0CSL0-03A(Replace: 0CSL0-02A)
P/No. : MFL62069312
Introduction
Preface
New era brings the more sophisticated and advanced buildings which in turn demands for specialized and optimized direct
expansion air conditioning systems. Also energy efficiency, environment friendly, low noise and low maintenance cost are
the features which are essential for these systems.
As a part of vertical integration LG makes all the key components in house, which gives an edge to LG to make better and
latest technology products with best quality in optimized time.
systems with are equipped with DC inverter technology and R410A refrigerant which is perfect solution to various
installation locations.
This Engineering product data book incorporates information about the product itself, its installation and designing for
system.
The comprehensive study of this book will improve your knowledge about the system and its application in details.
LG Electronics Inc.
Air Conditioning & Energy Solution Company
General information
1. Model line up
2. Nomenclature
1. Model line up
Model Name
Category Type Chassis Capacity class, kBtu/h
General information
18 21 24 30 36 42 48 54
ATNQ18GPLE3
TP ATNQ21GPLE3 ATNQ24GPLE5 ATNQ36GPLE5
ATNQ18GPLE5
TN ATNQ24GNLE3
Ceiling
4way
cassette ATNQ48GMLE3 ATNQ54GMLE3
TM ATNQ24GMLE6 ATNQ30GMLE3 ATNQ36GMLE3 ATNQ42GMLE3
ATNQ48GMLE5 ATNQ54GMLE5
TQ ATNQ18GQLE5 ATNQ24GQLE5
AVNQ18GJLA0 AVNQ24GJLA0
VJ AVNQ21GJLA0
AVNQ18GJLA2 AVNQ24GJLA2
AVNQ36GKLA0
Ceiling suspended VK AVNQ30GKLA0
AVNQ36GKLA2
AVNQ48GLLA0 AVNQ54GLLA0
VL AVNQ42GLLA0
AVNQ48GLLA2 AVNQ54GLLA2
BH ABNQ18GHLA0 ABNQ21GHLA0
Middle
static
BG ABNQ24GGLA0 ABNQ30GGLA0 ABNQ36GGLA0
Pressure(1)
ABNQ18GL2A0
Low L2 ABNQ21GL2A0
ABNQ18GL2A1
static
pressure ABNQ24GL3A0
L3
ABNQ24GL3A1
APNQ36GRA1
PR4 APNQ30GRA1
APNQ36GRA2
Floor standing
APNQ48GTA1
PT2 APNQ42GTA1
APNQ48GTA2
A T N Q 24 G N L E 3
Serial Number
Functions
A : Basic
E : Elevation grille
Look : Basic
Chassis Name
Electrical Ratings
G : 220-240V, 1Ø, 50Hz / 220V, 1Ø, 60Hz
L : 380-415V, 3Ø, 50Hz / 380V, 3Ø, 60Hz
Capacity Code based on ‘kBtu/h’ units
Model Type
Q: Cooling Only
R410A Single A Indoor Unit
ATN : Ceiling cassette type indoor unit
AVN : Convertible, Ceiling suspended type indoor unit
ABN : Ceiling concealed duct type indoor unit
APN : Floor Standing type indoor unit
Indoor units
Drain pump O O
E.S.P. control X X
Installation Electric heater X X
High ceiling operation* O O
Auto Elevation Grille PTEGM0 PTEGM0
Hot start X X
Reliability Self diagnosis O O
Soft dry operation X X
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) O O
Auto restart O O
Child lock* O O
Convenience Forced operation O O
Group control* O O
Sleep mode O O
Timer(on/off) O O
Timer(weekly)* O O
Two thermistor control* O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller O(PQWRCQ0FDB) O(PQWRCQ0FDB)
General central controller (Non LGAP) X X
CAC
Network Soluation(LGAP) X O
Network
Dry contact X PQDSA(1) / PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor X X
Others
Group Control wire PZCWRCG3 PZCWRCG3
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
ATNQ24GPLE5 / ATNQ24GQLE5
ATNQ18GPLE5
Category Functions ATNQ36GPLE5 / ATNQ48GMLE5
ATNQ18GQLE5
ATNQ54GMLE5
Air supply outlet 4 4
Airflow direction control(left & right) X X
Airflow direction control(up & down) Auto Auto
Auto swing(left & right) X X
Air flow Auto swing(up & down) O O
Airflow steps(fan/cool/heat) 4/5/- 4/5/-
Chaos wind(auto wind) O O
Jet cool O O
Swirl wind O O
Triple filter (Deodorizing) X X
Plasma air purifier PTPKM0 PTPKM0
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump O O
E.S.P. control X X
Indoor units
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 840 × 204 × 840 840 × 204 × 840
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 33-1/16 x 8-1/32 x 33-1/16
Net Weight Body kg (lbs) 20.5 (45.2) 20.5 (45.2)
Heat (Row x Column x Fins per inch) x No. - (2 x 8 x 19) x 1 (2 x 8 x 19) x 1
Exchanger Face Area m2 0.35 0.35
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 17.0 / 15.0 / 13.0 20.0 / 18.0 / 16.0
Air Flow Rate
Indoor units
H/M/L ft3/min 600 / 530 / 459 706 / 636 / 565
Type - BLDC BLDC
Fan Motor
Output W x No. 40 x 1 40 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 32 40 / 38 / 36
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 1.00
Casing Color - - -
WxHxD mm 840 × 246 × 840 840 × 288 × 840
Dimensions Body
WxHxD inch 33-1/16 x 9-11/16 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16
Net Weight Body kg (lbs) 22.0 (48.5) 24.6 (54.2)
Heat (Row x Column x Fins per inch) x No. - (2 x 10 x 19) x 1 (2 x 12 x 19) x 1
Exchanger Face Area m2 0.43 0.53
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 23.0 / 21.0 / 19.0 30.0 / 28.0 / 26.0
Air Flow Rate
H/M/L ft3/min 812 / 742 / 671 1,060 / 989 / 918
Type - BLDC BLDC
Indoor units
Fan Motor
Output W x No. 166.3 x 1 166.3 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 40 / 38 / 36 43 / 41 / 39
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 1.00 1.00
Casing Color - - -
WxHxD mm 840 × 288 × 840 840 × 288 × 840
Dimensions Body
WxHxD inch 33-1/16 x 11-11/32 x 33-1/16 33-1/16 x 11-11/32 x 33-1/16
Net Weight Body kg (lbs) 24.6 (54.2) 28.0 (61.7)
1# (Row x Column x Fins per inch) x No. - (2 x 12 x 19) x 1 (2 × 12 × 19) × 1
Heat
2# (Row x Column x Fins per inch) x No. - (1 × 10 × 19) × 1
Exchanger
Face Area m 2
0.53 0.53
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 30.0 / 28.0 / 26.0 32.0 / 30.0 / 28.0
Air Flow Rate
H/M/L ft3/min 1,060 / 989 / 918 1,130 / 1,060 / 989
Indoor units
Type - BLDC BLDC
Fan Motor
Output W x No. 166.3 x 1 135.8 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.4 (7.2)
Sound Pressure Level H/M/L dB(A) 43 / 41 / 39 44 / 42 / 40
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0 / 25.0 Ø 32.0 / 25.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 840 × 204 × 840 570 × 256 × 570
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 22-7/16 x 8-7/16 x 22-7/16
Net Weight Body kg (lbs) 19.6 (43.2) 15 (33)
Heat (Row x Column x Fins per inch) x No. - (2 x 8 x 21) x 1 (2 x 10x 18) x 1
Exchanger Face Area m2 0.33(3.55) 0.27(2.9)
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 17.0 / 15.0 / 13.0 13.0 / 12.0 / 11.0
Air Flow Rate
H/M/L ft3/min 600 / 530 / 459 459 / 424 / 388
Type - BLDC BLDC
Indoor units
Fan Motor
Output W x No. 50.3 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.1 (4.5)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 32 43 / 41 / 38
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UQC
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 700 × 22 ×700
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 27-9/16 x 7/8 x 27-9/16
Net weight kg (lbs) 5.0 (11.0) 3.0 (6.6)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 840 × 204 × 840 570 × 256 × 570
Dimensions Body
WxHxD inch 33-1/16 x 8-1/32 x 33-1/16 22-7/16 x 8-7/16 x 22-7/16
Net Weight Body kg (lbs) 19.7 (43.4) 15 (33)
Heat (Row x Column x Fins per inch) x No. - (2 x 8 x 21) x 1 (2 x 10x 18) x 1
Exchanger Face Area m2 0.33(3.55) 0.27(2.9)
Type - Turbo Fan Turbo Fan
Fan H/M/L m3/min 18.0 / 16.0 / 14.0 13.0 / 12.0 / 11.0
Air Flow Rate
H/M/L ft3/min 636 / 565 / 494 459 / 424 / 388
Type - BLDC BLDC
Indoor units
Fan Motor
Output W x No. 50.3 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.5 (5.3)
Sound Pressure Level H/M/L dB(A) 40 / 38 / 36 43 / 41 / 38
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UQC
Casing Color - Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 700 × 22 ×700
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 27-9/16 x 7/8 x 27-9/16
Net weight kg (lbs) 5.0 (11.0) 3.0 (6.6)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Indoor units
Fan Motor
Output W x No. 50.3 x 1 135.8 x 1 135.8 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.6 (7.7) 3.6 (7.7)
Sound Pressure Level H/M/L dB(A) 43 / 41 / 39 46 / 44 / 42 46 / 44 / 42
Sound Power Level Cooling dB(A) - - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/32)
Safety Devices - Fuse Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18) 4C x 0.75 (18)
Model Name - PT-UMC1 PT-UMC1 PT-UMC1
Casing Color - Morning Fog Morning Fog Morning Fog
Decoration
WxHxD mm 950 × 25 × 950 950 × 25 × 950 950 × 25 × 950
Panel Dimensions
WxHxD inch 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32 37-13/32 x 31/32 x 37-13/32
Net weight kg (lbs) 5.0 (11.0) 5.0 (11.0) 5.0 (11.0)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
TP Chassis
ATNQ18GPLE3
ATNQ21GPLE3
ATNQ18GPLE5
ATNQ24GPLE5
ATNQ36GPLE5
1.3 Dimensions
ATNQ24GNLE3
TN Chassis
Indoor units
TM Chassis
ATNQ30GMLE3
ATNQ36GMLE3
ATNQ42GMLE3
ATNQ48GMLE3
ATNQ54GMLE3
ATNQ24GMLE6
ATNQ48GMLE5
ATNQ54GMLE5
ATNQ18GQLE5
ATNQ24GQLE5
TQ Chassis
Indoor units
Thermistor for
Evaporator inlet
temperature
(flare connection)
ATNQ18GPLE3 ATNQ18GPLE5
Ø12.7(1/2) Ø6.35(1/4)
ATNQ21GPLE3 ATNQ18GQLE5
ATNQ24GNLE3 ATNQ24GMLE6
ATNQ30GMLE3 ATNQ24GPLE5
ATNQ36GMLE3 ATNQ24GQLE5 Ø15.88(5/8) Ø9.52(3/8)
ATNQ42GMLE3 ATNQ36GPLE5
ATNQ48GMLE3 ATNQ48GMLE5
Indoor units
Models : ATNQ18GPLE5 / ATNQ24GPLE5 / ATNQ36GPLE5 / ATNQ48GMLE5 / ATNQ54GMLE5
2.7m
2.0 2.0
1.5 1.5 2m
0.5 0.5
1.0 1.0
1m
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
Indoor units
Temperature [°C]
2.7m
18 18
24 24 2m
20 20
22 22 1m
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
2.7m
2.5 2.5
2.0 2.0
1.5 1.5 2m
1.0 1.0
1m
0.5 0.5
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
Temperature [°C]
2.7m
24 18 18 24
2m
20 20
22 1m
22
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
2.7m
3.0 3.0
2.0 2.0 2m
1.5 1.5
1.0 1.0
1m
0.5 0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
Indoor units
2.7m
18 18
2m
20 20
24 24
22 22 1m
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
3.2m
4.0 4.0
3.0 3.0
2.0 2.0
1.5 1.5 2m
1.0 1.0
1m
0.5 0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
3.2m
24 18 18 24
20 20
2m
22 1m
22
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
3.2m
4.0 4.0
3.0 3.0
2.0 2.0
2m
1.5 1.5
1.0 1.0 1m
0.5 0.5
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
Temperature [°C]
Indoor units
3.2m
18 18 24
24
20 20
2m
22 22
1m
0m
5m 4m 3m 2m 1m 0m 1m 2m 3m 4m 5m
2.7m
2.0 2.0 2m
1.5 1.5
1.0 1m
1.0
0.5 0.5
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
Temperature [°C]
2.7m
18 18
20 20 2m
22 22
1m
24 24
0m
4m 3m 2m 1m 0m 1m 2m 3m 4m
ATNQ36GMLE3 43 41 39 ATNQ36GPLE5 43 41 39
ATNQ42GMLE3 44 42 40 ATNQ48GMLE5 46 44 42
ATNQ48GMLE3 44 42 40 ATNQ54GMLE5 46 44 42
ATNQ54GMLE3 44 42 40
ATNQ24GMLE6 40 38 36
Indoor units
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
ATNQ48GMLE5 ATNQ54GMLE5
80 80
n High n High
70 70
Octave Band Sound Pressure Level (0dB = 20µPa)
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
4 13
6. UP/DOWN AIRFLOW Button
5 Used to stop or start louver movement and set the desired
6 14 up/down airflow direction.
7 7. ON TIMER Button
8 15
16 Used to set the time of starting operation.
8. SLEEP TIMER Button
9 17 Used to set the time of sleeping operation.
9. SET / CLEAR Button
Used to set/clear the timer.
Used to set the current time(if it input for 3sec.)
10. PLASMA Button (OPTIONAL)
Used to start or stop the plasma-purification function.
Operation Mode 11. ROOM TEMPERATURE SETTING Button
Used to select the room temperature.
Cooling Mode 12. OPERATION MODE SELECTION Button
Used to select the operation mode.
Auto Mode or Auto Changeover 13. INDOOR FAN SPEED SELECTION Button
Used to select fan speed in four steps low, medium, high
Dehumidification mode and chaos.
14. ROOM TEMPERATURE CHECKING Button
Heating Mode Used to check the room temperature.
15. OFF TIMER Button
Fan Mode Used to set the time of stopping operation.
16. TIMER SETTING(Up/Down)/LIGHT Button
• Cooling Model( ), Heat Pump Model( ) Used to set the timer.
Used to adjust the brightness.(if it is not time adjust mode)
17. RESET Button
Used to reset the remote controller.
Indoor units
Controller
1.9.1 Accessories
Check whether the following accessories are included with your unit.
1) Standard accessories
Quantity 1 EA 1 EA 8 EA 8 EA 1 SET
Discharge
Suction
more
10 or
frequent opening
and closing of door)
or more
500 or 500 or
1000
more more
H
• Countermeasure method
Unit : mm
① Air conditioner must be able to operate in high ceiling
conditioner.
Floor
② Plan to install the circulator.
③ The air discharge port is made to give more airflow to the
NOTE down wood directions.
Above figure means minimum value. Please keep these ④ The gate or exit of the building is protected by dual door
value at least. system.
• High Ceiling mode selection 2) In case the floor or surfaces of the place
Capacity ≤ 9.0 kW >9.0kW Mode Selection to be air conditioned is in direct contact
H ≤ 2.3m H ≤ 2.7m Low Ceiling with the outdoor air
Ceiling 2.3m < H ≤ 2.7m 2.7m < H ≤ 3.2m Standard
• The floor of the heating room indirect contact with
Height 2.7m < H ≤ 3.1m 3.2m < H ≤ 3.6m High Ceiling
the storeroom, garage or the outside air receives
3.1m < H ≤ 3.6m 3.6m < H ≤ 4.2m Super High Ceiling
the cold air at the floor and the floor temperature
decrease will feel cold at the feet.
Indoor
1500 or more
1500 or more
Low temperature
of the floor
Insulation required)
Outdoor side Garage
Outdoor side
1500 or more
In such places where the feet comes in direct contact
with floors will give a cold feeling to the floor.
CAUTION
Indoor units
ceiling slab(near by the sea, river, lake,
spa)
• In case of temperature of 30 degree and humidity
above 80%, the units body as well as the piping
insulation should be strengthened.
Refer to the picture given below.
Lighting
False ceiling
TP/TN/TM Series
875(Ceiling opening)
787(Hanging bolt) NOTE
Indoor units
Unit:mm
TQ/TR Series
585~660
517
570
585~660
523
517
570
319
461 Unit:mm
• Installing of the accessories (except for the decoration (2) Adjust the unit to the right position for installa-
panel) before installing the indoor unit is easier. tion.
(3) Assure that the unit is horizontal.
1) Install the indoor unit temporarily.
• The indoor unit is equipped with a built-in drain pump
• Attach the hanger bracket to the suspension bolt. Be sure and float switch. At each of the unit's 3 corners, verify
to fix it securely by using a nut and washer from the upper that it is level by using awater-level or a water-filled
and lower sides of the hanger bracket. vinyl tube. (Otherwise it will result in the malfunctioning
of unit and cause water to drip.)
Hanging bolt
(W3/8 or M10) (4) Remove the washer fixing plate used for
Nut
Flat washer for M10 preventing the washer from falling and tighten
(W3/8 or M10)
(accessory) the upper nut.
Spring washer
(M10) (5) Remove the paper pattern for installation
Flat washer for M10
(accessory)
3) For existing ceilings
Indoor units
(1) Adjust the height and position of the unit.
180mm(TR,Q Chassis)
Ceiling
150mm(TP Chassis)
Keep the length of the bolt (2) Perform steps 3 and 4 in "5.1 For new ceilings".
from the bracket to 40mm
CAUTION
2) For new ceilings
• Make sure to insulate any field piping all the way to the
(1) Refer to the paper pattern for ceiling opening piping connection inside the unit. Any exposed piping
dimension. may cause condensation or burns if touched.
• The center of the ceiling opening is indicated on the
paper pattern for installation.
The center of the unit is indicated on the label attached
to the unit and on the paper pattern for installation.
• First remove paper packaging material from the
4 corners of the paper pattern for installation , fix the
paper pattern to the unit with screws.
• Ceiling height is shown on the side of the paper pattern
for installation. Adjust the height of the unit according to
this indication.
Upward
Pipe clamp 1. Remove the packing and take out air inlet grille from
routing
not allowed front panel.
Indoor unit
Front grille
Maintenance
drain port
300mm or less
1 -1.5m
Indoor units
700 or less
Drain
Drain Pump port Glue the joint
Drain hose connection Hook
Use the clip (accessory)
Drain pan
Indoor units
CN-VANE 1,2 CN-DISPLAY
Screw
Air conditioner
unit
Ceiling
board
Decorative panel
Fit the insulator (this part) and
be careful for cool air leakage
Remote
controller
cord
Bad example Air conditioner unit Connection 1
cord
Indoor units
CAUTION
body to wire the outdoor unit, indoor units and the remote
20
controller. mm
Power wire
r
Indoor units
• For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
exerted on the terminal block.
It is forbidden to connect wiring of different thicknesses.
• Use an appropriate screwdriver for tightening the terinal
screws. A screwdriver with a small head will strip the head
and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
WARNING
• Make sure that the screws of the terminal are free from
looseness.
Indoor units
Drain pump X X
E.S.P. control X X
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) X X
Auto Restart O O
Child lock* O O
Convenience Forced operation O O
Group control* O O
Sleep mode X X
Timer(on/off) O O
Timer(weekly)* O O
Two thermistor control* O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller PQRCVCL0Q / PQRCVCL0QW PQRCVCL0Q / PQRCVCL0QW
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller O O
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSA(1) / PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor X X
Others
Group Control wire X X
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
AVNQ24GJLA2 / AVNQ36GKLA2
Category Functions AVNQ18GJLA2
AVNQ48GLLA2 / AVNQ54GLLA2
Air supply outlet 1 1
Airflow direction control (left & right) Manual Manual
Airflow direction control (up & down) Auto Auto
Auto swing (left & right) - -
Air flow Auto swing (up & down) O O
Airflow steps (fan/cool/heat) 4/5/- 4/5/-
Chaos wind(auto wind) X X
Jet cool O O
Swirl wind X X
Triple filter (Deodorizing) X X
Plasma air purifier X X
Air purifying
Allergy Safe filter X X
Long-life prefilter (washable / anti-fungus) O O
Drain pump X X
E.S.P. control X X
Installation Electric heater X X
Indoor units
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - - -
WxHxD mm 950 × 650 × 220 950 × 650 × 220
Dimensions Body
WxHxD inch 37-13/32 x 25-19/32 x 8-21/32 37-13/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 20.5(45.2) 20.5(45.2)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.20 (2.15) 0.20 (2.15)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 12.4 / 11.4 / 10.4 12.4 / 11.4 / 10.4
Air Flow Rate
Indoor units
H/M/L ft3/min 438 / 403 / 367 438 / 403 / 367
Type - BLDC BLDC
Fan Motor
Output W x No. 60 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 44 / 43 / 41 44 / 43 / 41
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG)
2
4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.70
Casing Color - - -
WxHxD mm 950 × 650 × 220 1,350 × 650 × 220
Dimensions Body
WxHxD inch 37-13/32 x 25-19/32 x 8-21/32 53-5/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 20.5(45.2) 29.0(63.9)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.20 (2.15) 0.32 (3.42)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 12.4 / 11.4 / 10.4 21.4 / 19.8 / 18.2
Air Flow Rate
H/M/L ft3/min 438 / 403 / 367 756 / 699 / 643
Type - BLDC BLDC
Indoor units
Fan Motor
Output W x No. 60 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 44 / 43 / 41 45 / 43 / 41
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.70 0.90
Casing Color - - -
WxHxD mm 1,350 × 650 × 220 1,750 × 650 × 220
Dimensions Body
WxHxD inch 53-5/32 x 25-19/32 x 8-21/32 68-29/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 29.0(63.9) 35.0 (77.2)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.32 (3.42) 0.44 (4.68)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 21.4 / 19.8 / 18.2 28.6 / 26.9 / 25.2
Air Flow Rate
H/M/L ft3/min 756 / 699 / 643 1,010 / 950 / 890
Type - BLDC BLDC
Indoor units
Fan Motor
Output W x No. 60 x 1 60 x 2
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 45 / 43 / 41 47 / 46 / 44
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.90 0.90
Casing Color - - -
WxHxD mm 1,750 × 650 × 220 1,750 × 650 × 220
Dimensions Body
WxHxD inch 68-29/32 x 25-19/32 x 8-21/32 68-29/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 35.0 (77.2) 35.0 (77.2)
Heat (Row x Column x Fins per inch) x No. - (3 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.44 (4.68) 0.44 (4.68)
Type - Cross flow fan Cross flow fan
Fan H/M/L m3/min 28.6 / 26.9 / 25.2 31.5 / 29.7 / 28.0
Air Flow Rate
H/M/L ft3/min 1,010 / 950 / 890 1,112 / 1,049 / 989
Type - BLDC BLDC
Indoor units
Fan Motor
Output W x No. 60 x 2 60 x 2
Dehumidification Rate l / h (pts/h) 3.6 (7.7) 3.6 (7.7)
Sound Pressure Level H/M/L dB(A) 47 / 46 / 44 48 / 47 / 45
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 21.5 / 16.0 Ø 21.5 / 16.0
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.60 0.60
Casing Color - Morning Fog Morning Fog
WxHxD mm 950 × 650 × 220 950 × 650 × 220
Dimensions Body
WxHxD inch 37-13/32 x 25-19/32 x 8-21/32 37-13/32 x 25-19/32 x 8-21/32
Net Weight Body kg (lbs) 19.7 (43.4) 20.7 (45.6)
Heat (Row x Column x Fins per inch) x No. - (2 x 14 x 21) x 1 (3 x 14 x 21) x 1
Exchanger Face Area m2 (ft2) 0.19 (2.05) 0.19 (2.05)
Type - Cross Flow Fan Cross Flow Fan
Fan H/M/L m3/min 12.4 / 11.4 / 10.4 13.9 / 12.9 / 11.9
Air Flow Rate
H/M/L ft3/min 438 / 403 / 367 491 / 456 / 420
Type - BLDC BLDC
Indoor units
Fan Motor
Output W x No. 60 x 1 60 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.1 (4.5)
Sound Pressure Level H/M/L dB(A) 44 / 43 / 41 44 / 43 / 41
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.5(27/32) / 16.0(5/8) Ø 21.5(27/32) / 16.0(5/8)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Fan Motor
Output W x No. 60 x 2 60 x 2 60 x 2
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 2.7 (5.7) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 47 / 46 / 44 47 / 46 / 44 48 / 47 / 45
Sound Power Level Cooling dB(A) - - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 21.5(27/32) / 16.0(5/8) Ø 21.5(27/32) / 16.0(5/8) Ø 21.5(27/32) / 16.0(5/8)
Safety Devices - Fuse Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
AVNQ18GJLA0
AVNQ21GJLA0
AVNQ24GJLA0
AVNQ18GJLA2
AVNQ24GJLA2
2.3 Dimensions
2. Ceiling suspended
VK Chassis
AVNQ30GKLA0
AVNQ36GKLA0
AVNQ36GKLA2
AVNQ42GLLA0
AVNQ48GLLA0
AVNQ54GLLA0
AVNQ48GLLA2
AVNQ54GLLA2
2. Ceiling suspended
Thermistor for
evaporator outlet
temperature
Indoor units
Thermistor for
evaporator outlet
temperature
Indoor units
(flare connection)
Thermistor for
evaporator outlet
temperature
(flare connection)
Indoor units
Models : AVNQ30KLA0 / AVNQ36KLA0 / AVNQ42GLLA0 / AVNQ48GLLA0 / AVNQ54GLLA0
Cooling
Discharge angle:40°
2.5
2.5
1m
2.0
Indoor units
Temperature [°C]
2.7m
2m
26
24 38
24 25
16 1m
36
20
23 28
22 30 32 34
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Cooling
Discharge angle:40°
2m
3.0
3.0
0.5
1m 2.5
2.5 0.5
2.0
1.0 2.0
0.5 1.0 1.5 1.0 1.5
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Temperature [°C]
2.7m
25
2m
22 36
23
24 26
16 1m
20 34
22 28 32 26
30
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Model : AVNQ42GLLA0
Cooling
Discharge angle:10°
1
1m
0.5
0.25
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Temperature [°C]
19 17 15 2.7m
21
23
Indoor units
25
2m
27
1m
31
29
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Cooling
Discharge angle:10°
1m
0.25
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Temperature [°C]
18 16 14 2.7m
20
24 22
28 2m
26
1m
30
28
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Cooling
Discharge angle:10°
1m
0.5
0.25
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Temperature [°C]
18 16 2.7m
20 14
Indoor units
22
24 2m
26
1m
28 30
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
AVNQ36GKLA0 45 43 41
AVNQ42GLLA0 47 46 44
AVNQ48GLLA0 47 46 44
AVNQ54GLLA0 48 47 45
AVNQ18GJLA0 AVNQ30GKLA0
AVNQ21GJLA0 AVNQ24GJLA0 AVNQ36GKLA0
80 80 80
70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)
70 70 70
Indoor units
NC-15 NC-15 NC-15
10 10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
AVNQ24GJLA2 AVNQ36GKLA2
80 80
70 70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Control
panel g 7 v Indoor fan speed button: Adjusts the
fan speed.
Operation mode selection button*:
Selects the operation mode.
A C Cooling operation (A) / Auto operation or
f D B
auto changeover (C) / Dehumidifying
E
operation (D) / Heating operation (B) /
Air circulation (E)
Indoor units
- Bolts for Mount Bracket
- Connecting Tube(mm)
• Gas side : Ø9.52, Ø12.7
• Liquid side : Ø6.35
- Connecting Cable Vinyl tape (Wide)
• To carry out the drainage
- Drain Hose Extended test, remove the air filters
and pour water into the heat
exchanger.
Saddle • Apply after carrying out a
drainage test.
2.9.1 Accessories
Check the following accessories are included with your unit.
1) Standard accessories
• Owner's manual
• Installation manual
Step 1
More than 50mm
(Ceiling installation)
Step 2
Right side cover
Backside
Left side
cover
Backside
Step 3
Indoor units
tomside so as to drain well. Spring Washer - M10
Plate Washer - M10
[Unit : mm]
DIMENSION
A B
MODEL
CAUTION
VL 1655 320
Tighten the nut and bolt to prevent unit falling.
VK 1255 320
• Drill the piping hole on the wall slightly tilted to the out-
VJ 855 320
door side using a Ø 70 hole-core drill.
Anchor nut
Wall
Ceiling
B Indoor Outdoor
Nut Washer A
Suspension
bolts
Suspension bolt
5~7mm
Suspension
bolts
Spring
washer Nut
Hangen
Max.
12mm Washer
CAUTION
Front of view
- The unit must be horizontal or inclined at angle.
- The inclination should be less than or equal to 1°or in between 10 to 20mm inclined in drain direction as shown in fig.
Ceiling
Indoor units
10~20mm
Side of view
- The unit must be declined to the bottomside of the unit when finished installation.
Ceiling
5~10mm
Indoor units
drain exit.
Bracket
• Heat insulation
• Drain piping
Use the heat insulation material for the refrig-erant piping
- The drain hose should point downward for easy drain flow. which has an excellent heat-resis-tance (over 120°C).
Downward Precautions in high humidity circumstance:This air condi-
slope
tioner has been tested accordingto the "KS Standard
Conditions with Mist" andconfirmed that there is not any
default.However, if it is operated for a long time inhigh
humid atmosphere (dew point tempera-ture: more than
23°C), water drops are liablto fall. In this case, add heat
- Do not make drain piping like the following. insulation material according to the following procedure:
Air
Refrigerant piping
Water Water Waving
leakage leakage Indoor unit
Thermal insulator
(accessory)
Tip of drain
hose dipped Less than
in water 50mm gap - Heat insulation material to be prepared...Adiabatic glass
wool with thickness 10 to 20mm.
Water
leakage - Stick glass wool on all air conditioners thatare located in
Ditch
ceiling atmosphere.
- Be sure to execute heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thick-
ness more than 8 mm.
CAUTION
2) Wiring connection • Make sure that the screws of the terminal are fixed tightly.
1(L) 2(N) 3
Electric wire
Indoor units
2. Tightening torque for the terminal screws.
① Use the correct screw driver for tightening the terminal
screws. If the blade of screwdriver is too small, the head
of the screw might be damaged, and the screw will not be
properly tightened.
② If the terminal screws are tightened too hard, screws
might be damaged.
3. Do not connect wires of different gauge to the
same grounding terminal. Loose connection may
deteriorate protection.
Indoor units
E.S.P. control O O
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) X X
Auto Restart O O
Child lock O O
Convenience Forced operation X X
Group control O O
Sleep mode X X
Timer(on/off) X X
Timer(weekly) X X
Two thermistor control O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller O O
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller X X
General central controller (Non LGAP) X X
Network Network Solution(LGAP) X O
function Dry contact X PQDSB**
PI 485(for Indoor Unit) X X
Zone controller ABZCA ABZCA
Special
CTI(Communication transfer interface) X X
function kit
Electronic thermostat X X
Others Remote temperature sensor PQRSTA0 PQRSTA0
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
78 (8) 78 (8)
Type - BLDC BLDC
Fan Motor
Output W x No. 154 x 1 154 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 37 / 35 / 33 37 / 35 / 33
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG) 2
4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Indoor units
78 (8) 98 (10)
Type - BLDC BLDC
Fan Motor
Output W x No. 154 x 1 154 x 1
Dehumidification Rate l / h (pts/h) 2.5 (5.3) 2.7 (5.7)
Sound Pressure Level H/M/L dB(A) 42 / 39 / 36 42 / 39 / 36
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG) 2
4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
98 (10) 98 (10)
Type - BLDC BLDC
Fan Motor
Output W x No. 154 x 1 350 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.4 (7.2)
Sound Pressure Level H/M/L dB(A) 42 / 39 / 36 44 / 42 / 40
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Indoor units
98 (10) 98 (10)
Type - BLDC BLDC
Fan Motor
Output W x No. 350 x 1 185 x 2
Dehumidification Rate l / h (pts/h) 3.6 (7.7) 3.6 (7.7)
Sound Pressure Level H/M/L dB(A) 44 / 42 / 40 46 / 44 / 42
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
ABNQ24GGLA0
ABNQ30GGLA0
ABNQ36GGLA0
BG Chassis
Indoor units
ABNQ42GRLA0
ABNQ48GRLA0
ABNQ54GRLA0
BR Chassis
Indoor units
Thermistor for
evaporator inlet
temperature
Indoor units
Liquid pipe connection port
(flare connection)
Indoor units
Models : ABNQ24GGLA0
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118) 14(137)
80 14.8 - - - -
90 19.0 14.4 - - -
100 23.3 19.7 13.9 - -
110 26.9 24.3 19.8 14.1 -
120 31.2 28.2 25.2 20.1 14.4
130 34.9 32.4 29.5 25.4 20.5
Models : ABNQ42GRLA0
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118)
85 31.5 - - -
90 36.3 29.8 - -
95 41.3 34.5 28.4 -
100 45.4 39.7 33.5 27.3
105 - 44.1 38.6 33.1
110 - - 44.2 38.9
115 - - - 44.7
Models : ABNQ48GRLA0
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118)
Indoor units
85 31.5 - - -
90 36.3 29.8 - -
95 41.3 34.5 28.4 -
100 45.4 39.7 33.5 27.3
105 - 44.1 38.6 33.1
110 - - 44.2 38.9
115 - - - 44.7
Models : ABNQ54GRLA0
(Unit: CMM)
Static Pressure[mmAq(Pa)]
Setting Value
6(59) 8(78) 10(98) 12(118) 14(137)
95 41.3 - - - -
100 45.4 39.7 - - -
105 49.5 44.1 38.6 - -
110 - 48.5 44.2 38.9 -
115 - - 49.8 44.7 42.2
120 - - - 50.5 48.1
h ABNQ42GRLA0 / ABNQ48GRLA0
As far as possible do not set ESP 82,83
Table 2
Indoor units
ABNQ36GGLA0 42 39 36
ABNQ42GRLA0 44 42 40
ABNQ48GRLA0 44 42 40
ABNQ54GRLA0 46 44 42
70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)
70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)
Operation
1 Displays the operating conditions.
display
SLO
LO
1 Room
MED
Used to set the room temperature
HI
2 temperature
SHI when required.
Indoor units
VANE
setting
2
3 Fan speed Used to set the desired fan speed.
3
4
Operation starts when this button is
ROOM
5
4 On/Off pressed, and stops when the button
TEMP
is pressed again.
Room
5 temperature Used to check the room temperature.
checking
Remote controller
HI
SHI
VANE
Indoor units
HI
SHI
VANE
Remote controller
3.9.1 Accessories
Check whether the following accessories are included with your unit.
1) Standard accessories
Insulation for Screws for
Name Clamp metal Drain hose Clamp (Other)
fitting duct flanges
• Owner's manual
• Installation manual
• Washers(8 pcs.)
Shape for gas pipe
355
Indoor units
120
Inspection
hatch 600 x 600
[BG Chassis]
1232
② A place where the unit will be leveled and that can sup- ⑨ Secure the installation plates on the suspension bolts
port the weight of the unit. (adjust level roughly) using nuts, washers and spring
washers.
③ A place where the unit can withstand its vibration.
④ A place where service can be easily performed.
Old building New building
M10 Nut x4
(Local
M10 SP. washer x 4 supply)
M10 washer x4
1 Set anchor
2 Plate washer
M10 washer x4 3 Spring washer
Indoor units
(Local 4 Nut
M10 SP. washer x 4 supply)
M10 Nut x4 5 Suspension
bolts
CAUTION
Liquid pipe
Indoor units
4) Caution for gradient of unit and drain
Refrigerant pipe and thermal
insulation(Local supply) piping
- Without drain pump
Clamp for insulation ① Always lay the drain with downward inclination (1/50 to
(Local supply) 1/100).
Insulation Prevent any upward flow or reverse flow in any part.
(Local supply)
② 10mm or thicker formed thermal insulation shall always
Union for gas pipe be provided for the drain pipe.
or more or more
Approx 2~3mm 50mm 50mm
Overlap with
insulation
CAUTION
• Make sure to insulate any field piping all the way to the
piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
Drain pipe
⑤ A circuit breaker capable of shutting down the power
Unit (Local supply)
supply to the entire system must be installed.
Elbow
Drain pump
Indoor units
of its service agent.
WARNING
Indoor units
E.S.P. control O O
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) X X
Auto Restart O O
Child lock O O
Convenience Forced operation X X
Group control O O
Sleep mode X X
Timer(on/off) X X
Timer(weekly) X X
Two thermistor control O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller O O
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller X X
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSB**
function
PI 485(for Indoor Unit) X X
Zone control ABZCA ABZCA
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others
Group Control wire PZCWRCG3 PZCWRCG3
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
Indoor units
25 (2.54) 25 (2.54)
Type - BLDC BLDC
Fan Motor
Output W x No. 19 x 1 19 x 1
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.3 (4.9)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 31 36 / 34 / 31
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 6.35 (1/4)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 12.7 (1/2)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4 Ø 25.4 / 20.4
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Fan Motor
Output W x No. 19 x 2
Dehumidification Rate l / h (pts/h) 2.5 (5.3)
Sound Pressure Level H/M/L dB(A) 39 / 35 / 32
Sound Power Level Cooling dB(A) -
Liquid mm(inch) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4 / 20.4
Safety Devices - Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Indoor units
Fan Motor
Output W x No. 19 x 1 19 x 2
Dehumidification Rate l / h (pts/h) 2.1 (4.5) 2.5 (5.3)
Sound Pressure Level H/M/L dB(A) 36 / 34 / 31 39 / 35 / 32
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 25.4(1) / 20.4(13/16) Ø 25.4(1) / 20.4(13/16)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
L2/L3 Chassis
ABNQ18GL2A0
ABNQ21GL2A0
ABNQ24GL3A0
ABNQ18GL2A1
ABNQ24GL3A1
4.3 Dimensions
5
20 D
A B C D
135
974 900 933 860
ABNQ21GL2A0
34
190 ABNQ24GL3A0 1,174 1,100 1,133 1,060
100
94
292
67 119
1
700
628
220
4
L1 : 366
L2 : 561
L3 : 755 C
6 Gravity point
20
4. Ceiling concealed duct – Low static pressure
190
155
L1 : 75
L2 : 78
L3 : 81
B Air suction
A
Air discharge
Power supply connection
Drain pipe connection
Gas pipe connection
Liquid pipe connection
4. Ceiling concealed duct – Low static pressure
4.4 Piping diagrams
: Refrigerant Flow
Evaporator Out
Temperature
Thermistor
Evaporator In
Sirocco Fan Temperature
Thermistor
Indoor Unit
Indoor units
Inlet Air
Temperature
Thermistor
ABNQ24GL3A0
Ø 15.88 (5/8) Ø 9.52 (3/8)
ABNQ24GL3A1
Indoor units
16 CMM 100 107 115 121 127
ABNQ24GL3A1
12 CMM 90 97 105 114 122
[Notes]
1. To get the desired Airflow & E.S.P. combination from the table set the matching value from the table. Value other than
that in table will not give the combinations of airflow & E.S.P. which are mentioned in the table.
2. Table data is based at 230V. According to the fluctuation of voltage, air flow rate varies.
Note :
1. The above table shows the correlation between the air rates and E.S.P.
Indoor units
ABNQ18GL2A1 36 34 31
ABNQ24GL3A1 39 35 32
70
Octave Band Sound Pressure Level (0dB = 20μPa)
70
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
20 NC-25 20 NC-25
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Operation
1 Displays the operating conditions.
display
SLO
LO
1 Room
MED
Used to set the room temperature
HI
2 temperature
when required.
Indoor units
SHI
VANE
setting
2
3 Fan speed Used to set the desired fan speed.
3
4
Operation starts when this button is
ROOM
5
4 On/Off pressed, and stops when the button
TEMP
is pressed again.
Room
5 temperature Used to check the room temperature.
checking
Air filters
Indoor units
SLO
LO
MED
Remote Controller
HI
SHI
VANE
4.9.1 Accessories
Check the following accessories are included with your unit.
1) Standard accessories
• Owner's manual
• Installation manual
unit.
1 Set anchor
2 Plate washer
3 Spring washer
Thermal insulation for refrigerant pipe
4 Nut (Local supply) Thermal insulation for
Indoor units
al
5 Suspension piping(Local supply)
bolts
Overlap with
4.9.5 Connecting pipes to the indoor insulation
unit
Make sure that there is no clearance here.
1) Refrigerant piping work
please refer “REFRIGERANT PIPING WORK”.
2) Piping insulation CAUTION
① Perform heat insulation work completely on both gas and • Make sure to insulate any field piping all the way to the
the liquid pipe. Because improper insulation will result piping connection inside the unit. Any exposed piping
condensate formation over pipe. may cause condensation or burns if touched.
Use the heat insulation material for the refrigerant piping
which has an excellent heat resistance (over 248°F).
② Precautions in high humidity circumstance: This air con-
ditioner has been tested according to the "KS
Conditions" and confirmed that there is not any default.
However, if it is operated for a long time in high humid
atmosphere (dew point temperature: more than 73°F),
water drops are liable to fall. In this case, add heat
insulation material according to the following procedure:
③ Heat insulation material : Adiabatic glass wool with thick-
ness 13/32 to 13/16 inch.
④ Stick glass wool on all air conditioners that are located in
ceiling atmosphere.
CAUTION
Correct method
1/50~1/100
Drain Pipe
Indoor units
① All field supplied parts and materials, electric works must
Thermal insulation conform to local codes.
(Local supply) Use copper wire only.
Drain pipe
② Follow the "WIRING DIAGRAM” attached to the unit
Unit (Local supply)
body to wire the outdoor unit, indoor units and the remote
controller.
③ All wiring must be performed by an authorized electri-
Elbow cian.
④ This system consists of multiple indoor units. Mark each
Drain pump indoor unit as unit A, unit B..., and be sure the terminal
board wiring to the outdoor unit and ID unit are properly
matched. If wiring and piping between the outdoor unit
5) Checking the drainage and an indoor unit are mismatched, the system may
cause a malfunction.
① Remove the air filter.
⑤ A circuit breaker capable of shutting down the power
supply to the entire system must be installed.
2) Wiring connection
Connect the wires to the terminals on the control board ind
vidually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the
terminal No. are the same as those of indoor unit respec-
tively
1(L) 2(N) 3
• Make sure that the screws of the terminal are fixed Round crimp-style terminal
tightly.
Electric wire
Indoor units
CAUTION
Indoor units
E.S.P. control X X
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning O X
Auto operation(artificial intelligence) O O
Auto restart O O
Child lock O O
Convenience Forced operation X O
Group control X X
Sleep mode X O
Timer(on/off) O O
Timer(weekly) X O
Two thermistor control X O
Wired remote controller X X
Deluxe wired remote controller X X
Individual
Simple wired remote controller X X
control
Simple Wired remote controller(for hotel use) X X
Wireless remote controller O O
General central controller (Non LGAP) X X
CAC Network Soluation(LGAP) O O
Network Dry contact PQDSA(1)/PQDSB(1) / PQDSBC PQDSA(1)/PQDSB(1)
function PDI(power distribution indicator) X X
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor X X
Others
Group Control wire X X
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.50 0.50
Casing Color - - -
WxHxD mm 590 × 1,840 × 320 590 × 1,840 × 320
Dimensions Body
WxHxD inch 23-7/32 x 72-7/16 x 12-19/32 23-7/32 x 72-7/16 x 12-19/32
Net Weight Body kg (lbs) 36.0 (79.4) 36.0 (79.4)
Heat (Row x Column x Fins per inch) x No. - (3 x 38 x 19) x 1 (3 x 38 x 19) x 1
Exchanger Face Area m2 (ft2) 0.30 (3.26) 0.30 (3.26)
Type - Sirocco Sirocco
Fan SH / H / M / L m3/min 23.5 / 21.0 / 17.0 / 14.0 23.5 / 21.0 / 17.0 / 14.0
Indoor units
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.91 0.91
Casing Color - - -
WxHxD mm 590 × 1,840 × 460 590 × 1,840 × 460
Dimensions Body
WxHxD inch 23-7/32 x 72-7/16 x 18-1/8 23-7/32 x 72-7/16 x 18-1/8
Net Weight Body kg (lbs) 49.0 (108.0) 49.0 (108.0)
Heat (Row x Column x Fins per inch) x No. - (3 x 38 x 19) x 1 (3 x 38 x 19) x 1
Exchanger Face Area m (ft )
2 2
0.39 (4.17) 0.39 (4.17)
Type - Sirocco Sirocco
Fan SH / H / M / L m /min
3
38.0 / 32.0 / 28.0 / 24.0 38.0 / 32.0 / 28.0 / 24.0
Air Flow Rate
SH / H / M / L ft3/min 1,342 / 1,130 / 989 / 848 1,342 / 1,130 / 989 / 848
Indoor units
Type - BLDC BLDC
Fan Motor
Output W x No. 224 x 1 224 x 1
Dehumidification Rate l / h (pts/h) 5.2 (11.0) 5.2 (11.0)
Sound Pressure Level SH / H / M / L dB(A) 56 / 53 / 50 / 47 56 / 53 / 50 / 47
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 21.0 / 17.0 Ø 21.0 / 17.0
- Fuse Fuse
Safety Devices
Thermal Protector for Fan Motor Thermal Protector for Fan Motor
Power and Communication Cable (included Earth) No. x mm2 (AWG) 3C x 1.0 (18) 3C x 1.0 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
220-240, 1, 50 220-240, 1, 50
Power Supply V, Ø, Hz
220, 1, 60 220, 1, 60
Power Input W - -
Running Current A 0.90 1.00
Casing Color -
WxHxD mm 590 × 1,840 × 320 590 × 1,840 × 460
Dimensions Body
WxHxD inch 23-7/32 x 72-7/16 x 12-19/32 43-5/16 x 7-15/32 x 18-1/8
Net Weight Body kg (lbs) 36.0 (79.4) 49.0 (108.0)
Heat (Row x Column x Fins per inch) x No. - (3 x 38 x 19) x 1 (3 x 38 x 19) x 1
Exchanger Face Area m (ft )
2 2
0.30 (3.26) 0.39 (4.17)
Type - Sirocco Fan Sirocco Fan
Fan SH / H / M / L m /min
3
23.5 / 21.0 / 17.0 / 14.0 38.0 / 32.0 / 28.0 / 24.0
Air Flow Rate
SH / H / M / L ft3/min 830 / 742 / 600 / 494 1,342 / 1,130 / 989 / 848
Indoor units
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Indoor units
PT2 Chassis
APNQ42GTA1
APNQ48GTA1
APNQ48GTA2
5. Floor standing
Th3 Th1
Th2
M
Fan
Indoor units
: Refrigerant Flow
0.2
Indoor units
Temperature [°C]
2.7m
20
14 2m
16 12
18
1m
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Cooling
Discharge angle:90°
0.5 1.0
1.5 1.0
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
Temperature [°C]
2.7m
17
2m
15 13
19
1m
0m
8m 7m 6m 5m 4m 3m 2m 1m 0m
APNQ36GRA1 54 50 46 43
APNQ42GTA1 56 53 50 47
APNQ48GTA1 56 53 50 47
APNQ36GRA2 54 50 46 43
APNQ48GTA2 56 53 50 47
l Low l Low
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Control
No. Description
panel
1
1 Remote control operation lamp
2 5 Power ON/OFF button : Operation will start when
4 2 | this button is pressed, and stop when the button is
pressed again.
3 6
Indoor fan speed button : To select the desired fan
7 3
speed.
8 9
4 Temperature setting button
10 11
Indoor units
5 A Cooling button
12 13
6 Auto cleaning button
Core Drill
200mm
70mm
70mm
90mm
Indoor units
5.9.3 Electric wiring work
CAUTION
1) General instructions
• The connecting cable connected to the indoor and out-
① All field supplied parts and materials, electric works must door unit should be complied with the following specifi-
conform to local codes. Use copper wire only.
cations (This equipment shall be provided with a cord
② Follow the "WIRING DIAGRAM” attached to the unit set complying with the national regulation).
body to wire the outdoor unit, indoor units and the remote
10±3mm
controller.
③ All wiring must be performed by an authorized electri- mm
±5
35
cian.
③ This system consists of multiple indoor units. Mark each GN
/Y
indoor unit as unit A, unit B...., and be sure the terminal L
board wiring to the outdoor unit and indoor unit are prop- 20
mm
erly matched. If wiring and piping between the outdoor NORMAL
unit and an indoor unit are mismatched, the system may CROSS-SECTIONAL
AREA 0.75mm2
cause a malfunction.
④ A circuit breaker capable of shutting down the power • If the supply cord is damaged, it must be replaced by a
supply to the entire system must be installed. special cord or assembly available from the manufactur-
er of its service agent.
2) Wiring Connection
① Connect the wires to the terminals on the control board
CAUTION
individually according to the outdoor unit connection.
• The Power cord connected to the unit should be select-
ed according to the following specifications.
Power wire
r
It is forbidden to
Connect same thickness It is forbidden to connect connect wiring of 3. Connect the cables to the connector in the control box.
wiring to both sides. two to one side. different thicknesses.
Indoor unit
Outdoor unit
Main power
• For wiring, use the designated power wire and connect 4. Secure the control cover to the original position with the
firmly, then secure to prevent outside pressure being screw.
exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal 5. Close the inlet grille.
screws. A screwdriver with a small head will strip the head
and make proper tighterning impossible.
• Over-tightening the terminal screws may break them. CAUTION
CAUTION
• For test run, carry out the cooling operation firstly even
Thermometer
during heating season. If heating operation is carried out
firstly, it leads to the trouble of compressor. Then atten-
tion must be paid.
• Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
Indoor units
CAUTION
2) Check the following items when installa- After the confirmation of the above conditions, prepare the
tion is complete wiring as follows:
After completing work, be sure to measure and record trial • Never fail to have an individual power specialized for the
run properties, and store measured data, etc. air conditioner. As for the method of wiring, be guided by
Measuring items are room temperature, outside tempera- the circuit diagram pasted on the inside of control box
ture, suction temperature, blow out temperature, wind veloc- cover.
ity, wind volume, voltage, current, presence of abnormal • Provide a circuit breaker switch between power source
vibration and noise, operating pressure, piping temperature, and the unit.
compressive pressure. • The screw which fasten the wiring in the casing of elec-
As to the structure and appearance, check following items. trical fittings are liable to come loose from vibrations to
- Is the circulation of air adequate? which the unit is subjected during the course of trans-
- Is the draining smooth? portation. Check them and make sure that they are all
- Is the heat insulation complete tightly fastened. (If they are loose, it could give rise to
(refrigerant and drain piping)? burn-out of the wires.)
- Is there any leakage of refrigerant? • Specification of power source.
- Is the remote controller switch operated? • Confirm that electrical capacity is sufficient.
- Is there any faulty wiring? • Be sure that the starting voltage is maintained at more
than 90 percent of the rated voltage marked on the name
- Are not terminal screws loosened?
plate.
M4......118N.cm{12kgf.cm} • Confirm that the cable thickness is as specified in the
M5......196N.cm{20kgf.cm} power sources specification.(Particularly note the rela-
M6......245N.cm{25kgf.cm} tion between cable length and thickness.)
M8......588N.cm{60kgf.cm} • Never fail to equip a leakage breaker where it is wet or
moist.
3) Connection of power supply • The following troubles would be caused by voltage drop-
down.
Connect the power supply cord to the independent power - Vibration of a magnetic switch, damage on the contact
supply. point there of, fuse breaking, disturbance to the normal
- Circuit breaker is required. function of a overload protection device.
Operate the unit for fifteen minutes or more. - Proper starting power is not given to the compressor.
Indoor units
Installation Electric heater X X
High ceiling operation X X
Auto Elevation Grille X X
Hot start X X
Reliability Self diagnosis O O
Soft dry operation O O
Auto changeover X X
Auto cleaning X X
Auto operation(artificial intelligence) O X
Auto Restart O O
Child lock O O
Convenience Forced operation X O
Group control O O
Sleep mode X X
Timer(on/off)* X X
Timer(weekly)* X X
Two thermistor control O O
Wired remote controller PQRCVSL0/PQRCVSL0QW PQRCVSL0/PQRCVSL0QW
Deluxe wired remote controller PQRCUDS0 / PQRCUDS0B / PQRCUDS0S PQRCUDS0 / PQRCUDS0B / PQRCUDS0S
Individual
Simple wired remote controller O O
control
Simple Wired remote controller(for hotel use) PQRCHCA0Q / PQRCHCA0QW PQRCHCA0Q / PQRCHCA0QW
Wireless remote controller X X
General central controller (Non LGAP) X X
CAC
Network Solution(LGAP) X O
Network
Dry contact X PQDSA(1)/PQDSB(1)
function
PI 485(for Indoor Unit) X X
Zone control X X
CTI(Communication transfer interface) X X
Special Electro thermostat X X
function kit Telecom shelter controller X X
Independent Power Module X X
CO2 Sensor X X
Remote temperature sensor PQRSTA0 PQRSTA0
Others
Group Control wire PZCWRCG3 PZCWRCG3
Note:
O: Applied, X: Not applied
** : For ceiling concealed duct models, auto-run function of dry contact is not applicabe.
Accessory model name : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate package.
8 (78) 8 (78)
Type - BLDC BLDC
Fan Motor
Output W x No. 136.5 x 1 136.5 x 1
Dehumidification Rate l / h (pts/h) 1.2 (2.6) 1.6 (3.4)
Sound Pressure Level H/M/L dB(A) 37 / 39 / 36 42 / 39 / 36
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 6.35 (1/4) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 12.7 (1/2) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/32) Ø 32.0(1-1/4) / 25.0(31/33)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm (AWG) 2
4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Indoor units
Fan Motor
Output W x No. 350 x 1 350 x 1
Dehumidification Rate l / h (pts/h) 2.7 (5.7) 3.0 (6.3)
Sound Pressure Level H/M/L dB(A) 42 / 39 / 36 44 / 42 / 40
Sound Power Level Cooling dB(A) - -
Liquid mm(inch) Ø 9.52 (3/8) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 15.88 (5/8) Ø 15.88 (5/8)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/34) Ø 32.0(1-1/4) / 25.0(31/35)
Safety Devices - Fuse Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Fan Motor
Output W x No. 400 x 1
Dehumidification Rate l / h (pts/h) 3.9 (8.2)
Sound Pressure Level H/M/L dB(A) 46 / 44 / 42
Sound Power Level Cooling dB(A) -
Liquid mm(inch) Ø 9.52 (3/8)
Piping
Gas mm(inch) Ø 19.05 (3/4)
Connections
Drain (O.D. / I.D.) mm Ø 32.0(1-1/4) / 25.0(31/36)
Safety Devices - Fuse
Power and Communication Cable (included Earth) No. x mm2 (AWG) 4C x 0.75 (18)
Notes :
1. All data are based on the following conditions:
- Cooling Temperature : Indoor 27°C(80.6°F) DB / 19°C(66.2°F) WB
Outdoor 35°C(95°F) DB / 24°C(75.2°F) WB
- Piping Length : Interconnected Pipe Length = 7.5m
- Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
2. Wiring cable size must comply with the applicable local and national code.
3. Due to our policy of innovation some specifications may be changed without notification.
4. Sound Level Values are measured at Anechoic chamber.
Therefore, these values can be increased owing to ambient conditions during operation.
5. The Net Weight will vary slightly with Vietnam models.
For more information, please refer to the Weight on Catalog.
Indoor units
Indoor units
Thermistor for
evaporator inlet
temperature
Indoor units
ABNQ24GM1A2
ABNQ36GM2A2 Ø 15.88 (5/8) Ø 9.52 (3/8)
ABNQ48GM3A2
ABNQ54GM3A2 Ø 19.05 (3/4) Ø 9.52 (3/8)
Indoor units
Models : ABNQ36GM2A2 / ABNQ48GM3A2 / ABNQ54GM3A2
Models : ABNQ24GM1A2
Indoor units
Static Pressure[mmAq(Pa)]
2(20) 2.5(25) 3(29) 4(39) 6(59) 8(78) 10(98) 12(118) 13(127) 14(137) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 18.0 94 96 101 106 109 115 121 126 131 134 137
ABNQ24GM1A2 MID 16.5 89 91 96 101 105 111 117 122 126 130 133
LOW 14.0 79 81 87 93 99 105 112 117 121 125 129
Models : ABNQ36GM2A2
Static Pressure[mmAq(Pa)]
4(39) 5(50) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 15(147)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 32.0 97 103 107 111 115 117 119 123 126 130 137
ABNQ36GM2A2 MID 28.0 91 96 101 105 109 112 115 118 122 125 131
LOW 23.0 80 89 93 98 104 107 111 114 118 121 127
Models : ABNQ48GM3A2
Static Pressure[mmAq(Pa)]
5(50) 6(59) 7(69) 8(78) 9(88) 10(98) 12(118) 14(137) 15(147) 16(157) 18(177)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 40.0 88 90 93 96 99 102 108 113 115 117 121
ABNQ48GM3A2 MID 34.0 80 87 88 91 94 97 103 109 111 112 117
LOW 28.0 75 79 80 88 90 93 99 105 107 109 114
Models : ABNQ54GM3A2
Static Pressure[mmAq(Pa)]
4(39) 5(50) 6(59) 7(69) 8(78) 9(88) 10(98) 11(108) 12(118) 13(127) 14(137)
Model Step CMM
Setting Value
32:01 32:02 32:03 32:04 32:05 32:06 32:07 32:08 32:09 32:10 32:11
HIGH 50.0 94 97 98 103 107 109 112 114 117 119 121
ABNQ54GM3A2 MID 45.0 89 93 94 98 102 104 106 109 112 114 117
LOW 40.0 83 84 90 93 98 99 102 105 108 110 113
Table 2
Indoor units
Lower Limit of External Upper Limit of External
Standard
Model Mode Set Value CMM Static Pressure Static Pressure
ESP[mmAq(Pa)]
[mmAq(Pa)] [mmAq(Pa)]
Hi 106 16.5
ABNQ18GM1A2 Mid 102 8(78) 14.5 2.0(20) 10(98)
Low 98 13.0
Hi 121 18.0
ABNQ24GM1A2 Mid 117 10(98) 16.5 2.0(20) 10(98)
Low 112 14.0
Hi 119 32.0
ABNQ36GM2A2 Mid 115 10(98) 28.0 4.0(39) 10(98)
Low 109 23.0
Hi 90 40.0
ABNQ48GM3A2 Mid 87 6(56) 34.0 5.0(49) 14(137)
Low 79 28.0
Hi 98 50.0
ABNQ54GM3A2 Mid 94 6(56) 45.0 4.0(39) 14(137)
Low 90 40.0
Notes
1. To get the desired Airflow & E.S.P. combination of the 5. If it is zero static pressure, please set value the below
table, set the matching value from the table. Otherwise, table.
the airflow & E.S.P. combination indicated in table would- Mode Value
n't be obtained.
ABNQ18GM1A2 106
2. Table data is based on 230V. According to the fluctuation ABNQ24GM1A2 115
of voltage, the air flow rate would be varied. ABNQ36GM2A2 119
3. The unexpected set value would cause mal-function. ABNQ48GM3A2 90
4. Refer to the specifications pages for Factory Set(E.S.P.) ABNQ54GM3A2 98
values.
ABNQ54GM3A2 46 44 42
70 70 70
Octave Band Sound Pressure Level (0dB = 20μPa)
ABNQ48GM3A2 ABNQ54GM3A2
80 80
70 70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65 NC-65
60 60
NC-60 NC-60
NC-55 NC-55
50 50
NC-50 NC-50
NC-45 NC-45
40 40
NC-40 NC-40
NC-35 NC-35
30 30
NC-30 NC-30
NC-25 NC-25
20 20
Approximate Approximate
NC-20 NC-20
Hearing Hearing
Threshold Threshold
NC-15 NC-15
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz) Octave Band Center Frequency (Hz)
Operation
1 Displays the operating conditions.
display
SLO
LO
1 Room
MED
Used to set the room temperature
HI
2 temperature
SHI when required.
Indoor units
VANE
setting
2
3 Fan speed Used to set the desired fan speed.
3
4
Operation starts when this button is
ROOM
5
4 On/Off pressed, and stops when the button
TEMP
is pressed again.
Room
5 temperature Used to check the room temperature.
checking
Air outlet
vents
SLO
LO
MED
HI
SHI
VANE
ROOM
Remote
Controller
TEMP
6.9.1 Accessories
Check the following accessories are included with your unit.
1) Standard accessories
M1/M2/M3 Chassis
• Owner's manual
• Installation manual
for gas pipe
Shape
Indoor units
unit.
• The servicing inspection hole in the ceiling should be as
large as the product.
• The selection of the servicing hole should be approved 20 or more
by the customer.
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
CASE 1
Position of suspension Bolt
• Apply a joint-canvas between the unit and duct to absorb unnecessary vibration.
• Install the unit leaning to a drainage hole side as a figure for easy water drainage.
E
G
Indoor units
C
D
J
A
B
F
I
H
Drain hole
(Unit:mm)
Dimension
A B C D E F G H I J
Chassis name
M1 933.4 971.6 619.2 700 30 270 15.2 858 201.4 900
M2 1283.4 1321.6 619.2 689.6 30 270 15.2 1208 201.4 1250
M3 1283.4 1321.6 619.2 689.6 30 360 15.2 1208 291.4 1250
M10 Nut X4
(Local
M10 SP. washer X 4 supply)
M10 washer X4
Indoor units
M10 washer X4
(Local CAUTION
M10 SP. washer X 4 supply)
M10 Nut X4 • Tighten the nut and bolt to prevent the unit falling.
1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
CAUTION
• Make sure to insulate any field piping all the way to the
piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
CAUTION
Wrong method
1. Decline Installation of indoor unit is very important for
the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting
pipe should be 7/32 inch.
Indoor units
4) Caution for gradient of unit and drain piping
- Without drain pump:
• Always lay the drain with downward inclination (1/50 to
1/100). Prevent any upward flow or reverse flow in any part. - With drain pump
• 7/32 inch or thicker formed thermal insulation shall always
① Possible drain head height is upto 27 6/19 inch. So the
be provided for the drain pipe.
drain head should be below 27 6/19 inch.
② Keep the drain hose downward upto 1/50~1/100 inclina-
Correct method tion. Prevent any upward flow or reverse flow in any part.
Attached drain hose ③ 7/32 inch or thicker insulation should be provided for the
Downward 1/50~1/100 or more drain pipe.
Bottom of unit
or more or more
50mm 50mm
Approx 2~3mm
1/50~1/100
Drain Pipe
27 9/16 inch ~ 700mm
(27-9/16 inch)
Pipe clamp
Drain Pump
Indoor unit
Hanger
Max 300mm distance Hanger Bracket
1~15m 1/50~1/100 slope
Metal
Max 700mm
Maintenance
drain port clamp
Thermal insulation
6.9.5 Electric wiring work
(Local supply) 1) General instructions
Drain pipe
Unit (Local supply) ① All field supplied parts and materials, electric works must
conform to local codes.
Use copper wire only.
② Follow the "WIRING DIAGRAM” attached to the unit
Elbow body to wire the outdoor unit, indoor units and the remote
controller.
Drain pump ③ All wiring must be performed by an authorized electri-
cian.
④ This system consists of multiple indoor units. Mark each
5) Checking the drainage indoor unit as unit A, unit B..., and be sure the terminal
board wiring to the outdoor unit and ID unit are properly
① Remove the air filter. matched. If wiring and piping between the outdoor unit
and an indoor unit are mismatched, the system may
cause a malfunction.
Indoor units
Air filters
2) Wiring connection
Connect the wires to the terminals on the control board ind
vidually according to the outdoor unit connection.
• Ensure that the color of the wires of outdoor unit and the
② Check the drainage terminal No. are the same as those of indoor unit respec-
• Spray one or two glasses of water on the evaporator. tively
• Ensure that water flows through the drain hose from indoor
unit without any leakage.
Terminal Block Indoor
1(L) 2(N) 3
Air Conditioner