DKG - 217
ﻛﻨﺘﺮﻟﺮ ﺍﺳﺘﺎﺭﺕ ﺩﺳﺘﻲ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻫﻤﺮﺍﻩ ﺳﻨﻜﺮﻭﻧﺴﻜﻮﭖ ﻭ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ
ﺍﻣﻜﺎﻧﺎﺕ
ﺛﺒﺖ ﺭﺧﺪﺍﺩﻫﺎ ﺑﻪ ﻫﻤﺮﺍﻩ ﺛﺒﺖ ﺯﻣﺎﻥ • ﺍﺳﺘﺎﺭﺕ ﻭ ﺍﺳﺘﭗ ﺩﺳﺘﻲ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ •
ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺁﻣﺎﺭﻱ • ﮐﻨﺘﺮﻝ ﻣﻮﺗﻮﺭ •
ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ • ﻣﺤﺎﻓﻈﺖ ﮊﻧﺮﺍﺗﻮﺭ •
ﭘﻮﺭﺕ ﺳﺮﻳﺎﻝ RS-232 • ﺍﺧﻄﺎﺭﻫﺎ ﻭ ﺁﻻﺭﻡ ﻫﺎﻱ ﺩﺍﺧﻠﻲ •
ﻧﻈﺎﺭﺕ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﺑﻪ ﻃﺮﻳﻖ :ﻣﺤﻠﻲ ،ﺷﺒﮑﻪ ،ﺍﻳﻨﺘﺮﻧﺖ ﻭ ﻣﻮﺩﻡ • ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ 3ﻓﺎﺯ •
ﻧﻈﺎﺭﺕ ،ﻗﺮﺍﺋﺖ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ • ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ) (CTﮊﻧﺮﺍﺗﻮﺭ ﺗﻚ ﻓﺎﺯ •
ﻧﻤﺎﻳﺸﮕﺮ ﻫﺎﻱ LED • ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﻣﻮﺗﻮﺭ •
ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺁﻧﺎﻟﻮﮒ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﻱ 2 : • ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺩﻣﺎﻱ ﻣﺎﻳﻊ ﺧﻨﮏ ﮐﻨﻨﺪﻩ ﻣﻮﺗﻮﺭ •
ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﻱ 5 : • ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺗﻮﺍﻥ ﺍﮐﺘﻴﻮ ﮊﻧﺮﺍﺗﻮﺭ ) ﺗﻜﻔﺎﺯ( •
ﺧﺮﻭﺟﻲ ﻫﺎﻱ ﺭﻟﻪ ﺍﻱ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﻱ 2 : • ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺿﺮﻳﺐ ﺗﻮﺍﻥ ﻣﻮﺗﻮﺭ ) ﺗﻜﻔﺎﺯ( •
ﻣﺠﻤﻮﻉ ﺧﺮﻭﺟﻲ ﻫﺎﻱ ﺭﻟﻪ ﺍﻱ 5: • ﻧﺸﺎﻧﮕﺮ ﺩﺭﺧﻮﺍﺳﺖ ﺗﻌﻤﻴﺮ ﺩﻭﺭﻩ ﺍﻱ •
ﻗﺎﺑﻠﻴﺖ ﮔﺴﺘﺮﺵ ﻭﺭﻭﺩﻱ ﻭ ﺧﺮﻭﺟﻲ ﻫﺎ • ﺷﻤﺎﺭﻧﺪﻩ ﺳﺎﻋﺖ ﻛﺎﺭ ﻣﻮﺗﻮﺭ •
ﻗﻄﻊ ﺍﺳﺘﺎﺭﺕ • ﻗﺎﺑﻠﻴﺖ ﺍﺳﺘﺎﺭﺕ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ •
ﻧﺸﻠﻦ ﺩﻫﻨﺪﻩ ﺳﻨﻜﺮﻭﻧﺴﻜﻮﭖ ﺑﻮﺳﻴﻠﻪ LED • ﻣﺼﺮﻑ ﺗﻮﺍﻥ ﺻﻔﺮ ﺩﺭ ﺣﺎﻟﺖ ﺑﻴﻜﺎﺭﻱ •
• ﻭﺭﻭﺩﻱ ﻭﻟﺘﺎﮊ ﺗﻜﻔﺎﺯ ﺑﺎﺱ ﺑﺎﺭ • ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺗﻐﻴﻴﺮﺍﺕ ﻭﻟﺘﺎﮊ ،ﻓﺮﻛﺎﻧﺲ ﻭ
ﺿﺮﻳﺐ ﺗﻮﺍﻥ ﺟﻬﺖ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ
1
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻓﻬﺮﺳﺖ
-1ﻧﺼﺐ
1-1ﻣﻌﺮﻓﻲ ﻛﻨﺘﺮﻟﺮ
1-2ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ
1- 3ﺳﻴﻢ ﻛﺸﻲ ﻛﻨﺘﺮﻟﺮ
-2ﻭﺭﻭﺩﻱ ﻫﺎ ﻭ ﺧﺮﻭﺟﻲ ﻫﺎ
-3ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ
LED 3-1ﻫﺎﻱ ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ
3-2ﻧﻤﺎﻳﺸﮕﺮ ﺩﻳﺠﻴﺘﺎﻟﻲ
-4ﺁﻻﺭﻡ ﻫﺎ ﻭ ﻫﺸﺪﺍﺭﻫﺎ
-5ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﻴﺎﺗﻲ
-6ﺩﻳﮕﺮ ﺧﺼﻮﺻﻴﺎﺕ
6-1ﻋﻤﻠﮑﺮﺩ ﺑﻪ ﺻﻮﺭﺕ Remote Start
6-2ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ
6-3ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ
6-4ﮔﺮﻡ ﻛﻦ ﻣﻮﺗﻮﺭ
6-5ﻧﻤﺎﻳﺸﮕﺮ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ
6-6ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ
6-7ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ
6-8ﻣﺎﻧﻴﺘﻮﺭﻳﻨﮓ ﻭ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ
- 7ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺁﻣﺎﺭﻱ
-8ﻧﮕﻬﺪﺍﺭﻱ
2
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻓﻬﺮﺳﺖ
ﺧﻮﺍﻫﺸﻤﻨﺪ ﺍﺳﺖ ﺟﻬﺖ ﺩﺭﻳﺎﻓﺖ ﺍﻃﻼﻋﺎﺕ ﺑﻴﺸﺘﺮ ﺑﺎ ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ ﻧﻤﺎﻳﻨﺪﮔﻲ
ﺍﻧﺤﺼﺎﺭﻱ ﻣﺤﺼﻮﻻﺕ DATACOMﺗﺮﻛﻴﻪ ﺩﺭ ﺍﻳﺮﺍﻥ ﻭ ﻣﻨﻄﻘﻪ ﺧﻠﻴﺞ ﻓﺎﺭﺱ
ﺗﻤﺎﺱ ﺣﺎﺻﻞ ﻓﺮﻣﺎﻳﻴﺪ.
ﺗﻠﻔﻦ 021-22883169 – 70:
ﭘﺴﺖ ﺍﻟﻜﺘﺮﻭﻧﻴﻜﻲ sales@dornamehr.com :
3
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
1-1ﻣﻌﺮﻓﻲ ﻛﻨﺘﺮﻟﺮ
ﺳﻴﺴﺘﻢ ﺍﺭﺍﺋﻪ ﺷﺪﻩ ﮐﻨﺘﺮﻝ ﻭ ﺣﻔﺎﻇﺖ ﺍﺯ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﺮ ﻋﻬﺪﻩ ﺩﺍﺭﺩ .ﮐﺎﺭﺑﺮﻱ ﻭ ﻧﺼﺐ ﻳﻮﻧﻴﺖ
ﻃﺮﺍﺣﻲ ﺷﺪﻩ ﺑﺴﻴﺎﺭ ﺭﺍﺣﺖ ﻣﻲ ﺑﺎﺷﺪ ﻭ ﻣﻌﻤﻮﻻ ﻧﻴﺎﺯﻱ ﺑﻪ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺁﻥ ﻭﺟﻮﺩ ﻧﺪﺍﺭﺩ ﻭ ﻣﻘﺎﺩﻳﺮ ﭘﻴﺶ
ﻓﺮﺽ ﺁﻥ ﺑﺮﺍﻱ ﺑﻴﺸﺘﺮ ﮐﺎﺭﺑﺮﺩﻫﺎ ﻣﻨﺎﺳﺐ ﻣﻲ ﺑﺎﺷﻨﺪ .ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ،
ﮐﻨﺘﺮﻝ ﮐﺎﻣﻞ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﻣﻤﮑﻦ ﻣﻲ ﺳﺎﺯﺩ .ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺁﻥ ﺑﺮ ﺭﻭﻱ ﺣﺎﻓﻈﻪ
ﻣﻮﻗﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻣﻲ ﺷﻮﻧﺪ ،ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﺑﺮﻧﺎﻣﻪ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺫﺧﻴﺮﻩ ﺷﺪﻩ ﻭ ﺣﺘﻲ
ﺩﺭ ﺻﻮﺭﺕ ﻗﻄﻌﻲ ﻛﺎﻣﻞ ﺑﺮﻕ ﺑﺎﻗﻲ ﺧﻮﺍﻫﺪ ﻣﺎﻧﺪ .
4
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻧﮑﺘﻪ :ﺑﺮﺍﻱ ﻋﻤﻠﮑﺮﺩ ﺻﺤﻴﺢ ﻛﻨﺘﺮﻟﺮ ،ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺯﻣﻴﻦ ﺷﻮﺩ ﺩﺭ ﻏﻴﺮ
ﺍﻳﻦ ﺻﻮﺭﺕ ﻣﻤﻜﻦ ﺍﺳﺖ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻭﻟﺘﺎﮊ ﻭ ﻓﺮﮐﺎﻧﺲ ﺻﺤﻴﺢ ﻧﺒﺎﺷﻨﺪ .
ﺧﺮﻭﺟﻲ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ 5ﺁﻣﭙﺮ ﺑﺎﺷﺪ ،ﺑﺎﺯﻩ ﺟﺮﻳﺎﻥ ﺑﺮ ﺣﺴﺐ ﻧﻴﺎﺯ ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ ﺍﺳﺖ
)ﺑﻴﻦ 10/5ﻭ (9000 /5ﺧﺮﻭﺟﻲ ﻫﺮ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﻪ ﻭﺳﻴﻠﻪ ﺯﻭﺝ ﮐﺎﺑﻞ ﺟﺪﺍﮔﺎﻧﻪ
ﺍﻱ ﺑﻪ ﺳﻴﺴﺘﻢ ﻣﺘﺼﻞ ﺷﻮﺩ ﻭ ﺑﺎﺯﻩ ﺗﻐﺬﻳﻪ ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺑﺮﺍﻱ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺣﺪﺍﻗﻞ 5VAﺑﺎﺷﺪ ﻭ
ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮﻫﺎﻱ ﺑﺎ ﺩﻗﺖ 1ﺩﺭﺻﺪ ﺗﻮﺻﻴﻪ ﻣﻲ ﺷﻮﺩ .
ﺍﮔﺮ ﻫﻤﻪ ﺳﻨﺴﻮﺭﻫﺎﻱ ﺁﻧﺎﻟﻮﮒ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﺍﺻﻠﻲ ﻭﺻﻞ ﺑﺎﺷﻨﺪ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﻧﻤﺎﻳﺸﮕﺮ ﮐﻤﮑﻲ ﻣﻘﺪﻭﺭ
ﻧﻤﻲ ﺑﺎﺷﺪ ،ﺑﻪ ﻋﺒﺎﺭﺕ ﺩﻳﮕﺮ ﻛﻨﺘﺮﻟﺮ ﻣﻤﮑﻦ ﺍﺳﺖ ﺻﺪﻣﻪ ﺑﺒﻴﻨﺪ .ﺍﮔﺮ ﻧﻤﺎﻳﺸﮕﺮ ﻓﺸﺎﺭ ﻭ ﺩﻣﺎ ﺩﺭ
ﮐﻨﺘﺮﻝ ﭘﻨﻞ ﮊﻧﺮﺍﺗﻮﺭ ﻭﺟﻮﺩ ﺩﺍﺭﻧﺪ ،ﺳﻨﺴﻮﺭﻫﺎ ﺭﺍ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺻﻞ ﻧﮑﻨﻴﺪ .ﺗﻨﻈﻴﻤﺎﺕ ﮐﺎﺭﺧﺎﻧﻪ ﺟﻬﺖ
ﺳﻨﺴﻮﺭﻫﺎﻱ ﻛﻨﺘﺮﻟﺮﺍﺯ ﻧﻮﻉ VDOﻣﻲ ﺑﺎﺷﻨﺪ .ﻟﺬﺍ ﺍﻧﺘﺨﺎﺏ ﺳﻨﺴﻮﺭﻫﺎﻳﻲ ﻣﺘﻔﺎﻭﺕ ﺍﺯ ﻃﺮﻳﻖ ﻣﻨﻮﻱ
ﻛﻨﺘﺮﻟﺮ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻧﻤﻲ ﺑﺎﺷﺪ ).ﻟﻄﻔﺎ ﻗﺴﻤﺖ Programmingﺭﺍ ﺑﺮﺭﺳﻲ ﻓﺮﻣﺎﺋﻴﺪ(
ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﻪ ﺻﻮﺭﺕ ﺑﺎﺯ ﻳﺎ ﺑﺴﺘﻪ ﻣﻲ ﺑﺎﺷﻨﺪ ﻭ ﻫﻤﭽﻨﻴﻦ ﻣﻲ ﺗﻮﺍﻧﺪ
ﺑﻪ ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ BAT+ﻭ BAT-ﻣﺘﺼﻞ ﮔﺮﺩﺩ.
ﺗﺮﻣﻴﻨﺎﻝ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﻋﻤﻞ ﺟﺮﻳﺎﻥ ﺗﺤﺮﻳﻚ ﺭﺍ ﻧﻴﺰ ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ ﺑﻨﺎﺑﺮﺍﻳﻦ ﺍﺣﺘﻴﺎﺝ ﺑﻪ ﻻﻣﭗ ﺷﺎﺭﮊ
ﺧﺎﺭﺟﻲ ﻧﻴﺴﺖ.
5
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
: RS232-Serial Portﺍﻳﻦ ﮐﺎﻧﮑﺘﻮﺭ ﺟﻬﺖ ﺍﺭﺗﺒﺎﻁ ﺳﺮﻳﺎﻝ ﺑﺮﺍﻱ ﻭﺭﻭﺩﻱ ﻭ ﺧﺮﻭﺟﻲ ﺍﻃﻼﻋﺎﺕ
ﺑﺮﺍﻱ ﺍﻫﺪﺍﻑ ﻣﺨﺘﻠﻒ ﻣﺎﻧﻨﺪ ﻛﻨﺘﺮﻝ ﻭ ﻧﻤﺎﻳﺶ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ) (Remote Monitoringﻭﺑﺮﻧﺎﻣﻪ
ﺭﻳﺰﻱ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ) ( Remote Programmingﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﺪﻩ ﺍﺳﺖ .
6
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Term Function Technical data Description
Battery 12+ﻳﺎ 24ﻭﻟﺖDC ﺗﺮﻣﻴﻨﺎﻝ ﻣﺜﺒﺖ ﻣﻨﺒﻊ DCﺑﺎﻳﺪ ﺑﻪ ﺍﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ ﻣﺘﺼﻞ ﮔﺮﺩﺩ ﻭ ﻛﻨﺘﺮﻟﺮ ﺑﺎ ﻫﺮ ﺩﻭ
12 Positive
ﺑﺎﻃﺮﻱ 12ﻳﺎ 24ﻭﻟﺖ ﻣﻲ ﺗﻮﺍﻧﺪ ﮐﺎﺭ ﮐﻨﺪ .
Relay-1 ﺧﺮﻭﺟﻲ ﺍﻳﻦ ﺭﻟﻪ ﻓﺎﻧﮑﺸﻦ ﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺍﺷﺘﻪ ﮐﻪ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ
14 )(Stop relay
10A/28VDC ﺧﻮﺍﻫﺪ ﺑﻮﺩ .
ﺭﻟﻪ ﺗﻮﻗﻒ
Start Relay ﺧﺮﻭﺟﻲ ﺍﻳﻦ ﺭﻟﻪ ﻋﻤﻞ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﺭﺍ ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ.
15 10A/28VDC
Fuel Relay ﺧﺮﻭﺟﻲ ﺍﻳﻦ ﺭﻟﻪ ﺑﺮﺍﻱ ﮐﻨﺘﺮﻝ ﺳﻮﻟﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ
16 10A/28VDC ﺩﺍﺧﻠﻲ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ 16ﺟﻬﺖ ﺗﻐﺬﻳﻪ ﺟﺮﻳﺎﻥ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﻣﺘﺼﻞ ﻣﻲ ﺑﺎﺷﺪ .
Charge ﻭﺭﻭﺩﻱ ﻭ ﺧﺮﻭﺟﻲ ﺗﺮﻣﻴﻨﺎﻝ D+ﺍﺯ ﺷﺎﺭﮊﺭ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻧﺼﺐ ﻧﻤﺎﺋﻴﺪ ﺍﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ ﻋﻤﻞ
17 ﺗﻐﺬﻳﻪ ﺟﺮﻳﺎﻥ ﺗﺤﺮﻳﻚ ﺭﺍ ﺍﻧﺠﺎﻡ ﺩﺍﺩﻩ ﻭ ﻭﻟﺘﺎﮊ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﺭﺍ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻣﻲ
ﻛﻨﺪ .
18 Relay-2 ﺧﺮﻭﺟﻲ ﺍﻳﻦ ﺭﻟﻪ ﻓﺎﻧﮑﺸﻦ ﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺍﺷﺘﻪ ﮐﻪ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ
)(Alarm relay
10A/28VDC ﺧﻮﺍﻫﺪ ﺑﻮﺩ .
ﺭﻟﻪ ﺧﻄﺎ
19 Low Oil ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻫﺎ ﺧﺼﻮﺻﻴﺖ ﺑﺮﻧﺎﻣﻪ ﭘﺬﻳﺮﻱ ﺭﺍ ﺗﻮﺳﻂ ﻣﻨﻮﻱ Programﺩﺍﺭﺍ
Pressure
ﻣﻲ ﺑﺎﺷﻨﺪ .ﻫﺮ ﻭﺭﻭﺩﻱ ﻣﻲ ﺗﻮﺍﻧﺪ ﺑﻪ ﺻﻮﺭﺕ ﮐﻨﺘﺎﮐﺖ Normally Close
20 High Temp
ﻳﺎ Normally Openﻓﻌﺎﻝ ﺷﻮﺩ ﻭ ﺑﻪ ﻫﺮ ﻳﮏ ﺍﺯﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ ) Battery+
21 Dead Bus
Enable ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﻳﺎ (Battery-ﻣﺘﺼﻞ ﮔﺮﺩﺩ ﻭ ﻧﺤﻮﻩ ﺍﺗﺼﺎﻝ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ .
22 Emergency ﺑﺮﺍﻱ ﺟﺰﺋﻴﺎﺕ ﺑﻴﺸﺘﺮ ﮐﺎﻓﻲ ﺍﺳﺖ ﺑﻪ ﻗﺴﻤﺖ Programmingﻣﺮﺍﺟﻌﻪ
Stop
23 Spare ﻧﻤﺎﻳﻴﺪ .
7
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Generator ﺯﺭﺩ ﺍﻳﻦ LEDﺑﻪ ﺻﻮﺭﺕ ﭼﺸﻤﻚ ﺯﻥ ﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ﻣﻲ
ﺑﺎﺷﺪ ﻭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰ ﻱ ﺷﺪﻩ ﺑﺎﺷﺪ
ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ.
Bus ﺯﺭﺩ ﺍﻳﻦ LEDﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺑﺎﺷﺪ
ﺭﻭﺷﻦ ﻣﻲ ﮔﺮﺩﺩ .
Synchronized ﺯﺭﺩ ﺍﻳﻦ LEDﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻓﻌﺎﻝ ﺍﺳﺖ ﺑﻪ ﺻﻮﺭﺕ
ﭼﺸﻤﻚ ﺯﻥ ﺑﻮﺩﻩ ﻭ ﻫﻨﮕﺎﻣﻲ ﻛﻪ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﺭﻭﺷﻦ
ﻣﻲ ﻣﺎﻧﺪ.
8
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Function Color Description
)Redﺭﻧﮓ ﻗﺮﻣﺰ ( ﺗﻌﻤﻴﺮﺍﺕ ﺩﻭﺭﻩ ﺍﻱ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻭ LEDﭘﺲ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ
Service Request
ﻛﺎﺭﻱ ﻳﺎ ﺑﻌﺪ ﺍﺯ ﺗﻤﺎﻡ ﺷﺪﻥ ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ ﻗﺒﻠﻲ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ .
ﭼﻨﺎﻧﭽﻪ ﺧﻄﺎ ﺑﺎﻋﺚ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﮔﺮﺩﺩ LEDﻣﺘﻨﺎﺳﺐ ﺑﺎ ﺧﻄﺎ ﺑﻪ
ﻃﻮﺭ ﺩﺍﺋﻢ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ﻭ ﺍﮔﺮ ﺣﺎﻟﺖ ﻫﺸﺪﺍﺭ ﺑﻮﺟﻮﺩ ﺁﻣﺪﻩ ﺑﺎﺷﺪ LED
ﺁﻻﺭﻡ ﻣﺮﺑﻮﻃﻪ ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ .ﺁﻻﺭﻡ ﻫﺎ ﺑﺮ ﭘﺎﻳﻪ
Alarm Group )Redﺭﻧﮓ ﻗﺮﻣﺰ ( ﺍﻭﻟﻮﻳﺖ ﺑﻨﺪﻱ ﻋﻤﻞ ﺧﻮﺍﻫﻨﺪ ﻧﻤﻮﺩ ﺑﺎ ﺑﻮﺟﻮﺩ ﺁﻣﺪﻥ ﻳﮏ ﺧﻄﺎ ،ﺧﻄﺎﻫﺎﻱ ﺑﺎ
ﺍﻭﻟﻮﻳﺖ ﺑﺮﺍﺑﺮ ﻳﺎ ﭘﺎﻳﻴﻦ ﺗﺮ ﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﻨﺪ ﺷﺪ.
3-2ﻧﻤﺎﻳﺸﮕﺮﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ
ﻛﻨﺘﺮﻟﺮ ﺩﺍﺭﺍﻱ 3ﻋﺪﺩ ﻧﻤﺎﻳﺸﮕﺮ Seven Segmentﺍﺳﺖ ،ﺁﻧﻬﺎ ﻧﻤﺎﻳﺸﮕﺮ :
-ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ
-ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺳﺮﻭﻳﺲ
-ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ
-ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ
ﺑﺎ ﺩﮐﻤﻪ Menuﻣﻲ ﺗﻮﺍﻥ ﺻﻔﺤﺎﺕ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭ ﻫﺮ ﮔﺮﻭﻩ ﺭﺍ ﻋﻮﺽ ﻧﻤﻮﺩ .
ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ Menuﺻﻔﺤﻪ ﮔﺮﻭﻫﻬﺎﻱ ﺑﻌﺪﻱ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ .
9
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
10
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﺍﮔﺮ ﺩﮐﻤﻪ Alarm Muteﻓﺸﺎﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ،ﺧﺮﻭﺟﻲ ﺭﻟﻪ ﺁﮊﻳﺮﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ .ﻫﺮ ﭼﻨﺪ
ﺧﻄﺎﻱ ﻣﺮﺑﻮﻃﻪ ﻭﺟﻮﺩ ﺩﺍﺷﺘﻪ ﻭ ﺑﺎﻋﺚ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻥ ﻋﻤﻠﻜﺮﺩ ﺳﻴﺴﺘﻢ ﺷﻮﺩ.
-ﺁﻻﺭﻡ ﻫﺎﻱ ﻣﻮﺟﻮﺩ ﻣﻤﮑﻦ ﺍﺳﺖ ﺑﻪ ﻭﺳﻴﻠﻪ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ﻫﺎﻱ Run /Stopﻛﻨﺘﺮﻟﺮ ﺍﺯ ﺑﻴﻦ
ﻣﻲ ﺭﻭﻧﺪ .
ﺑﻴﺸﺘﺮ ﺁﻻﺭﻡ ﻫﺎ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻫﺴﺘﻨﺪ ﺑﻪ ﻗﺴﻤﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﺮﺍﻱ ﺗﻨﻈﻴﻤﺎﺕ ﺁﻻﺭﻡ ﻣﺮﺍﺟﻌﻪ
ﻧﻤﺎﻳﻴﺪ .
11
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻣﺤﺪﻭﺩﻩ (P-017) Warningﻭ (P-018) Alarmﻫﺮﻳﻚ ﺑﺮﺍﻱ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺑﻪ ﺻﻮﺭﺕ ﺟﺪﺍ
ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻫﺴﺘﻨﺪ .
: Start Failﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﻲ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺑﺮﻧﺎﻣﻪ
ﺭﻳﺰﻱ ﺷﺪﻩ ) (P-035ﺟﻬﺖ ﺍﺳﺘﺎﺭﺕ ﺭﻭﺷﻦ ﻧﺸﻮﺩ.
: Over Loadﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺣﺪﺍﻗﻞ ﻳﮑﻲ ﺍﺯ ﺟﺮﻳﺎﻧﻬﺎﻱ ﻓﺎﺯﻫﺎﻱ
ﮊﻧﺮﺍﺗﻮﺭ ﺑﺎﻻﺗﺮ ﺍﺯ ﭘﺎﺭﺍﻣﺘﺮ ﺗﻨﻈﻴﻢ ﺷﺪﻩ (P-002) Over Current Limitﺑﺎﺷﺪ ﻭ ﻳﺎ
ﺑﻴﺸﺘﺮﺍﺯ ﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ﺗﻮﺍﻧﻲ ﮐﻪ ﺩﺭ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ
) Excess Power(P-003ﺑﺎﺷﺪ ﻭ ﺯﻣﺎﻥ ﺍﺭﺍﺋﻪ ﺍﻳﻦ ﺗﻮﺍﻥ ﺑﻴﺶ ﺍﺯ ﺯﻣﺎﻧﻲ ﺑﺎﺷﺪ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ
) Over Current/Excess Power Timer(P-511ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺍﺳﺖ .ﺍﮔﺮ ﺟﺮﻳﺎﻥ ﻭﺗﻮﺍﻥ
ﺑﻪ ﭘﺎﻳﻴﻦ ﺗﺮ ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﻗﺒﻞ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺗﺎﻳﻤﺮ ﺑﺮﺳﺪ ﻫﻴﭻ ﮔﻮﻧﻪ ﺧﻄﺎﻳﻲ ﺍﻋﻼﻡ ﻧﺨﻮﺍﻫﺪ
ﺷﺪ .ﭼﻨﺎﻧﭽﻪ ) Over Current Limit (P-002ﻭ ) Excess Power (P-003ﺑﻪ ﻣﻘﺪﺍﺭ
ﺻﻔﺮ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﻮﻧﺪ ﻣﻘﺎﺩﻳﺮ ﻣﺮﺑﻮﻃﻪ ﺣﺬﻑ ﻣﻲ ﺷﻮﻧﺪ.
:Low/High Voltageﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﻭﻟﺘﺎﮊ ﻳﮑﻲ ﺍﺯ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭﺍﺯ
ﺣﺪﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ) ( P-006/P007ﺧﺎﺭﺝ ﮔﺮﺩﺩ .ﺍﻳﻦ ﺧﻄﺎ ﺑﻌﺪ ﺍﺯ
ﺭﻭﺷﻦ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﻭ ﭘﺲ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ Hold OFFﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ
) ( P-023ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ،ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ .
12
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
:Low/High Batteryﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺧﺎﺭﺝ ﺍﺯ ﻣﺤﺪﻭﺩﻩ
ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ .ﺩﺭ ﻃﻮﻝ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﺍﻳﻦ ﺧﻄﺎ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻧﻤﻲ ﺷﻮﺩ .
ﺍﺧﻄﺎﺭ ﺑﺮﺍﻱ ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﺳﻄﺢ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ) ( P-012ﻭ ﺑﺮﺍﻱ ﺑﺎﻻ ﺑﻮﺩﻥ ﺳﻄﺢ ﻭﻟﺘﺎﮊ
ﺍﺧﻄﺎﺭﻫﺎﻱ ) Warning (P-013ﻭ ) Alarm (P-014ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻗﺎﺑﻞ ﺗﻌﺮﻳﻒ ﻣﻲ
ﺑﺎﺷﻨﺪ .
: Charge Alternatorﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺩﻳﻨﺎﻡ ﺩﭼﺎﺭ ﺍﺷﻜﺎﻝ ﺷﻮﺩ
)ﻳﺎ ﺗﺴﻤﻪ ﭘﺎﺭﻩ ﺷﻮﺩ( ﻭﺿﻌﻴﺖ ﺍﻳﻦ ﺍﻳﺮﺍﺩ ﻣﻨﺠﺮ ﺑﻪ ﺧﻄﺎ ﻭ ﻳﺎ ﻫﺸﺪﺍﺭ ﻫﺎﻱ ﺯﻳﺮ ﻣﻲ ﮔﺮﺩﺩ .
ﺑﺮﻧﺎﻣﻪ )(P-038
: Reverse Powerﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﻛﻪ ﺗﻮﺍﻥ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ) (KWﺩﺭ
ﻓﺎﺯ Uﻣﻨﻔﻲ ﻭ ﻳﺎ ﺑﻴﺶ ﺍﺯ ﺣﺪ ) Reverse Power (P-042ﺟﻬﺖ Over Current
(P-511) Excess Power Timer/ﺑﺎﺷﺪ .ﭼﻨﺎﻧﭽﻪ ﻣﻘﺪﺍﺭ Reverse Powerﺑﻪ ﻛﻤﺘﺮ ﺍﺯ
ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﻗﺒﻞ ﺍﺯ ﺗﻤﺎﻡ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﻳﻤﺮ ﺑﺮﺳﺪ ﻫﻴﭻ ﮔﻮﻧﻪ ﺁﻻﺭﻣﻲ ﺍﻋﻼﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ.
ﺍﮔﺮ ﻣﻘﺪﺍﺭ (P-042) Reverse Powerﺑﻪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﺗﻨﻈﻴﻢ ﮔﺮﺩﺩ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ
ﺣﺬﻑ ﺧﻮﺍﻫﺪ ﺷﺪ.
: Spareﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻳﮑﻲ ﺍﺯ ﻭﺭﻭﺩﻱ ﻫﺎﻱ Spareﺳﻴﮕﻨﺎﻟﻲ ﺩﺭﻳﺎﻓﺖ
ﺷﻮﺩ .
-5ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﻴﺎﺗﻲ
ﺩﺳﺘﮕﺎﻩ ﺑﺎ ﻓﺸﺮﺩﻥ ﺩﻛﻤﻪ RUNﺑﺮ ﺭﻭﻱ ﺻﻔﺤﻪ ﺟﻠﻮﻱ ﻛﻨﺘﺮﻟﺮ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭ ﺑﺎ ﻓﺸﺮﺩﻥ ﺩﻛﻤﻪ
STOPﺧﺎﻣﻮﺵ ﻣﻲ ﺷﻮﺩ .ﭼﻨﺎﻧﭽﻪ ﻫﻴﭻ ﺩﻛﻤﻪ ﺍﻱ ﺭﻭﺷﻦ ﻧﺸﻮﺩ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻃﻮﺭ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺑﻌﺪ ﺍﺯ
5ﺩﻗﻴﻘﻪ ﺧﺎﻣﻮﺵ ﻣﻲ ﺷﻮﺩ .ﺩﺭ ﺻﻮﺭﺕ ﻧﻴﺎﺯ ﻣﻲ ﺗﻮﺍﻥ ﺣﺎﻟﺖ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺭﺍ ﺑﺎ ﺑﺮﻧﺎﻣﻪ
ﺭﻳﺰﻱ ﭘﺎﺭﺍﻣﺘﺮ P-050ﺑﻪ ﺻﻮﺭﺕ ﻏﻴﺮ ﻓﻌﺎﻝ ﺩﺭ ﺁﻭﺭﺩ.
13
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﺩﺭ ﺯﻣﺎﻥ ﺭﻭﺷﻦ ﺑﻮﺩﻥ ﺩﺳﺘﮕﺎﻩ ﭼﻨﺎﻧﭽﻪ ﻣﺠﺪﺩﺍ" ﺩﻛﻤﻪ RUNﻓﺸﺮﺩﻩ ﺷﻮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ
ﺷﺪﻩ ﻭ LEDﺯﺭﺩ ﺭﻧﮓ ﺁﻥ ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﻚ ﺯﺩﻥ ﻣﻲ ﻧﻤﺎﻳﺪ ﻭ ﭘﺲ ﺍﺯ ﺍﻳﻨﻜﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﻱ
ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﺑﺎﺷﺪ LED ،ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭ ﺑﻪ ﺻﻮﺭﺕ ﺛﺎﺑﺖ
ﺭﻭﺷﻦ ﺑﺎﻗﻲ ﻣﻲ ﻣﺎﻧﺪ.
ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ STOPﻓﺸﺮﺩﻩ ﺷﻮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺷﺪﻩ ﻭﻟﻲ ﺩﺳﺘﮕﺎﻩ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ،
ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ STOPﻣﺠﺪﺩﺍ" ﻓﺸﺮﺩﻩ ﺷﻮﺩ ﻭ ﭘﺲ ﺍﺯ ﺁﻥ ﺑﻪ ﻣﺪﺕ 5ﺩﻗﻴﻘﻪ ﻫﻴﭻ ﺩﻛﻤﻪ ﺍﻱ ﻓﺸﺮﺩﻩ
ﻧﺸﻮﺩ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻃﻮﺭ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ.
ﺯﻣﺎﻧﻲ ﻛﻪ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﺣﺎﻝ ﻛﺎﺭ ﺍﺳﺖ ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ RUNﻓﺸﺮﺩﻩ ﺷﻮﺩ LEDﺯﺭﺩ ﺭﻧﮓ
ﺳﻨﻜﺮﻭﻧﺎﻳﺰﺭ ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﻚ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻛﺮﺩ ﻭ ﺩﺳﺘﮕﺎﻩ ﺣﺎﻟﺖ ﺳﻨﻜﺮﻭﻥ ﺑﻮﺩﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺑﺎ ﺑﺎﺱ
ﺑﺎﺭ ﺭﺍ ﭼﻚ ﺧﻮﺍﻫﺪ ﻛﺮﺩ ،ﭼﻨﺎﻧﭽﻪ ﺑﺎﺱ ﺑﺎﺭ ﺑﺮﻕ ﺩﺍﺭ ﻧﺒﺎﺷﺪ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﺎ
ﺳﻴﮕﻨﺎﻝ Dead Bus Enableﻓﻌﺎﻝ ﻧﻤﻮﺩ ﭼﻨﺎﻧﭽﻪ ﺑﺎﺱ ﺑﺎﺭ ﻓﻌﺎﻝ ﺑﺎﺷﺪ ﻭ ﺗﻤﺎﻡ ﺣﺎﻟﺘﻬﺎﻱ ﺳﻨﻜﺮﻭﻥ
ﻣﻮﺟﻮﺩ ﺑﺎﺷﺪ) (∆v, ∆f, ∆θر ون ل و LEDزرد &ن دا "#رو!
ﻥ.
ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ STOPﻓﺸﺮﺩﻩ ﺷﻮﺩ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻩ ﻭ LEDﺁﻥ
) (Synchronizedﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ .ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ﻭ ﺑﺎ ﻓﺸﺎﺭ
ﺩﺍﺩﻥ ﻣﺠﺪﺩ ﺩﻛﻤﻪ STOPﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ.
ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺯﻣﺎﻥ ﺩﺍﺭ ﻧﺒﻮﺩﻩ ﻭ ﺗﺎ ﺯﻣﺎﻧﻲ ﻛﻪ ﺷﺮﺍﻳﻂ ﺳﻨﻜﺮﻭﻥ ﺗﺤﻘﻖ ﻳﺎﺑﺪ ﺍﻳﻦ ﻋﻤﻞ ﺍﺩﺍﻣﻪ
ﻣﻲ ﻳﺎﺑﺪ ﻭ ﺍﻳﻦ ﻋﻤﻞ ﺑﻪ ﺻﻮﺭﺕ ﺩﺳﺘﻲ ﻭ ﻳﺎ ﺍﺯ ﻃﺮﻳﻖ ﺳﻴﮕﻨﺎﻝ Remote Startﺧﺎﺗﻤﻪ ﻣﻲ ﻳﺎﺑﺪ.
ﭼﻨﺎﻧﭽﻪ ﺩﺭ ﻫﺮ ﺣﺎﻟﺘﻲ ﺍﺯ ﺣﺎﻟﺘﻬﺎﻱ ﻛﺎﺭﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎﻳﻲ ﺍﺗﻔﺎﻕ ﺍﻓﺘﺪ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻏﻴﺮ
ﻓﻌﺎﻝ ﺷﺪﻩ ﻭ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ LEDﺳﻴﮕﻨﺎﻝ ﺧﻄﺎﻱ ﻣﺮﺑﻮﻃﻪ ﺑﻪ ﻃﻮﺭ ﺩﺍﺋﻢ
ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ،ﻛﻨﺘﺮﻟﺮ ﺗﺎ ﺯﻣﺎﻧﻲ ﻛﻪ ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎ ﺑﻮﺳﻴﻠﻪ ﺩﻛﻤﻪ STOPﺑﺮﻃﺮﻑ ﻧﺸﻮﺩ ﺧﺎﻣﻮﺵ
ﻧﺨﻮﺍﻫﺪ ﺷﺪ.
ﻭﺭﻭﺩﻱ (9) Remote Startﻫﻤﻴﺸﻪ ﻓﻌﺎﻝ ﺑﻮﺩﻩ ﻭ ﻧﻴﺎﺯﻱ ﺑﻪ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻧﺪﺍﺭﺩ .ﺣﺎﻟﺖ
Remote Startﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﺩﻳﺎﮔﺮﺍﻡ ﺯﻳﺮ ﺑﺮﺭﺳﻲ ﻧﻤﻮﺩ.
14
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻫﺸﺪﺍﺭ
ﺑﻪ ﻫﻴﭻ ﻋﻨﻮﺍﻥ ﻭﻟﺘﺎﮊﻱ ﺑﺎﻻﺗﺮ ﺍﺯ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻣﺘﺼﻞ ﻧﻨﻤﺎﻳﻴﺪ ﺩﺭ ﻏﻴﺮ ﺍﻳﻦ
ﺻﻮﺭﺕ ﺧﺴﺎﺭﺕ ﺟﺪﻱ ﺑﻪ ﺍﻳﻦ ﺩﺳﺘﮕﺎﻩ ﻭﺍﺭﺩ ﺧﻮﺍﻫﺪ ﺁﻣﺪ.
ﺳﻴﮕﻨﺎﻝ Remote Startﻣﻌﺎﺩﻝ ﺳﻪ ﺑﺎﺭ ﻓﺸﺮﺩﻥ ﺩﻛﻤﻪ RUNﻣﻲ ﺑﺎﺷﺪ ﻭ ﺑﻪ ﻣﻌﻨﺎﻱ ﺯﻳﺮ ﺍﺳﺖ :
-ﺭﻭﺷﻦ ﺷﺪﻥ ﺩﺳﺘﮕﺎﻩ
-ﺭﻭﺷﻦ ﺷﺪﻥ ﻣﻮﺗﻮﺭ
-ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ
15
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﭼﻨﺎﻧﭽﻪ ﺑﺨﻮﺍﻫﻴﻢ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻳﻚ ﺑﺎﺱ ﺑﻲ ﺑﺮﻕ ﻣﺘﺼﻞ ﻧﻤﺎﻳﻴﻢ ﺍﻳﻦ ﻋﻤﻞ ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﺎ ﺳﻴﮕﻨﺎﻝ
Dead Bus Enableﺍﻧﺠﺎﻡ ﺩﺍﺩ ﻭ ﭼﻨﺎﻧﭽﻪ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﺑﺎﺱ ﺑﺮﻕ ﺩﺍﺭ ﻣﺘﺼﻞ ﺷﻮﺩ ﺍﺑﺘﺪﺍ ﻋﻤﻞ
ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺍﻧﺠﺎﻡ ﮔﺸﺘﻪ ﻭ ﭘﺲ ﺍﺯ ﺍﻳﻨﻜﻪ ﻛﻠﻴﻪ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺳﻨﻜﺮﻭﻥ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺧﻮﺩ ﺑﺎﺷﻨﺪ
ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﺑﺎﺱ ﺑﺮﻕ ﺩﺍﺭ ﻣﺘﺼﻞ ﺧﻮﺍﻫﺪ ﺷﺪ.
: 6-2ﺳﻨﻜﺮﻭﻥ ﭼﻚ
ﺍﻳﻦ ﺩﺳﺘﮕﺎﻩ ﺣﺎﻟﺖ ﺳﻨﻜﺮﻭﻥ ﺭﺍ ﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﻭ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ
ﺷﺪﻩ ﺑﺎﺷﻨﺪ ﭼﻚ ﻛﺮﺩﻩ ﻭ LEDﻣﺮﺑﻮﻃﻪ ﺑﻪ ﺻﻮﺭﺕ ﭼﺸﻤﻚ ﺯﻥ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ،ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ
LEDﻫﺎﻱ ﺳﻨﻜﺮﻭﻧﺴﻜﻮﭖ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭ ﻣﻘﺪﺍﺭ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﻧﺸﺎﻥ
ﻣﻲ ﺩﻫﺪ.
ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺗﻮﺳﻂ ﻛﻨﺘﺮﻟﺮ ﻣﺘﺸﻜﻞ ﺍﺯ ﺍﺭﺯﻳﺎﺑﻲ ﺷﺮﻭﻁ ﺫﻳﻞ ﺩﺭ ﺧﻼﻝ ﺳﻴﻜﻞ ﻫﺎﻱ ﻛﺎﺭﻱ
ﻣﺘﻮﺍﻟﻲ ﺑﺎﺱ ﺑﺎﺭ ﻣﻲ ﺑﺎﺷﺪ.
-ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﻣﻲ ﺑﺎﻳﺴﺘﻲ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺗﻮﺳﻂ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ P-004ﻭ P-005ﺑﺎﺷﺪ.
-ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ ﻣﻲ ﺑﺎﻳﺴﺘﻲ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺗﻮﺳﻂ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ P-006ﻭ P-007
ﺑﺎﺷﺪ.
-ﺍﺧﺘﻼﻑ ﻓﺮﻛﺎﻧﺲ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭﺑﻴﺶ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ P-039
ﻧﺒﺎﺷﺪ.
-ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭ ﺑﻴﺶ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮP-040
ﻧﺒﺎﺷﺪ.
-ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭ ﺑﻴﺶ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ P-041
ﻧﺒﺎﺷﺪ.
ﭼﻨﺎﻧﭽﻪ ﺣﺎﻟﺘﻬﺎﻱ ﻣﺘﻮﺍﻟﻲ ﺑﺎﻻ ﺩﺭ ﺷﺮﺍﻳﻂ ﻛﺎﺭﻱ ﺳﻴﻜﻞ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﻫﺎﻱ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺑﺎﺷﻨﺪ
ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺳﺮﻳﻌﺎ" ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ .
ﭼﻨﺎﻧﭽﻪ ﺣﺎﻟﺘﻬﺎﻱ ﻣﺘﻮﺍﻟﻲ ﺳﻴﻜﻞ ﻛﺎﺭﻱ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺫﻛﺮ ﺷﺪﻩ ﻧﺒﺎﺷﺪ ﺭﻟﻪ
ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺳﺮﻳﻌﺎ" ﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ.
16
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻫﺸﺪﺍﺭ
ﭘﻴﺸﻨﻬﺎﺩ ﻣﻲ ﺷﻮﺩ ﻛﻪ ﺍﺯ ﻛﻨﺘﺎﻛﺘﻮﺭ ﻭ ﻛﻠﻴﺪﻫﺎﻱ ﺑﺎ ﻗﻄﻊ ﻭ ﻭﺻﻞ ﺳﺮﻳﻊ ﺍﺳﺘﻔﺎﺩﻩ ﺷﻮﺩ.
ﺳﻴﺴﺘﻢ ﻗﺎﺑﻠﻴﺖ ﺗﻄﺒﻴﻖ ﺑﺎ ﻫﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﻳﺎ ﺩﻣﺎ ﺭﺍ ﺩﺍﺭﺍﺳﺖ .ﺑﻪ ﻃﻮﺭ ﻛﻠﻲ ﻣﺸﺨﺼﻪ ﺳﻨﺴﻮﺭﻫﺎﻱ
ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﺩﺭ ﺩﺍﺧﻞ ﺣﺎﻓﻈﻪ ﻛﻨﺘﺮﻟﺮ ﺛﺒﺖ ﺷﺪﻩ ﺍﺳﺖ ﻭ ﺍﺯ ﺭﻭﻱ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ .
ﺳﻨﺴﻮﺭﻫﺎﻱ ﻏﻴﺮ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺰ ﻣﻤﮑﻦ ﺍﺳﺖ ﺑﺎ ﻭﺍﺭﺩ ﻛﺮﺩﻥ ﻣﺸﺨﺼﺎﺕ ﺁﻧﻬﺎ ﺩﺭ ﺟﺪﻭﻝ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ
ﺑﺎﺷﻨﺪ .
17
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎ :
ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ P-020ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ .ﺍﻧﻮﺍﻉ ﺳﻨﺴﻮﺭﻫﺎﻱ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﻋﺒﺎﺭﺗﻨﺪ
ﺍﺯ :
: 0ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ P-143ﻭ P-154ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ
ﺍﺳﺖ.
VDO : 1
DATCON DAH Type : 2
DATCON DAL Type : 3
18
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﺗﻮﺟﻪ LED :ﻣﺮﺑﻮﻁ ﺑﻪ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ ﺗﺎﺛﻴﺮﻱ ﺩﺭ ﻋﻤﻠﮑﺮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ
ﺩﺍﺷﺖ .
ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﻪ ﺩﻭ ﺻﻮﺭﺕ ،ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻭ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺗﻌﻤﻴﺮﺍﺕ
ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺭﺍ ﺩﺍﺭﺍ ﻣﻲ ﺑﺎﺷﺪ .ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ) (P-044ﺑﺎ
ﻣﺮﺣﻠﻪ ﻫﺎﻱ 50ﺳﺎﻋﺘﻪ ﺍﺳﺖ ﻭ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﻧﻴﺰ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ) (P-045ﺑﺎ
ﻣﺮﺣﻠﻪ ﻫﺎﻱ 1ﻣﺎﻫﻪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺍﺳﺖ .ﺍﮔﺮ ﻫﺮ ﻳﮏ ﺍﺯ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﮔﻔﺘﻪ ﺷﺪﻩ ﺑﺎ ﻋﺪﺩ ﺻﻔﺮ ﺑﺮﻧﺎﻣﻪ
ﺭﻳﺰﻱ ﺷﻮﻧﺪ ﺍﻳﻦ ﺑﻪ ﺁﻥ ﻣﻌﻨﻲ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ﮐﻪ ﺍﺯ ﺁﻥ ﭘﺎﺭﺍﻣﺘﺮﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﺷﻮﺩ .ﺑﻪ ﻋﻨﻮﺍﻥ ﻣﺜﺎﻝ ﺍﮔﺮ
ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻪ ﺩﺍﺭﻱ ﺑﺮﺍﺑﺮ ﺻﻔﺮ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ ،ﺑﻪ ﺍﻳﻦ ﻣﻌﻨﻲ ﺍﺳﺖ ﮐﻪ ﺳﻴﺴﺘﻢ
ﻓﻘﻂ ﺑﺮ ﺍﺳﺎﺱ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﭘﺎﺳﺦ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ﻭ ﻫﻤﭽﻨﻴﻦ ﺍﮔﺮ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻧﻴﺰ ﺻﻔﺮ
ﺷﻮﺩ ﺍﻳﻦ ﺑﻪ ﻣﻌﻨﻲ ﺍﺳﺖ ﮐﻪ ﻧﻤﺎﻳﺸﮕﺮ Service Requestﻏﻴﺮ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ .
ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺣﺪ ﺯﻣﺎﻧﻲ ﻳﺎ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺑﻪ ﭘﺎﻳﺎﻥ ﺑﺮﺳﺪ LEDﻣﺮﺑﻮﻁ ﺑﻪ Service
Requestﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ .
ﺑﺮﺍﻱ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﺍﻳﻦ LEDﻭ Resetﺗﻌﻤﻴﺮﺍﺕ ﺩﻭﺭﻩ ﺍﻱ ﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﺩﻭ ﺩﮐﻤﻪ Lamp
Testﻭ Alarm Muteﺭﺍ ﺑﺮﺍﻱ ﻣﺪﺕ 5ﺛﺎﻧﻴﻪ ﺑﻪ ﺻﻮﺭﺕ ﻫﻤﺰﻣﺎﻥ ﻧﮕﻪ ﺩﺍﺭﻳﺪ .ﻧﻤﺎﻳﺸﮕﺮ ﺑﺎﻻﻳﻲ
ﻋﺒﺎﺭﺕ " " SERﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ .
19
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺯﻣﺎﻥ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﻭ ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺫﺧﻴﺮﻩ ﻣﻲ ﺷﻮﻧﺪ ﻭ
ﺑﺎ ﻗﻄﻊ ﺑﺮﻕ ﺳﻴﺴﺘﻢ ﭘﺎﮎ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ .
ﺯﻣﺎﻥ ﺑﺎﻗﻲ ﻣﺎﻧﺪﻩ ﺑﺮﺍﻱ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﻭﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺩﺭ ﻣﻨﻮﻱ ﺁﻣﺎﺭﻱ ،ﺑﺎ ﻧﮕﻪ
ﺩﺍﺷﺘﻦ ﺩﮐﻤﻪ Menuﺑﻪ ﻣﺪﺕ 1ﺛﺎﻧﻴﻪ ،ﻗﺎﺑﻞ ﻣﺸﺎﻫﺪﻩ ﺧﻮﺍﻫﺪ ﺑﻮﺩ .
ﺑﺎ ﻓﺸﺮﺩﻥ ﻛﻠﻴﺪ Menuﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺗﻮﺳﻂ ﻧﻤﺎﻳﺸﮕﺮ " ) " Htsﺑﺮ ﺣﺴﺐ ﺳﺎﻋﺖ(
ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ،ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ Menuﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ 3 ،ﺭﻗﻢ ﺍﻭﻝ ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ
ﻣﻮﺗﻮﺭ ﻭ ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻣﺠﺪﺩ ﻛﻠﻴﺪ Menuﻧﻤﺎﻳﺸﮕﺮ " ) " Htsﺑﺮ ﺣﺴﺐ ﺳﺎﻋﺖ( ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﻲ
ﺷﻮﺩ ﻭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ Menuﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ 3ﺭﻗﻢ ﺁﺧﺮ ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ
ﺧﻮﺍﻫﻨﺪ ﺩﺍﺩ.
ﺑﺎ ﻓﺸﺮﺩﻥ ﻛﻠﻴﺪ Menuﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺗﻮﺳﻂ ﻧﻤﺎﻳﺸﮕﺮ ﺑﺮﺍﻱ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻧﻤﺎﻳﺸﮕﺮ " ttS
" ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ، ،ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ Menuﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ 3 ،ﺭﻗﻢ ﺍﻭﻝ ﺭﻭﺯﻫﺎﻱ
ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﻭ ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻣﺠﺪﺩ ﻛﻠﻴﺪ Menuﻧﻤﺎﻳﺸﮕﺮ " ) " ttSﺑﺮ ﺣﺴﺐ ﺳﺎﻋﺖ(
ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﻭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ Menuﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ 3ﺭﻗﻢ ﺁﺧﺮ ﺭﻭﺯﻫﺎﻱ
ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﻨﺪ ﺩﺍﺩ.
20
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
: 6-5ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ
ﻛﻨﺘﺮﻟﺮ ﺍﻣﻜﺎﻥ Programmingﻭ Monitoringﺭﺍ ﺍﺯ ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ ﺍﻳﺠﺎﺩ ﻣﻲ ﻛﻨﺪ .ﺩﺭ
ﺑﺮﻧﺎﻣﻪ ﺑﺮﺍﻱ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﮐﺮﺩﻥ ﻭ ﻣﻮﻧﻴﺘﻮﺭﻳﻨﮓ ﺍﺯ ﻣﻮﺩﻡ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ .
ﺍﮔﺮ ﺍﺯ ﻣﻮﺩﻡ ﺍﺳﺘﻔﺎﺩﻩ ﺷﻮﺩ ،ﭘﺎﺭﺍﻣﺘﺮ ) ( P-043ﺑﺎﻳﺪ ﺑﺮﺍﺑﺮ ﺑﺎ 1ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ ،ﺩﺭ ﻏﻴﺮ ﺍﻳﻦ
ﺻﻮﺭﺕ ﻣﻤﮑﻦ ﺍﺳﺖ ﺧﻄﺎ ﺍﺗﻔﺎﻕ ﺑﻴﺎﻓﺘﺪ .
ﻛﻨﺘﺮﻟﺮ ﻳﮏ ﺳﺮﻱ ﺍﺯ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺍﻓﺰﺍﻳﺸﻲ ﻏﻴﺮ ﻗﺎﺑﻞ ﺭﻳﺴﺖ ﺭﺍ ﺑﺮﺍﻱ ﺛﺒﺖ ﺑﺮﺧﻲ ﺍﺯ ﻭﻗﺎﻳﻊ ﻓﺮﺍﻫﻢ
ﻣﻲ ﺁﻭﺭﺩ ﻛﻪ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ :
-ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ
-ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺭﻭﺷﻦ ﺷﺪﻥ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ
ﻧﻤﻲ ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﺫﺧﻴﺮﻩ ﻣﻲ ﺷﻮﻧﺪ ﻭ ﺩﺭ ﺻﻮﺭﺕ ﻗﻄﻊ ﺑﺮﻕ ﺍﺯ ﺑﻴﻦ
ﺭﻭﻧﺪ .
ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﻱ ﺁﻣﺎﺭﻱ ﺗﻨﻬﺎ ﺍﺯ ﻃﺮﻳﻖ PCﻗﺎﺑﻞ ﻧﻤﺎﻳﺶ ﻫﺴﺘﻨﺪ ﻭ ﺩﺳﺘﺮﺳﻲ ﺑﻪ ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﻓﻘﻂ
ﺩﺭ ﺻﻮﺭﺕ ﮐﺎﺭ ﺑﺎ ﻧﺮﻡ ﺍﻓﺰﺍﺭ ﺍﻣﮑﺎﻥ ﭘﺬﻳﺮ ﺍﺳﺖ ﻭ ﻣﺸﺎﻫﺪﻩ ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﺩﺭ ﻛﻨﺘﺮﻟﺮ ﺍﻣﮑﺎﻥ ﭘﺬﻳﺮ
ﻧﻤﻲ ﺑﺎﺷﺪ .
21
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
-8ﻧﮕﻬﺪﺍﺭﻱ
ﺩﺭ ﺻﻮﺭﺕ ﻧﻴﺎﺯ ﺑﺮﺍﻱ ﺗﻤﻴﺰ ﮐﺮﺩﻥ ﺁﻥ ﺍﺯ ﭘﺎﺭﭼﻪ ﻧﻤﺪﺍﺭ ﺍﺳﺘﻔﺎﺩﻩ ﮐﻨﻴﺪ ﻭ ﺍﺯ ﻣﻮﺍﺩ ﺷﻴﻤﻴﺎﻳﻲ ﺍﺳﺘﻔﺎﺩﻩ
ﻧﮑﻨﻴﺪ .
ﺍﺯ ﺣﺎﻟﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺭ ﺗﻨﻈﻴﻢ ﺗﺎﻳﻤﺮﻫﺎ ،ﺗﻌﺮﻳﻒ ﺣﺪﻭﺩ ﮐﺎﺭ ﺳﻴﺴﺘﻢ ﻭ ﭘﻴﮑﺮﺑﻨﺪﻱ ﺳﻴﺴﺘﻢ ﺍﺳﺘﻔﺎﺩﻩ
ﻣﻲ ﺷﻮﺩ .
ﺑﺮﺍﻱ ﻭﺍﺭﺩ ﺷﺪﻥ ﺑﻪ ﺍﻳﻦ ﺣﺎﻟﺖ ﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﺩﮐﻤﻪ Menuﺭﺍ ﺑﺮﺍﻱ ﻣﺪﺕ 5ﺛﺎﻧﻴﻪ ﻧﮕﻪ ﺩﺍﺭﻳﺪ ،
ﺑﺮﺍﻱ ﺍﻳﻦ ﻛﺎﺭ ﻻﺯﻡ ﺍﺳﺖ ﮐﻪ ﻭﺭﻭﺩﻱ ) Program Lockﺗﺮﻣﻴﻨﺎﻝ (24ﺑﺎﺯ ﺑﺎﺷﺪ .ﺍﮔﺮ ﻭﺭﻭﺩﻱ
ﻣﺮﺑﻮﻃﻪ ﺯﻣﻴﻦ ﺷﻮﺩ ﺍﺟﺎﺯﻩ ﺗﻐﻴﻴﺮﺍﺕ ﻏﻴﺮ ﻣﺠﺎﺯ ﺩﺭ ﻣﻘﺎﺩﻳﺮ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺩﺍﺩﻩ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ﺍﺯ ﺍﻳﻨﺮﻭ
ﺗﻮﺻﻴﻪ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﺭﺍ ﺣﺘﻤﺎ ﺑﻪ ﺯﻣﻴﻦ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ .
ﺣﺎﻟﺖ Programﺗﺎﺛﻴﺮﻱ ﺩﺭ ﻋﻤﻠﮑﺮﺩ ﻛﻨﺘﺮﻟﺮ ﻧﺪﺍﺭﺩ ﺍﺯ ﺍﻳﻨﺮﻭﻣﻲ ﺗﻮﺍﻥ ﺩﺭ ﻣﻮﺍﻗﻌﻲ ﮐﻪ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ
ﺩﺭﺣﺎﻝ ﮐﺎﺭ ﺍﺳﺖ ﻭﺍﺭﺩ ﺍﻳﻦ ﺣﺎﻟﺖ ﺷﺪ ﻭ ﻣﻘﺎﺩﻳﺮ ﺭﺍ ﺗﻐﻴﻴﺮ ﺩﺍﺩ .
ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺍﺭﺩ ﺣﺎﻟﺖ Programﻣﻲ ﺷﻮﺩ ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ Menuﻓﺸﺮﺩﻩ ﺷﻮﺩ
ﻧﻤﺎﻳﺸﮕﺮ ﺷﻤﺎﺭﻩ ﭘﺎﺭﺍﻣﺘﺮ ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ﻭ ﺑﺎ ﺭﻫﺎ ﺷﺪﻥ ﺩﻛﻤﻪ Menuﻧﻤﺎﻳﺸﮕﺮ ﻣﻘﺪﺍﺭ ﭘﺎﺭﺍﻣﺘﺮ
ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ﻭ ﺍﻭﻟﻴﻦ ﺷﻤﺎﺭﻩ ﺑﺮﻧﺎﻣﻪ ” “000ﻣﻲ ﺑﺎﺷﺪ.
ﻫﺮ ﺑﺎﺭ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ Menuﺳﺒﺐ ﺭﻓﺘﻦ ﺑﻪ ﭘﺎﺭﺍﻣﺘﺮ ﺷﻤﺎﺭﻩ ﺑﻌﺪ ﻣﻲ ﺷﻮﺩ .ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻭ ﻧﮕﻪ
ﺩﺍﺷﺘﻦ ﺩﮐﻤﻪ Menuﺑﺎﻋﺚ ﺍﻓﺰﺍﻳﺶ ﺑﺎ ﮔﺎﻡ 10ﺗﺎﻳﻲ ﺩﺭ ﺷﻤﺎﺭﻩ ﭘﺎﺭﺍﻣﺘﺮ ﻣﻲ ﺷﻮﺩ .ﺑﻌﺪ ﺍﺯ ﺭﺳﻴﺪﻥ
ﺑﻪ ﺁﺧﺮﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺩﻭﺑﺎﺭﻩ ﺍﻭﻟﻴﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ .
22
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﺑﺮﺍﻱ ﺍﻓﺰﺍﻳﺶ ﻭ ﻛﺎﻫﺶ ﻣﻘﺪﺍﺭ ﻳﮏ ﭘﺎﺭﺍﻣﺘﺮ ﺍﺯ ﺩﮐﻤﻪ ﻫﺎﻱ ﻭ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﺪ .ﺑﺮﺍﻱ ﺍﻓﺰﺍﻳﺶ /
ﻛﺎﻫﺶ ﻣﻘﺪﺍﺭ ﻳﮏ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺎ ﮔﺎﻡ 10ﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﺩﮐﻤﻪ ﻫﺎﻱ ﻭ ﺭﺍ ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﻭ ﻧﮕﻪ
ﺩﺍﺭﻳﺪ .
ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﻧﮕﻬﺪﺍﺭﻱ ﻣﻲ ﺷﻮﻧﺪ ﺍﺯ ﺍﻳﻨﺮﻭ ﺑﺎ ﻗﻄﻊ ﺑﺮﻕ ﺍﻳﻦ ﻣﻘﺎﺩﻳﺮ
ﺣﻔﻆ ﺧﻮﺍﻫﻨﺪ ﺷﺪ .
ﺑﺮﺍﻱ ﺧﺮﻭﺝ ﺍﺯ ﺣﺎﻟﺖ Progarmﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﻳﮑﻲ ﺍﺯ ﺩﮐﻤﻪ ﻫﺎﻱ ﺗﻐﻴﻴﺮﺣﺎﻟﺖ ﺭﺍ ﻓﺸﺎﺭ ﺩﻫﻴﺪ
ﻭ ﻳﺎ ﻛﻠﻴﺪﻫﺎﻱ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺑﻪ ﻣﺪﺕ 1ﺩﻗﻴﻘﻪ ﺩﺳﺖ ﻧﺰﻧﻴﺪ .
ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ
Pgm Definition Unit Std.val Description
ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻭﺍﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺮﺡ
ﻛﺎﺭﺧﺎﻧﻪ
ﻧﺴﺒﺖ ﺗﺒﺪﻳﻞ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ
0 ﺟﺮﻳﺎﻥ ﺍﻭﻟﻴﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ A 500
ﻣﻲ ﺷﻮﺩ .ﻫﻤﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﻫﺎﻱ ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ ﺩﺍﺭﺍﻱ
ﻧﺴﺒﺖ ﺗﺒﺪﻳﻞ ﻳﻜﺴﺎﻥ ﺑﺎﺷﻨﺪ .ﺛﺎﻧﻮﻳﻪ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﺑﺎﻳﺪ 5ﺁﻣﭙﺮ
ﺑﺎﺷﺪ .ﺑﺮﺍﻱ ﻣﻘﺎﺩﻳﺮ ﺑﺎﻻﻱ 990ﺁﻣﭙﺮ %10ﻣﻘﺪﺍﺭ ﺣﻘﻴﻘﻲ ﺭﺍ
ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﺪ ،ﺍﻳﻦ ﻣﻘﺎﺩﻳﺮ ﺑﻪ ﺻﻮﺭﺕ ﻛﻴﻠﻮ ﺁﻣﭙﺮ ﻧﻤﺎﻳﺶ
ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ.
23
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Pgm Definition Unit Std.val Description
ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻭﺍﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺮﺡ
ﻛﺎﺭﺧﺎﻧﻪ
ﺍﮔﺮ ﻣﻘﺪﺍﺭ ﺗﻮﺍﻥ ﺍﺯ ﺍﻳﻦ ﺣﺪ ﺩﺭ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ
P-024ﺑﺎﻻﺗﺮ ﺭﻭﺩ ﭘﻴﻐﺎﻡ OverLoadﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ
3 ﻣﺤﺪﻭﺩﻳﺖ ﺍﺿﺎﻓﻪ ﺗﻮﺍﻥ KW 350
ﺷﺪ .ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻤﻲ ﺑﺎﻳﺪ ﻣﻄﺎﺑﻖ ﺑﺎ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ
ﭘﺎﺭﺍﻣﺘﺮ P-000ﺑﺎﺷﺪ.
4 ﻣﺤﺪﻭﺩﻩ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ V 100 ﭼﻨﺎﻧﭽﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﺑﺎﺱ ﺑﺎﺭ ﭘﺎﻳﻴﻦ ﺗﺮ ﺍﺯ ﺣﺪ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺑﺎﺷﺪ
ﺑﺪﻳﻦ ﻣﻌﻨﺎﺳﺖ ﻛﻪ ﺑﺎﺱ ﺑﺎﺭ ﺑﺪﻭﻥ ﺑﺮﻕ ﺍﺳﺖ .
5 ﻣﺤﺪﻭﺩﻩ ﺑﺎﻻﻱ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ V 500 ﭼﻨﺎﻧﭽﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﺑﺎﺱ ﺑﺎﺭ ﺑﺎﻻ ﺗﺮ ﺍﺯ ﺣﺪ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺑﺎﺷﺪ
ﺑﺪﻳﻦ ﻣﻌﻨﺎﺳﺖ ﻛﻪ ﺑﺎﺱ ﺑﺎﺭ ﺑﺪﻭﻥ ﺑﺮﻕ ﺍﺳﺖ .
ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻳﮑﻲ ﺍﺯ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ
ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ )ﺩﺭ ﺷﺮﺍﻳﻄﻲ ﮐﻪ ﺯﻳﺮ ﺑﺎﺭ ﺍﺳﺖ( ،ﺁﻻﺭﻡ
6 ﺣﺪ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ V 180
ﻭﻟﺘﺎﮊ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ .
24
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Pgm Definition Unit Std.val Description
ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻭﺍﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺮﺡ
ﻛﺎﺭﺧﺎﻧﻪ
ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﻻﻱ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ
ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ،ﺁﻻﺭﻡ Speedﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ
11 ﺁﻻﺭﻡ ﺑﺎﻻﺭﻓﺘﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺍﺯ Hz 57 ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﮐﺮﺩ .ﺍﻳﻦ ﺁﻻﺭﻡ ﺗﻨﻬﺎ ﺩﺭ ﺯﻣﺎﻧﻲ ﮐﻪ ﻣﻮﺗﻮﺭ
ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ Runﺍﺳﺖ ﻭ ﺑﻌﺪ ﺍﺯ ﺗﺎﺧﻴﺮﻱ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ P-023ﺗﻌﻴﻴﻦ
ﻣﻲ ﮔﺮﺩﺩ ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ
ﺍﮔﺮ ﻭﻟﺘﺎﺯ ﺑﺎﻃﺮﻱ ﺑﻪ ﺯﻳﺮ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ
ﻫﺸﺪﺍﺭ ﭘﺎﻳﻴﻦ ﺁﻣﺪﻥ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺍﺯ
12 ﺑﺮﺳﺪ ،ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ Batteryﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ .
V 9.0
ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ
ﺍﮔﺮ ﺩﻣﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺗﻮﺳﻂ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺁﻧﺎﻟﻮﮒ ﺍﺯ
C 90 ﺩﻣﺎﻱ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮ ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ
17 ﻫﺸﺪﺍﺭ ﺑﺎﻻ ﺑﻮﺩﻥ ﺩﻣﺎﻱ ﺁﺏ
ﺷﻮﺩ ،ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ High Tempﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ
ﺷﺪ .
25
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Pgm Definition Unit Std.val Description
ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻭﺍﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺮﺡ
ﻛﺎﺭﺧﺎﻧﻪ
ﺍﮔﺮ ﺩﻣﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺗﻮﺳﻂ ﻭﺭﻭﺩﻱ ﺁﻧﺎﻟﻮﮒ ﺍﺯ
ﺩﻣﺎﻱ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮ ﺷﻮﺩ ،ﺁﻻﺭﻡ ﻣﺮﺑﻮﻁ ﺑﻪ
18 ﺁﻻﺭﻡ ﺑﺎﻻ ﺑﻮﺩﻥ ﺩﻣﺎﻱ ﺁﺏ C 98
High Tempﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ
ﺧﻮﺍﻫﺪ ﮐﺮﺩ .
ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ
: 0ﺳﻨﺴﻮﺭ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺴﺖ ﻭ ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ
ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ P-131ﺗﺎ P-142ﺗﻌﻴﻴﻦ
ﻣﻲ ﮔﺮﺩﺩ .
- 1
VDO 0-7bars (10-180 ohms) : 1
19 ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ
VDO 0-10bars (280-20 ohms) : 2
DATCON 0-7bars (240-33 ohms) : 3
DATCON0-10bars (240-33 ohms) : 4
DATCON 0-7bars (0-90 ohms) : 5
DATCON 0-10bars (0-90 ohms) : 6
DATCON 0-7bars (75-10 ohms) : 7
26
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Pgm Definition Unit Std.val Description
ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻭﺍﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺮﺡ
ﻛﺎﺭﺧﺎﻧﻪ
22 ﺣﺮﺍﺭﺕ ﮔﺮﻡ ﻛﻦ ﻣﻮﺗﻮﺭ ºC 50 ﭼﻨﺎﻧﭽﻪ ﻧﻴﺎﺯ ﺑﺎﺷﺪ ﻣﻮﺗﻮﺭ ﺑﺪﻭﻥ ﺑﺎﺭ ﻛﺎﺭ ﻛﺮﺩﻩ ﺗﺎ ﺑﻪ ﺣﺮﺍﺭﺕ
ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺑﺮﺳﺪ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺗﻌﻴﻴﻦ ﻛﻨﻨﺪﻩ ﻣﻘﺪﺍﺭ ﺣﺮﺍﺭﺕ
ﻣﻲ ﺑﺎﺷﺪ.
ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮﻱ ﺭﺍ ﺗﻌﺮﻳﻒ ﻣﻲ ﮐﻨﺪ ﮐﻪ ﺑﻌﺪ ﺍﺯ
23 ﺗﺎﻳﻤﺮ ﺗﺎﺧﻴﺮ Sec 8
Runﺷﺪﻥ ﻣﻮﺗﻮﺭ،ﺩﺭ ﺁﻥ ﺯﻣﺎﻥ Faultﻫﺎ ﻓﻌﺎﻝ ﻧﻤﻲ ﺷﻮﻧﺪ .
27
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Pgm Definition Unit Std.val Description
ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻭﺍﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺮﺡ
ﻛﺎﺭﺧﺎﻧﻪ
ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮﻳﻦ ﺣﺪ ﺯﻣﺎﻥ ﺭﺍ ﺑﺮﺍﻱ ﺗﻮﻗﻒ ﻣﻮﺗﻮﺭ ﺗﻌﻴﻴﻦ
ﻣﻲ ﮐﻨﺪ .ﺩﺭ ﻃﻮﻝ ﺍﻳﻦ ﺯﻣﺎﻥ ﺭﻟﻪ ﺧﺮﻭﺟﻲ Stopﻓﻌﺎﻝ
34 ﺗﺎﻳﻤﺮ ﺧﺎﻣﻮﺵ ﺷﺪﻥ Sec 10 ﺧﻮﺍﻫﺪ ﺷﺪ ) .ﺍﻟﺒﺘﻪ ﺍﮔﺮ ﺑﻪ ﻭﺳﻴﻠﻪ ﺑﺮﻧﺎﻣﻪ ﺗﻌﺮﻳﻒ ﺷﻮﺩ( ﺍﮔﺮ
ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﻣﺘﻮﻗﻒ ﻧﺸﻮﺩ ،ﺁﻻﺭﻡ
Stop Failﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ .
ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮﻳﻦ ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻣﺸﺨﺺ
35 ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ - 3
ﻣﻲ ﮐﻨﺪ .
ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺪﺕ ﺯﻣﺎﻧﻲ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ ﮐﻪ ﺧﺮﻭﺟﻲ
Hornﺩﺭ ﻃﻮﻝ ﺁﻥ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺑﻮﺩ .
36 ﺗﺎﻳﻤﺮ ﺁﮊﻳﺮ Sec 10
ﺍﮔﺮ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ 0ﺑﺎﺷﺪ ﺑﻪ ﻣﻌﻨﻲ ﻧﺎﻣﺤﺪﻭﺩ ﺑﻮﺩﻥ ﻣﺪﺕ ﺯﻣﺎﻥ
ﺁﮊﻳﺮ ﻣﻲ ﺑﺎﺷﺪ.
ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺭﻭﺵ ﮔﺮﻡ ﻛﺮﺩﻥ ﻣﻮﺗﻮﺭ ﺗﻌﻴﻴﻦ ﻣﻲ ﺷﻮﺩ ﻭ
- 0 ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺗﺎ ﺯﻣﺎﻧﻲ ﻛﻪ ﻣﻮﺗﻮﺭ ﮔﺮﻡ ﻧﺸﻮﺩ ﻗﺎﺑﻠﻴﺖ ﭘﺬﻳﺮﻓﺘﻦ
ﺑﺎﺭ ﺭﺍ ﻧﺪﺍﺭﺩ.
37 ﻧﻮﻉ ﮔﺮﻡ ﻛﻦ ﻣﻮﺗﻮﺭ : 0ﻣﻮﺗﻮﺭ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﺯﻣﺎﻥ ﺗﺎﻳﻤﺮ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ
P-029ﮔﺮﻡ ﻣﻲ ﺷﻮﺩ .
: 1ﻣﻮﺗﻮﺭ ﺗﺎ ﻣﺤﺪﻭﺩﻩ ﻣﻘﺪﺍﺭ ﺩﻣﺎﻱ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ P-
022ﮔﺮﻡ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻳﺎ ﺣﺪﺍﻗﻞ ﺩﺭ ﺯﻣﺎﻥ ﺗﻌﻴﻴﻦ ﺷﺪﻩ
ﭘﺎﺭﺍﻣﺘﺮ P-029ﮔﺮﻡ ﺧﻮﺍﻫﺪ ﺷﺪ.
40 ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ V 10 ﭼﻨﺎﻧﺠﻪ ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭ ﺑﺎﻻﻱ
ﻣﺤﺪﻭﺩﻩ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﺍﻧﺠﺎﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ
41 ﺍﺧﺘﻼﻑ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ deg . 5 ﭼﻨﺎﻧﺠﻪ ﺍﺧﺘﻼﻑ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭ
ﺑﺎﻻﻱ ﻣﺤﺪﻭﺩﻩ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﺍﻧﺠﺎﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ
28
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
Pgm Definition Unit Std.val Description
ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ ﻭﺍﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺮﺡ
ﻛﺎﺭﺧﺎﻧﻪ
ﭼﻨﺎﻧﭽﻪ ﻣﻘﺪﺍﺭ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺗﻮﺍﻥ ﺍﻛﺘﻴﻮ ﻓﺎﺯ Uﮊﻧﺮﺍﺗﻮﺭ
ﻣﻨﻔﻲ ﺑﺎﺷﺪ ﻭ ﺑﺎﻻﻱ ﺯﻣﺎﻥ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ
KW P-024ﺑﺮﻭﺩ ﺍﻋﻼﻡ ﺧﻄﺎﻱ Reverse Powerﺍﻧﺠﺎﻡ
42 ﻣﺤﺪﻭﺩﻩ ﺗﻮﺍﻥ ﻣﻌﻜﻮﺱ 0
ﺧﻮﺍﻫﺪ ﺷﺪ .ﻣﻘﺪﺍﺭ ﺗﻮﺍﻥ ﻭﺍﺭﺩ ﺷﺪﻩ ﺑﺎﻳﺪ ﺑﺮﺣﺴﺐ ﻣﺸﺨﺼﻪ
ﭘﺎﺭﺍﻣﺘﺮ P-000ﻭﺍﺭﺩ ﮔﺮﺩﺩ ﻭ ﭼﻨﺎﻧﭽﻪ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻪ ﻣﻘﺪﺍﺭ
ﺻﻔﺮ ﺗﻨﻈﻴﻢ ﮔﺮﺩﺩ ﻋﻤﻞ ﭼﻚ ﻛﺮﺩﻥ Reverse Power
ﻏﻴﺮ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ .
: 0ﻣﻮﺩﻡ ﻣﺘﺼﻞ ﻧﻴﺴﺖ .ﺍﺯ ﭘﻮﺭﺕ ﺳﺮﻳﺎﻝ ﺑﺮﺍﻱ ﺍﺗﺼﺎﻝ ﺑﻪ PC
ﺍﺗﺼﺎﻝ ﻣﻮﺩﻡ - 0
43 ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ .
: 1ﻣﻮﺩﻡ ﻣﺘﺼﻞ ﺍﺳﺖ .
LEDﻣﺮﺑﻮﻁ ﺑﻪ Service Requestﺑﻌﺪ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ
ﺍﻳﻦ ﺯﻣﺎﻥ ﺍﺯ ﺁﺧﺮﻳﻦ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ
44 ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ Hours 200
ﺷﺪ .
)ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ(
ﺩﺭ ﺻﻮﺭﺕ ﺍﻧﺘﺨﺎﺏ ﻋﺪﺩ 0ﻧﻴﺎﺯ ﺑﻪ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ
ﺑﺮﺍﻱ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ ﺑﻮﺩ .
LEDﻣﺮﺑﻮﻁ ﺑﻪ Service Requestﺑﻌﺪ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ
ﺍﻳﻦ ﺯﻣﺎﻥ ﺍﺯ ﺁﺧﺮﻳﻦ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺷﺪ
ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ
45 Month 6 ﺩﺭ ﺻﻮﺭﺕ ﺍﻧﺘﺨﺎﺏ ﻋﺪﺩ 0ﻧﻴﺎﺯ ﺑﻪ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ
)ﻣﺎﻫﺎﻧﻪ(
ﺑﺮﺍﻱ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ ﺑﻮﺩ
46 Not Used
47 Not Used
48 Not Used
49 Not Used
50 Not Used
ﭘﺎﺭﺍﻣﺘﺮ P-051ﻭ P-052ﻋﻤﻠﻴﺎﺕ ﻣﺨﺘﻠﻒ ﺭﺍ ﺑﺮﺍﻱ ﺭﻟﻪ ﻫﺎﻱ ﺧﺮﻭﺟﻲ ﺗﻌﺮﻳﻒ ﻣﻴﻨﻤﺎﻳﻨﺪ .ﺍﻳﻦ
ﻛﻨﺘﺮﻟﺮ 5ﺭﻟﻪ ﺧﺮﻭﺟﻲ ﺩﺍﺭﺩ ﻭ 2ﻋﺪﺩ ﺍﺯ ﺁﻧﻬﺎ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻫﺴﺘﻨﺪ .ﺭﻟﻪ ﻫﺎﻳﻲ ﮐﻪ ﻋﻤﻠﻴﺎﺕ ﺛﺎﺑﺖ
ﺩﺍﺭﻧﺪ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ Start ، Fuelﻭ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ .
29
DKG217 ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
. ﻓﺎﻧﮑﺸﻦ ﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﺮﺍﻱ ﺭﻟﻪ ﻫﺎﻱ ﺧﺮﻭﺟﻲ ﺩﺭ ﺷﮑﻞ ﺯﻳﺮ ﻧﺸﺎﻥ ﺩﺍﺩﻩ ﺷﺪﻩ ﺍﺳﺖ
. ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﺭﺍ ﺑﺮ ﻋﻬﺪﻩ ﺩﺍﺭﻧﺪP-088 ﺗﺎP-053 ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺷﻤﺎﺭﻩ
: ﺍﻣﻜﺎﻧﺎﺕ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ
Operation -( ﻫﺸﺪﺍﺭ ﻭ ﻏﻴﺮﻩ، ﻋﻤﻠﻴﺎﺕ ﺑﺮ ﺭﻭﻱ ﻭﺭﻭﺩ ﺳﻴﮕﻨﺎﻝ ﺑﻪ ﺳﻴﺴﺘﻢ )ﺁﻻﺭﻡ-
Fault Monitoring – ﺩﺭﻧﻈﺮ ﮔﺮﻓﺘﻦ ﺳﻴﮕﻨﺎﻟﻬﺎﻱ ﺧﻄﺎ-
Latching – ﻗﻔﻞ ﺷﺪﻥ ﺑﺮ ﺭﻭﻱ ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎ-
Switching – (Bat- ﻭBat+) ﭘﻼﺭﻳﺘﻪ-
(NC,NO) ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ-
Response Delay – ﺗﺎﺧﻴﺮ ﺩﺭ ﭘﺎﺳﺨﮕﻮﻳﻲ-
30
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻭﺭﻭﺩﻱ ) (Switchﮐﻢ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﺭﻭﻏﻦ )(Low Oil Pressure Switch
Prog Description Std
: 0ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ Hornﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(
53 ﻋﻤﻠﮑﺮﺩ 0
) Warning : 2ﺭﻟﻪ Hornﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(
: 3ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ
: 0ﻫﻤﻴﺸﻪ
54 ﻧﻤﺎﻳﺶ Fault 1
: 1ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ Hold Off
: 2ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ
: 0ﻗﻔﻞ ﺷﻮﺩ
55 ﻗﻔﻞ ﺷﺪﻥ 1
: 1ﻗﻔﻞ ﻧﺸﻮﺩ
: 0ﻧﺮﻣﺎﻟﻲ Open
56 ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ 0
: 1ﻧﺮﻣﺎﻟﻲ Close
: 0ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ
57 ﺳﻮﺋﻴﭽﻴﻨﮓ 0
: 1ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ
: 0ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ
58 ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ 1
: 1ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ ) 4ﺛﺎﻧﻴﻪ(
32
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻭﺭﻭﺩﻱ ﺫﺧﻴﺮﻩ ﺧﻄﺎ ) (Spare-1 Fault
Prog Description Std
: 0ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ Hornﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(
77 ﻋﻤﻠﮑﺮﺩ 0
) Warning : 2ﺭﻟﻪ Hornﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(
: 3ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ
: 0ﻫﻤﻴﺸﻪ
78 ﻧﻤﺎﻳﺶ Fault 0
: 1ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ Hold Off
: 2ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ
: 0ﻗﻔﻞ ﺷﻮﺩ
79 ﻗﻔﻞ ﺷﺪﻥ 0
: 1ﻗﻔﻞ ﻧﺸﻮﺩ
: 0ﻧﺮﻣﺎﻟﻲ Open
80 ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ 0
: 1ﻧﺮﻣﺎﻟﻲ Close
: 0ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ
81 Switching 0
: 1ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ
: 0ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ
82 ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ 1
: 1ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ ) 4ﺛﺎﻧﻴﻪ(
ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ P-089ﺗﺎ P-100ﻣﺸﺨﺼﺎﺕ ﺍﻫﻢ -ﺑﺎﺭ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ .
ﻣﺸﺨﺼﺎﺕ ﺣﺪﺍﮐﺜﺮ ﺩﺭ 6ﻧﻘﻄﻪ ﺗﻌﻴﻴﻦ ﻣﻲ ﮔﺮﺩﺩ .ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﺍﻓﺰﺍﻳﺶ
ﺍﻫﻢ ﺍﺯ ﭘﺎﻳﻴﻦ ﺑﻪ ﺑﺎﻻ ﻭﺍﺭﺩ ﺷﻮﻧﺪ .ﺑﺮﺍﻱ ﻧﻘﺎﻃﻲ ﮐﻪ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﺷﻮﻧﺪ ﺑﺎﻳﺪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ
ﺷﻮﺩ .ﻣﺸﺨﺼﺎﺕ ﺯﻳﺮ ﻣﺸﺨﺼﺎﺕ ﻳﮏ ﺳﻨﺴﻮﺭ ﺍﺳﺖ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ ﻧﻤﻮﻧﻪ ﻭ ﻣﺜﺎﻝ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ
ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ .
34
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﭘﺎﺭﺍﻣﺘﺮ P-101ﺗﺎ P-112ﻣﺸﺨﺼﺎﺕ ﺍﻫﻢ -ﺩﺭﺟﻪ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ .ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ
ﺣﺪﺍﮐﺜﺮ ﺩﺭ 6ﻧﻘﻄﻪ ﺗﻌﻴﻴﻦ ﻣﻲ ﮔﺮﺩﺩ .ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﺍﻓﺰﺍﻳﺶ ﺍﻫﻢ ﺍﺯ ﭘﺎﻳﻴﻦ
ﺑﻪ ﺑﺎﻻ ﻭﺍﺭﺩ ﺷﻮﻧﺪ .ﺑﺮﺍﻱ ﻧﻘﺎﻃﻲ ﮐﻪ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﺷﻮﻧﺪ ﺑﺎﻳﺪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﺷﻮﺩ .ﻣﺸﺨﺼﺎﺕ
ﺯﻳﺮ ﻣﺸﺨﺼﺎﺕ ﻳﮏ ﺳﻨﺴﻮﺭ ﺍﺳﺖ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ ﻧﻤﻮﻧﻪ ﻭ ﻣﺜﺎﻝ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻣﻲ
ﺷﻮﺩ .
35
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
-11ﺭﻓﻊ ﻋﻴﺐ
ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎﮊ ACﻳﺎ ﻓﺮﮐﺎﻧﺲ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭﺳﺖ ﻧﻴﺴﺖ : •
-ﺍﺗﺼﺎﻝ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺑﻪ ﺯﻣﻴﻦ ﺭﺍ ﭼﮏ ﮐﻨﻴﺪ ) .ﺍﻳﻦ ﺁﻳﺘﻢ ﺿﺮﻭﺭﻱ ﺍﺳﺖ( ﺑﺮﺍﻱ ﺁﺯﻣﺎﻳﺶ ﺍﻳﻦ
ﺍﻣﺮ ﺗﺮﻣﻴﻨﺎﻝ BAT-ﻭ ﺗﺮﻣﻴﻨﺎﻝ ﻧﻮﻝ ﺭﺍ ﺑﻪ ﻳﻜﺪﻳﮕﺮ ﺍﺗﺼﺎﻝ ﺩﺍﺩﻩ ﻭ ﭼﻚ ﻛﻨﻴﺪ ﻛﻪ ﺍﻳﺮﺍﺩ
ﺑﺮﻃﺮﻑ ﻣﻲ ﺷﻮﺩ.
-ﻣﻴﺰﺍﻥ ﺧﻄﺎ ﺩﺭ ﺧﻮﺍﻧﺪﻥ ﻣﻘﺎﺩﻳﺮ ﺑﺮﺍﻱ ﮐﻨﺘﺮﻟﺮ ﺑﺮﺍﺑﺮ -/+ 3ﺍﺳﺖ .
-ﺍﮔﺮ ﻭﻗﺘﻲ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ،ﺧﻄﺎ ﺩﺭ ﺧﻮﺍﻧﺪﻥ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻣﺸﺎﻫﺪﻩ ﺷﻮﺩ ،
ﺍﻳﻦ ﺧﻄﺎ ﻣﻤﮑﻦ ﺍﺳﺖ ﻣﺮﺑﻮﻁ ﺑﻪ ﺷﺎﺭﮊﺭ)ﺩﻳﻨﺎﻡ( ﻳﺎ ﺭﮔﻮﻻﺗﻮﺭ ﻭﻟﺘﺎﮊ ﺑﺎﺷﺪ .ﺍﺗﺼﺎﻝ ﺷﺎﺭﮊﺭ ﺭﺍ
ﺍﺯ ﻣﻮﺗﻮﺭ ﺟﺪﺍ ﮐﻨﻴﺪ ﻭ ﭼﮏ ﮐﻨﻴﺪ ﮐﻪ ﺁﻳﺎ ﺧﻄﺎ ﺑﺮﻃﺮﻑ ﺷﺪﻩ ﻳﺎ ﺧﻴﺮ .
-ﺍﮔﺮ ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩ ﺍﺭﺩ ﺧﻄﺎ ﺩﺭ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻭﺟﻮﺩ ﺩﺍﺷﺖ ،
ﺷﺎﺭﮊﺭ )ﺩﻳﻨﺎﻡ( ﻣﻤﮑﻦ ﺍﺳﺖ ﺩﭼﺎﺭ ﻣﺸﮑﻞ ﺷﺪﻩ ﺑﺎﺷﺪ .
ﻣﻘﺎﺩﻳﺮ Cosφﻭ ﻳﺎ KWﻣﻨﻔﻲ ﻫﺴﺘﻨﺪ ﺑﺎ ﻭﺟﻮﺩ ﺍﻳﻨﻜﻪ ﻗﺮﺍﺋﺖ ﺟﺮﻳﺎﻥ ﺻﺤﻴﺢ ﺍﺳﺖ . •
-ﭘﻼﺭﻳﺘﻪ CTﻫﺎ ﺩﺭﺳﺖ ﻣﺘﺼﻞ ﻧﺸﺪﻩ ﺍﻧﺪ .ﭘﻼﺭﻳﺘﻪ CTﻫﺎ ﺭﺍ ﺗﺼﺤﻴﺢ ﻧﻤﺎﻳﻴﺪ.
ﺧﺮﻭﺟﻲ ﻫﺎﻱ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮﻫﺎﻱ ﺟﺮﻳﺎﻥ ﺭﺍ ﺩﺭ ﺻﻮﺭﺗﻲ ﮐﻪ ﺍﺯ ﺁﻧﻬﺎ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﮐﻨﻴﺪ ،ﺍﺗﺼﺎﻝ ﮐﻮﺗﺎﻩ
ﻧﻤﺎﻳﻴﺪ .
36
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
ﻫﻨﮕﺎﻣﻲ ﻛﻪ ﻓﺮﻣﺎﻥ ﺭﻭﺷﻦ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﺳﻠﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﻓﻌﺎﻝ ﺷﺪﻩ ﺍﻣﺎ •
ﻣﻮﺗﻮﺭ ﺭﻭﺷﻦ ﻧﻤﻲ ﺷﻮﺩ ﻭ LEDﻣﺮﺑﻮﻁ ﺑﻪ Oil Pressuerﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﻣﻲ ﻛﻨﺪ:
-ﻭﺭﻭﺩﻱ Oil Pressureﻛﻨﺘﺮﻟﺮ ﺑﺎ ﻭﻟﺘﺎﮊ ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ ﺗﻐﺬﻳﻪ ﻧﮕﺮﺩﻳﺪﻩ.
Oil Pressure Switch -ﻭﺻﻞ ﻧﻴﺴﺖ .
-ﺳﻴﻢ Oil Pressure Switchﻗﻄﻊ ﺷﺪﻩ ﺍﺳﺖ .
Oil Pressure Switch -ﺧﺮﺍﺏ ﻣﻲ ﺑﺎﺷﺪ .
-ﻛﻨﺘﺎﻛﺖ Oil Pressure Switchﺑﺎ ﺗﺎﺧﻴﺮ ﺑﺴﺘﻪ ﻣﻲ ﺷﻮﺩ .ﺩﺭ ﺻﻮﺭﺕ ﺑﺴﺘﻪ ﺑﻮﺩﻥ ﺍﻳﻦ
ﻛﻨﺘﺎﻛﺖ ﻛﻨﺘﺮﻟﺮ ﺍﺳﺘﺎﺭﺕ ﻣﻲ ﺷﻮﺩ Oil Pressure Switch .ﺑﺎﻳﺪ ﺗﻌﻮﻳﺾ ﮔﺮﺩﺩ .
ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﻭﻗﻮﻉ ﺍﻭﻟﻴﻦ ﺍﺳﺘﺎﺭﺕ ﺭﻭﺷﻦ ﻧﻤﻲ ﺷﻮﺩ ،ﻛﻨﺘﺮﻟﺮ ﺩﻭﺑﺎﺭﻩ ﺍﺳﺘﺎﺭﺕ ﻧﻤﻲ ﺯﻧﺪ ﻭ •
LEDﻣﺮﺑﻮﻁ ﺑﻪ Oil Pressureﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﻛﺮﺩﻩ ﺍﺳﺖ:
-ﻛﻨﺘﺎﻛﺖ Oil Pressure Switchﺑﺎ ﺗﺎﺧﻴﺮ ﺑﺴﺘﻪ ﻣﻲ ﺷﻮﺩ .ﻣﺎﺩﺍﻣﻴﻜﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺟﻮﺩ
ﻛﻨﺘﺎﻛﺖ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺩﺭ ﻭﺭﻭﺩﻱ ﺗﺸﺨﻴﺺ ﺩﺍﺩﻩ ﺍﺳﺖ ﻓﺮﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺩﺍﺩﻩ ﻧﻤﻲ ﺷﻮﺩ.
ﻣﻮﺗﻮﺭ ﺍﺳﺘﺎﺭﺕ ﺯﺩﻩ ﻭ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ﻭﻟﻲ ﺁﻻﺭﻡ Start Failﻓﻌﺎﻝ ﺷﺪﻩ ﻭ ﺳﭙﺲ ﻣﻮﺗﻮﺭ •
ﺧﺎﻣﻮﺵ ﻣﻲ ﺷﻮﺩ.
-ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﻣﺘﺼﻞ ﻧﺸﺪﻩ ،ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎﮊ ACﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻝ Uﻭ ﻧﻮﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺩﺭ
ﭘﺸﺖ ﻛﻨﺘﺮﻟﺮ ﺩﺭ ﺣﺎﻟﻲ ﻛﻪ ﻣﻮﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻧﻤﺎﻳﻴﺪ .ﺍﻣﻜﺎﻥ ﺳﻮﺧﺘﻦ ﻣﺤﺎﻓﻆ ﻓﺎﺯ
ﮊﻧﺮﺍﺗﻮﺭ ﻭﺟﻮﺩ ﺩﺍﺭﺩ .ﺍﻣﻜﺎﻥ ﻗﻄﻊ ﺷﺪﻥ ﺳﻴﻢ ﻓﺎﺯ ﺍﺯ ﻛﻨﺘﺮﻟﺮ ﻭﺟﻮﺩ ﺩﺍﺭﺩ .ﭼﻨﺎﻧﭽﻪ ﻫﻤﻪ ﺍﺭﺗﺒﺎﻃﺎﺕ
ﺻﺤﻴﺢ ﺑﺎﺷﺪ ﻛﻠﻴﻪ ﻓﻴﻮﺯﻫﺎ ﺭﺍ ﻗﻄﻊ ﻧﻤﻮﺩﻩ ﻭ ﺳﭙﺲ ﻣﺠﺪﺩﺍ" ﻓﻴﻮﺯﻫﺎ ﺭﺍ ﺑﻪ ﺗﺮﺗﻴﺐ ﺍﺯ ﻓﻴﻮﺯ ﺗﻐﺬﻳﻪ DCﻭ
ﺩﺭ ﺍﻧﺘﻬﺎ ﻓﻴﻮﺯ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ.
37
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
38
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
-13ﻣﺸﺨﺼﺎﺕ ﻓﻨﻲ
39
ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ DKG217 ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ
-14ﺩﻳﺎﮔﺮﺍﻡ ﻧﺼﺐ
40