to the indoor
Keep the length of 30±3 mm
(TR,Q Chassis) or 15±3 mm unit
(TP, N, M Chassis) between the air
conditioner bottom surface and the
ceiling surface 1) Refrigerant piping work
Set screw of
paper model (4 pieces)
Paper model please refer “REFRIGERANT PIPING WORK”.
for installation
Open the ceiling board
along the outer edge of the
2) Piping insulation
paper model
① Perform heat insulation work completely on both gas and
• The following parts is option. the liquid pipe. Because improper insulation will result
- Hanging Bolt - W 3/8 or M10 condensate formation over pipe.
- Nut - W 3/8 or M10 ② Use the heat insulation material for the refrigerant piping
- Spring Washer - M10 which has an excellent heat resistance (over 120°C).
- Plate Washer - M10
③ Precautions in high humidity circumstance:
Drill the piping hole on the wall slightly tilted to the out-
door side using a Ø 70 hole-core drill. ④ Refer to insulation work

CAUTION
2) For new ceilings
• Make sure to insulate any field piping all the way to the
(1) Refer to the paper pattern for ceiling opening piping connection inside the unit. Any exposed piping
dimension. may cause condensation or burns if touched.
• The center of the ceiling opening is indicated on the
paper pattern for installation.
The center of the unit is indicated on the label attached
to the unit and on the paper pattern for installation.
• First remove paper packaging material from the
4 corners of the paper pattern for installation , fix the
paper pattern to the unit with screws.
• Ceiling height is shown on the side of the paper pattern
for installation. Adjust the height of the unit according to
this indication.

Cooling Only R410A(50/60Hz) _ 27


1. Ceiling cassette 4-way
3) Indoor unit drain piping 1.9.7 Decoration panel
• Drain piping must have down-slope (1/50 to 1/100): be sure
not to provide up-and-down slope to prevent reversal flow. The decoration panel has its installation
• During drain piping connection, be careful not to exert direction.
extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the Before installing the decoration panel, always
indoor unit is 32mm. remove the paper template.

Upward
Pipe clamp 1. Remove the packing and take out air inlet grille from
routing
not allowed front panel.
Indoor unit

Front grille
Maintenance
drain port

300mm or less
1 -1.5m
Indoor units

700 or less

2. Remove the Corner covers of the panel.


Drain raising pipe
Clamp metal(attached) Drain hose(attached)

Piping material: Polyvinyl chloride pipe VP-25 and pipe


fittings
• Be sure to execute heat insulation on the drain piping. Coner cover
• Install the drain raising pipes at a right angle to the
indoor unit and no more than 300mm from the unit.

Heat insulation material: Polyethylene foam with thick-


ness more than 8 mm.

3. Fit the panel on the unit by inserting hooks as shown in


4) Drain test picture.
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:

Feed water Flexible drain hose


(accessory)
Main
drain pipe Hook clip

Drain
Drain Pump port Glue the joint
Drain hose connection Hook
Use the clip (accessory)

Drain pan

• Connect the main drain pipe to the exterior and leave it


provisionally until the test comes to an end.
• Feed water to the flexible drain hose and check the pip-
ing for leakage.
• Be sure to check the drain pump for normal operating
and noise when electrical wiring is complete.
• When the test is complete, connect the flexible drain
hose to the drain port on the indoor unit.

28 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
4. Insert two screws on diagonal corners of panel. Do not 7. Connect one display connector and two vane control
tighten the bolts completely. (The fixing screws are connectors of front panel to indoor unit PCB.
included in the indoor unit box.) The position marking on PCB is as:
Check the alignment of panel with the ceiling. Height Display connector : CN-DISPLAY
can be adjusted using hanging bolts as shown in pic- Vane control connector: CN-VANE 1,2
ture. Insert the other two screws and tighten all screws
completely.

Indoor units
CN-VANE 1,2 CN-DISPLAY

8. Close the cover for control box.

5. Fit the corner covers.

9. Install the air inlet grille and Filter on the panel.

6. Open two screws of control panel cover.

Screw

Cooling Only R410A(50/60Hz) _ 29


1. Ceiling cassette 4-way
2) Wiring Connection
CAUTION
① Open the control box cover and connect the Remote
Install certainly the decoration panel. controller cord and Indoor power wires.
Cool air leakage causes sweating.
② Remove the control box cover for electrical connection
‘ Water drops fall.
between the indoor and outdoor unit.
(Remove screws ①)
Good example ③ Use the cord clamper to fix the cord.

Air conditioner
unit

Ceiling
board
Decorative panel
Fit the insulator (this part) and
be careful for cool air leakage
Remote
controller
cord
Bad example Air conditioner unit Connection 1
cord
Indoor units

Air Cool air leakage between the 1


indoor unit and Control box cover
(no good) the outdoor (On which the
unit Electric Wiring
Connection is put)
Ceiling
board
Decorative
panel

CAUTION

• The connected cable connected to the indoor and out-


1.9.8 Electric wiring work door unit should be complied with the following specifica-
tions (Rubber insulation, type H05RN-F approved by
1) General instructions HAR or SAA).
① All field supplied parts and materials, electric works must
conform to local codes. NORMAL
Use copper wire only. CROSS-SECTIONAL
GN AREA 0.75mm 2
② Follow the "WIRING DIAGRAM” attached to the unit /YL

body to wire the outdoor unit, indoor units and the remote
20
controller. mm

③ All wiring must be performed by an authorized electri-


cian. • If the supply cord is damaged, it must be replaced by a
④ This system consists of multiple indoor units. Mark each special cord or assembly available from the manufacturer
indoor unit as unit A, unit B..., and be sure the terminal of its service agent.
board wiring to the outdoor unit and indoor units are
properly matched. If wiring and piping between the out-
door unit and an indoor units are mismatched, the sys-
tem may cause a malfunction.
⑤ A circuit breaker capable of shutting down the power
supply to the entire system must be installed.

30 _ Cooling Only R410A(50/60Hz)


1. Ceiling cassette 4-way
Precautions when laying power wiring Connect same thickness wiring to both sides.
Use round pressure terminals for connections to the power
terminal block.

Round pressure terminal

Power wire
r

When none are available, follow the instructions


It is forbidden to connect two to one side.
below.
• Do not connect wiring of different thicknesses to the power
terminal block. (Slack in the power wiring may cause
abnormal heat.)
• When connecting wiring which is the same thickness, do
as shown in the figure below.

Indoor units
• For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
exerted on the terminal block.
It is forbidden to connect wiring of different thicknesses.
• Use an appropriate screwdriver for tightening the terinal
screws. A screwdriver with a small head will strip the head
and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.

WARNING

• Make sure that the screws of the terminal are free from
looseness.

Cooling Only R410A(50/60Hz) _ 31


2. Ceiling suspended
2.1 List of functions
2.2 Specifications
2.3 Dimensions
2.4 Piping diagrams
2.5 Wiring diagrams
2.6 Air flow and temperature distributions (Reference data)
2.7 Sound levels
2.8 Controller
2.9 Installation
2. Ceiling suspended
2.1 List of functions
AVNQ24GJLA0 / AVNQ30GKLA0
AVNQ18GJLA0
Category Functions AVNQ36GKLA0 / AVNQ42GLLA0
AVNQ21GJLA0
AVNQ48GLLA0 / AVNQ54GLLA0
Air supply outlet 1 1
Airflow direction control (left & right) Manual Manual
Airflow direction control (up & down) Auto Auto
Auto swing (left & right) - -
Air flow Auto swing (up & down) O O
Airflow steps (fan/cool/heat) 4/5/- 4/5/-
Chaos wind(auto wind) X X
Jet cool O O
Swirl wind X X
Triple filter (Deodorizing) X X
Plasma air purifier X X
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O

Indoor units
Drain pump X X
E.S.P. control X X
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) X X
Auto Restart O O
Child lock* O O
Convenience Forced operation O O
Group control* O O
Sleep mode X X
Timer(on/off) O O
Timer(weekly)* O O
Two thermistor control* O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller O O
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSA(1) / PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor X X
Others
Group Control wire X X

Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Cooling Only 50Hz/R410A _ 1


2. Ceiling suspended

AVNQ24GJLA2 / AVNQ36GKLA2
Category Functions AVNQ18GJLA2
AVNQ48GLLA2 / AVNQ54GLLA2
Air supply outlet 1 1
Airflow direction control (left & right) Manual Manual
Airflow direction control (up & down) Auto Auto
Auto swing (left & right) - -
Air flow Auto swing (up & down) O O
Airflow steps (fan/cool/heat) 4/5/- 4/5/-
Chaos wind(auto wind) X X
Jet cool O O
Swirl wind X X
Triple filter (Deodorizing) X X
Plasma air purifier X X
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump X X
E.S.P. control X X
Installation Electric heater X X
Indoor units

High ceiling operation X X


Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation X X
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) O O
Auto Restart O O
Child lock* O O
Convenience Forced operation O O
Group control* O O
Sleep mode O O
Timer(on/off) O O
Timer(weekly)* O O
Two thermistor control* O O
Wired remote controller PQRCVSL0QW/PQRCVSL0 PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller O O
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSA(1)/PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others
Group Control wire PZCWRCG3 PZCWRCG3
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

2 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
2.2 Specifications
Model Name AVNQ18GJLA0 AVNQ21GJLA0

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 950 × 650 × 220 950 × 650 × 220
Dimensions Body
WxHxD inch 37-13/32 x 25-19/32 x 8-21/32 37-13/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 20.5(45.2) 20.5(45.2)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.20 (2.15) 0.20 (2.15)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 12.4 / 11.4 / 10.4 12.4 / 11.4 / 10.4
Air Flow Rate

Indoor units
H/M/L ft3/min 438 / 403 / 367 438 / 403 / 367
Type - BLDC BLDC
Fan Motor
Output W x No. 60 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 44 / 43 / 41 44 / 43 / 41
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only 50Hz/R410A _ 3


2. Ceiling suspended

Model Name AVNQ24GJLA0 AVNQ30GKLA0

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.70
Casing Color - - -
WxHxD mm 950 × 650 × 220 1,350 × 650 × 220
Dimensions Body
WxHxD inch 37-13/32 x 25-19/32 x 8-21/32 53-5/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 20.5(45.2) 29.0(63.9)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.20 (2.15) 0.32 (3.42)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 12.4 / 11.4 / 10.4 21.4 / 19.8 / 18.2
Air Flow Rate
H/M/L ft3/min 438 / 403 / 367 756 / 699 / 643
Type - BLDC BLDC
Indoor units

Fan Motor
Output W x No. 60 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 44 / 43 / 41 45 / 43 / 41
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

4 _ Cooling Only 50Hz/R410A


2. Ceiling suspended

Model Name AVNQ36GKLA0 AVNQ42GLLA0

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.70 0.90
Casing Color - - -
WxHxD mm 1,350 × 650 × 220 1,750 × 650 × 220
Dimensions Body
WxHxD inch 53-5/32 x 25-19/32 x 8-21/32 68-29/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 29.0(63.9) 35.0 (77.2)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.32 (3.42) 0.44 (4.68)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 21.4 / 19.8 / 18.2 28.6 / 26.9 / 25.2
Air Flow Rate
H/M/L ft3/min 756 / 699 / 643 1,010 / 950 / 890
Type - BLDC BLDC

Indoor units
Fan Motor
Output W x No. 60 x 1 60 x 2
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 45 / 43 / 41 47 / 46 / 44
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only 50Hz/R410A _ 5


2. Ceiling suspended

Model Name AVNQ48GLLA0 AVNQ54GLLA0

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.90 0.90
Casing Color - - -
WxHxD mm 1,750 × 650 × 220 1,750 × 650 × 220
Dimensions Body
WxHxD inch 68-29/32 x 25-19/32 x 8-21/32 68-29/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 35.0 (77.2) 35.0 (77.2)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.44 (4.68) 0.44 (4.68)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 28.6 / 26.9 / 25.2 31.5 / 29.7 / 28.0
Air Flow Rate
H/M/L ft3/min 1,010 / 950 / 890 1,112 / 1,049 / 989
Type - BLDC BLDC
Indoor units

Fan Motor
Output W x No. 60 x 2 60 x 2
Dehumidification Rate l / h (pts/h) 3.6 (7.7) 3.6 (7.7)
Sound Pressure Level H/M/L dB(A) 47 / 46 / 44 48 / 47 / 45
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

6 _ Cooling Only 50Hz/R410A


2. Ceiling suspended

Model Name AVNQ18GJLA2 AVNQ24GJLA2

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - Morning Fog Morning Fog
WxHxD mm 950 × 650 × 220 950 × 650 × 220
Dimensions Body
WxHxD inch 37-13/32 x 25-19/32 x 8-21/32 37-13/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 19.7 (43.4) 20.7 (45.6)
Heat (Row x Column x Fins per inch) x No. - (2 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.19 (2.05) 0.19 (2.05)
Type - Cross Flow Fan Cross Flow Fan
Fan H/M/L m3/min 12.4 / 11.4 / 10.4 13.9 / 12.9 / 11.9
Air Flow Rate
H/M/L ft3/min 438 / 403 / 367 491 / 456 / 420
Type - BLDC BLDC

Indoor units
Fan Motor
Output W x No. 60 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.1 (4.5)
Sound Pressure Level H/M/L dB(A) 44 / 43 / 41 44 / 43 / 41
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.5(27/32) / 16.0(5/8) Ø 21.5(27/32) / 16.0(5/8)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only 50Hz/R410A _ 7


2. Ceiling suspended

Model Name AVNQ36GKLA2 AVNQ48GLLA2 AVNQ54GLLA2

220-240, 1, 50 220-240, 1, 50 220-240, 1, 50


Power Supply V, Ø, Hz
220, 1, 60 220-240, 1, 50 220-240, 1, 50
Power Input W - - -
Running Current A 0.70 0.90 0.90
Casing Color - Morning Fog Morning Fog Morning Fog
WxHxD mm 1,350 × 650 × 220 1,750 × 650 × 220 1,750 × 650 × 220
Dimensions Body
WxHxD inch 53-5/32 x 25-19/32 x 8-21/32 68-29/32 x 25-19/32 x 8-21/32 68-29/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 28.3 (62.4) 35.0 (77.2) 35.0 (77.2)
Heat (Row x Column x Fins per inch) x No. - (2 x 14 x 21) x 1 (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.31 (3.34) 0.44 (4.68) 0.44 (4.68)
Type - Cross Flow Fan Cross Flow Fan Cross Flow Fan
Fan H/M/L m3/min 21.4 / 19.8 / 18.2 30.0 / 28.3 / 26.6 31.5 / 29.7 / 28.0
Air Flow Rate
H/M/L ft3/min 756 / 699 / 643 1,059 / 999 / 939 1,059 / 999 / 939
Type - BLDC BLDC BLDC
Indoor units

Fan Motor
Output W x No. 60 x 2 60 x 2 60 x 2
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 2.7 (5.7) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 47 / 46 / 44 47 / 46 / 44 48 / 47 / 45
Sound Power Level Cooling dB(A) - - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 21.5(27/32) / 16.0(5/8) Ø 21.5(27/32) / 16.0(5/8) Ø 21.5(27/32) / 16.0(5/8)
Safety Devices - Fuse Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

8 _ Cooling Only 50Hz/R410A


VJ Chassis

AVNQ18GJLA0
AVNQ21GJLA0
AVNQ24GJLA0
AVNQ18GJLA2
AVNQ24GJLA2
2.3 Dimensions
2. Ceiling suspended

Cooling Only 50Hz/R410A _ 9


Indoor units
Indoor units

VK Chassis

AVNQ30GKLA0
AVNQ36GKLA0
AVNQ36GKLA2

10 _ Cooling Only 50Hz/R410A


2. Ceiling suspended

1. Unit should be installed in complance with the


installation manual in the product box.
Air suction grille
2. Unit shall be grounded in accordance with the
local regulations or applicable national codes. Display & signal receiver
3. The unit is powered from the outdoor unit.
So power cable should be connected with the outdoor unit. Front air discharge grille
VL Chassis

AVNQ42GLLA0
AVNQ48GLLA0
AVNQ54GLLA0
AVNQ48GLLA2
AVNQ54GLLA2
2. Ceiling suspended

Cooling Only 50Hz/R410A _ 11


Indoor units
2. Ceiling suspended
2.4 Piping diagrams
6.4 Piping
Models diagrams
: AVNQ18GJLA0 / AVNQ21GJLA0 / AVNQ24GJLA0

Gas pipe connection port


Heat exchanger
(flare connection)

Cooling Cross Flow Fan Thermistor for


evaporator outlet
temperature Thermistor for
M suction air
temperature

Thermistor for
evaporator outlet
temperature
Indoor units

Liquid pipe connection port


(flare connection)

Description PCB Connector

Thermistor for suction air temperature CN-ROOM

Thermistor for evaporator inlet temperature CN-PIPE / IN

Thermistor for evaporator outlet temperature CN-PIPE / OUT

n Refrigerant pipe connection port diameters [Unit : mm(inch)]

Model Gas Liquid


AVNQ18GJLA0
AVNQ21GJLA0 Ø 12.7 (1/2) Ø 6.35 (1/4)
AVNQ18GJLA2
AVNQ24GJLA0
Ø 15.88 (5/8) Ø 9.52 (3/8)
AVNQ24GJLA2

12 _ Cooling Only 50Hz/R410A


2. Ceiling suspended

Models : AVNQ30GKLA0 / AVNQ36GKLA0

Gas pipe connection port


Heat exchanger
(flare connection)

Cooling Cross Flow Fan Thermistor for


evaporator outlet
temperature Thermistor for
M M suction air
temperature

Thermistor for
evaporator outlet
temperature

Liquid pipe connection port

Indoor units
(flare connection)

Description PCB Connector

Thermistor for suction air temperature CN-ROOM

Thermistor for evaporator inlet temperature CN-PIPE / IN

Thermistor for evaporator outlet temperature CN-PIPE / OUT

n Refrigerant pipe connection port diameters [Unit : mm(inch)]

Model Gas Liquid


AVNQ30GKLA0
AVNQ36GKLA0 Ø 15.88 (5/8) Ø 9.52 (3/8)
AVNQ36GKLA2

Cooling Only 50Hz/R410A _ 13


2. Ceiling suspended

Models : AVNQ42GLLA0 / AVNQ48GLLA0 / AVNQ54GLLA0

Gas pipe connection port


Heat exchanger
(flare connection)

Cooling Cross Flow Fan Thermistor for


evaporator outlet
temperature Thermistor for
M M suction air
temperature

Thermistor for
evaporator outlet
temperature

Liquid pipe connection port


Indoor units

(flare connection)

Description PCB Connector

Thermistor for suction air temperature CN-ROOM

Thermistor for evaporator inlet temperature CN-PIPE / IN

Thermistor for evaporator outlet temperature CN-PIPE / OUT

n Refrigerant pipe connection port diameters [Unit : mm(inch)]

Model Gas Liquid


AVNQ42GLLA0
AVNQ48GLLA0 Ø 15.88 (5/8) Ø 9.52 (3/8)
AVNQ48GLLA2
AVNQ54GLLA0
Ø 19.05 (3/4) Ø 9.52 (3/8)
AVNQ54GLLA2

14 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
2.5 Wiring diagrams

Models : AVNQ18GJLA0 / AVNQ21GJLA0 / AVNQ24GJLA0

Indoor units
Models : AVNQ30KLA0 / AVNQ36KLA0 / AVNQ42GLLA0 / AVNQ48GLLA0 / AVNQ54GLLA0

Cooling Only 50Hz/R410A _ 15


2. Ceiling suspended

Model : AVNQ18GJLA2 / AVNQ24GJLA2


Indoor units

Model : AVNQ36GKLA2 / AVNQ48GLLA2 / AVNQ54GLLA2

16 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
2.6 Air flow and temperature distributions (Reference data)
Model : AVNQ18GJLA0 / AVNQ21GJLA0 / AVNQ24GJLA0 / AVNQ18GJLA2 / AVNQ24GJLA2

Cooling
Discharge angle:40°

Air velocity [m/s]


2.7m
0.5
2m

2.5
2.5
1m
2.0

1.0 0.5 2.0


1.5 0.5 1.0
0.5 1.5
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Indoor units
Temperature [°C]
2.7m

2m
26
24 38
24 25

16 1m

36
20
23 28
22 30 32 34
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Model : AVNQ30GKLA0 / AVNQ36GKLA0 / AVNQ36GKLA2

Cooling
Discharge angle:40°

Air velocity [m/s]


2.7m

2m
3.0
3.0
0.5

1m 2.5
2.5 0.5

2.0
1.0 2.0
0.5 1.0 1.5 1.0 1.5
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [°C]
2.7m

25
2m
22 36
23
24 26
16 1m

20 34
22 28 32 26
30
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Cooling Only 50Hz/R410A _ 17


2. Ceiling suspended

Model : AVNQ42GLLA0

Cooling
Discharge angle:10°

Air velocity [m/s]


2.7m
3
2 2.5
1.5 1
0.5 2m
0.25

1
1m
0.5

0.25
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [°C]

19 17 15 2.7m
21
23
Indoor units

25
2m
27

1m
31
29

0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Model : AVNQ48GLLA0 / AVNQ48GLLA2

Cooling
Discharge angle:10°

Air velocity [m/s]


2.5 3 2.7m
0. 5 2
1.5 0.5
2m
0.25
1

1m

0.25
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [°C]

18 16 14 2.7m
20
24 22

28 2m

26

1m

30
28
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

18 _ Cooling Only 50Hz/R410A


2. Ceiling suspended

Model : AVNQ54GLLA0 / AVNQ54GLLA2

Cooling
Discharge angle:10°

Air velocity [m/s]


3 2.7m
2.5
1 2
0.5
2m
1.5
0.25

1m
0.5
0.25
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [°C]

18 16 2.7m
20 14

Indoor units
22
24 2m
26

1m

28 30
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Cooling Only 50Hz/R410A _ 19


2. Ceiling suspended
2.7 Sound levels
Overall
Notes :
- Data is valid at nominal operation condition
1m - Reference accoustic pressure 0dB = 20μPa.
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
1m

room in which the equipment is installed.


Microphone
- The operating conditions are assumed to be standard.

Sound Level(H/M/L) [dB(A)]


Model
H M L
AVNQ18GJLA0 44 43 41
AVNQ21GJLA0 44 43 41
AVNQ24GJLA0 44 43 41
AVNQ30GKLA0 45 43 41
Indoor units

AVNQ36GKLA0 45 43 41
AVNQ42GLLA0 47 46 44
AVNQ48GLLA0 47 46 44
AVNQ54GLLA0 48 47 45

Sound Pressure Level

AVNQ18GJLA0 AVNQ30GKLA0
AVNQ21GJLA0 AVNQ24GJLA0 AVNQ36GKLA0
80 80 80

70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)


Octave Band Sound Pressure Level (dB re 20μPa )

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

20 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
AVNQ42GLLA0
AVNQ48GLLA0 AVNQ54GLLA0
AVNQ48GLLA2 AVNQ54GLLA2 AVNQ18GJLA2
80 80 80

70 70 70

Octave Band Sound Pressure Level (0dB = 20μPa)


Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (dB re 20μPa )


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold

Indoor units
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

AVNQ24GJLA2 AVNQ36GKLA2
80 80

70 70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (dB re 20μPa )

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

Cooling Only 50Hz/R410A _ 21


2. Ceiling suspended
2.8 Controller
Wireless remote control
Control Display
Description
panel screen

Plasma button*: Purifies the air by


Display
a F removing particles that enter the indoor
unit.
screen
Sleep mode auto button*: Sets the
l = sleep mode auto operation.

Temperature adjustment buttons:


e y Adjusts the room temperature when cool-
ing and heating.

d - On/Off button: Turns the power on/off.


Indoor units

Control
panel g 7 v Indoor fan speed button: Adjusts the
fan speed.
Operation mode selection button*:
Selects the operation mode.
A C Cooling operation (A) / Auto operation or
f D B
auto changeover (C) / Dehumidifying
E
operation (D) / Heating operation (B) /
Air circulation (E)

Jet cooling/heating button*: Warms up


Operation Mode
h N or cools down the indoor temperature
within a short period of time.
Cooling Mode

i j Air flow direction button: Adjusts the air


H I flow direction vertically or horizontally.
Auto Operation

Temperature display button: Displays the


Dehumidification mode
k S room temperature. Also changes unit
from °C to °F if pressed for 5 seconds.
Heating Mode

m n z Timer button: Sets the current time and


Fan Mode the start / end time.
• Cooling Model( ), Heat Pump Model( ) Navigation and functions button*:
c Adjusts the time and sets the special
functions.
b J G
J: Auto clean / G: Operates energy sav-
u ing cooling / LIGHT : Adjusts the bright-
ness of the indoor unit display

Set/clear button: Sets or cancels func-


p -
tions.

Reset button: Resets the air conditioner


r -
settings.

22 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
2.9 Installation
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

1) Installation parts provided


Ceiling Mounting There should be no space
- Installation Plate (VE, 1pcs) between ceiling and the unit.
- Washer Bolt (M8×L25, 4pcs, type "A")
Sleeve
- Floor Mount Bracket (1pcs) Bushing-Sleeve
Putty(Gum Type Sealer)
- Drain Hose, Insulated Bend the pipe as closely
More than
- Drain Hose Hanger and screw 20cm on the wall as possible,
More than 5cm but be careful that it
(Left and right doesn't break.
are identical)
2) The other installation parts
needed
- Suspension Bolt

Indoor units
- Bolts for Mount Bracket
- Connecting Tube(mm)
• Gas side : Ø9.52, Ø12.7
• Liquid side : Ø6.35
- Connecting Cable Vinyl tape (Wide)
• To carry out the drainage
- Drain Hose Extended test, remove the air filters
and pour water into the heat
exchanger.
Saddle • Apply after carrying out a
drainage test.

Gas side piping (Optional Part)


Liquid side piping (Optional Part)
Additional drain pipe

2.9.1 Accessories
Check the following accessories are included with your unit.

1) Standard accessories

Washer for Insulation for


Name Drain hose Clamp metal Clamp (Other)
hanging backet fitting
Quantity 1 EA 1 EA 8 EA 6 EA 1 set

• Owner's manual
• Installation manual

Diagram for gas pipe

for liquid pipe

Cooling Only 50Hz/R410A _ 23


2. Ceiling suspended
2.9.2 Selection of the best location 2.9.3 Installation
• There should not be any heat source or steam near the VJ/K/L Chassis
unit.
• There should not be any obstacles to the air circulation. 1) Open the cover
• There should be provision of easy condensate drain. The wall you select shou
• Taking into accounting the noise prevention criteria, spot ① Remove four screws from side-cover.
the installation location. ② Unlock side-cover from side panel slightly (Tap the side-
• Do not install the unit near the door way. cover with your palm on the backside)
• Keep proper distances, of the unit, from ceiling, fence, ③ Knock out the pipe hole from the left sidecover with nip-
floor, walls and other obstacles as shown in figure. per/plier.
• The indoor unit must have the maintenance space.
• The mounting ceiling or wall should be strong and solid
enough to protect it from the vibration. CAUTION

• Hold the side-cover with other hand while tapping to


prevent it to fall down.
R
More than More than
200mm 200mm
Indoor units

Step 1
More than 50mm

(Ceiling installation)

Step 2
Right side cover

Backside

Left side
cover

Backside
Step 3

24 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
2) Mounting the anchor nut and bolt
Hanging bolt
① Prepare 4 suspension bolts. (Each bolts length should be (W3/8 or M10)
same.) Nut
(W3/8 or M10) Flat washer
② Measure and mark the position for the Suspension bolts for M10
and the piping hole. (accessory)
Spring washer
③ Drill the hole for anchor nut on the ceiling. (M10) Flat washer
④ Insert the nuts and washer onto the suspension bolts for for M10
(accessory)
locking the suspension bolts on the ceiling.
Nut
⑤ Mount the suspension bolts to the anchor-nuts firmly. (W3/8 or M10)
⑥ Secure the hangers onto the Suspension bolts (adjust
level roughly.) using nuts, washers and spring washers.
⑦ Adjust a level with a level gauge on the direction of left- - The following parts is option.
right, back-forth by adjusting suspension bolts.
Hanging Bolt - W 3/8 or M10
⑧ Adjust a level on the direction of top-bottom by adjusting
supension bolts. Then the unit will be declined to the bot- Nut - W 3/8 or M10

Indoor units
tomside so as to drain well. Spring Washer - M10
Plate Washer - M10
[Unit : mm]

DIMENSION
A B
MODEL
CAUTION
VL 1655 320
Tighten the nut and bolt to prevent unit falling.
VK 1255 320
• Drill the piping hole on the wall slightly tilted to the out-
VJ 855 320
door side using a Ø 70 hole-core drill.

Anchor nut

Wall
Ceiling
B Indoor Outdoor
Nut Washer A
Suspension
bolts
Suspension bolt
5~7mm

Suspension
bolts
Spring
washer Nut
Hangen
Max.
12mm Washer

Cooling Only 50Hz/R410A _ 25


2. Ceiling suspended

CAUTION

Installation Information For Declination


- Install declination of the indoor unit is very important for the drain of the convertible type air conditioner.
- Minimum thickness of the insulation for the connecting pipe shall be 10mm.
- If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be declined to the bot-
tomside.

Front of view
- The unit must be horizontal or inclined at angle.
- The inclination should be less than or equal to 1°or in between 10 to 20mm inclined in drain direction as shown in fig.

Ceiling
Indoor units

10~20mm

Side of view
- The unit must be declined to the bottomside of the unit when finished installation.

Ceiling

5~10mm

26 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
2.9.4 Piping and drainage • Drain test
• Indoor Unit Drain Piping - Use the following procedure to test the drain pump operation:

- Drain piping must have down-slope (1/50 to 1/100): be


sure not to provide up-and-down slope to prevent reversal
flow.
- During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
- Remove the rubber stopple before
connecting drain hose.
- Hook on the bracket after connecting the drain hose as
below. - Set the air direction louvers up-and-down to the
position(horizontally) by hand.
- Pour a glass of water on the evaporator using
a kettle.
Drain hose - Ensure the water flows through the drain hose
of the indoor unit without any leakage and goes out the

Indoor units
drain exit.
Bracket

• Heat insulation
• Drain piping
Use the heat insulation material for the refrig-erant piping
- The drain hose should point downward for easy drain flow. which has an excellent heat-resis-tance (over 120°C).
Downward Precautions in high humidity circumstance:This air condi-
slope
tioner has been tested accordingto the "KS Standard
Conditions with Mist" andconfirmed that there is not any
default.However, if it is operated for a long time inhigh
humid atmosphere (dew point tempera-ture: more than
23°C), water drops are liablto fall. In this case, add heat
- Do not make drain piping like the following. insulation material according to the following procedure:

Accumulated Fastening band


Do not raise drain water
(accessory)

Air

Refrigerant piping
Water Water Waving
leakage leakage Indoor unit
Thermal insulator
(accessory)
Tip of drain
hose dipped Less than
in water 50mm gap - Heat insulation material to be prepared...Adiabatic glass
wool with thickness 10 to 20mm.
Water
leakage - Stick glass wool on all air conditioners thatare located in
Ditch
ceiling atmosphere.
- Be sure to execute heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thick-
ness more than 8 mm.

Cooling Only 50Hz/R410A _ 27


2. Ceiling suspended
2.9.5 Electric wiring work
CAUTION
1) General instructions
• The connecting cable connected to the indoor and out-
① All field supplied parts and materials, electric works must door unit should be complied with the following specifi-
conform to local codes. Use copper wire only. cations (Rubber insulation, type H05RN-F approved by
② Follow the "WIRING DIAGRAM” attached to the unit HAR or SAA).
body to wire the outdoor unit, indoor units and the remote
NORMAL
controller. CROSS-SECTIONAL
③ All wiring must be performed by an authorized electri- GN
/Y
AREA 0.75mm2
L
cian.
20
③ This system consists of multiple indoor units. Mark each mm

indoor unit as unit A, unit B...., and be sure the terminal


board wiring to the outdoor unit and indoor unit are prop- • If the supply cord is damaged, it must be replaced by a
erly matched. If wiring and piping between the outdoor special cord or assembly available from the manufactur-
unit and an indoor unit are mismatched, the system may er of its service agent.
cause a malfunction.
④ A circuit breaker capable of shutting down the power
supply to the entire system must be installed.
Indoor units

CAUTION

2) Wiring connection • Make sure that the screws of the terminal are fixed tightly.

- Connecting cables to the indoor unit


① Remove the terminal block cover for electrical connection CAUTION
between the indoor and out-door unit.
② Use the cord clamper to fix the cord. • Make sure to attach the sealing material (field supplied) to hole of
wiring to prevent the infiltration of foreign particle from outside.
Otherwise a short-circuit may occur inside the electric parts box
• When clamping the wires, be sure no pressure is applied to the wire
connections by using the included clamping material to make
appropriate clamps. Also, when wiring, make sure the cover on the
electric parts box fits snugly by arranging the wires neatly and
attaching the electric parts box cover firmly. When attaching the
Terminal block cover
electric parts box cover, make sure no wires get caught in the
edges. Pass wiring through the holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between the units,
- Wiring Connection and other electrical wiring do not pass through the same locations
① Connect the wires to the terminals on thecontrol board outside of the unit, separating them properly, otherwise electrical
individually according to the out-door unit connection. noise (external static) could cause mistaken operation or breakage.
1(L) 2(N) 3

1(L) 2(N) 3

28 _ Cooling Only 50Hz/R410A


2. Ceiling suspended
NOTE

1. Use round crimp-style terminals for connecting


wires to the power supply terminal block.
If unavailable, observe the following points when
wiring.
① Do not connect wires of different gauge to the same
power supply terminal.
② Use the specified electric wire. connect the wire securely
to the terminal. Lock the wire down without applying
excessive force to the terminal.

Attach insulation sleeve

Round crimp-style terminal

Electric wire

Indoor units
2. Tightening torque for the terminal screws.
① Use the correct screw driver for tightening the terminal
screws. If the blade of screwdriver is too small, the head
of the screw might be damaged, and the screw will not be
properly tightened.
② If the terminal screws are tightened too hard, screws
might be damaged.
3. Do not connect wires of different gauge to the
same grounding terminal. Loose connection may
deteriorate protection.

Connect wires of the same gauge to both sides

4. Outside of the unit, keep proper separation


between transmission and power supply wiring.
The equipment may malfunction if subjected to
electrical (external) noise.
5. Never connect power supply wiring to the terminal
block for remote controller wiring. A mistake of the
sort could damage the entire system.
6. Use only specified wire and tightly connect wires to
terminals. Be careful wires do not place external
stress on terminals. Keep wiring in neat order and
so as not to obstruct other equipment such as pop-
ping open the electric parts box cover. Make sure
the cover closes tight. Incomplete connections
could result in overheating, and in worse case,
electric shock or fire.

Cooling Only 50Hz/R410A _ 29


3. Ceiling concealed duct - Middle static Pressure(1)
3.1 List of functions
3.2 Specifications
3.3 Dimensions
3.4 Piping diagrams
3.5 Wiring diagrams
3.6 External pressure setting for
3.7 Sound levels
3.8 Controller
3.9 Installation
3. Ceiling concealed duct - Middle static Pressure(1)
3.1 List of functions
ABNQ24GGLA0 / ABNQ30GGLA0
ABNQ18GHLA0
Category Functions ABNQ36GGLA0 / ABNQ42GRLA0
ABNQ21GHLA0
ABNQ48GRLA0 / ABNQ54GRLA0
Air supply outlet 2 2
Airflow direction control (left & right) X X
Airflow direction control (up & down) X X
Auto swing (left & right) X X
Air flow Auto swing (up & down) X X
Airflow steps (fan/cool/heat) 3/3/- 3/3/-
Chaos wind(auto wind) X X
Jet cool X X
Swirl wind X X
Triple filter (Deodorizing) X X
Air purifying Plasma air purifier X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump ABDPG ABDPG

Indoor units
E.S.P. control O O
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) X X
Auto Restart O O
Child lock O O
Convenience Forced operation X X
Group control O O
Sleep mode X X
Timer(on/off) X X
Timer(weekly) X X
Two thermistor control O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller O O
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller X X
General central controller (Non LGAP) X X
Network Network Solution(LGAP) X O
function Dry contact X PQDSB**
PI 485(for Indoor Unit) X X
Zone controller ABZCA ABZCA
Special
CTI(Communication transfer interface) X X
function kit
Electronic thermostat X X
Others Remote temperature sensor PQRSTA0 PQRSTA0

Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Cooling Only R410A(50/60Hz) _ 1


3. Ceiling concealed duct - Middle static Pressure(1)
3.2 Specifications
Model Name ABNQ18GHLA0 ABNQ21GHLA0
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 1.00 1.00
WxHxD mm 880 × 260 × 450 880 × 260 × 450
Dimensions Body
WxHxD inch 34-21/32 x 10-1/4 x 17-23/32 34-21/32 x 10-1/4 x 17-23/32
Net Weight Body kg (lbs) 26.0 (57.3) 26.0 (57.3)
Heat (Row x Column x Fins per inch) x No. - (3 x 10 x 21) x 1 (3 x 10 x 21) x 1
Exchanger Face Area m2 (ft2) 0.15 (1.63) 0.15 (1.63)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 16.5 / 14.5 / 13.0 16.5 / 14.5 / 13.0
Fan
Flow Mode H/M/L ft3/min 583 / 512 / 459 583 / 512 / 459
Rate (Factory Set) External Static Pressure Pa (mmAq)
Indoor units

78 (8) 78 (8)
Type - BLDC BLDC
Fan Motor
Output W x No. 154 x 1 154 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 37 / 35 / 33 37 / 35 / 33
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG) 2
4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

2 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)

Model Name ABNQ24GGLA0 ABNQ30GGLA0


220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 1.50 1.50
WxHxD mm 1,180 × 298 × 450 1,180 × 298 × 450
Dimensions Body
WxHxD inch 46-15/32 x 11-23/32 x 17-23/32 46-15/32 x 11-23/32 x 17-23/32
Net Weight Body kg (lbs) 33.0 (72.8) 35.0 (77.2)
Heat (Row x Column x Fins per inch) x No. - (3 x 12 x 21) x 1 (3 x 10 x 19) x 1
Exchanger Face Area m2 (ft2) 0.26 (2.77) 0.21 (2.29)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 16.5 / 14.5 / 13.0 32.0 / 29.0 / 26.0
Fan
Flow Mode H/M/L ft3/min 583 / 512 / 459 1,130 / 1,024 / 918
Rate (Factory Set) External Static Pressure Pa (mmAq)

Indoor units
78 (8) 98 (10)
Type - BLDC BLDC
Fan Motor
Output W x No. 154 x 1 154 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 42 / 39 / 36 42 / 39 / 36
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG) 2
4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 3


3. Ceiling concealed duct - Middle static Pressure(1)

Model Name ABNQ36GGLA0 ABNQ42GRLA0


220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 1.50 2.30
WxHxD mm 1,180 × 298 × 450 1,230 × 380 × 590
Dimensions Body
WxHxD inch 46-15/32 x 11-23/32 x 17-23/32 48-7/16 x 14-31/32 x 23-7/32
Net Weight Body kg (lbs) 35.0 (77.2) 52.0 (114.6)
Heat (Row x Column x Fins per inch) x No. - (3 x 10 x 19) x 1 (3 x 16 x 18) x 1
Exchanger Face Area m2 (ft2) 0.21 (2.29) 0.36 (3.87)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 32.0 / 29.0 / 26.0 38.0 / 36.0 / 32.0
Fan
Flow Mode H/M/L ft3/min 1,130 / 1,024 / 918 1,342 / 1,271 / 1,130
Rate (Factory Set) External Static Pressure Pa (mmAq)
Indoor units

98 (10) 98 (10)
Type - BLDC BLDC
Fan Motor
Output W x No. 154 x 1 350 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.4 (7.2)
Sound Pressure Level H/M/L dB(A) 42 / 39 / 36 44 / 42 / 40
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

4 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)

Model Name ABNQ48GRLA0 ABNQ54GRLA0


220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 2.30 2.40
WxHxD mm 1,230 × 380 × 590 1,230 × 380 × 590
Dimensions Body
WxHxD inch 48-7/16 x 14-31/32 x 23-7/32 48-7/16 x 14-31/32 x 23-7/32
Net Weight Body kg (lbs) 52.0 (114.6) 49.0 (108.0)
Heat (Row x Column x Fins per inch) x No. - (3 x 16 x 18) x 1 (3 x 16 x 18) x 1
Exchanger Face Area m2 (ft2) 0.36 (3.87) 0.36 (3.87)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 40.0 / 35.0 / 30.0 50.0 / 45.0 / 40.0
Fan
Flow Mode H/M/L ft3/min 1,413 / 1,236 / 1,060 1,766 / 1,589 / 1,413
Rate (Factory Set) External Static Pressure Pa (mmAq)

Indoor units
98 (10) 98 (10)
Type - BLDC BLDC
Fan Motor
Output W x No. 350 x 1 185 x 2
Dehumidification Rate l / h (pts/h) 3.6 (7.7) 3.6 (7.7)
Sound Pressure Level H/M/L dB(A) 44 / 42 / 40 46 / 44 / 42
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 5


3. Ceiling concealed duct - Middle static Pressure(1)
3.3 Dimensions
ABNQ18GHLA0
ABNQ21GHLA0
BH Chassis
Indoor units

6 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)

ABNQ24GGLA0
ABNQ30GGLA0
ABNQ36GGLA0
BG Chassis

Indoor units

Cooling Only R410A(50/60Hz) _ 7


3. Ceiling concealed duct - Middle static Pressure(1)

ABNQ42GRLA0
ABNQ48GRLA0
ABNQ54GRLA0
BR Chassis
Indoor units

8 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)
3.4 Piping diagrams

Gas pipe connection port


Heat exchanger
(flare connection)

Cooling Thermistor for


Sirocco Fan evaporator outlet
temperature Thermistor for
M suction air
temperature

Thermistor for
evaporator inlet
temperature

Indoor units
Liquid pipe connection port
(flare connection)

Description PCB Connector

Thermistor for suction air temperature CN-ROOM

Thermistor for evaporator inlet temperature CN-PIPE / IN

Thermistor for evaporator outlet temperature CN-PIPE / OUT

n Refrigerant pipe connection port diameters


[Unit : mm(inch)]

Model Gas Liquid


ABNQ18GHLA0
Ø 12.7 (1/2) Ø 6.35 (1/4)
ABNQ21GHLA0
ABNQ24GGLA0
ABNQ30GGLA0
ABNQ36GGLA0 Ø 15.88 (5/8) Ø 9.52 (3/8)
ABNQ42GRLA0
ABNQ48GRLA0
ABNQ54GRLA0 Ø 19.05 (3/4) Ø 9.52 (3/8)

Cooling Only R410A(50/60Hz) _ 9


3. Ceiling concealed duct - Middle static Pressure(1)
3.5 Wiring diagrams

Models : ABNQ18GHLA0 / ABNQ21GHLA0 / ABNQ24GGLA0 / ABNQ30GGLA0 / ABNQ36GGLA0


Indoor units

Models : ABNQ42GRLA0 / ABNQ48GRLA0

10 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)
Models : ABNQ54GRLA0

Indoor units

Cooling Only R410A(50/60Hz) _ 11


3. Ceiling concealed duct - Middle static Pressure(1)
3.6 External pressure setting for
Table 1

Models : ABNQ18GHLA0, ABNQ21GHLA0


(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
2.5(25) 4(39) 6(59) 8(78)
100 12.8 - - -
105 13.9 - - -
110 15.2 12.7 - -
115 16.5 14.0 - -
120 17.8 15.3 12.7 -
125 - 16.5 14.0 -
130 - 17.8 15.3 12.6
135 - - 16.5 13.5
140 - - 17.5 14.5
145 - - - 16.5
Indoor units

Models : ABNQ24GGLA0
(Unit: CMM)

Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118) 14(137)
80 14.8 - - - -
90 19.0 14.4 - - -
100 23.3 19.7 13.9 - -
110 26.9 24.3 19.8 14.1 -
120 31.2 28.2 25.2 20.1 14.4
130 34.9 32.4 29.5 25.4 20.5

Models : ABNQ30GGLA0 / ABNQ36GGLA0


(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
4(49) 6(59) 8(78) 10(98)
100 20.8 - - -
105 23.2 19.5 - -
110 26.0 21.5 - -
115 - 23.5 19.1 -
120 - 26.3 21.6 -
125 - - 24.0 19.9
130 - - 27.0 22.7
135 - - - 25.9

12 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)

Models : ABNQ42GRLA0
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118)
85 31.5 - - -
90 36.3 29.8 - -
95 41.3 34.5 28.4 -
100 45.4 39.7 33.5 27.3
105 - 44.1 38.6 33.1
110 - - 44.2 38.9
115 - - - 44.7

Models : ABNQ48GRLA0
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118)

Indoor units
85 31.5 - - -
90 36.3 29.8 - -
95 41.3 34.5 28.4 -
100 45.4 39.7 33.5 27.3
105 - 44.1 38.6 33.1
110 - - 44.2 38.9
115 - - - 44.7

Models : ABNQ54GRLA0
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118) 14(137)
95 41.3 - - - -
100 45.4 39.7 - - -
105 49.5 44.1 38.6 - -
110 - 48.5 44.2 38.9 -
115 - - 49.8 44.7 42.2
120 - - - 50.5 48.1

h ABNQ42GRLA0 / ABNQ48GRLA0
As far as possible do not set ESP 82,83

Cooling Only R410A(50/60Hz) _ 13


3. Ceiling concealed duct - Middle static Pressure(1)

Table 2

Lower Limit of Upper Limit of


Standard ESP External Static External Static
Model Mode Set value CMM
(mmAq(Pa)) Pressure Pressure
(mmAq(Pa)) (mmAq(Pa))
Hi 1450 16.5
ABNQ18GHLA0 Mid 1400 8 (78) 14.5 2.5(25) 8 (78)
Low 1340 13.0
Hi 1450 16.5
ABNQ21GHLA0 Mid 1400 8 (78) 14.5 2.5(25) 8 (78)
Low 1340 13.0
Hi 1270 16.5
ABNQ24GGLA0 Mid 1210 8 (78) 14.5 2.5(25) 8 (78)
Low 1090 13.0
Hi 1370 32.0
Indoor units

ABNQ30GGLA0 Mid 1310 10 (98) 29.0 4.0(39) 10 (98)


Low 1260 26.0
Hi 1370 32.0
ABNQ36GGLA0 Mid 1310 10 (98) 29.0 4.0(39) 10 (98)
Low 1260 26.0
Hi 1060 38.0
ABNQ42GRLA0 Mid 1020 10 (98) 36.0 5.0(49) 10 (98)
Low 990 32.0
Hi 1100 40.0
ABNQ48GRLA0 Mid 1060 10 (98) 35.0 5.0(49) 10 (98)
Low 1030 30.0
Hi 1240 50.0
ABNQ54GRLA0 Mid 1200 10 (98) 45.0 5.0(49) 10 (98)
Low 1150 40.0

14 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)
3.7 Sound levels
Overall
Notes :
DISCHARGE SUCTION
- Data is valid at nominal operation condition
DUCT DUCT - Reference accoustic pressure 0dB = 20μPa.
- Sound level will vary depending on a range of factors such as the
construction(acoustic absorption coefficient) of particular room in
2m 1.5m
1m which the equipment is installed.
1m - The operating conditions are assumed to be standard.

Sound Level(H/M/L) [dB(A)]


Model
H M L
ABNQ18GHLA0 37 35 33
ABNQ21GHLA0 37 35 33
ABNQ24GGLA0 42 39 36
ABNQ30GGLA0 42 39 36

Indoor units
ABNQ36GGLA0 42 39 36
ABNQ42GRLA0 44 42 40
ABNQ48GRLA0 44 42 40
ABNQ54GRLA0 46 44 42

Sound pressure level


ABNQ18GHLA0 ABNQ30GGLA0
ABNQ21GHLA0 ABNQ24GGLA0 ABNQ36GGLA0
80 80 80

70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65 NC-65 NC-65


60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

Cooling Only R410A(50/60Hz) _ 15


3. Ceiling concealed duct - Middle static Pressure(1)
ABNQ42GRLA0 ABNQ48GRLA0 ABNQ54GRLA0
80 80 80

70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Indoor units

16 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)
3.8 Controller
Wireless remote control
The controls will look like the following.

Appearance Functions(Button Descriptions)

No. Name Function

Operation
1 Displays the operating conditions.
display
SLO
LO
1 Room
MED
Used to set the room temperature
HI
2 temperature
SHI when required.

Indoor units
VANE
setting
2
3 Fan speed Used to set the desired fan speed.
3

4
Operation starts when this button is
ROOM
5
4 On/Off pressed, and stops when the button
TEMP
is pressed again.

Room
5 temperature Used to check the room temperature.
checking

Cooling Only R410A(50/60Hz) _ 17


3. Ceiling concealed duct - Middle static Pressure(1)
3.9 Installation
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air outlet vents Air filters


(Optional)
Air intake vents
SLO
LO
MED

Remote controller
HI

SHI

VANE
Indoor units

Air Supply Air filter


Can be installed
inside return grill.
Air return
SLO
LO
MED

HI

SHI

VANE

Remote controller
3.9.1 Accessories
Check whether the following accessories are included with your unit.

1) Standard accessories
Insulation for Screws for
Name Clamp metal Drain hose Clamp (Other)
fitting duct flanges

Quantity 1 EA 1 EA 1 set 6 EA 1 set

• Owner's manual
• Installation manual
• Washers(8 pcs.)
Shape for gas pipe

for liquid pipe

18 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)
3.9.2 Selection of the best location NOTE
Install the air conditioner in the location that satisfies the fol- If the service panel is at the top of the unit, then provide
lowing conditions. sufficient service clearance as per convenience.
• The place shall easily bear a load of the indoor unit.
• The place should have enough area for inspection as
2) Relative positions of indoor unit, suspension bolt
shown in figure.
and inspection hatch size
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suitable dimen-
sion “H” is necessary to get a slope to drain as figure.) [BH Chassis] [Unit : mm]
• The place shall easily connect with the outdoor unit.
932
• The place where the unit is not affected by an electrical noise.
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the unit.

355

Indoor units
120
Inspection
hatch 600 x 600

[BG Chassis]
1232

[Unit : mm] H= 20 or more


355

3.9.3 Ceiling dimension, also hanging


bolt location and service space
1) Select an installation site where the following con- 150
ditions are fulfilled and also that meets with your Inspection
hatch 600 x 600
customer's approval.
• If supporting structural members are not strong enough
[BR Chassis]
to take the units weight, the unit could fall out of place
and cause serious injury. 1281
• Where sufficient clearance of maintenance and service
can be ensured.
• Where optimum air distribution can be ensured.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
477

• Where piping between indoor and outdoor units is pos-


sible within the allowable limit (Refer to the installation
manual of the outdoor unit.)
• Keep the indoor and outdoor units, power cable and
transmission wiring, at least 1 m from TVs and radios, 150
to prevent distorted pictures and static.(Depending on
Inspection
the type and source of the electrical waves, static may hatch 600 x 600
be heard even when more than 1 m away.)

Cooling Only R410A(50/60Hz) _ 19


3. Ceiling concealed duct - Middle static Pressure(1)
3.9.4 Position of suspension bolt ⑦ Insert the set anchor and washer on the suspension bolts
for locking the suspension bolts on the ceiling.
① Install the unit leaning to a drainage hole side as given in
the figure above for easy water drainage. ⑧ Mount the suspension bolts to the set anchor firmly.

② A place where the unit will be leveled and that can sup- ⑨ Secure the installation plates on the suspension bolts
port the weight of the unit. (adjust level roughly) using nuts, washers and spring
washers.
③ A place where the unit can withstand its vibration.
④ A place where service can be easily performed.
Old building New building

M10 Nut x4
(Local
M10 SP. washer x 4 supply)
M10 washer x4
1 Set anchor
2 Plate washer
M10 washer x4 3 Spring washer
Indoor units

(Local 4 Nut
M10 SP. washer x 4 supply)
M10 Nut x4 5 Suspension
bolts

⑤ Select and mark the position for fixing bolts.


⑥ Drill the hole for set anchor on the face of ceiling.

CAUTION

• Tighten the nut and bolt to prevent unit from


falling.

20 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)
3.9.5 Connection pipes to the indoor unit 3) Indoor unit drain piping
1) Refrigerant piping work ① During drain piping connection, be careful not to exert
extra force on the drain port on the indoor unit.
please refer “REFRIGERANT PIPING WORK”.
② The outside diameter of the drain connection on the
2) Piping insulation indoor unit is 32mm.
① Perform heat insulation work completely on both gas and Piping material: Polyvinyl chloride pipe inner diameter
the liquid pipe. Because improper insulation will result Ø 25mm and pipe fitting
due condensate formation over pipe.
② Use the heat insulation material for the refrigerant piping CAUTION
which has an excellent heat resistance (over 120°C).
1. Decline Installation of indoor unit is very important for
③ Precautions in high humidity circumstance.
the drain of the duct type air conditioner.
④ Refer to the insulation works. 2. Minimum thickness of the insulation for the connecting
pipe should be 5mm.

Liquid pipe

Indoor units
4) Caution for gradient of unit and drain
Refrigerant pipe and thermal
insulation(Local supply) piping
- Without drain pump
Clamp for insulation ① Always lay the drain with downward inclination (1/50 to
(Local supply) 1/100).
Insulation Prevent any upward flow or reverse flow in any part.
(Local supply)
② 10mm or thicker formed thermal insulation shall always
Union for gas pipe be provided for the drain pipe.

Attached drain hose


Thermal insulation for refrigerant pipe
Downward 1/50~1/100 or more
(Local supply) Thermal insulation for Bottom of unit
piping(Local supply)

or more or more
Approx 2~3mm 50mm 50mm

Overlap with
insulation

Make sure that there is no clearance here.

※ U-trap is not required for low static model in which the


external static pressure is below 50 pa(5mm Aq)

CAUTION

• Make sure to insulate any field piping all the way to the
piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.

Cooling Only R410A(50/60Hz) _ 21


3. Ceiling concealed duct - Middle static Pressure(1)
- With drain pump 3.9.6 Electric wiring work
① Possible drain head is upto 700mm.
1) General instructions
② Keep the drain pipe downward stope upto 1/50~1/100.
Prevent any upward flow or reverse flow in any part. ① All field supplied parts and materials, electric works must
③ 10mm or thicker insulation should be provided for the conform to local codes.
drain pipe. Use copper wire only.
② Follow the "WIRING DIAGRAM” attached to the unit
body to wire the outdoor unit, indoor units and the remote
1/50~1/100 controller.
Drain Pipe
③ All wiring must be performed by an authorized electri-
MAX 700mm cian.
④ This system consists of multiple indoor units. Mark each
indoor unit as unit A, unit B..., and be sure the terminal
Drain Pump board wiring to the outdoor unit and indoor unit are prop-
erly matched. If wiring and piping between the outdoor
Thermal insulattion unit and an indoor unit are mismatched, the system may
(Local supply) cause a malfunction.
Indoor units

Drain pipe
⑤ A circuit breaker capable of shutting down the power
Unit (Local supply)
supply to the entire system must be installed.

Elbow

Drain pump

5) Checking the drain


① Remove the air filter.

② Check the drain.


• Poor eough water on the drain pan.
• Ensure that water flows through the drain pipe from indoor
unit without any leakage.

22 _ Cooling Only R410A(50/60Hz)


3. Ceiling concealed duct - Middle static Pressure(1)
2) Wiring connection NOTE
Connect the wires to the terminals on the control board indi-
vidually according to the outdoor unit connection. 1. Use round crimp-style terminals for connecting
wires to the power supply terminal block.
① Ensure that the color of the wires of outdoor unit and the If unavailable, observe the following points when
terminal No. are the same as those of indoor unit respec- wiring.
tively.
① Do not connect wires of different gauge to the same
power supply terminal.
Terminal block in indoor
② Use the specified electric wire. Connect the wire securely
1(L) 2(N) 3 4 to the terminal. Lock the wire down without applying
excessive force to the terminal.

Attach insulation sleeve


Connected to outdoor Unit (or BD unit)
Round crimp-style terminal

② If the supply cord is damaged, it must be replaced by a


special cord or assembly availible from the manufacturer Electric wire

Indoor units
of its service agent.

WARNING

• Make sure that the screws of the terminal are fixed


tightly.
Connect wires of the same gauge to both sides

2. Tightening torque for the terminal screws.


① Use the correct screwdriver for tightening the terminal
CAUTION screws. If the blade of screwdriver is too small, the head
of the screw might be damaged, and the screw will not
• Make sure to attach the sealing material or (field sup-
be properly tightened.
plied) to hole of wiring to prevent the infiltration of foreign
particle from outside. Otherwise a short-circuit may ② If the terminal screws are tightened too hard, screws
occur inside the electric parts box might be damaged.
• When clamping the wires, be sure no pressure is applied 3. Do not connect wires of different gauge to the
to the wire connections by using the included clamping same grounding terminal. Loose connection may
material to make appropriate clamps. Also, when wiring, deteriorate protection.
make sure the cover on the electric parts box fits snugly 4. Outside of the unit, keep proper separation
by arranging the wires neatly and attaching the electric between transmission and power supply wiring.
parts box cover firmly. When attaching the electric parts The equipment may malfunction if subjected to
box cover, make sure no wires get caught in the edges. electrical (external) noise.
Pass wiring through the holes to prevent damage to
them. 5. Never connect power supply wiring to the terminal
block for remote controller wiring. A mistake of
• Make sure the remote controller wiring, the wiring the sort could damage the entire system.
between the units, and other electrical wiring do not pass
through the same locations outside of the unit, separat- 6. Use only specified wire and tightly connect wires
ing them properly, otherwise electrical noise (external to terminals. Be careful wires do not place exter-
static) could cause product malfunction. nal stress on terminals. Keep wiring in neat order
and so as not to obstruct other equipment such as
popping open the electric parts box cover. Make
sure the cover closes tight. Incomplete connec-
tions could result in overheating, and in worse
case, electric shock or fire.

Cooling Only R410A(50/60Hz) _ 23


4. Ceiling concealed duct – Low static pressure
4.1 List of functions
4.2 Specifications
4.3 Dimensions
4.4 Piping diagrams
4.5 Wiring diagrams
4.6 External pressure setting for
4.7 Sound levels
4.8 Controller
4.9 Installation
4. Ceiling concealed duct – Low static pressure
4.1 List of functions
ABNQ18GL2A0
Category Functions ABNQ24GL3A0
ABNQ21GL2A0
Air supply outlet 2 2
Airflow direction control (left & right) X X
Airflow direction control (up & down) X X
Auto swing (left & right) X X
Air flow Auto swing (up & down) X X
Airflow steps (fan/cool/heat) 3/3/- 3/3/-
Chaos wind(auto wind) X X
Jet cool X X
Swirl wind X X
Triple filter (Deodorizing) X X
Plasma air purifier O O
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump X X

Indoor units
E.S.P. control O O
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) X X
Auto Restart O O
Child lock O O
Convenience Forced operation X X
Group control O O
Sleep mode X X
Timer(on/off) X X
Timer(weekly) X X
Two thermistor control O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller O O
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller X X
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSB**
function
PI 485(for Indoor Unit) X X
Zone control ABZCA ABZCA
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others
Group Control wire PZCWRCG3 PZCWRCG3
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Cooling Only R410A(50/60Hz) _ 1


4. Ceiling concealed duct – Low static pressure

Category Functions ABNQ18GL2A1 ABNQ24GL3A1


Air supply outlet 2 2
Airflow direction control (left & right) X X
Airflow direction control (up & down) X X
Auto swing (left & right) X X
Air flow Auto swing (up & down) X X
Airflow steps (fan/cool/heat) 3/3/- 3/3/-
Chaos wind(auto wind) X X
Jet cool X X
Swirl wind X X
Triple filter (Deodorizing) X X
Plasma air purifier O O
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump X X
E.S.P. control O O
Installation Electric heater X X
High ceiling operation X X
Indoor units

Auto Elevation Grille X X


Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) X X
Auto Restart O O
Child lock O O
Convenience Forced operation X O
Group control O O
Sleep mode X X
Timer(on/off) X X
Timer(weekly) X X
Two thermistor control O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller O O
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller X X
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSA(1)/PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others
Group Control wire PZCWRCG3 PZCWRCG3
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

2 _ Cooling Only R410A(50/60Hz)


4. Ceiling concealed duct – Low static pressure
4.2 Specifications
Model Name ABNQ18GL2A0 ABNQ21GL2A0
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 0.80 0.80
WxHxD mm 900 × 190 × 700 900 × 190 × 700
Dimensions Body
WxHxD inch 35-7/16 x 7-15/32 x 27-9/16 35-7/16 x 7-15/32 x 27-9/16
Net Weight Body kg (lbs) 22.0 (48.5) 22.0 (48.5)
Heat (Row x Column x Fins per inch) x No. - (2 x 11 x 18) x 1 (2 x 11 x 18) x 1
Exchanger Face Area m2 (ft2) 0.17 (1.81) 0.17 (1.81)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 15.0 / 12.5 / 10.0 17.5 / 14.0 / 12.0
Fan
Flow Mode H/M/L ft3/min 530 / 450 / 360 620 / 500 / 430
Rate (Factory Set) External Static Pressure Pa (mmAq)

Indoor units
25 (2.54) 25 (2.54)
Type - BLDC BLDC
Fan Motor
Output W x No. 19 x 1 19 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 31 36 / 34 / 31
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 3


4. Ceiling concealed duct – Low static pressure

Model Name ABNQ24GL3A0


220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60
Power Input W x No. -
Running Current A 1.00
WxHxD mm 1,100 × 190 × 700
Dimensions Body
WxHxD inch 43-5/16 x 7-15/32 x 27-9/16
Net Weight Body kg (lbs) 27.0 (59.5)
Heat (Row x Column x Fins per inch) x No. - (3 x 11 x 18) x 1
Exchanger Face Area m2 (ft2) 0.21 (2.31)
Type - Sirocco Fan
Air High-static H/M/L m3/min 20.0 / 16.0 / 12.0
Fan
Flow Mode H/M/L ft3/min 710 / 570 / 430
Rate (Factory Set) External Static Pressure Pa (mmAq) 25 (2.54)
Type - BLDC
Indoor units

Fan Motor
Output W x No. 19 x 2
Dehumidification Rate l / h (pts/h) 2.5 (5.3)
Sound Pressure Level H/M/L dB(A) 39 / 35 / 32
Sound Power Level Cooling dB(A) -
Liquid mm(inch) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4
Safety Devices - Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

4 _ Cooling Only R410A(50/60Hz)


4. Ceiling concealed duct – Low static pressure

Model Name ABNQ18GL2A1 ABNQ24GL3A1


220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 0.80 1.00
WxHxD mm 900 × 190 × 700 1,000 × 190 × 700
Dimensions Body
WxHxD inch 37-7/16 x 7-15/32 x 27-9/16 43-5/16 x 7-15/32 x 27-9/16
Net Weight Body kg (lbs) 23.0 (50.7) 27.0 (59.5)
Heat (Row x Column x Fins per inch) x No. - (2 x 11 x 18) x 1 (3 x 11 x 18) x 1
Exchanger Face Area m2 (ft2) 0.17 (1.81) 0.21 (2.31)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 15.0 / 12.5 / 10.0 20.0 / 16.0 / 12.0
Fan
Flow Mode H/M/L ft3/min 530 / 450 / 360 710 / 570 / 430
Rate (Factory Set) External Static Pressure Pa (mmAq) 25 (2.54) 25 (2.54)
Type - BLDC BLDC

Indoor units
Fan Motor
Output W x No. 19 x 1 19 x 2
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.5 (5.3)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 31 39 / 35 / 32
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4(1) / 20.4(13/16) Ø 25.4(1) / 20.4(13/16)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 5


Indoor units

L2/L3 Chassis

ABNQ18GL2A0
ABNQ21GL2A0
ABNQ24GL3A0
ABNQ18GL2A1
ABNQ24GL3A1
4.3 Dimensions

5
20 D
A B C D

6 _ Cooling Only R410A(50/60Hz)


ABNQ18GL2A0

135
974 900 933 860
ABNQ21GL2A0

34
190 ABNQ24GL3A0 1,174 1,100 1,133 1,060
100
94

292
67 119
1

700
628
220
4

L1 : 366
L2 : 561
L3 : 755 C
6 Gravity point

20
4. Ceiling concealed duct – Low static pressure

190
155
L1 : 75
L2 : 78
L3 : 81

B Air suction
A
Air discharge
Power supply connection
Drain pipe connection
Gas pipe connection
Liquid pipe connection
4. Ceiling concealed duct – Low static pressure
4.4 Piping diagrams

: Refrigerant Flow

Evaporator Out
Temperature
Thermistor

Evaporator In
Sirocco Fan Temperature
Thermistor

Indoor Unit

Indoor units
Inlet Air
Temperature
Thermistor

Description PCB Connector


Inlet Air Temperature Thermistor CN-ROOM
Evaporator In Temperature Thermistor CN-PIPE/IN
Evaporator Out Temperature Thermistor CN-PIPE/OUT

n Refrigerant pipe connection port diameters


[Unit : mm(inch)]

Model Gas Liquid


ABNQ18GL2A0
Ø 12.7 (1/2) Ø 6.35 (1/4)
ABNQ21GL2A0

ABNQ18GL2A1 Ø 12.7 (1/2) Ø 6.35 (1/4)

ABNQ24GL3A0
Ø 15.88 (5/8) Ø 9.52 (3/8)
ABNQ24GL3A1

Cooling Only R410A(50/60Hz) _ 7


4. Ceiling concealed duct – Low static pressure
4.5 Wiring diagrams
Model : ABNQ18GL2A0 / ABNQ21GL2A0 / ABNQ24GL3A0
Indoor units

Model : ABNQ18GL2A1 / ABNQ24GL3A1

8 _ Cooling Only R410A(50/60Hz)


4. Ceiling concealed duct – Low static pressure
4.6 External pressure setting for
Static pressure(mmAq) 0 1 2 3 4

Model Step(Hi/Mid/Low) Setting value

15 CMM 90 97 105 114 122


ABNQ18GL2A0
12.5 CMM 82 90 99 109 119
ABNQ18GL2A1
10 CMM 75 84 93 103 114

17.5 CMM 90 97 105 114 122

ABNQ21GL2A0 14 CMM 82 90 99 109 119

12 CMM 75 84 93 103 114

20 CMM 110 117 125 129 -


ABNQ24GL3A0

Indoor units
16 CMM 100 107 115 121 127
ABNQ24GL3A1
12 CMM 90 97 105 114 122

[Notes]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.

Cooling Only R410A(50/60Hz) _ 9


4. Ceiling concealed duct – Low static pressure
Models: ABNQ18GL2A0 / ABNQ21GL2A0 / ABNQ18GL2A1
(Unit : CMM)
Static Pressure(mmAq(Pa))
Setting Value
0 (0) 1 (10) 2 (20) 3 (30) 4 (40) 5 (50)
75 6.50 - - - - -
80 7.34 6.70 - - - -
85 8.20 7.55 6.69 - - -
90 9.07 8.43 7.56 6.47 - -
95 9.96 9.32 8.45 7.36 - -
100 10.87 10.22 9.36 8.27 6.96 -
105 11.79 11.15 10.28 9.19 7.89 6.35
110 12.73 12.09 11.22 10.14 8.83 7.30
115 13.69 13.05 12.18 11.09 9.78 8.25
120 14.67 14.02 13.16 12.07 10.76 9.23
125 15.66 15.01 14.15 13.06 11.75 10.22
130 16.67 16.02 15.16 14.07 12.76 11.23
135 - - 16.18 15.10 13.79 12.26
140 - - - 16.14 14.83 13.30
145 - - - - 15.89 14.36
Indoor units

Models: ABNQ24GL3A0 / ABNQ24GL3A1


(Unit : CMM)
Static Pressure(mmAq(Pa))
Setting Value
0 (0) 1 (10) 2 (20) 3 (30) 4 (40) 5 (50)
85 10.19 - - - - -
90 12.18 10.71 11.09 - - -
95 13.81 12.34 12.19 - - -
100 15.16 13.69 13.38 10.71 - -
105 16.30 14.83 14.36 11.85 - -
110 17.31 15.85 15.23 12.86 10.97 -
115 18.27 16.80 16.07 13.82 11.93 -
120 19.26 17.79 16.93 14.80 12.91 10.49
125 20.34 18.87 17.89 15.88 13.99 11.57
130 21.60 20.13 19.01 17.14 15.25 12.83
135 - 21.64 20.36 18.66 16.76 14.35
140 - - 22.01 20.50 18.61 16.19
145 - - - 22.75 20.86 18.44

Note :
1. The above table shows the correlation between the air rates and E.S.P.

10 _ Cooling Only R410A(50/60Hz)


4. Ceiling concealed duct – Low static pressure
4.7 Sound levels
Overall
Notes:
DISCHARGE SUCTION
1. Sound measured at 1.5m away from the center of the unit
DUCT DUCT 2. Operating condition
- Power source : 220-240V 50Hz / 220V 60Hz
- Cooling : Indoor temperature (27°C DB, 19°C WB),
2m 1.5m
1m Outdoor temperature (35°C DB, 24°C WB)
- Heating : Indoor temperature (20°C DB, 15°C WB),
Outdoor temperature (7°C DB, 6°C WB)
3. Reference accoustic pressure 0dB = 20μPa
❈ Measuring place : Anechoic chamber 4. Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
Sound Level(H/M/L) [dB(A)] room in which the equipment in installed.
Model 5. The operating condition is external static pressure 20Pa.
H M L
ABNQ18GL2A0 36 34 31
ABNQ21GL2A0 36 34 31
ABNQ24GL3A0 39 35 32

Indoor units
ABNQ18GL2A1 36 34 31
ABNQ24GL3A1 39 35 32

Sound pressure level


ABNQ18GL2A0
ABNQ21GL2A0 ABNQ24GL3A0
ABNQ18GL2A1 ABNQ24GL3A1
80 80

70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

70

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50

NC-50 NC-50

NC-45 NC-45
40 40

NC-40 NC-40

NC-35 NC-35
30 30

NC-30 NC-30

20 NC-25 20 NC-25

Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

Cooling Only R410A(50/60Hz) _ 11


4. Ceiling concealed duct – Low static pressure
4.8 Controller
Wireless remote control
The controls will look like the following.

Appearance Functions(Button Descriptions)

No. Name Function

Operation
1 Displays the operating conditions.
display
SLO
LO
1 Room
MED
Used to set the room temperature
HI
2 temperature
when required.
Indoor units

SHI

VANE
setting
2
3 Fan speed Used to set the desired fan speed.
3

4
Operation starts when this button is
ROOM
5
4 On/Off pressed, and stops when the button
TEMP
is pressed again.

Room
5 temperature Used to check the room temperature.
checking

12 _ Cooling Only R410A(50/60Hz)


4. Ceiling concealed duct – Low static pressure
4.9 Installation
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards.

Air outlet vents

Air filters

Indoor units
SLO
LO
MED

Remote Controller
HI

SHI

VANE

4.9.1 Accessories
Check the following accessories are included with your unit.

1) Standard accessories

Insulation for Screws for


Name Clamp metal Clamp (Other)
fitting duct flanges

Quantity 1 EA 1 set 1 set 8 EA

• Owner's manual
• Installation manual

Diagram for gas pipe

for liquid pipe

Cooling Only R410A(50/60Hz) _ 13


4. Ceiling concealed duct – Low static pressure
4.9.2 Selection of the best location 4.9.4 Position of suspension bolt
Install the air conditioner in the location that satisfies the fol- ① A place where the unit will be leveled and that can sup-
lowing conditions. port the weight of the unit.
• The place shall easily bear a load exceeding four times the ② A place where the unit can withstand its vibration.
indoor unit’s weight. ③ A place where service can be easily performed.
• The place shall be able to inspect the unit as the figure.
• The place where the unit shall be leveled.
M10 Nut x4
• The place shall allow easy water drainage.(Suitable (Local
M10 SP. washer x 4 supply)
dimension “H” is necessary to get a slope to drain as fig-
ure.) M10 washer x4

• The place shall easily connect with the outdoor unit.


• The place where the unit is not affected by an electrical
noise. M10 washer x4
(Local
• The place where air circulation in the room will be good. M10 SP. washer x 4 supply)
M10 Nut x4
• There should not be any heat source or steam near the
Indoor units

unit.

4.9.3 Ceiling dimension and hanging


bolt location and service space ④ Select and mark the position for fixing bolts.
1) Select an installation site where the fol- ⑤ Drill the hole for set anchor on the face of ceiling.
lowing conditions are fulfilled and that
meets with your customer's approval.
• If supporting structural members are not strong enough to
take the units weight, the unit could fall out of place and
cause serious injury.
• Where sufficient clearance of maintenance and service
can be ensured.
• Where optimum air distribution can be ensured.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where piping between indoor and outdoor units is possible
within the allowable limit (Refer to the installation manual
of the outdoor unit.)
CAUTION
• Keep the indoor and outdoor units, power cable and trans-
mission wiring, at least 3.3ft from TVs and radios, to pre- • Tighten the nut and bolt to prevent the unit falling.
vent distorted pictures and static.(Depending on the type
and source of the electrical waves, static may be heard
even when more than 3.3ft away.)

14 _ Cooling Only R410A(50/60Hz)


4. Ceiling concealed duct – Low static pressure
⑥ Insert the set anchor and washer onto the suspension
bolts for locking the suspension bolts on the ceiling.
⑦ Mount the suspension bolts to the set anchor firmly. Liquid pipe
⑧ Secure the installation plates onto the suspension bolts Refrigerant pipe and thermal
(adjust level roughly) using nuts, washers and spring insulation(Local supply)
washers.

Clamp for insulation


Old building New building (Local supply)
Insulation
(Local supply)
Union for gas pipe

1 Set anchor
2 Plate washer
3 Spring washer
Thermal insulation for refrigerant pipe
4 Nut (Local supply) Thermal insulation for

Indoor units
al
5 Suspension piping(Local supply)
bolts

Overlap with
4.9.5 Connecting pipes to the indoor insulation
unit
Make sure that there is no clearance here.
1) Refrigerant piping work
please refer “REFRIGERANT PIPING WORK”.
2) Piping insulation CAUTION
① Perform heat insulation work completely on both gas and • Make sure to insulate any field piping all the way to the
the liquid pipe. Because improper insulation will result piping connection inside the unit. Any exposed piping
condensate formation over pipe. may cause condensation or burns if touched.
Use the heat insulation material for the refrigerant piping
which has an excellent heat resistance (over 248°F).
② Precautions in high humidity circumstance: This air con-
ditioner has been tested according to the "KS
Conditions" and confirmed that there is not any default.
However, if it is operated for a long time in high humid
atmosphere (dew point temperature: more than 73°F),
water drops are liable to fall. In this case, add heat
insulation material according to the following procedure:
③ Heat insulation material : Adiabatic glass wool with thick-
ness 13/32 to 13/16 inch.
④ Stick glass wool on all air conditioners that are located in
ceiling atmosphere.

Cooling Only R410A(50/60Hz) _ 15


4. Ceiling concealed duct – Low static pressure
3) Indoor unit drain piping • Lay the drain hose with a downware inclination so water
will drain out.
① Drain piping must have down-slope (1/50 to 1/100): be
sure not to provide up-and-down slope to prevent rever- Thermal insulator
sal flow. (Local supply)
② During drain piping connection, be careful not to exert Drainage pipe
extra force on the drain port on the indoor unit. (Local supply)
Unit
③ The outside diameter of the drain connection on the
indoor unit is 1 1/4 inch.
Piping material: Polyvinyl chloride pipe inner diameter Make sure to be closed. Drainage hole
Ø1 inch and pipe fittings

CAUTION

1. Decline Installation of indoor unit is very important for Wrong method


the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting
pipe should be 7/32 inch.
Indoor units

4) Caution for gradient of unit and drain


piping
- Without drain pump:
• Always lay the drain with downward inclination (1/50 to
1/100).
Prevent any upward flow or reverse flow in any part.
• 7/32 inch or thicker formed thermal insulation shall always
be provided for the drain pipe.

Correct method

Attached drain hose


Downward
1/50~1/100 or more

Approx 3/32~5/32 inch

※ U-trap is not required for low static model in which the


external static pressure is below 50 pa(5mm Aq)

16 _ Cooling Only R410A(50/60Hz)


4. Ceiling concealed duct – Low static pressure
- With drain pump ② Check the drainage
① Possible drain head height is upto 27 6/19 inch. So the • Spray one or two glasses of water on the evaporator.
drain head should be below 27 6/19 inch. • Ensure that water flows through the drain hose from indoor
② Keep the drain hose downward upto 1/50~1/100 inclina- unit without any leakage.
tion.
Prevent any upward flow or reverse flow in any part.
③ 7/32 inch or thicker insulation should be provided for the
drain pipe.

1/50~1/100

Drain Pipe

MAX 27 9/16 inch

4.9.6 Electric wiring work


Drain Pump
1) General instructions

Indoor units
① All field supplied parts and materials, electric works must
Thermal insulation conform to local codes.
(Local supply) Use copper wire only.
Drain pipe
② Follow the "WIRING DIAGRAM” attached to the unit
Unit (Local supply)
body to wire the outdoor unit, indoor units and the remote
controller.
③ All wiring must be performed by an authorized electri-
Elbow cian.
④ This system consists of multiple indoor units. Mark each
Drain pump indoor unit as unit A, unit B..., and be sure the terminal
board wiring to the outdoor unit and ID unit are properly
matched. If wiring and piping between the outdoor unit
5) Checking the drainage and an indoor unit are mismatched, the system may
cause a malfunction.
① Remove the air filter.
⑤ A circuit breaker capable of shutting down the power
supply to the entire system must be installed.

2) Wiring connection
Connect the wires to the terminals on the control board ind
vidually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the
terminal No. are the same as those of indoor unit respec-
tively

Terminal block in indoor

1(L) 2(N) 3

Connected to outdoor unit(or BD Unit)

Cooling Only R410A(50/60Hz) _ 17


4. Ceiling concealed duct – Low static pressure
Clamping of cables
NOTE
① Arrange 2 power cables on the control panel.
② First, fasten the steel clamp with a screw to the inner 1. Use round crimp-style terminals for connecting
boss of control panel. wires to the power supply terminal block. If
③ For the cooling model, fix the other side of the clamp with unavailable, observe the following points when
a screw strongly. For the heat pump model, put the wiring.
0.75mm2 cable (thinner cable) on the clamp and tighten it
with a plastic clamp to the other boss of the control • Do not connect wires of different gauge to the same power
panel. supply terminal.
④ In Australia, the length of power supply cord measured • Use the specified electric wire. Connect the wire securely
from the entry of the power supply cord to the middle of to the terminal. Lock the wire down without applying
live pin on the power plug should be over 5.9ft. excessive force to the terminal.

CAUTION Attach insulation sleeve

• Make sure that the screws of the terminal are fixed Round crimp-style terminal
tightly.

Electric wire
Indoor units

CAUTION

• Make sure to attach the sealing material or (field sup-


plied) to hole of wiring to prevent the infiltration of foreign
particle from outside. Otherwise a short-circuit may
occur inside the electric parts box
Connect wires of the same gauge to both sides
• When clamping the wires, be sure no pressure is applied
to the wire connections by using the included clamping
material to make appropriate clamps. Also, when wiring, 2. Tightening torque for the terminal screws.
make sure the cover on the electric parts box fits snugly • Use the correct screwdriver for tightening the terminal
by arranging the wires neatly and attaching the electric screws. If the blade of screwdriver is too small, the
parts box cover firmly. When attaching the electric parts head of the screw might be damaged, and the screw
box cover, make sure no wires get caught in the edges. will not be properly tightened.
Pass wiring through the wiring through holes to prevent • If the terminal screws are tightened too hard, screws
damage to them. might be damaged.
• Make sure the remote controller wiring, the wiring 3. Do not connect wires of different gauge to the
between the units, and other electrical wiring do not same grounding terminal. Loose connection may
pass through the same locations outside of the unit, sep- deteriorate protection.
arating them properly, otherwise electrical noise (exter-
nal static) could cause product malfunction. 4. Outside of the unit, keep proper separation
between transmission and power supply wiring.
The equipment may malfunction if subjected to
electrical (external) noise.
5. Never connect power supply wiring to the terminal
block for remote controller wiring. A mistake of
the sort could damage the entire system.
6. Use only specified wire and tightly connect wires
to terminals. Be careful wires do not place
external stress on terminals. Keep wiring in neat
order and so as not to obstruct other equipment
such as popping open the electric parts box
cover. Make sure the cover closes tight.
Incomplete connections could result in overheat-
ing, and in worse case, electric shock or fire.

18 _ Cooling Only R410A(50/60Hz)


5. Floor standing
5.1 List of functions
5.2 Specifications
5.3 Dimensions
5.4 Piping diagrams
5.5 Wiring diagrams
5.6 Air flow and temperature distributions (Reference data)
5.7 Sound levels
5.8 Controller
5.9 Installation
5. Floor standing
5.1 List of functions
APNQ30GRA1 / APNQ36GRA1 APNQ36GRA2
Category Functions
APNQ42GTA1 / APNQ48GTA1 APNQ48GTA2
Air supply outlet 1 1
Airflow direction control(left & right) Auto Auto
Airflow direction control(up & down) Auto Auto
Auto swing(left & right) O O
Air flow Auto swing(up & down) O O
Airflow steps(fan/cool/heat) 4/4/- 4/4/-
Chaos wind(auto wind) X X
Jet cool/heat O/X O
Swirl wind X X
Triple filter (Deodorizing) X X
Plasma air purifier X X
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump X X

Indoor units
E.S.P. control X X
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning O X
Auto operation(artificial intelligence) O O
Auto restart O O
Child lock O O
Convenience Forced operation X O
Group control X X
Sleep mode X O
Timer(on/off) O O
Timer(weekly) X O
Two thermistor control X O
Wired remote controller X X
Deluxe wired remote controller X X
Individual
Simple wired remote controller X X
control
Simple Wired remote controller(for hotel use) X X
Wireless remote controller O O
General central controller (Non LGAP) X X
CAC Network Soluation(LGAP) O O
Network Dry contact PQDSA(1)/PQDSB(1) / PQDSBC PQDSA(1)/PQDSB(1)
function PDI(power distribution indicator) X X
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor X X
Others
Group Control wire X X
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Cooling Only R410A(50/60Hz) _ 1


5. Floor standing
5.2 Specifications
Model Name APNQ30GRA1 APNQ36GRA1

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.50 0.50
Casing Color - - -
WxHxD mm 590 × 1,840 × 320 590 × 1,840 × 320
Dimensions Body
WxHxD inch 23-7/32 x 72-7/16 x 12-19/32 23-7/32 x 72-7/16 x 12-19/32
Net Weight Body kg (lbs) 36.0 (79.4) 36.0 (79.4)
Heat (Row x Column x Fins per inch) x No. - (3 x 38 x 19) x 1 (3 x 38 x 19) x 1
Exchanger Face Area m2 (ft2) 0.30 (3.26) 0.30 (3.26)
Type - Sirocco Sirocco
Fan SH / H / M / L m3/min 23.5 / 21.0 / 17.0 / 14.0 23.5 / 21.0 / 17.0 / 14.0
Indoor units

Air Flow Rate


SH / H / M / L ft3/min 830 / 742 / 600 / 494 830 / 742 / 600 / 494
Type - BLDC BLDC
Fan Motor
Output W x No. 104 x 1 104 x 1
Dehumidification Rate l / h (pts/h) 4.3 (9.1) 4.3 (9.1)
Sound Pressure Level SH / H / M / L dB(A) 54 / 50 / 46 / 43 54 / 50 / 46 / 43
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.0 / 17.0 Ø 21.0 / 17.0
- Fuse Fuse
Safety Devices
Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75(18) 4C x 0.75(18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

2 _ Cooling Only R410A(50/60Hz)


5. Floor standing

Model Name APNQ42GTA1 APNQ48GTA1

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.91 0.91
Casing Color - - -
WxHxD mm 590 × 1,840 × 460 590 × 1,840 × 460
Dimensions Body
WxHxD inch 23-7/32 x 72-7/16 x 18-1/8 23-7/32 x 72-7/16 x 18-1/8
Net Weight Body kg (lbs) 49.0 (108.0) 49.0 (108.0)
Heat (Row x Column x Fins per inch) x No. - (3 x 38 x 19) x 1 (3 x 38 x 19) x 1
Exchanger Face Area m (ft )
2 2
0.39 (4.17) 0.39 (4.17)
Type - Sirocco Sirocco
Fan SH / H / M / L m /min
3
38.0 / 32.0 / 28.0 / 24.0 38.0 / 32.0 / 28.0 / 24.0
Air Flow Rate
SH / H / M / L ft3/min 1,342 / 1,130 / 989 / 848 1,342 / 1,130 / 989 / 848

Indoor units
Type - BLDC BLDC
Fan Motor
Output W x No. 224 x 1 224 x 1
Dehumidification Rate l / h (pts/h) 5.2 (11.0) 5.2 (11.0)
Sound Pressure Level SH / H / M / L dB(A) 56 / 53 / 50 / 47 56 / 53 / 50 / 47
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.0 / 17.0 Ø 21.0 / 17.0
- Fuse Fuse
Safety Devices
Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 3C x 1.0 (18) 3C x 1.0 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 3


5. Floor standing

Model Name APNQ36GRA2 APNQ48GTA2

220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.90 1.00
Casing Color -
WxHxD mm 590 × 1,840 × 320 590 × 1,840 × 460
Dimensions Body
WxHxD inch 23-7/32 x 72-7/16 x 12-19/32 43-5/16 x 7-15/32 x 18-1/8
Net Weight Body kg (lbs) 36.0 (79.4) 49.0 (108.0)
Heat (Row x Column x Fins per inch) x No. - (3 x 38 x 19) x 1 (3 x 38 x 19) x 1
Exchanger Face Area m (ft )
2 2
0.30 (3.26) 0.39 (4.17)
Type - Sirocco Fan Sirocco Fan
Fan SH / H / M / L m /min
3
23.5 / 21.0 / 17.0 / 14.0 38.0 / 32.0 / 28.0 / 24.0
Air Flow Rate
SH / H / M / L ft3/min 830 / 742 / 600 / 494 1,342 / 1,130 / 989 / 848
Indoor units

Type - BLDC BLDC


Fan Motor
Output W x No. 104 x 1 224 x 1
Dehumidification Rate l / h (pts/h) 4.3 (9.1) 5.2 (11.0)
Sound Pressure Level SH / H / M / L dB(A) 54 / 50 / 46 / 43 56 / 53 / 50 / 47
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.0(13/16) / 17(21/32) Ø 21.0(13/16) / 17(21/32)
- Fuse Fuse
Safety Devices
- -
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

4 _ Cooling Only R410A(50/60Hz)


5. Floor standing
5.3 Dimensions
APNQ30GRA1
APNQ36GRA1
APNQ36GRA2
PR4 Chassis

Indoor units

Cooling Only R410A(50/60Hz) _ 5


Indoor units

PT2 Chassis

APNQ42GTA1
APNQ48GTA1
APNQ48GTA2
5. Floor standing

6 _ Cooling Only R410A(50/60Hz)


5. Floor standing
5.4 Piping diagrams

Th3 Th1

Th2

M
Fan

Indoor units
: Refrigerant Flow

Location Description PCB Connector

Th1 Thermistor for indoor room temperature CN-ROOM/TH

Th2 Thermistor for evaporator inlet temperature CN-EVA/TH

Th3 Thermistor for evaporator outlet temperature CN-EVA/TH2

n Refrigerant pipe connection port diameters


[Unit : mm(inch)]

Model Gas Liquid


APNQ30GRA1
APNQ36GRA1
APNQ42GTA1
Ø15.88 (5/8) Ø9.52 (3/8)
APNQ48GTA1
APNQ36GRA2
APNQ48GTA2

Cooling Only R410A(50/60Hz) _ 7


5. Floor standing
5.5 Wiring diagrams
Model : APNQ30GRA1 / APNQ36GRA1 / APNQ36GRA2
Indoor units

Model : APNQ42GTA1 / APNQ48GTA1 / APNQ48GTA2

8 _ Cooling Only R410A(50/60Hz)


5. Floor standing
5.6 Air flow and temperature distributions (Reference data)
Model : APNQ30GRA1 / APNQ36GRA1 / APNQ36GRA2
Cooling
Discharge angle:90°

Air velocity [m/s]


2.7m
1.0 0.5 0.2
2.0 2.5 3.0 3.5 4.0 4.5 2m
1.5
1.0
0.6 1m
0.5
0.2
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

0.2

Indoor units
Temperature [°C]
2.7m
20
14 2m
16 12
18
1m

0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Model : APNQ42GTA1 / APNQ48GTA1 / APNQ48GTA2

Cooling
Discharge angle:90°

Air velocity [m/s]


2.7m
2.5 3.5 1.0
3.0 4.0 4.5 5.0 5.5 6.0 6.5 2m
2.0 7.0 7.5
1.0 0.5
2.0 0.2
0.2 1m

0.5 1.0
1.5 1.0
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Temperature [°C]
2.7m
17
2m
15 13

19
1m

0m
8m 7m 6m 5m 4m 3m 2m 1m 0m

Cooling Only R410A(50/60Hz) _ 9


5. Floor standing
5.7 Sound levels
Overall
Notes:
- Data is valid at nominal operation condition
- Reference accoustic pressure 0dB = 20μPa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
Mircrophone room in which the equipment is installed.
- The operating conditions are assumed to be standard.

Sound Levels dB(A)


Model
SH H M L
APNQ30GRA1 54 50 46 43
Indoor units

APNQ36GRA1 54 50 46 43
APNQ42GTA1 56 53 50 47
APNQ48GTA1 56 53 50 47
APNQ36GRA2 54 50 46 43
APNQ48GTA2 56 53 50 47

Sound pressure level


APNQ30GRA1 APNQ42GTA1
APNQ36GRA1 APNQ48GTA1
APNQ36GRA2 APNQ48GTA2
80 80
u S-High u S-High
n High n High
70 ▲ Middle 70 ▲ Middle
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

l Low l Low
NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

10 _ Cooling Only R410A(50/60Hz)


5. Floor standing
5.8 Controller
Wireless remote control
The controls will look like the following.

Control
No. Description
panel
1
1 Remote control operation lamp
2 5 Power ON/OFF button : Operation will start when
4 2 | this button is pressed, and stop when the button is
pressed again.
3 6
Indoor fan speed button : To select the desired fan
7 3
speed.
8 9
4 Temperature setting button
10 11

Indoor units
5 A Cooling button
12 13
6 Auto cleaning button

Dehumidification button : Can effectively remove


7 D humidity when at the time of rainy season or high
humidity.

Auto operation button : In operation this function,


air conditioner control the setting temperature by
8 C comparing room temperature and hot or cool level
customer set

9 Fan mode button

Air flow direction button(Up/down, Left/right) :


10 Adjust air flow direction vertically or horizontally.

Power cooling mode button : Powerful cooling is


11
performed

ON/OFF timer setting button : Set the time of start-


12
ing or stopping

13 Timer cancel button

Wireless Remote Control Puts all functions at your fingertips

Handling the remote control


• Aim at the signal receptor on the floor standing type air conditioner when operating.
• The remote control signal can be received at a distance of up to about 7meters.
• Be sure that there are no obstructions between the remote control and the signal receptor.
• Do not drop or throw the remote control.
• Do not place the remote control in a location exposed to direct sunlight, or next to a heating unit, or other heat source.

Cooling Only R410A(50/60Hz) _ 11


5. Floor standing
5.9 Installation
• Please read this instruction sheet completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

5.9.1 Select the best location


• There should not be any heat source or steam near the unit.
• There should not be any obstacles to prevent the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained. 300mm
• A place where noise prevention is taken into consideration.
300mm
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or mm
other obstacles. 300
Indoor units

• The indoor unit must keep the maintenance space.

5.9.2 Installation of Indoor unit


Wall

Core Drill

200mm
70mm
70mm
90mm

1. The mounting floor should be strong and solid INSIDE OUTSIDE


enough to prevent it from vibration.
Wall
2. Drill the piping hole with 70mm diameter hole-core Plastic tube
drill at either the right or the left of indoor unit. The (Bushing)
hole should be sightly slant to the outdoor side.
3. Insert the plastic tube through the hole.
Tilt
4. Cut the extruded outside part of the plastic tube, if
necessary.
Cut if necessary

More than 15mm

12 _ Cooling Only R410A(50/60Hz)


5. Floor standing
- When using knock-out hole to route the piping, insert the plastic
cover in knock-out hole in order to prevent the piping from dam-
aged by sharp edge of the hole.

Indoor units
5.9.3 Electric wiring work
CAUTION
1) General instructions
• The connecting cable connected to the indoor and out-
① All field supplied parts and materials, electric works must door unit should be complied with the following specifi-
conform to local codes. Use copper wire only.
cations (This equipment shall be provided with a cord
② Follow the "WIRING DIAGRAM” attached to the unit set complying with the national regulation).
body to wire the outdoor unit, indoor units and the remote
10±3mm
controller.
③ All wiring must be performed by an authorized electri- mm
±5
35
cian.
③ This system consists of multiple indoor units. Mark each GN
/Y
indoor unit as unit A, unit B...., and be sure the terminal L

board wiring to the outdoor unit and indoor unit are prop- 20
mm
erly matched. If wiring and piping between the outdoor NORMAL
unit and an indoor unit are mismatched, the system may CROSS-SECTIONAL
AREA 0.75mm2
cause a malfunction.
④ A circuit breaker capable of shutting down the power • If the supply cord is damaged, it must be replaced by a
supply to the entire system must be installed. special cord or assembly available from the manufactur-
er of its service agent.

2) Wiring Connection
① Connect the wires to the terminals on the control board
CAUTION
individually according to the outdoor unit connection.
• The Power cord connected to the unit should be select-
ed according to the following specifications.

Cooling Only R410A(50/60Hz) _ 13


5. Floor standing
3) Precautions when laying power wiring 4) Connecting the cable
Use round pressure terminals for connections to the The inside and outside connecting cable can be connected
power terminal block. after opening the inlet grille.
1. Open the inlet grille manually.
Round pressure terminal

Power wire
r

When none are available, follow the instructions below.


• Do not connect wiring of different thicknesses to the power
terminal block. (Slack in the power wiring may cause
abnormal heat.)
• When connecting wiring which is the same thickness, do
as shown in the figure below.

2. Open the control cover with Driver(⊕)


Indoor units

It is forbidden to
Connect same thickness It is forbidden to connect connect wiring of 3. Connect the cables to the connector in the control box.
wiring to both sides. two to one side. different thicknesses.

Indoor unit

Outdoor unit

Main power

• For wiring, use the designated power wire and connect 4. Secure the control cover to the original position with the
firmly, then secure to prevent outside pressure being screw.
exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal 5. Close the inlet grille.
screws. A screwdriver with a small head will strip the head
and make proper tighterning impossible.
• Over-tightening the terminal screws may break them. CAUTION

• The circuit diagram is not subject to change without


notice.
• Be sure to connect wires according to the wiring dia-
gram.
• Connect the wires firmly, so that not to be pulled out
easily.
• Connect the wires according to color codes by referring
the wiring diagram.

14 _ Cooling Only R410A(50/60Hz)


5. Floor standing
5.9.4 Test running 4) Evaluation of the performance
1) Precautions in test running Measure the temperature of the intake and discharge air.
Ensure the difference between the intake temperature and
- The initial power supply must provide at least 90% of the the discharge one is more than 8°C (Cooling).
rated voltage.
Otherwise, the air conditioner should not be operated.

CAUTION

• For test run, carry out the cooling operation firstly even
Thermometer
during heating season. If heating operation is carried out
firstly, it leads to the trouble of compressor. Then atten-
tion must be paid.
• Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)

- To cancel the test run, press any button.

Indoor units
CAUTION
2) Check the following items when installa- After the confirmation of the above conditions, prepare the
tion is complete wiring as follows:
After completing work, be sure to measure and record trial • Never fail to have an individual power specialized for the
run properties, and store measured data, etc. air conditioner. As for the method of wiring, be guided by
Measuring items are room temperature, outside tempera- the circuit diagram pasted on the inside of control box
ture, suction temperature, blow out temperature, wind veloc- cover.
ity, wind volume, voltage, current, presence of abnormal • Provide a circuit breaker switch between power source
vibration and noise, operating pressure, piping temperature, and the unit.
compressive pressure. • The screw which fasten the wiring in the casing of elec-
As to the structure and appearance, check following items. trical fittings are liable to come loose from vibrations to
- Is the circulation of air adequate? which the unit is subjected during the course of trans-
- Is the draining smooth? portation. Check them and make sure that they are all
- Is the heat insulation complete tightly fastened. (If they are loose, it could give rise to
(refrigerant and drain piping)? burn-out of the wires.)
- Is there any leakage of refrigerant? • Specification of power source.
- Is the remote controller switch operated? • Confirm that electrical capacity is sufficient.
- Is there any faulty wiring? • Be sure that the starting voltage is maintained at more
than 90 percent of the rated voltage marked on the name
- Are not terminal screws loosened?
plate.
M4......118N.cm{12kgf.cm} • Confirm that the cable thickness is as specified in the
M5......196N.cm{20kgf.cm} power sources specification.(Particularly note the rela-
M6......245N.cm{25kgf.cm} tion between cable length and thickness.)
M8......588N.cm{60kgf.cm} • Never fail to equip a leakage breaker where it is wet or
moist.
3) Connection of power supply • The following troubles would be caused by voltage drop-
down.
Connect the power supply cord to the independent power - Vibration of a magnetic switch, damage on the contact
supply. point there of, fuse breaking, disturbance to the normal
- Circuit breaker is required. function of a overload protection device.
Operate the unit for fifteen minutes or more. - Proper starting power is not given to the compressor.

Cooling Only R410A(50/60Hz) _ 15


6. Ceiling concealed duct – Middle static Pressure(2)
6.1 List of functions
6.2 Specifications
6.3 Dimensions
6.4 Piping diagrams
6.5 Wiring diagrams
6.6 External pressure setting for
6.7 Sound levels
6.8 Controller
6.9 Installation
6. Ceiling concealed duct – Middle static Pressure(2)
6.1 List of functions
ABNQ24GM1A2 / ABNQ36GM2A2
Category Functions ABNQ18GM1A2
ABNQ48GM3A2 / ABNQ54GM3A2
Air supply outlet 1 1
Airflow direction control (left & right) X X
Airflow direction control (up & down) X X
Auto swing (left & right) X X
Air flow Auto swing (up & down) X X
Airflow steps (fan/cool/heat) 3/3/- 3/3/-
Chaos wind(auto wind) X X
Jet cool X X
Swirl wind X X
Triple filter (Deodorizing) X X
Plasma air purifier X X
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump ABDPG ABDPG
E.S.P. control O O

Indoor units
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) O X
Auto Restart O O
Child lock O O
Convenience Forced operation X O
Group control O O
Sleep mode X X
Timer(on/off)* X X
Timer(weekly)* X X
Two thermistor control O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller O O
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller X X
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSA(1)/PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others
Group Control wire PZCWRCG3 PZCWRCG3

Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.

Cooling Only R410A(50/60Hz) _ 1


6. Ceiling concealed duct – Middle static Pressure(2)
6.2 Specifications
Model Name ABNQ18GM1A2 ABNQ24GM1A2
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 1.60 1.60
WxHxD mm 900 × 270 × 700 900 × 270 × 700
Dimensions Body
WxHxD inch 37-7/16 x 10-5/8 x 27-9/16 37-7/16 x 10-5/8 x 27-9/16
Net Weight Body kg (lbs) 23.1 (50.9) 24.2 (53.4)
Heat (Row x Column x Fins per inch) x No. - (2 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.21 (2.26) 0.21 (2.26)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 16.5 / 14.5 / 13.0 18.0 / 16.5 / 14.0
Fan
Flow Mode H/M/L ft3/min 582 / 512 / 459 635 / 583 / 494
Rate (Factory Set) External Static Pressure Pa (mmAq)
Indoor units

8 (78) 8 (78)
Type - BLDC BLDC
Fan Motor
Output W x No. 136.5 x 1 136.5 x 1
Dehumidification Rate l / h (pts/h) 1.2 (2.6) 1.6 (3.4)
Sound Pressure Level H/M/L dB(A) 37 / 39 / 36 42 / 39 / 36
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/33)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG) 2
4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

2 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)

Model Name ABNQ36GM2A2 ABNQ48GM3A2


220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W x No. - -
Running Current A 2.30 2.30
WxHxD mm 1,250 × 270 × 700 1,250 × 360 × 700
Dimensions Body
WxHxD inch 49-7/32 x 10-5/8 x 27-9/16 49-7/32 x 14-3/16 x 27-9/16
Net Weight Body kg (lbs) 35.1 (77.4) 40.0 (88.2)
Heat (Row x Column x Fins per inch) x No. - (2 x 14 x 21) x 1 (3 x 16 x 21) x 1
Exchanger Face Area m2 (ft2) 0.31 (3.34) 0.36 (3.88)
Type - Sirocco Fan Sirocco Fan
Air High-static H/M/L m3/min 32.0 / 28.0 / 23.0 40.0 / 34.0 / 28.0
Fan
Flow Mode H/M/L ft3/min 1,130 / 989 / 812 1,413 / 1201 / 989
Rate (Factory Set) External Static Pressure Pa (mmAq) 10 (98) 6 (59)
Type - BLDC BLDC

Indoor units
Fan Motor
Output W x No. 350 x 1 350 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.0 (6.3)
Sound Pressure Level H/M/L dB(A) 42 / 39 / 36 44 / 42 / 40
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/34) Ø 32.0(1-1/4) / 25.0(31/35)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

Cooling Only R410A(50/60Hz) _ 3


6. Ceiling concealed duct – Middle static Pressure(2)

Model Name ABNQ54GM3A2


220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60
Power Input W x No. -
Running Current A 2.40
WxHxD mm 1,250 × 360 × 700
Dimensions Body
WxHxD inch 49-7/32 x 14-3/16 x 27-9/16
Net Weight Body kg (lbs) 42.3 (93.3)
Heat (Row x Column x Fins per inch) x No. - (3 x 16 x 21) x 1
Exchanger Face Area m2 (ft2) 0.36 (3.88)
Type - Sirocco Fan
Air High-static H/M/L m3/min 50.0 / 45.0 / 40.0
Fan
Flow Mode H/M/L ft3/min 1,766 / 1589 / 1413
Rate (Factory Set) External Static Pressure Pa (mmAq) 6 (59)
Type - BLDC
Indoor units

Fan Motor
Output W x No. 400 x 1
Dehumidification Rate l / h (pts/h) 3.9 (8.2)
Sound Pressure Level H/M/L dB(A) 46 / 44 / 42
Sound Power Level Cooling dB(A) -
Liquid mm(inch) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/36)
Safety Devices - Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18)

Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.

4 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)
6.3 Dimensions

Supplied with product


ABNQ18GM1A2
ABNQ24GM1A2
M1 Chassis

Indoor units

Cooling Only R410A(50/60Hz) _ 5


6. Ceiling concealed duct – Middle static Pressure(2)

Supplied with product


ABNQ36GM2A2
M2 Chassis
Indoor units

6 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)

Supplied with product


ABNQ48GM3A2
ABNQ54GM3A2
M3 Chassis

Indoor units

Cooling Only R410A(50/60Hz) _ 7


6. Ceiling concealed duct – Middle static Pressure(2)
6.4 Piping diagrams

Gas pipe connection port


Heat exchanger
(flare connection)

Cooling Thermistor for


Sirocco Fan evaporator outlet
temperature Thermistor for
M suction air
temperature

Thermistor for
evaporator inlet
temperature
Indoor units

Liquid pipe connection port


(flare connection)

Description PCB Connector

Thermistor for suction air temperature CN-ROOM

Thermistor for evaporator inlet temperature CN-PIPE / IN

Thermistor for evaporator outlet temperature CN-PIPE / OUT

n Refrigerant pipe connection port diameters


[Unit : mm(inch)]

Model Gas Liquid

ABNQ18GM1A2 Ø 12.7 (1/2) Ø 6.35 (1/4)

ABNQ24GM1A2
ABNQ36GM2A2 Ø 15.88 (5/8) Ø 9.52 (3/8)
ABNQ48GM3A2
ABNQ54GM3A2 Ø 19.05 (3/4) Ø 9.52 (3/8)

8 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)
6.5 Wiring diagrams
Models : ABNQ18GM1A2 / ABNQ24GM1A2

Indoor units
Models : ABNQ36GM2A2 / ABNQ48GM3A2 / ABNQ54GM3A2

Cooling Only R410A(50/60Hz) _ 9


6. Ceiling concealed duct – Middle static Pressure(2)
6.6 External pressure setting for
Table 1
Models : ABNQ18GM1A2
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29) 4(39) 6(59) 8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 16.5 85 86 88 92 99 106 115 122 126 130 133
ABNQ18GM1A2 MID 14.5 75 77 85 88 93 102 111 118 121 126 129
LOW 13.0 71 73 76 85 89 98 107 114 117 122 125

Models : ABNQ24GM1A2
Indoor units

Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29) 4(39) 6(59) 8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 18.0 94 96 101 106 109 115 121 126 131 134 137
ABNQ24GM1A2 MID 16.5 89 91 96 101 105 111 117 122 126 130 133
LOW 14.0 79 81 87 93 99 105 112 117 121 125 129

Models : ABNQ36GM2A2

Static Pressure[mmAq(Pa)]
4(39) 5(50) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 32.0 97 103 107 111 115 117 119 123 126 130 137
ABNQ36GM2A2 MID 28.0 91 96 101 105 109 112 115 118 122 125 131
LOW 23.0 80 89 93 98 104 107 111 114 118 121 127

Models : ABNQ48GM3A2

Static Pressure[mmAq(Pa)]
5(50) 6(59) 7(69) 8(78) 9(88) 10(98) 12(118) 14(137) 15(147) 16(157) 18(177)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 40.0 88 90 93 96 99 102 108 113 115 117 121
ABNQ48GM3A2 MID 34.0 80 87 88 91 94 97 103 109 111 112 117
LOW 28.0 75 79 80 88 90 93 99 105 107 109 114

10 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)

Models : ABNQ54GM3A2

Static Pressure[mmAq(Pa)]
4(39) 5(50) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 14(137)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 50.0 94 97 98 103 107 109 112 114 117 119 121
ABNQ54GM3A2 MID 45.0 89 93 94 98 102 104 106 109 112 114 117
LOW 40.0 83 84 90 93 98 99 102 105 108 110 113

Table 2

Indoor units
Lower Limit of External Upper Limit of External
Standard
Model Mode Set Value CMM Static Pressure Static Pressure
ESP[mmAq(Pa)]
[mmAq(Pa)] [mmAq(Pa)]
Hi 106 16.5
ABNQ18GM1A2 Mid 102 8(78) 14.5 2.0(20) 10(98)
Low 98 13.0
Hi 121 18.0
ABNQ24GM1A2 Mid 117 10(98) 16.5 2.0(20) 10(98)
Low 112 14.0
Hi 119 32.0
ABNQ36GM2A2 Mid 115 10(98) 28.0 4.0(39) 10(98)
Low 109 23.0
Hi 90 40.0
ABNQ48GM3A2 Mid 87 6(56) 34.0 5.0(49) 14(137)
Low 79 28.0
Hi 98 50.0
ABNQ54GM3A2 Mid 94 6(56) 45.0 4.0(39) 14(137)
Low 90 40.0

Notes : Refer to the specifications pages for Factory Set(E.S.P.) values.

Notes
1. To get the desired Airflow & E.S.P. combination of the 5. If it is zero static pressure, please set value the below
table, set the matching value from the table. Otherwise, table.
the airflow & E.S.P. combination indicated in table would- Mode Value
n't be obtained.
ABNQ18GM1A2 106
2. Table data is based on 230V. According to the fluctuation ABNQ24GM1A2 115
of voltage, the air flow rate would be varied. ABNQ36GM2A2 119
3. The unexpected set value would cause mal-function. ABNQ48GM3A2 90
4. Refer to the specifications pages for Factory Set(E.S.P.) ABNQ54GM3A2 98
values.

Cooling Only R410A(50/60Hz) _ 11


6. Ceiling concealed duct – Middle static Pressure(2)
6.7 Sound levels
Overall
Notes :
DISCHARGE SUCTION
- Data is valid at nominal operation condition
DUCT DUCT - Reference accoustic pressure 0dB = 20μPa.
- Sound level will vary depending on a range of factors such as the
construction(acoustic absorption coefficient) of particular room in
2m 1.5m 2m which the equipment is installed.
- The operating conditions are assumed to be standard.

Sound Level(H/M/L) [dB(A)]


Model
H M L
ABNQ18GM1A2 37 39 36
ABNQ24GM1A2 42 39 36
ABNQ36GM2A2 42 39 36
ABNQ48GM3A2 44 42 40
Indoor units

ABNQ54GM3A2 46 44 42

Sound pressure level


ABNQ18GM1A2 ABNQ24GM1A2 ABNQ36GM2A2
80 80 80

70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)


NC-65 NC-65 NC-65
60 60 60
NC-60 NC-60 NC-60

NC-55 NC-55 NC-55


50 50 50
NC-50 NC-50 NC-50

NC-45 NC-45 NC-45


40 40 40
NC-40 NC-40 NC-40

NC-35 NC-35 NC-35


30 30 30
NC-30 NC-30 NC-30

NC-25 NC-25 NC-25


20 20 20
Approximate Approximate Approximate
NC-20 NC-20 NC-20
Hearing Hearing Hearing
Threshold Threshold Threshold
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

ABNQ48GM3A2 ABNQ54GM3A2
80 80

70 70
Octave Band Sound Pressure Level (0dB = 20μPa)

Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65 NC-65
60 60
NC-60 NC-60

NC-55 NC-55
50 50
NC-50 NC-50

NC-45 NC-45
40 40
NC-40 NC-40

NC-35 NC-35
30 30
NC-30 NC-30

NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)

12 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)
6.8 Controller
Wireless remote control
The controls will look like the following.

Appearance Functions(Button Descriptions)

No. Name Function

Operation
1 Displays the operating conditions.
display
SLO
LO
1 Room
MED
Used to set the room temperature
HI
2 temperature
SHI when required.

Indoor units
VANE
setting
2
3 Fan speed Used to set the desired fan speed.
3

4
Operation starts when this button is
ROOM
5
4 On/Off pressed, and stops when the button
TEMP
is pressed again.

Room
5 temperature Used to check the room temperature.
checking

Cooling Only R410A(50/60Hz) _ 13


6. Ceiling concealed duct – Middle static Pressure(2)
6.9 Installation
• Please read the instruction sheets completely before installing the product.
• When the power cord is damaged, replacement work shall be performed by authorized personnel only.
• Installation work must be performed in accordance with the national wiring standards.

Air inlet vents


Indoor units

Air outlet
vents

SLO
LO
MED

HI

SHI

VANE

ROOM
Remote
Controller
TEMP

6.9.1 Accessories
Check the following accessories are included with your unit.
1) Standard accessories
M1/M2/M3 Chassis

Washer for Clamp Insulation for


Name Drain hose Clamp metal hanging bracket (Tie Wrap) fitting Other
Quantity 1 EA 2 EA 8 EA 4 EA 1 set

• Owner's manual
• Installation manual
for gas pipe
Shape

for liquid pipe

• Screws for fixing panels are attached to decoration panel.

14 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)
6.9.2 Selection of the best location Top view (Unit: mm)
Inspection hole
Install the air conditioner in the location that satisfies the 600 x 600
following conditions. Air inlet vents
• The place shall easily bear a load exceeding four times Control box
the indoor unit’s weight.
• The place shall be able to inspect the unit as given in
the figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.
(Suitable dimension “H” is necessary to get a slope to 600 1000 600
drain as figure.) Air outlet vents
• The place shall easily connect with the outdoor unit. Front
• The place where the unit is not affected by an electrical
noise.
Side view (unit: mm)
• The place where air circulation in the room will be good .
• There should not be any heat source or steam near the

Indoor units
unit.
• The servicing inspection hole in the ceiling should be as
large as the product.
• The selection of the servicing hole should be approved 20 or more
by the customer.
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure

Cooling Only R410A(50/60Hz) _ 15


6. Ceiling concealed duct – Middle static Pressure(2)
6.9.3 Ceiling dimension and hanging bolt location and service space
n Installation of Unit
Install the unit above the ceiling correctly.

CASE 1
Position of suspension Bolt
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side as a figure for easy water drainage.

E
G
Indoor units

C
D

J
A
B
F
I

H
Drain hole

(Unit:mm)
Dimension
A B C D E F G H I J
Chassis name
M1 933.4 971.6 619.2 700 30 270 15.2 858 201.4 900
M2 1283.4 1321.6 619.2 689.6 30 270 15.2 1208 201.4 1250
M3 1283.4 1321.6 619.2 689.6 30 360 15.2 1208 291.4 1250

16 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)
CASE 2
Position of console Bolt
① A place where the unit will be leveled and that can sup-
port the weight of the unit.
② A place where the unit can withstand its vibration.
③ A place where service can be easily performed.

M10 Nut X4
(Local
M10 SP. washer X 4 supply)
M10 washer X4

Indoor units
M10 washer X4
(Local CAUTION
M10 SP. washer X 4 supply)
M10 Nut X4 • Tighten the nut and bolt to prevent the unit falling.

⑥ Insert the set anchor and washer onto the suspension


bolts for locking the suspension bolts on the ceiling.
⑦ Mount the suspension bolts to the set anchor firmly.
⑧ Secure the installation plates onto the suspension bolts
(adjust level roughly) using nuts, washers and spring
washers.

④ Select and mark the position for fixing bolts.


⑤ Drill the hole for set anchor on the face of ceiling. Old building New building

1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts

Cooling Only R410A(50/60Hz) _ 17


6. Ceiling concealed duct – Middle static Pressure(2)
6.9.4 Connecting pipes to the indoor unit
1) Refrigerant piping work Liquid pipe
Refrigerant pipe and thermal
please refer “REFRIGERANT PIPING WORK”. insulation(Local supply)

2) Piping insulation Clamp for insulation


① Perform heat insulation work completely on both gas and (Local supply)
the liquid pipe. Because improper insulation will result Insulation
condensate formation over pipe. (Local supply)
Use the heat insulation material for the refrigerant piping Union for gas pipe
which has an excellent heat resistance (over 248°F).
② Precautions in high humidity circumstance: This air con-
ditioner has been tested according to the "KS
Conditions" and confirmed that there is not any default. Thermal insulation for refrigerant pipe
However, if it is operated for a long time in high humid (Local supply) Thermal insulation for
atmosphere (dew point temperature: more than 73°F), piping(Local supply)
Indoor units

water drops are liable to fall. In this case, add heat


insulation material according to the following procedure:
③ Heat insulation material : Adiabatic glass wool with thick-
Overlap with
ness 13/32 to 13/16 inch.
insulation
④ Stick glass wool on all air conditioners that are located in
ceiling atmosphere. Make sure that there is no clearance here.

CAUTION

• Make sure to insulate any field piping all the way to the
piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.

18 _ Cooling Only R410A(50/60Hz)


6. Ceiling concealed duct – Middle static Pressure(2)
3) Indoor unit drain piping • Lay the drain hose with a downware inclination so water
will drain out.
① Drain piping must have down-slope (1/50 to 1/100): be
sure not to provide up-and-down slope to prevent rever- Thermal insulator
sal flow. (Local supply)
② During drain piping connection, be careful not to exert Drainage pipe
extra force on the drain port on the indoor unit. (Local supply)
③ The outside diameter of the drain connection on the Unit
indoor unit is 1 1/4 inch.
Piping material: Polyvinyl chloride pipe inner diameter
Ø1 inch and pipe fittings Make sure to be closed. Drainage hole

CAUTION
Wrong method
1. Decline Installation of indoor unit is very important for
the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting
pipe should be 7/32 inch.

Indoor units
4) Caution for gradient of unit and drain piping
- Without drain pump:
• Always lay the drain with downward inclination (1/50 to
1/100). Prevent any upward flow or reverse flow in any part. - With drain pump
• 7/32 inch or thicker formed thermal insulation shall always
① Possible drain head height is upto 27 6/19 inch. So the
be provided for the drain pipe.
drain head should be below 27 6/19 inch.
② Keep the drain hose downward upto 1/50~1/100 inclina-
Correct method tion. Prevent any upward flow or reverse flow in any part.
Attached drain hose ③ 7/32 inch or thicker insulation should be provided for the
Downward 1/50~1/100 or more drain pipe.
Bottom of unit
or more or more
50mm 50mm

Approx 2~3mm

1/50~1/100

Drain Pipe
27 9/16 inch ~ 700mm
(27-9/16 inch)

Pipe clamp
Drain Pump
Indoor unit

Hanger
Max 300mm distance Hanger Bracket
1~15m 1/50~1/100 slope
Metal
Max 700mm

Maintenance
drain port clamp

Flexible drain hose


Insulation

Cooling Only R410A(50/60Hz) _ 19


6. Ceiling concealed duct – Middle static Pressure(2)

Thermal insulation
6.9.5 Electric wiring work
(Local supply) 1) General instructions
Drain pipe
Unit (Local supply) ① All field supplied parts and materials, electric works must
conform to local codes.
Use copper wire only.
② Follow the "WIRING DIAGRAM” attached to the unit
Elbow body to wire the outdoor unit, indoor units and the remote
controller.
Drain pump ③ All wiring must be performed by an authorized electri-
cian.
④ This system consists of multiple indoor units. Mark each
5) Checking the drainage indoor unit as unit A, unit B..., and be sure the terminal
board wiring to the outdoor unit and ID unit are properly
① Remove the air filter. matched. If wiring and piping between the outdoor unit
and an indoor unit are mismatched, the system may
cause a malfunction.
Indoor units

Air outlet vents


⑤ A circuit breaker capable of shutting down the power
supply to the entire system must be installed.

Air filters
2) Wiring connection
Connect the wires to the terminals on the control board ind
vidually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the
② Check the drainage terminal No. are the same as those of indoor unit respec-
• Spray one or two glasses of water on the evaporator. tively
• Ensure that water flows through the drain hose from indoor
unit without any leakage.
Terminal Block Indoor
1(L) 2(N) 3

20 _ Cooling Only R410A(50/60Hz)


P/No.: MFL62069312

Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com

All rights reserved


Printed in Korea November / 2014 The air conditioners manufactured by LG have received ISO9001 certificate for
The specifications, designs, and quality assurance and ISO14001 certificate for environmental management system.
information in this brochure are subject to
change without notice.