SPECIFICATION SHEET AEROFOAM® XLPE AF/QC/012 Rev:01 W.e.f: 06/03/2014


A. Pipe insulation

Cross-linked closed cell polyolefin foam with permanent bonded Alupet foil. Generally used for
thermal insulation of chilled water, AC and condensate piping.

Thermal Conductivity: 0.034 W/m∙K at 23º C, as per ASTM C518 standard


Density (foam core only): 25 kg/m³
Water Vapour Permeability: 0.00 permeability as per ASTM E96 standard
Water Absorption: 0.3% by volume as per BS EN 12087:1997 Method 2A
Fire resistance: Class O as per BS 476 Part 7 (Surface Spread of Flame) and Part 6
(Fire Propagation)
Smoke Density and Toxicity: Ds ≤ 200, in accordance with ISO 5659-2 IMO Resolution MSC
61(67), 1996; Annex 1, Part 2
R=0.77 as per BS 6853
Working temperature: from -80º C to 105º C (as per DIN EN 14706)
Deflection compression set: > 35% for 25 mm as per ASTM D3575
2
VOC level: < 4 µg / m / hr (as per ASTM D5116)
Chemical analysis: Cl < 25 mg/kg as per ASTM C871
Resistance to corrosion: Excellent as per ASTM B117
Antifungal: Yes as per ASTM G21
Antimicrobial: Yes as per ISO 22196
Environmental concerns: ODP = 0; GWP < 5 (proved by test report issued by accredited lab)

Our Insulation material is UL listed, CE marked and CFC & HCFC free (proved by test report issued
by accredited lab).

Chilled water systems:

For indoor applications (ambient temperature: 24 °C; line temperature: 4.5 – 5.5 °C; relative
humidity: 50%; pipe diameters: up to 6”) we recommend a minimum thickness of 12 mm.
For outdoor applications (ambient temperature: 46 °C; line temperature: 4.5 – 5.5 °C; relative
humidity: 65%) we recommend a minimum thickness of 20 mm (pipe diameters up to 2 1/2”) and 25
mm (pipe diameters up to 6”).

Page 2 of 3

SPECIFICATION SHEET AEROFOAM® XLPE AF/QC/012 Rev:01 W.e.f: 06/03/2014


B. Ductwork insulation

Cross-linked closed cell polyolefin foam with self-adhesive coating, permanent bonded with reinforced
Alupet foil. Generally used for thermal insulation of air ducts.

Thermal Conductivity: 0.034 W/m∙K at 23º C, as per ASTM C518 standard


Density (foam core only): 25 kg/m³
Water Vapour Permeability: 0.00 permeability as per ASTM E96 standard
Water Absorption: 0.3% by volume as per BS EN 12087:1997 Method 2A
Fire resistance: Class O as per BS 476 Part 7 (Surface Spread of Flame) and Part 6
(Fire Propagation)
Smoke Density and Toxicity: Ds ≤ 200, in accordance with ISO 5659-2 IMO Resolution MSC
61(67), 1996; Annex 1, Part 2
R=0.77 as per BS 6853
Working temperature: from -80º C to 105º C (as per DIN EN 14706)
Deflection compression set: > 35% for 25 mm as per ASTM D3574
2
VOC level: < 4 µg / m / hr (as per ASTM D5116)
Chemical analysis: Cl < 25 mg/kg as per ASTM C871
Resistance to corrosion: Excellent as per ASTM B117
Antifungal: Yes as per ASTM G21
Antimicrobial: Yes as per ISO 22196
Environmental concerns: ODP = 0; GWP < 5 (proved by test report issued by accredited lab)

Our Insulation material is UL listed, CE marked and CFC & HCFC free (proved by test report issued
by accredited lab).

Ventilation ducts:

For indoor applications (ambient temperature: 24 °C; line temperature: 11 °C; relative humidity:
50%) we recommend a minimum thickness of 12 mm.
For outdoor applications (ambient temperature: 46 °C; line temperature: 11 °C; relative humidity:
65%) we recommend a minimum thickness of 25 mm.

All statements and technical information are true to the best of our knowledge and are based on tests
conducted by us. However, before using, user shall determine the suitability of the product for
intended use.

Page 3 of 3

SPECIFICATION SHEET AEROFOAM® XLPE AF/QC/012 Rev:01 W.e.f: 06/03/2014

You might also like