‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪DKG - 217‬‬
‫ﻛﻨﺘﺮﻟﺮ ﺍﺳﺘﺎﺭﺕ ﺩﺳﺘﻲ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻫﻤﺮﺍﻩ ﺳﻨﻜﺮﻭﻧﺴﻜﻮﭖ ﻭ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ‬

‫ﺍﻣﻜﺎﻧﺎﺕ‬
‫ﺛﺒﺖ ﺭﺧﺪﺍﺩﻫﺎ ﺑﻪ ﻫﻤﺮﺍﻩ ﺛﺒﺖ ﺯﻣﺎﻥ‬ ‫•‬ ‫ﺍﺳﺘﺎﺭﺕ ﻭ ﺍﺳﺘﭗ ﺩﺳﺘﻲ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫•‬
‫ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺁﻣﺎﺭﻱ‬ ‫•‬ ‫ﮐﻨﺘﺮﻝ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ‬ ‫•‬ ‫ﻣﺤﺎﻓﻈﺖ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫•‬
‫ﭘﻮﺭﺕ ﺳﺮﻳﺎﻝ ‪RS-232‬‬ ‫•‬ ‫ﺍﺧﻄﺎﺭﻫﺎ ﻭ ﺁﻻﺭﻡ ﻫﺎﻱ ﺩﺍﺧﻠﻲ‬ ‫•‬
‫ﻧﻈﺎﺭﺕ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ ﺑﻪ ﻃﺮﻳﻖ‪ :‬ﻣﺤﻠﻲ ‪ ،‬ﺷﺒﮑﻪ ‪ ،‬ﺍﻳﻨﺘﺮﻧﺖ ﻭ ﻣﻮﺩﻡ‬ ‫•‬ ‫ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ ‪ 3‬ﻓﺎﺯ‬ ‫•‬
‫ﻧﻈﺎﺭﺕ ‪ ،‬ﻗﺮﺍﺋﺖ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ‬ ‫•‬ ‫ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ)‪ (CT‬ﮊﻧﺮﺍﺗﻮﺭ ﺗﻚ ﻓﺎﺯ‬ ‫•‬
‫ﻧﻤﺎﻳﺸﮕﺮ ﻫﺎﻱ ‪LED‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺁﻧﺎﻟﻮﮒ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﻱ ‪2 :‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺩﻣﺎﻱ ﻣﺎﻳﻊ ﺧﻨﮏ ﮐﻨﻨﺪﻩ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﻱ ‪5 :‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺗﻮﺍﻥ ﺍﮐﺘﻴﻮ ﮊﻧﺮﺍﺗﻮﺭ ) ﺗﻜﻔﺎﺯ(‬ ‫•‬
‫ﺧﺮﻭﺟﻲ ﻫﺎﻱ ﺭﻟﻪ ﺍﻱ ﻗﺎﺑﻞ ﭘﻴﮑﺮﺑﻨﺪﻱ ‪2 :‬‬ ‫•‬ ‫ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺿﺮﻳﺐ ﺗﻮﺍﻥ ﻣﻮﺗﻮﺭ ) ﺗﻜﻔﺎﺯ(‬ ‫•‬
‫ﻣﺠﻤﻮﻉ ﺧﺮﻭﺟﻲ ﻫﺎﻱ ﺭﻟﻪ ﺍﻱ ‪5:‬‬ ‫•‬ ‫ﻧﺸﺎﻧﮕﺮ ﺩﺭﺧﻮﺍﺳﺖ ﺗﻌﻤﻴﺮ ﺩﻭﺭﻩ ﺍﻱ‬ ‫•‬
‫ﻗﺎﺑﻠﻴﺖ ﮔﺴﺘﺮﺵ ﻭﺭﻭﺩﻱ ﻭ ﺧﺮﻭﺟﻲ ﻫﺎ‬ ‫•‬ ‫ﺷﻤﺎﺭﻧﺪﻩ ﺳﺎﻋﺖ ﻛﺎﺭ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﻗﻄﻊ ﺍﺳﺘﺎﺭﺕ‬ ‫•‬ ‫ﻗﺎﺑﻠﻴﺖ ﺍﺳﺘﺎﺭﺕ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ‬ ‫•‬
‫ﻧﺸﻠﻦ ﺩﻫﻨﺪﻩ ﺳﻨﻜﺮﻭﻧﺴﻜﻮﭖ ﺑﻮﺳﻴﻠﻪ ‪LED‬‬ ‫•‬ ‫ﻣﺼﺮﻑ ﺗﻮﺍﻥ ﺻﻔﺮ ﺩﺭ ﺣﺎﻟﺖ ﺑﻴﻜﺎﺭﻱ‬ ‫•‬
‫• ﻭﺭﻭﺩﻱ ﻭﻟﺘﺎﮊ ﺗﻜﻔﺎﺯ ﺑﺎﺱ ﺑﺎﺭ‬ ‫• ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺗﻐﻴﻴﺮﺍﺕ ﻭﻟﺘﺎﮊ ‪ ،‬ﻓﺮﻛﺎﻧﺲ ﻭ‬
‫ﺿﺮﻳﺐ ﺗﻮﺍﻥ ﺟﻬﺖ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ‬
‫‪1‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻓﻬﺮﺳﺖ‬

‫‪ -1‬ﻧﺼﺐ‬
‫‪ 1-1‬ﻣﻌﺮﻓﻲ ﻛﻨﺘﺮﻟﺮ‬
‫‪ 1-2‬ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ‬
‫‪ 1- 3‬ﺳﻴﻢ ﻛﺸﻲ ﻛﻨﺘﺮﻟﺮ‬
‫‪ -2‬ﻭﺭﻭﺩﻱ ﻫﺎ ﻭ ﺧﺮﻭﺟﻲ ﻫﺎ‬
‫‪ -3‬ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ‬
‫‪ LED 3-1‬ﻫﺎﻱ ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ‬
‫‪ 3-2‬ﻧﻤﺎﻳﺸﮕﺮ ﺩﻳﺠﻴﺘﺎﻟﻲ‬
‫‪ -4‬ﺁﻻﺭﻡ ﻫﺎ ﻭ ﻫﺸﺪﺍﺭﻫﺎ‬
‫‪ -5‬ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﻴﺎﺗﻲ‬
‫‪ -6‬ﺩﻳﮕﺮ ﺧﺼﻮﺻﻴﺎﺕ‬
‫‪ 6-1‬ﻋﻤﻠﮑﺮﺩ ﺑﻪ ﺻﻮﺭﺕ ‪Remote Start‬‬
‫‪ 6-2‬ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ‬
‫‪ 6-3‬ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ‬
‫‪ 6-4‬ﮔﺮﻡ ﻛﻦ ﻣﻮﺗﻮﺭ‬
‫‪ 6-5‬ﻧﻤﺎﻳﺸﮕﺮ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ‬
‫‪ 6-6‬ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ‬
‫‪ 6-7‬ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ‬
‫‪ 6-8‬ﻣﺎﻧﻴﺘﻮﺭﻳﻨﮓ ﻭ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ‬
‫‪ - 7‬ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺁﻣﺎﺭﻱ‬
‫‪ -8‬ﻧﮕﻬﺪﺍﺭﻱ‬

‫‪2‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻓﻬﺮﺳﺖ‬

‫‪ -9‬ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻛﻨﺘﺮﻟﺮ‬


‫‪ -10‬ﺭﻓﻊ ﻋﻴﺐ‬
‫‪ -11‬ﺍﻋﻼﻡ ﺗﻄﺎﺑﻖ ﻫﺎ‬
‫‪ -12‬ﻣﺸﺨﺼﺎﺕ ﻓﻨﻲ‬
‫‪ -13‬ﺩﻳﺎﮔﺮﺍﻡ ﻧﺼﺐ‬
‫‪ -14‬ﻧﻘﺸﻪ ﻧﺼﺐ‬

‫ﺧﻮﺍﻫﺸﻤﻨﺪ ﺍﺳﺖ ﺟﻬﺖ ﺩﺭﻳﺎﻓﺖ ﺍﻃﻼﻋﺎﺕ ﺑﻴﺸﺘﺮ ﺑﺎ ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ ﻧﻤﺎﻳﻨﺪﮔﻲ‬
‫ﺍﻧﺤﺼﺎﺭﻱ ﻣﺤﺼﻮﻻﺕ ‪ DATACOM‬ﺗﺮﻛﻴﻪ ﺩﺭ ﺍﻳﺮﺍﻥ ﻭ ﻣﻨﻄﻘﻪ ﺧﻠﻴﺞ ﻓﺎﺭﺱ‬
‫ﺗﻤﺎﺱ ﺣﺎﺻﻞ ﻓﺮﻣﺎﻳﻴﺪ‪.‬‬
‫ﺗﻠﻔﻦ ‪021-22883169 – 70:‬‬
‫ﭘﺴﺖ ﺍﻟﻜﺘﺮﻭﻧﻴﻜﻲ ‪sales@dornamehr.com :‬‬

‫‪3‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ 1-1‬ﻣﻌﺮﻓﻲ ﻛﻨﺘﺮﻟﺮ‬

‫ﺳﻴﺴﺘﻢ ﺍﺭﺍﺋﻪ ﺷﺪﻩ ﮐﻨﺘﺮﻝ ﻭ ﺣﻔﺎﻇﺖ ﺍﺯ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﺮ ﻋﻬﺪﻩ ﺩﺍﺭﺩ ‪ .‬ﮐﺎﺭﺑﺮﻱ ﻭ ﻧﺼﺐ ﻳﻮﻧﻴﺖ‬
‫ﻃﺮﺍﺣﻲ ﺷﺪﻩ ﺑﺴﻴﺎﺭ ﺭﺍﺣﺖ ﻣﻲ ﺑﺎﺷﺪ ﻭ ﻣﻌﻤﻮﻻ ﻧﻴﺎﺯﻱ ﺑﻪ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺁﻥ ﻭﺟﻮﺩ ﻧﺪﺍﺭﺩ ﻭ ﻣﻘﺎﺩﻳﺮ ﭘﻴﺶ‬
‫ﻓﺮﺽ ﺁﻥ ﺑﺮﺍﻱ ﺑﻴﺸﺘﺮ ﮐﺎﺭﺑﺮﺩﻫﺎ ﻣﻨﺎﺳﺐ ﻣﻲ ﺑﺎﺷﻨﺪ ‪ .‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ‪،‬‬
‫ﮐﻨﺘﺮﻝ ﮐﺎﻣﻞ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﻣﻤﮑﻦ ﻣﻲ ﺳﺎﺯﺩ ‪ .‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺁﻥ ﺑﺮ ﺭﻭﻱ ﺣﺎﻓﻈﻪ‬
‫ﻣﻮﻗﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻣﻲ ﺷﻮﻧﺪ ‪ ،‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﺑﺮﻧﺎﻣﻪ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺫﺧﻴﺮﻩ ﺷﺪﻩ ﻭ ﺣﺘﻲ‬
‫ﺩﺭ ﺻﻮﺭﺕ ﻗﻄﻌﻲ ﻛﺎﻣﻞ ﺑﺮﻕ ﺑﺎﻗﻲ ﺧﻮﺍﻫﺪ ﻣﺎﻧﺪ ‪.‬‬

‫‪ -‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﻗﺎﺑﻞ ﺍﻧﺪﺍﺯﻱ ﮔﻴﺮﻱ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ ‪:‬‬


‫‪ -‬ﻭﻟﺘﺎﮊﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﻧﻮﻝ‬
‫‪ -‬ﻭﻟﺘﺎﮊﻓﺎﺯ ‪ V‬ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﻧﻮﻝ‬
‫‪ -‬ﻭﻟﺘﺎﮊﻓﺎﺯ ‪ W‬ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﻧﻮﻝ‬
‫‪ -‬ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﺟﺮﻳﺎﻥ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ KW -‬ﮊﻧﺮﺍﺗﻮﺭ ﻓﺎﺯ‪U‬‬
‫‪ Cos ø‬ﮊﻧﺮﺍﺗﻮﺭ ﻓﺎﺯ‪U‬‬ ‫‪-‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ‬
‫‪ -‬ﺩﻣﺎﻱ ﺳﺮﺩﮐﻨﻨﺪﻩ‬
‫‪ -‬ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ‬
‫‪ -‬ﺍﺧﺘﻼﻑ ﻓﺮﻛﺎﻧﺲ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪U‬‬
‫‪ -‬ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪U‬‬
‫‪ -‬ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪U‬‬

‫‪4‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ 1-2‬ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪:‬‬


‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺑﺮﺍﻱ ﻧﺼﺐ ﺑﻪ ﺻﻮﺭﺕ ﺗﺎﺑﻠﻮﻳﻲ ﻃﺮﺍﺣﻲ ﺷﺪﻩ ﺍﺳﺖ ﻭ ﮐﺎﺭﺑﺮ ﻧﺒﺎﻳﺪ ﺑﻪ ﺟﺰ ﻗﺴﻤﺖ‬
‫ﺟﻠﻮﻱ ﻛﻨﺘﺮﻟﺮ ﺑﻪ ﺑﻘﻴﻪ ﺍﺟﺰﺍﺀ ﺩﺳﺘﺮﺳﻲ ﺩﺍﺷﺘﻪ ﺑﺎﺷﺪ ‪.‬‬
‫ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﻋﻤﻮﺩﻱ ﺑﺮ ﺭﻭﻱ ﻳﮏ ﺳﻄﺢ ﺗﺨﺖ ﺑﺎﺷﺪ ‪.‬‬
‫ﺍﺑﻌﺎﺩ ﻛﻨﺘﺮﻟﺮ ‪ 151×111‬ﻣﻴﻠﻴﻤﺘﺮ ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﻭ ﻻﺯﻡ ﺍﺳﺖ ﮐﻪ ﺍﻳﻦ ﺍﺑﻌﺎﺩ ﺩﺭ ﺍﺑﺘﺪﺍ ﺑﺮ ﺭﻭﻱ ﺗﺎﺑﻠﻮ‬
‫ﻣﺸﺨﺺ ﮔﺮﺩﻳﺪﻩ ﻭ ﺑﻌﺪ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺟﺎ ﮔﺬﺍﺭﻱ ﻧﻤﺎﻳﻴﺪ‪.‬‬

‫ﻧﮑﺘﻪ ‪ :‬ﺑﺮﺍﻱ ﻋﻤﻠﮑﺮﺩ ﺻﺤﻴﺢ ﻛﻨﺘﺮﻟﺮ ‪ ،‬ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺯﻣﻴﻦ ﺷﻮﺩ ﺩﺭ ﻏﻴﺮ‬
‫ﺍﻳﻦ ﺻﻮﺭﺕ ﻣﻤﻜﻦ ﺍﺳﺖ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻭﻟﺘﺎﮊ ﻭ ﻓﺮﮐﺎﻧﺲ ﺻﺤﻴﺢ ﻧﺒﺎﺷﻨﺪ ‪.‬‬

‫ﺧﺮﻭﺟﻲ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ ‪ 5‬ﺁﻣﭙﺮ ﺑﺎﺷﺪ ‪ ،‬ﺑﺎﺯﻩ ﺟﺮﻳﺎﻥ ﺑﺮ ﺣﺴﺐ ﻧﻴﺎﺯ ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ ﺍﺳﺖ‬
‫)ﺑﻴﻦ ‪ 10/5‬ﻭ ‪ (9000 /5‬ﺧﺮﻭﺟﻲ ﻫﺮ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﻪ ﻭﺳﻴﻠﻪ ﺯﻭﺝ ﮐﺎﺑﻞ ﺟﺪﺍﮔﺎﻧﻪ‬
‫ﺍﻱ ﺑﻪ ﺳﻴﺴﺘﻢ ﻣﺘﺼﻞ ﺷﻮﺩ ﻭ ﺑﺎﺯﻩ ﺗﻐﺬﻳﻪ ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺑﺮﺍﻱ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺣﺪﺍﻗﻞ ‪ 5VA‬ﺑﺎﺷﺪ ﻭ‬
‫ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮﻫﺎﻱ ﺑﺎ ﺩﻗﺖ ‪ 1‬ﺩﺭﺻﺪ ﺗﻮﺻﻴﻪ ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫ﺍﮔﺮ ﻫﻤﻪ ﺳﻨﺴﻮﺭﻫﺎﻱ ﺁﻧﺎﻟﻮﮒ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﺍﺻﻠﻲ ﻭﺻﻞ ﺑﺎﺷﻨﺪ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﻧﻤﺎﻳﺸﮕﺮ ﮐﻤﮑﻲ ﻣﻘﺪﻭﺭ‬
‫ﻧﻤﻲ ﺑﺎﺷﺪ ‪ ،‬ﺑﻪ ﻋﺒﺎﺭﺕ ﺩﻳﮕﺮ ﻛﻨﺘﺮﻟﺮ ﻣﻤﮑﻦ ﺍﺳﺖ ﺻﺪﻣﻪ ﺑﺒﻴﻨﺪ ‪ .‬ﺍﮔﺮ ﻧﻤﺎﻳﺸﮕﺮ ﻓﺸﺎﺭ ﻭ ﺩﻣﺎ ﺩﺭ‬
‫ﮐﻨﺘﺮﻝ ﭘﻨﻞ ﮊﻧﺮﺍﺗﻮﺭ ﻭﺟﻮﺩ ﺩﺍﺭﻧﺪ ‪ ،‬ﺳﻨﺴﻮﺭﻫﺎ ﺭﺍ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺻﻞ ﻧﮑﻨﻴﺪ ‪.‬ﺗﻨﻈﻴﻤﺎﺕ ﮐﺎﺭﺧﺎﻧﻪ ﺟﻬﺖ‬
‫ﺳﻨﺴﻮﺭﻫﺎﻱ ﻛﻨﺘﺮﻟﺮﺍﺯ ﻧﻮﻉ ‪ VDO‬ﻣﻲ ﺑﺎﺷﻨﺪ ‪ .‬ﻟﺬﺍ ﺍﻧﺘﺨﺎﺏ ﺳﻨﺴﻮﺭﻫﺎﻳﻲ ﻣﺘﻔﺎﻭﺕ ﺍﺯ ﻃﺮﻳﻖ ﻣﻨﻮﻱ‬
‫ﻛﻨﺘﺮﻟﺮ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻧﻤﻲ ﺑﺎﺷﺪ ‪ ).‬ﻟﻄﻔﺎ ﻗﺴﻤﺖ ‪ Programming‬ﺭﺍ ﺑﺮﺭﺳﻲ ﻓﺮﻣﺎﺋﻴﺪ(‬

‫ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﻪ ﺻﻮﺭﺕ ﺑﺎﺯ ﻳﺎ ﺑﺴﺘﻪ ﻣﻲ ﺑﺎﺷﻨﺪ ﻭ ﻫﻤﭽﻨﻴﻦ ﻣﻲ ﺗﻮﺍﻧﺪ‬
‫ﺑﻪ ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ ‪ BAT+‬ﻭ ‪ BAT-‬ﻣﺘﺼﻞ ﮔﺮﺩﺩ‪.‬‬
‫ﺗﺮﻣﻴﻨﺎﻝ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﻋﻤﻞ ﺟﺮﻳﺎﻥ ﺗﺤﺮﻳﻚ ﺭﺍ ﻧﻴﺰ ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ ﺑﻨﺎﺑﺮﺍﻳﻦ ﺍﺣﺘﻴﺎﺝ ﺑﻪ ﻻﻣﭗ ﺷﺎﺭﮊ‬
‫ﺧﺎﺭﺟﻲ ﻧﻴﺴﺖ‪.‬‬

‫‪5‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -2‬ﻭﺭﻭﺩﻱ ﻫﺎ ﻭ ﺧﺮﻭﺟﻲ ﻫﺎ ‪:‬‬

‫‪ : RS232-Serial Port‬ﺍﻳﻦ ﮐﺎﻧﮑﺘﻮﺭ ﺟﻬﺖ ﺍﺭﺗﺒﺎﻁ ﺳﺮﻳﺎﻝ ﺑﺮﺍﻱ ﻭﺭﻭﺩﻱ ﻭ ﺧﺮﻭﺟﻲ ﺍﻃﻼﻋﺎﺕ‬
‫ﺑﺮﺍﻱ ﺍﻫﺪﺍﻑ ﻣﺨﺘﻠﻒ ﻣﺎﻧﻨﺪ ﻛﻨﺘﺮﻝ ﻭ ﻧﻤﺎﻳﺶ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ) ‪ (Remote Monitoring‬ﻭﺑﺮﻧﺎﻣﻪ‬
‫ﺭﻳﺰﻱ ﺍﺯ ﺭﺍﻩ ﺩﻭﺭ) ‪ ( Remote Programming‬ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﺪﻩ ﺍﺳﺖ ‪.‬‬

‫‪Term‬‬ ‫‪Function‬‬ ‫‪Technical data‬‬ ‫‪Description‬‬


‫ﺍﻳﻦ ﺧﺮﻭﺟﻲ ﻭﻟﺘﺎﮊ ﻛﻨﺘﺎﻛﺘﻮﺭ ﮊﻧﺮﺍﺗﻮﺭﻫﺎ ﺭﺍ ﺟﻬﺖ ﭘﺎﺭﺍﻟﻞ ﻛﺮﺩﻥ ﺗﺎﻣﻴﻦ ﻣﻲ‬
‫ﻧﻤﺎﻳﺪ‪.‬ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭﻫﺎ ﻳﺎ ﻓﺮﻛﺎﻧﺲ ﺁﻧﻬﺎ ﻭ ﻳﺎ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺁﻧﻬﺎ ﺩﺭ‬
‫‪1‬‬ ‫‪Check Synch‬‬ ‫ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﻧﺴﺒﺖ ﺑﻪ ﺑﺎﺱ ﺑﺎﺭ ﻧﺒﺎﺷﺪ ﺍﻳﻦ ﺭﻟﻪ ﻓﻌﺎﻝ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ﺧﺮﻭﺟﻲ ﺭﻟﻪ ﺍﻱ ‪ 16‬ﺁﻣﭙﺮ‬
‫‪AC‬‬ ‫ﻭ ﭼﻨﺎﻧﭽﻪ ﺑﺎﺱ ﺑﺎﺭ ﺑﺮﻕ ﺩﺍﺭ ﻧﺒﺎﺷﺪ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺑﺎ ﺍﻋﻤﺎﻝ ﺳﻴﮕﻨﺎﻝ ﺑﻪ‬
‫ﻭﺭﻭﺩﻱ ‪ Dead Bus Enable‬ﺣﺬﻑ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬
‫‪2‬‬ ‫‪U‬‬ ‫ﻓﺎﺯﻫﺎﻱ ﻭﺭﻭﺩﻱ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫ﻓﺎﺯﻫﺎﻱ ﻭﺭﻭﺩﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻫﺎ ﻣﺘﺼﻞ ﻧﻤﺎﺋﻴﺪ ﻭ ﻣﺤﺪﻭﺩﻩ ﺑﺎﻻ ﻭ‬
‫‪3‬‬ ‫‪V‬‬ ‫‪ 300-0‬ﻭﻟﺖ ‪AC‬‬ ‫ﭘﺎﻳﻴﻦ ﮊﻧﺮﺍﺗﻮﺭ ﻧﻴﺰ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫‪4‬‬ ‫‪W‬‬
‫‪Generator‬‬ ‫ﻭﺭﻭﺩﻱ ‪ 0‬ﺗﺎ ‪ 300‬ﻭﻟﺖ‬ ‫ﺗﺮﻣﻴﻨﺎﻝ ﺧﻨﺜﻲ ﺑﺮﺍﻱ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪5‬‬ ‫‪Neutral‬‬
‫‪AC‬‬
‫‪Bus Bar‬‬ ‫ﻭﺭﻭﺩﻱ ‪ 0‬ﺗﺎ ‪ 300‬ﻭﻟﺖ‬ ‫ﺗﺮﻣﻴﻨﺎﻝ ﺧﻨﺜﻲ ﺑﺮﺍﻱ ﻓﺎﺯﻫﺎﻱ ﺑﺎﺱ ﺑﺎﺭ‬
‫‪6‬‬ ‫‪Neutral‬‬
‫‪AC‬‬
‫ﻭﺭﻭﺩﻱ ﻓﺎﺯ ﺑﺎﺱ ﺑﺎﺭ ‪ 0‬ﺗﺎ‬ ‫ﻭﺭﻭﺩﻱ ﺟﻬﺖ ﺍﺗﺼﺎﻝ ﻓﺎﺯ ﺑﺎﺱ ﺑﺎﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺎﻻ ﻭ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﻗﺎﺑﻞ‬
‫‪7‬‬ ‫‪R‬‬
‫‪ 300‬ﻭﻟﺖ ‪AC‬‬ ‫ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻣﻲ ﺑﺎﺷﺪ‬
‫‪8‬‬ ‫‪Not Used‬‬
‫ﻭﻟﺘﺎﮊ ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﺟﻬﺖ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﻭ ﻓﻌﺎﻝ ﻛﺮﺩﻥ ﻋﻤﻞ‬
‫ﺳﻨﻜﺮﻭﻥ ﺍﻋﻤﺎﻝ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬
‫‪9‬‬ ‫‪Remote Start‬‬ ‫ﻭﺭﻭﺩﻱ‬ ‫ﻫﺸﺪﺍﺭ‪:‬‬
‫ﻭﻟﺘﺎﮊ ﺑﻴﺶ ﺍﺯ ﻭﻟﺘﺎﮊ ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ ﺑﻪ ﺍﻳﻦ ﻣﺤﺪﻭﺩﻩ ﺍﻋﻤﺎﻝ ﻧﻨﻤﺎﻳﻴﺪ ﺩﺭ ﻏﻴﺮ ﺍﻳﻦ‬
‫ﺻﻮﺭﺕ ﺁﺳﻴﺐ ﺟﺪﻱ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺍﺭﺩ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬
‫ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺘﺼﻞ ﻣﯽ ﮔﺮﺩﺩ ‪ .‬ﺳﻨﺴﻮﺭ ﺭﺍ ﺑﻪ ﻭﺳﻴﻠﻪ ﯼ‬
‫‪Oil Pressure‬‬ ‫ﻭﺭﻭﺩﯼ ‪ 0‬ﺗﺎ ‪ 5000‬ﺍﻫﻢ‬ ‫ﺩﻳﮕﺮﯼ ﻣﺘﺼﻞ ﻧﻨﻤﺎﺋﻴﺪ ‪ .‬ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺸﺨﺼﻪ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺩﺍﺷﺘﻪ ﻭ ﺍﻧﻮﺍﻉ‬
‫‪10‬‬
‫‪Sender‬‬
‫ﺳﻨﺴﻮﺭﻫﺎ ﻧﻴﺰ ﺑﻪ ﺁﻥ ﻭﺻﻞ ﻣﯽ ﺷﻮﻧﺪ ‪.‬‬
‫ﺳﻨﺴﻮﺭ ﺩﻣﺎﯼ ﺁﺏ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺘﺼﻞ ﻣﯽ ﮔﺮﺩﺩ ‪ .‬ﺳﻨﺴﻮﺭ ﺭﺍ ﺑﻪ ﻭﺳﻴﻠﻪ‬
‫‪11‬‬ ‫‪Coolant Temp‬‬ ‫ﻭﺭﻭﺩﯼ ‪ 0‬ﺗﺎ ‪ 5000‬ﺍﻫﻢ‬ ‫ﺩﻳﮕﺮﯼ ﻣﺘﺼﻞ ﻧﻨﻤﺎﺋﻴﺪ ‪ .‬ﺍﻳﻦ ﻭﺭﻭﺩﯼ ﻣﺸﺨﺼﻪ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﯼ ﺩﺍﺷﺘﻪ ﻭ ﺍﻧﻮﺍﻉ‬
‫‪Sender‬‬
‫ﺳﻨﺴﻮﺭﻫﺎ ﻧﻴﺰ ﺑﻪ ﺁﻥ ﻣﺘﺼﻞ ﻣﯽ ﮔﺮﺩﺩ ‪.‬‬

‫‪6‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Term‬‬ ‫‪Function‬‬ ‫‪Technical data‬‬ ‫‪Description‬‬

‫‪Battery‬‬ ‫‪ 12+‬ﻳﺎ‪ 24‬ﻭﻟﺖ‪DC‬‬ ‫ﺗﺮﻣﻴﻨﺎﻝ ﻣﺜﺒﺖ ﻣﻨﺒﻊ ‪ DC‬ﺑﺎﻳﺪ ﺑﻪ ﺍﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ ﻣﺘﺼﻞ ﮔﺮﺩﺩ ﻭ ﻛﻨﺘﺮﻟﺮ ﺑﺎ ﻫﺮ ﺩﻭ‬
‫‪12‬‬ ‫‪Positive‬‬
‫ﺑﺎﻃﺮﻱ ‪ 12‬ﻳﺎ ‪ 24‬ﻭﻟﺖ ﻣﻲ ﺗﻮﺍﻧﺪ ﮐﺎﺭ ﮐﻨﺪ ‪.‬‬

‫‪13‬‬ ‫‪Ground‬‬ ‫‪ 0‬ﻭﻟﺖ ‪DC‬‬ ‫ﺍﺗﺼﺎﻝ ﻣﻨﻔﯽ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ‬

‫‪Relay-1‬‬ ‫ﺧﺮﻭﺟﻲ‬ ‫ﺍﻳﻦ ﺭﻟﻪ ﻓﺎﻧﮑﺸﻦ ﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺍﺷﺘﻪ ﮐﻪ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ‬
‫‪14‬‬ ‫)‪(Stop relay‬‬
‫‪10A/28VDC‬‬ ‫ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫ﺭﻟﻪ ﺗﻮﻗﻒ‬
‫‪Start Relay‬‬ ‫ﺧﺮﻭﺟﻲ‬ ‫ﺍﻳﻦ ﺭﻟﻪ ﻋﻤﻞ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﺭﺍ ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ‪.‬‬
‫‪15‬‬ ‫‪10A/28VDC‬‬
‫‪Fuel Relay‬‬ ‫ﺧﺮﻭﺟﻲ‬ ‫ﺍﻳﻦ ﺭﻟﻪ ﺑﺮﺍﻱ ﮐﻨﺘﺮﻝ ﺳﻮﻟﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ‬
‫‪16‬‬ ‫‪10A/28VDC‬‬ ‫ﺩﺍﺧﻠﻲ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ ‪ 16‬ﺟﻬﺖ ﺗﻐﺬﻳﻪ ﺟﺮﻳﺎﻥ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﻣﺘﺼﻞ ﻣﻲ ﺑﺎﺷﺪ ‪.‬‬

‫‪Charge‬‬ ‫ﻭﺭﻭﺩﻱ ﻭ ﺧﺮﻭﺟﻲ‬ ‫ﺗﺮﻣﻴﻨﺎﻝ ‪ D+‬ﺍﺯ ﺷﺎﺭﮊﺭ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻧﺼﺐ ﻧﻤﺎﺋﻴﺪ ﺍﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ ﻋﻤﻞ‬
‫‪17‬‬ ‫ﺗﻐﺬﻳﻪ ﺟﺮﻳﺎﻥ ﺗﺤﺮﻳﻚ ﺭﺍ ﺍﻧﺠﺎﻡ ﺩﺍﺩﻩ ﻭ ﻭﻟﺘﺎﮊ ﺷﺎﺭﮊ ﺩﻳﻨﺎﻡ ﺭﺍ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻣﻲ‬
‫ﻛﻨﺪ ‪.‬‬
‫‪18‬‬ ‫‪Relay-2‬‬ ‫ﺧﺮﻭﺟﻲ‬ ‫ﺍﻳﻦ ﺭﻟﻪ ﻓﺎﻧﮑﺸﻦ ﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺍﺷﺘﻪ ﮐﻪ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ‬
‫)‪(Alarm relay‬‬
‫‪10A/28VDC‬‬ ‫ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫ﺭﻟﻪ ﺧﻄﺎ‬
‫‪19‬‬ ‫‪Low Oil‬‬ ‫ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻫﺎ ﺧﺼﻮﺻﻴﺖ ﺑﺮﻧﺎﻣﻪ ﭘﺬﻳﺮﻱ ﺭﺍ ﺗﻮﺳﻂ ﻣﻨﻮﻱ ‪ Program‬ﺩﺍﺭﺍ‬
‫‪Pressure‬‬
‫ﻣﻲ ﺑﺎﺷﻨﺪ ‪ .‬ﻫﺮ ﻭﺭﻭﺩﻱ ﻣﻲ ﺗﻮﺍﻧﺪ ﺑﻪ ﺻﻮﺭﺕ ﮐﻨﺘﺎﮐﺖ ‪Normally Close‬‬
‫‪20‬‬ ‫‪High Temp‬‬
‫ﻳﺎ‪ Normally Open‬ﻓﻌﺎﻝ ﺷﻮﺩ ﻭ ﺑﻪ ﻫﺮ ﻳﮏ ﺍﺯﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ ) ‪Battery+‬‬
‫‪21‬‬ ‫‪Dead Bus‬‬
‫‪Enable‬‬ ‫ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ‬ ‫ﻳﺎ ‪ (Battery-‬ﻣﺘﺼﻞ ﮔﺮﺩﺩ ﻭ ﻧﺤﻮﻩ ﺍﺗﺼﺎﻝ ﺍﺯ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪.‬‬
‫‪22‬‬ ‫‪Emergency‬‬ ‫ﺑﺮﺍﻱ ﺟﺰﺋﻴﺎﺕ ﺑﻴﺸﺘﺮ ﮐﺎﻓﻲ ﺍﺳﺖ ﺑﻪ ﻗﺴﻤﺖ ‪ Programming‬ﻣﺮﺍﺟﻌﻪ‬
‫‪Stop‬‬
‫‪23‬‬ ‫‪Spare‬‬ ‫ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫‪24‬‬ ‫‪Progam Lock‬‬


‫ﺗﺮﻣﻴﻨﺎﻟﻬﺎﻱ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻫﺎ ﻣﺘﺼﻞ ﻣﻲ‬
‫ﻧﻤﺎﻳﻴﻢ ‪ .‬ﻳﮏ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﺭﺍ ﺑﻪ ﺩﻳﮕﺮ ﻭﺳﺎﻳﻞ ﻣﺘﺼﻞ ﻧﻨﻤﺎﺋﻴﺪ ‪ .‬ﺑﻪ ﻋﺒﺎﺭﺕ‬
‫‪25‬‬ ‫‪CURR U+‬‬
‫ﺩﻳﮕﺮ ﺑﺮﺍﻱ ﻛﻨﺘﺮﻟﺮ ﺧﻄﺎ )‪ (Fail‬ﺍﺗﻔﺎﻕ ﻣﻲ ﺍﻓﺘﺪ ‪ .‬ﺗﺮﻣﻴﻨﺎﻝ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ‬
‫ﺭﺍ ﺑﻪ ﺗﺮﻣﻴﻨﺎﻝ ﻣﺘﻨﺎﺳﺐ ﺑﻪ ﺁﻥ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ ﻭﺍﺯ ﺯﻣﻴﻦ ﻛﺮﺩﻥ) ‪ (Grounding‬ﺟﺮﻳﺎﻥ ‪5A-AC‬‬
‫ﻭ ﺗﺮﻣﻴﻨﺎﻝ ﻣﺸﺘﺮﮎ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻨﻤﺎﻳﻴﺪ‪ .‬ﺑﮑﺎﺭ ﺑﺮﺩﻥ ﺍﺗﺼﺎﻻﺕ ﺩﺭﺳﺖ ﺣﻴﺎﺗﻲ ﺍﺳﺖ‬
‫‪ ،‬ﺍﮔﺮ ﺗﻮﺍﻥ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻣﻨﻔﻲ ﺑﻮﺩ ﺟﻬﺖ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ‬
‫‪26‬‬ ‫‪CURR U-‬‬
‫) ‪ (Current Transformer‬ﺭﺍ ﺗﻐﻴﻴﺮﺩﻫﻴﺪ ‪ .‬ﺳﻴﻢ ﭘﻴﭻ ﺛﺎﻧﻮﻳﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ‬
‫ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ ‪ 5A‬ﺁﻣﭙﺮﺑﺎﺷﺪ‪ .‬ﺑﻪ ﻃﻮﺭ ﻣﺜﺎﻝ ) ‪( 200/5‬‬

‫‪7‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ LED 3-1‬ﻫﺎﻱ ﺻﻔﺤﻪ ﻧﻤﺎﻳﺶ ‪:‬‬

‫ﻛﻨﺘﺮﻟﺮ ﺩﺍﺭﺍﻱ ‪ 30‬ﻋﺪﺩ ‪ LED‬ﺍﺳﺖ ﻛﻪ ﺑﻪ ‪ 4‬ﮔﺮﻭﻩ ﺗﻘﺴﻴﻢ ﺷﺪﻩ ﺍﻧﺪ‪.‬‬


‫‪ :Group 1‬ﺳﻨﻜﺮﻭﻧﺴﻜﻮﭖ ‪ ،‬ﺍﻳﻦ ﮔﺮﻭﻩ ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ﻟﺤﻈﻪ ﺍﻱ ﺯﺍﻭﻳﻪ ﻓﺎﺯ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻭﻟﺘﺎﮊ ﻓﺎﺯ‬
‫‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫‪ : Group 2‬ﻭﺿﻌﻴﺖ ‪ ،‬ﺍﻳﻦ ﮔﺮﻭﻩ ﻧﺸﺎﻥ ﺩﻫﻨﺪﻩ ﻭﺿﻌﻴﺖ ﺟﺮﻳﺎﻥ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭﻭ ﺧﺮﻭﺟﻲ‬
‫ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫‪ Warning & Alarms :Group 3‬ﺍﻋﻼﻡ ﻭﺿﻌﻴﺖ ﻫﺸﺪﺍﺭ‪ ،‬ﺍﻳﻦ ﮔﺮﻭﻩ ﻭﺟﻮﺩ ﻭﺿﻌﻴﺖ ﻏﻴﺮ‬
‫ﻋﺎﺩﻱ ﺭﺍ ﺩﺭ ﻃﻮﻝ ﻋﻤﻠﮑﺮﺩ ﺭﺍ ﻧﺸﺎﻥ ﻣﻲ ﺩﻫﺪ ‪.‬‬
‫‪ :Group 4‬ﺍﻳﻦ ﮔﺮﻭﻩ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺫﻳﻞ ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ‪.‬‬

‫‪Function‬‬ ‫‪Color‬‬ ‫‪Description‬‬


‫‪Synchroscope‬‬ ‫ﻗﺮﻣﺰ ﻭ ﺯﺭﺩ‬ ‫ﻭﻗﺘﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﺑﺎﺷﻨﺪ‬
‫‪ LED‬ﻫﺎﻱ ﺑﺎﺱ ﺑﺎﺭ ﺑﻪ ﺻﻮﺭﺕ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﺩﺭ ﺍﻳﻦ‬
‫ﺣﺎﻟﺖ ﻓﻘﻂ ﻳﻚ ‪ LED‬ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ﻛﻪ ﻧﺸﺎﻧﮕﺮ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﻴﻦ‬
‫ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪U‬ﮊﻧﺮﺍﺗﻮﺭ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫ﭼﻨﺎﻧﭽﻪ ‪LED‬ﻫﺎﻱ ﺳﻤﺖ ﺭﺍﺳﺖ ﺭﻭﺷﻦ ﺑﺎﺷﺪ ﻧﺸﺎﻧﮕﺮ ﭘﻴﺶ ﻓﺎﺯ ﺑﻮﺩﻥ ﻓﺎﺯ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﺑﺎﺱ ﺑﺎﺭ ﻣﻲ ﺑﺎﺷﺪ ﻭ ﺍﮔﺮ ‪LED‬ﻫﺎ ﻱ ﺳﻤﺖ ﭼﭗ ﺭﻭﺷﻦ‬
‫ﺑﺎﺷﺪ ﻧﺸﺎﻧﮕﺮ ﭘﺲ ﻓﺎﺯ ﺑﻮﺩﻥ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﺑﺎﺱ ﺑﺎﺭ ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﺣﺮﻛﺖ‬
‫ﺧﺎﻣﻮﺵ ﺭﻭﺷﻦ ﺷﺪﻥ ‪ LED‬ﻫﺎ ﺍﺯ ﭼﭗ ﺑﻪ ﺭﺍﺳﺖ ﻧﺸﺎﻧﮕﺮ ﺑﺎﻻﺗﺮ ﺑﻮﺩﻥ‬
‫ﻓﺮﻛﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﺣﺮﻛﺖ ﺭﺍﺳﺖ ﺑﻪ ﭼﭗ ‪ LED‬ﻫﺎ‬
‫ﻧﺸﺎﻧﮕﺮ ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﻓﺮﻛﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺴﺒﺖ ﺑﻪ ﻓﺮﻛﺎﻧﺲ ﺑﺎﺱ ﺑﺎﺭ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬

‫‪Generator‬‬ ‫ﺯﺭﺩ‬ ‫ﺍﻳﻦ ‪ LED‬ﺑﻪ ﺻﻮﺭﺕ ﭼﺸﻤﻚ ﺯﻥ ﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ﻣﻲ‬
‫ﺑﺎﺷﺪ ﻭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰ ﻱ ﺷﺪﻩ ﺑﺎﺷﺪ‬
‫ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ‪.‬‬
‫‪Bus‬‬ ‫ﺯﺭﺩ‬ ‫ﺍﻳﻦ ‪ LED‬ﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺑﺎﺷﺪ‬
‫ﺭﻭﺷﻦ ﻣﻲ ﮔﺮﺩﺩ ‪.‬‬
‫‪Synchronized‬‬ ‫ﺯﺭﺩ‬ ‫ﺍﻳﻦ ‪LED‬ﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻓﻌﺎﻝ ﺍﺳﺖ ﺑﻪ ﺻﻮﺭﺕ‬
‫ﭼﺸﻤﻚ ﺯﻥ ﺑﻮﺩﻩ ﻭ ﻫﻨﮕﺎﻣﻲ ﻛﻪ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﺭﻭﺷﻦ‬
‫ﻣﻲ ﻣﺎﻧﺪ‪.‬‬

‫‪8‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Function‬‬ ‫‪Color‬‬ ‫‪Description‬‬
‫‪ )Red‬ﺭﻧﮓ ﻗﺮﻣﺰ (‬ ‫ﺗﻌﻤﻴﺮﺍﺕ ﺩﻭﺭﻩ ﺍﻱ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻭ ‪ LED‬ﭘﺲ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ‬
‫‪Service Request‬‬
‫ﻛﺎﺭﻱ ﻳﺎ ﺑﻌﺪ ﺍﺯ ﺗﻤﺎﻡ ﺷﺪﻥ ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ ﻗﺒﻠﻲ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ‪.‬‬

‫ﭼﻨﺎﻧﭽﻪ ﺧﻄﺎ ﺑﺎﻋﺚ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﮔﺮﺩﺩ ‪ LED‬ﻣﺘﻨﺎﺳﺐ ﺑﺎ ﺧﻄﺎ ﺑﻪ‬
‫ﻃﻮﺭ ﺩﺍﺋﻢ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ﻭ ﺍﮔﺮ ﺣﺎﻟﺖ ﻫﺸﺪﺍﺭ ﺑﻮﺟﻮﺩ ﺁﻣﺪﻩ ﺑﺎﺷﺪ ‪LED‬‬
‫ﺁﻻﺭﻡ ﻣﺮﺑﻮﻃﻪ ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ ‪ .‬ﺁﻻﺭﻡ ﻫﺎ ﺑﺮ ﭘﺎﻳﻪ‬
‫‪Alarm Group‬‬ ‫‪ )Red‬ﺭﻧﮓ ﻗﺮﻣﺰ (‬ ‫ﺍﻭﻟﻮﻳﺖ ﺑﻨﺪﻱ ﻋﻤﻞ ﺧﻮﺍﻫﻨﺪ ﻧﻤﻮﺩ ﺑﺎ ﺑﻮﺟﻮﺩ ﺁﻣﺪﻥ ﻳﮏ ﺧﻄﺎ ‪ ،‬ﺧﻄﺎﻫﺎﻱ ﺑﺎ‬
‫ﺍﻭﻟﻮﻳﺖ ﺑﺮﺍﺑﺮ ﻳﺎ ﭘﺎﻳﻴﻦ ﺗﺮ ﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﻨﺪ ﺷﺪ‪.‬‬

‫ﺍﻳﻦ ﮔﺮﻭﻩ ﻧﻤﺎﻳﺸﮕﺮﻭﺍﺣﺪﻫﺎﻱ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺑﺮ ﺭﻭﻱ ﻧﻤﺎﻳﺸﮕﺮ‬


‫ﻣﻲ ﺑﺎﺷﺪ‪ .‬ﻫﻨﮕﺎﻣﻴﮑﻪ ﻣﻮﺗﻮﺭ ﺩﺭ ﺣﺎﻟﺖ ﻛﺎﺭﺍﺳﺖ ﺍﻳﻦ ﻭﺍﺣﺪ ﻓﺮﮐﺎﻧﺲ‬
‫‪Unit Group‬‬ ‫‪ )Red‬ﺭﻧﮓ ﻗﺮﻣﺰ (‬ ‫ﮊﻧﺮﺍﺗﻮﺭﺭﺍ ﻧﺸﺎﻥ ﻣﻲ ﺩﻫﺪ ‪ ،‬ﺩﺭ ﻏﻴﺮ ﺍﻳﻦ ﺻﻮﺭﺕ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺭﺍ ﻧﻤﺎﻳﺶ‬
‫ﺧﻮﺍﻫﺪ ﺩﺍﺩ ﻭ ﻣﻘﺎﺩﻳﺮ ﻣﺨﺘﻠﻒ ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﻗﺎﺑﻞ ﻧﻤﺎﻳﺶ ﻣﻲ‬
‫ﺑﺎﺷﻨﺪ ‪.‬‬

‫‪ 3-2‬ﻧﻤﺎﻳﺸﮕﺮﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ‬
‫ﻛﻨﺘﺮﻟﺮ ﺩﺍﺭﺍﻱ ‪ 3‬ﻋﺪﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ Seven Segment‬ﺍﺳﺖ ‪ ،‬ﺁﻧﻬﺎ ﻧﻤﺎﻳﺸﮕﺮ ‪:‬‬
‫‪ -‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ‬
‫‪ -‬ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺳﺮﻭﻳﺲ‬
‫‪ -‬ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ‬
‫‪ -‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ‬
‫ﺑﺎ ﺩﮐﻤﻪ ‪ Menu‬ﻣﻲ ﺗﻮﺍﻥ ﺻﻔﺤﺎﺕ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭ ﻫﺮ ﮔﺮﻭﻩ ﺭﺍ ﻋﻮﺽ ﻧﻤﻮﺩ ‪.‬‬
‫ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﺻﻔﺤﻪ ﮔﺮﻭﻫﻬﺎﻱ ﺑﻌﺪﻱ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪.‬‬

‫‪ -‬ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﺑﺎﺱ ﺑﺎﺭ ﻧﺴﺒﺖ ﺑﻪ ﻧﻮﻝ‬


‫‪ -‬ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ )‪ (U-V-W‬ﻧﺴﺒﺖ ﺑﻪ ﻧﻮﻝ‬
‫‪ -‬ﺟﺮﻳﺎﻥ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﻓﺮﻛﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ‪ ،‬ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬

‫‪9‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -‬ﺗﻮﺍﻥ ﺍﻛﺘﻴﻮ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬


‫‪ -‬ﻓﺸﺎﺭ ﺭﻭﻏﻦ ) ﺑﺎﺭ(‬
‫‪ -‬ﺣﺮﺍﺭﺕ ﺁﺏ ) ﺳﺎﻧﺘﻴﮕﺮﺍﺩ(‬
‫‪ -‬ﺍﺧﺘﻼﻑ ﻓﺮﻛﺎﻧﺲ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪ -‬ﺍﺧﺘﻼﻑ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﺑﺎ ﻓﺸﺮﺩﻥ ﻭ ﻧﮕﻪ ﺩﺍﺷﺘﻦ ﺩﻛﻤﻪ ‪ Menu‬ﺑﻪ ﻣﺪﺕ ‪ 1‬ﺛﺎﻧﻴﻪ ﻧﻤﺎﻳﺸﮕﺮ ﮔﺮﻭﻩ ﺷﻤﺎﺭﻧﺪﻩ ﺳﺮﻭﻳﺲ ﺭﺍ ﺑﻪ‬
‫ﺻﻮﺭﺕ ﺯﻳﺮ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ‪.‬‬
‫‪ -‬ﺳﺎﻋﺖ ﻛﺎﺭ ﻛﻠﻲ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺳﺎﻋﺖ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ‬

‫‪Alarm & Warning -4‬‬


‫ﺁﻻﺭﻡ ﻫﺎ ﻭﺿﻌﻴﺖ ﻏﻴﺮﻋﺎﺩﻱ ﺭﺍ ﺩﺭﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻧﻤﺎﻳﺶ ﺩﺭﻣﻲ ﺁﻭﺭﻧﺪ ﮐﻪ ﺍﺯﻧﻈﺮﺍﻭﻟﻮﻳﺖ ﺑﻨﺪﻱ ﺑﻪ ‪2‬‬
‫ﻗﺴﻤﺖ ﺗﻘﺴﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ‪:‬‬

‫‪ Alarms -1‬ﺁﻻﺭﻣﻬﺎ ‪ :‬ﺣﺎﻟﺘﻬﺎﻱ ﺯﻳﺮ ﺍﺯ ﻣﻬﻤﺘﺮﻳﻦ ﺩﻻﻳﻞ ﻭ ﻭﺿﻌﻴﺖ ﺧﻄﺎﻫﺎ ﻣﻲ ﺑﺎﺷﻨﺪ‪.‬‬


‫‪ -‬ﺭﻭﺷﻦ ﺑﻮﺩﻥ ﺩﺍﺋﻢ ‪ LED‬ﻣﺮﺑﻮﻃﻪ ﻭﺿﻌﻴﺖ ﺁﻻﺭﻡ ﺭﺍ ﮔﺰﺍﺭﺵ ﻣﻲ ﺩﻫﻨﺪ‬
‫‪ -‬ﻗﻄﻊ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺑﻪ ﻃﻮﺭ ﺁﻧﻲ‬
‫‪ -‬ﺗﻮﻗﻒ ﻓﻮﺭﻱ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﻋﻤﻠﻜﺮﺩ ﺭﻟﻪ ﻫﺎﻱ ﺧﺮﻭﺟﻲ ﺁﮊﻳﺮ ‪ ،‬ﻫﺸﺪﺍﺭ ﻭ ﺧﻄﺎ ﻋﻤﻞ ﮐﻨﻨﺪ ‪) .‬ﺍﮔﺮ ﺍﻳﻦ ﺭﻟﻪ ﻫﺎ ﺩﺭ ﻫﻨﮕﺎﻡ‬
‫ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺍﻧﺘﺨﺎﺏ ﺷﺪﻩ ﺑﺎﺷﻨﺪ(‬

‫‪ Warning -2‬ﻫﺸﺪﺍﺭﻫﺎ ‪:‬ﭼﻨﻴﻦ ﺣﺎﻟﺘﻲ ﺳﺒﺐ‪:‬‬


‫‪ LED -‬ﻣﺮﺑﻮﻃﻪ ﭼﺸﻤﮏ ﺑﺰﻧﻨﺪ ﻋﻤﻠﻜﺮﺩ ﺭﻟﻪ ﻫﺎﻱ ﺧﺮﻭﺟﻲ ﻫﺸﺪﺍﺭ ﻭ ﺧﻄﺎ ﻋﻤﻞ ﮐﻨﻨﺪ ‪) .‬ﺍﮔﺮ‬
‫ﺍﻳﻦ ﺭﻟﻪ ﻫﺎ ﺩﺭ ﻫﻨﮕﺎﻡ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺍﻧﺘﺨﺎﺏ ﺷﺪﻩ ﺑﺎﺷﻨﺪ(‪.‬‬

‫‪10‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫ﺍﮔﺮ ﺩﮐﻤﻪ ‪ Alarm Mute‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ‪ ،‬ﺧﺮﻭﺟﻲ ﺭﻟﻪ ﺁﮊﻳﺮﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﻫﺮ ﭼﻨﺪ‬
‫ﺧﻄﺎﻱ ﻣﺮﺑﻮﻃﻪ ﻭﺟﻮﺩ ﺩﺍﺷﺘﻪ ﻭ ﺑﺎﻋﺚ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻥ ﻋﻤﻠﻜﺮﺩ ﺳﻴﺴﺘﻢ ﺷﻮﺩ‪.‬‬

‫ﺁﻻﺭﻡ ﻫﺎ ﺑﺮ ﺍﺳﺎﺱ ﺍﻭﻟﻮﻳﺖ ﻭﻗﻮﻉ ﭘﺎﺳﺦ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﻧﺪ ‪:‬‬


‫‪ -‬ﺍﮔﺮ ﺧﻄﺎ ﻭﺟﻮﺩ ﺩﺍﺷﺘﻪ ﺑﺎﺷﺪ ‪ ،‬ﺧﻄﺎ ﻫﺎ ﻭ ﻫﺸﺪﺍﺭﻫﺎﻱ ﺯﻳﺮ ﻗﺎﺑﻞ ﻗﺒﻮﻝ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ ‪.‬‬
‫‪ -‬ﺍﮔﺮ ﻫﺸﺪﺍﺭ ﻭﻗﻮﻉ ﻳﺎﻓﺘﻪ ﺑﺎﺷﺪ ‪ ،‬ﻫﺸﺪﺍﺭﻫﺎﻱ ﺯﻳﺮ ﻗﺎﺑﻞ ﻗﺒﻮﻝ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ‪.‬‬
‫ﺁﻻﺭﻡ ﻫﺎ ﻣﻤﮑﻦ ﺍﺳﺖ ﺍﺯ ﻧﻮﻉ ﻗﻔﻞ ﺷﻮﻧﺪﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﮔﺮﺩﻧﺪ ﻭ ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﺩﺭ ﺻﻮﺭﺕ ﺍﺯ ﺑﻴﻦ‬
‫ﺭﻓﺘﻦ ﺁﻻﺭﻡ ‪ ،‬ﺁﻻﺭﻡ ﻫﺎ ﻓﻌﺎﻝ ﺑﺎﻗﻲ ﻣﻲ ﻣﺎﻧﻨﺪ ﻭ ﺟﻠﻮﻱ ﮐﺎﺭﮐﺮﺩ ﺳﻴﺴﺘﻢ ﺭﺍ ﺧﻮﺍﻫﻨﺪ ﮔﺮﻓﺖ ‪.‬‬

‫‪ -‬ﺁﻻﺭﻡ ﻫﺎﻱ ﻣﻮﺟﻮﺩ ﻣﻤﮑﻦ ﺍﺳﺖ ﺑﻪ ﻭﺳﻴﻠﻪ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ﻫﺎﻱ ‪ Run /Stop‬ﻛﻨﺘﺮﻟﺮ ﺍﺯ ﺑﻴﻦ‬
‫ﻣﻲ ﺭﻭﻧﺪ ‪.‬‬
‫ﺑﻴﺸﺘﺮ ﺁﻻﺭﻡ ﻫﺎ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻫﺴﺘﻨﺪ ﺑﻪ ﻗﺴﻤﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﺮﺍﻱ ﺗﻨﻈﻴﻤﺎﺕ ﺁﻻﺭﻡ ﻣﺮﺍﺟﻌﻪ‬
‫ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫‪ : Pressure Low Oil‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻭﺭﻭﺩﻱ ﺩﻳﺠﻴﺘﺎﻝ‬


‫‪ Low Oil Pressure‬ﺳﻴﮕﻨﺎﻟﻲ ﺩﺭﻳﺎﻓﺖ ﺷﻮﺩ ﻭ ﻳﺎ ﻣﻘﺪﺍﺭ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻓﺸﺎﺭﺭﻭﻏﻦ ﺳﻴﺴﺘﻢ‬
‫ﮐﻪ ﺍﺯ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺳﻨﺠﻴﺪﻩ ﻣﻲ ﺷﻮﺩ ‪ ،‬ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ ‪.‬‬
‫ﻣﺤﺪﻭﺩﻩ ‪ (P-015) Warning‬ﻭ ‪ (P-016) Alarm‬ﻫﺮ ﻳﻚ ﺑﺮﺍﻱ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺑﻪ‬
‫ﺻﻮﺭﺕ ﺟﺪﺍ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻫﺴﺘﻨﺪ‪ .‬ﺍﻳﻦ ﺧﻄﺎ ﺑﻌﺪ ﺍﺯﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﻭ ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ‬
‫ﺗﺎﺧﻴﺮ ‪ Hold OFF‬ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ) ‪ ( P-023‬ﻗﺎﺑﻞ ﺗﻨﻈﻴﻢ ﺍﺳﺖ ‪ ،‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﻫﻤﭽﻨﻴﻦ ﺍﮔﺮ ﺩﺭ ﻟﺤﻈﻪ ﻭﻗﻮﻉ ﺍﺳﺘﺎﺭﺕ ﺳﻮﺋﻴﭻ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ‪ ،‬ﺑﺎﺯ ﺷﻮﺩ ﻣﻮﺗﻮﺭ ﺍﺳﺘﺎﺭﺕ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ﻭ‬
‫‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressure‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ ‪ .‬ﻫﻨﮕﺎﻣﻴﮑﻪ ﺳﻮﺋﻴﭻ ﻓﺸﺎﺭ‬
‫ﺭﻭﻏﻦ ﺩﻭﺑﺎﺭﻩ ﺑﺴﺘﻪ ﺷﻮﺩ ‪ ،‬ﺳﻴﺴﺘﻢ ﺑﻪ ﺻﻮﺭﺕ ﻋﺎﺩﻱ ﺑﻪ ﮐﺎﺭ ﻧﺨﻮﺍﻫﺪ ﻛﺮﺩ‪.‬‬

‫‪ : High Temperature‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺍﺯﺳﻮﺋﻴﭻ ﺩﻣﺎﻱ ﺑﺎﻻ‬


‫)‪ (High Temp‬ﺳﻴﮕﻨﺎﻟﻲ ﺩﺭﻳﺎﻓﺖ ﺷﻮﺩ ﻭ ﻳﺎ ﻣﻘﺪﺍﺭ ﺩﻣﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺳﻴﺴﺘﻢ ﮐﻪ ﺗﻮﺳﻂ‬
‫ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺳﻨﺠﻴﺪﻩ ﻣﻲ ﺷﻮﺩ ‪ ،‬ﺑﺎﻻﻱ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ ‪.‬‬

‫‪11‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻣﺤﺪﻭﺩﻩ ‪ (P-017) Warning‬ﻭ ‪ (P-018) Alarm‬ﻫﺮﻳﻚ ﺑﺮﺍﻱ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺑﻪ ﺻﻮﺭﺕ ﺟﺪﺍ‬
‫ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻫﺴﺘﻨﺪ ‪.‬‬

‫‪ : Over/Under Speed‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﻲ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﺭﺝ‬


‫ﺍﺯﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ ‪ .‬ﺍﻳﻦ ﺧﻄﺎ ﭘﺲ ﺍﺯﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﻭ ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ‬
‫ﺗﺎﺧﻴﺮ ‪ Hold OFF‬ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ) ‪ ( P-023‬ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ‪ ،‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫‪P-‬‬ ‫ﺣﺪﻫﺎﻱ ﺑﺎﻻ ﻭ ﭘﺎﻳﻴﻦ ﺑﺮﺍﻱ ‪ Warning‬ﻭ ‪ Alarm‬ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ )‪ P-008‬ﻭ ‪ P-009‬ﻭ‬
‫‪ 010‬ﻭ ‪ ( P-011‬ﺑﻪ ﺻﻮﺭﺕ ﺟﺪﺍ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻣﻲ ﺑﺎﺷﻨﺪ ‪.‬‬

‫‪ : Start Fail‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﻲ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺑﺮﻧﺎﻣﻪ‬
‫ﺭﻳﺰﻱ ﺷﺪﻩ )‪ (P-035‬ﺟﻬﺖ ﺍﺳﺘﺎﺭﺕ ﺭﻭﺷﻦ ﻧﺸﻮﺩ‪.‬‬

‫‪ : Over Load‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺩﺭ ﺻﻮﺭﺗﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺣﺪﺍﻗﻞ ﻳﮑﻲ ﺍﺯ ﺟﺮﻳﺎﻧﻬﺎﻱ ﻓﺎﺯﻫﺎﻱ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺑﺎﻻﺗﺮ ﺍﺯ ﭘﺎﺭﺍﻣﺘﺮ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ‪ (P-002) Over Current Limit‬ﺑﺎﺷﺪ ﻭ ﻳﺎ‬
‫ﺑﻴﺸﺘﺮﺍﺯ ﺣﺪ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﺗﻮﺍﻧﻲ ﮐﻪ ﺩﺭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ‬
‫)‪ Excess Power(P-003‬ﺑﺎﺷﺪ ﻭ ﺯﻣﺎﻥ ﺍﺭﺍﺋﻪ ﺍﻳﻦ ﺗﻮﺍﻥ ﺑﻴﺶ ﺍﺯ ﺯﻣﺎﻧﻲ ﺑﺎﺷﺪ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫)‪ Over Current/Excess Power Timer(P-511‬ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ‪ .‬ﺍﮔﺮ ﺟﺮﻳﺎﻥ ﻭﺗﻮﺍﻥ‬
‫ﺑﻪ ﭘﺎﻳﻴﻦ ﺗﺮ ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﻗﺒﻞ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺗﺎﻳﻤﺮ ﺑﺮﺳﺪ ﻫﻴﭻ ﮔﻮﻧﻪ ﺧﻄﺎﻳﻲ ﺍﻋﻼﻡ ﻧﺨﻮﺍﻫﺪ‬
‫ﺷﺪ‪ .‬ﭼﻨﺎﻧﭽﻪ )‪ Over Current Limit (P-002‬ﻭ )‪ Excess Power (P-003‬ﺑﻪ ﻣﻘﺪﺍﺭ‬
‫ﺻﻔﺮ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﻮﻧﺪ ﻣﻘﺎﺩﻳﺮ ﻣﺮﺑﻮﻃﻪ ﺣﺬﻑ ﻣﻲ ﺷﻮﻧﺪ‪.‬‬

‫‪ :Low/High Voltage‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﻭﻟﺘﺎﮊ ﻳﮑﻲ ﺍﺯ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭﺍﺯ‬
‫ﺣﺪﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ )‪ ( P-006/P007‬ﺧﺎﺭﺝ ﮔﺮﺩﺩ ‪ .‬ﺍﻳﻦ ﺧﻄﺎ ﺑﻌﺪ ﺍﺯ‬
‫ﺭﻭﺷﻦ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﻭ ﭘﺲ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮ ‪ Hold OFF‬ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫) ‪ ( P-023‬ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺍﺳﺖ ‪ ،‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫‪12‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ :Low/High Battery‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ﮐﻪ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺧﺎﺭﺝ ﺍﺯ ﻣﺤﺪﻭﺩﻩ‬
‫ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺑﺎﺷﺪ ‪ .‬ﺩﺭ ﻃﻮﻝ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ﺍﻳﻦ ﺧﻄﺎ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻧﻤﻲ ﺷﻮﺩ ‪.‬‬
‫ﺍﺧﻄﺎﺭ ﺑﺮﺍﻱ ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﺳﻄﺢ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ ( P-012‬ﻭ ﺑﺮﺍﻱ ﺑﺎﻻ ﺑﻮﺩﻥ ﺳﻄﺢ ﻭﻟﺘﺎﮊ‬
‫ﺍﺧﻄﺎﺭﻫﺎﻱ )‪ Warning (P-013‬ﻭ )‪ Alarm (P-014‬ﺩﺭ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻗﺎﺑﻞ ﺗﻌﺮﻳﻒ ﻣﻲ‬
‫ﺑﺎﺷﻨﺪ ‪.‬‬

‫‪ : Charge Alternator‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺩﻳﻨﺎﻡ ﺩﭼﺎﺭ ﺍﺷﻜﺎﻝ ﺷﻮﺩ‬
‫)ﻳﺎ ﺗﺴﻤﻪ ﭘﺎﺭﻩ ﺷﻮﺩ( ﻭﺿﻌﻴﺖ ﺍﻳﻦ ﺍﻳﺮﺍﺩ ﻣﻨﺠﺮ ﺑﻪ ﺧﻄﺎ ﻭ ﻳﺎ ﻫﺸﺪﺍﺭ ﻫﺎﻱ ﺯﻳﺮ ﻣﻲ ﮔﺮﺩﺩ ‪.‬‬
‫ﺑﺮﻧﺎﻣﻪ )‪(P-038‬‬
‫‪ : Reverse Power‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﻛﻪ ﺗﻮﺍﻥ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ )‪ (KW‬ﺩﺭ‬
‫ﻓﺎﺯ ‪ U‬ﻣﻨﻔﻲ ﻭ ﻳﺎ ﺑﻴﺶ ﺍﺯ ﺣﺪ )‪ Reverse Power (P-042‬ﺟﻬﺖ ‪Over Current‬‬
‫‪ (P-511) Excess Power Timer/‬ﺑﺎﺷﺪ‪ .‬ﭼﻨﺎﻧﭽﻪ ﻣﻘﺪﺍﺭ ‪ Reverse Power‬ﺑﻪ ﻛﻤﺘﺮ ﺍﺯ‬
‫ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﻗﺒﻞ ﺍﺯ ﺗﻤﺎﻡ ﺷﺪﻥ ﺯﻣﺎﻥ ﺗﺎﻳﻤﺮ ﺑﺮﺳﺪ ﻫﻴﭻ ﮔﻮﻧﻪ ﺁﻻﺭﻣﻲ ﺍﻋﻼﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ‪.‬‬
‫ﺍﮔﺮ ﻣﻘﺪﺍﺭ‪ (P-042) Reverse Power‬ﺑﻪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﺗﻨﻈﻴﻢ ﮔﺮﺩﺩ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬
‫ﺣﺬﻑ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫‪ : Emergency Stop‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻭﺭﻭﺩﻱ ﻣﺮﺑﻮﻁ ﺑﻪ‬


‫‪ Emergency Stop‬ﺳﻴﮕﻨﺎﻝ ﺩﺭﻳﺎﻓﺖ ﺷﻮﺩ ‪.‬‬

‫‪ : Spare‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺯﻣﺎﻧﻲ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺍﺯ ﻳﮑﻲ ﺍﺯ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ‪ Spare‬ﺳﻴﮕﻨﺎﻟﻲ ﺩﺭﻳﺎﻓﺖ‬
‫ﺷﻮﺩ ‪.‬‬

‫‪ -5‬ﺣﺎﻟﺘﻬﺎﻱ ﻋﻤﻠﻴﺎﺗﻲ‬
‫ﺩﺳﺘﮕﺎﻩ ﺑﺎ ﻓﺸﺮﺩﻥ ﺩﻛﻤﻪ ‪ RUN‬ﺑﺮ ﺭﻭﻱ ﺻﻔﺤﻪ ﺟﻠﻮﻱ ﻛﻨﺘﺮﻟﺮ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭ ﺑﺎ ﻓﺸﺮﺩﻥ ﺩﻛﻤﻪ‬
‫‪ STOP‬ﺧﺎﻣﻮﺵ ﻣﻲ ﺷﻮﺩ ‪ .‬ﭼﻨﺎﻧﭽﻪ ﻫﻴﭻ ﺩﻛﻤﻪ ﺍﻱ ﺭﻭﺷﻦ ﻧﺸﻮﺩ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻃﻮﺭ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺑﻌﺪ ﺍﺯ‬
‫‪ 5‬ﺩﻗﻴﻘﻪ ﺧﺎﻣﻮﺵ ﻣﻲ ﺷﻮﺩ‪ .‬ﺩﺭ ﺻﻮﺭﺕ ﻧﻴﺎﺯ ﻣﻲ ﺗﻮﺍﻥ ﺣﺎﻟﺖ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺭﺍ ﺑﺎ ﺑﺮﻧﺎﻣﻪ‬
‫ﺭﻳﺰﻱ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-050‬ﺑﻪ ﺻﻮﺭﺕ ﻏﻴﺮ ﻓﻌﺎﻝ ﺩﺭ ﺁﻭﺭﺩ‪.‬‬

‫‪13‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﺩﺭ ﺯﻣﺎﻥ ﺭﻭﺷﻦ ﺑﻮﺩﻥ ﺩﺳﺘﮕﺎﻩ ﭼﻨﺎﻧﭽﻪ ﻣﺠﺪﺩﺍ" ﺩﻛﻤﻪ ‪ RUN‬ﻓﺸﺮﺩﻩ ﺷﻮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ‬
‫ﺷﺪﻩ ﻭ ‪ LED‬ﺯﺭﺩ ﺭﻧﮓ ﺁﻥ ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﻚ ﺯﺩﻥ ﻣﻲ ﻧﻤﺎﻳﺪ ﻭ ﭘﺲ ﺍﺯ ﺍﻳﻨﻜﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﻱ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺷﺪﻩ ﺑﺎﺷﺪ ‪ LED ،‬ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭ ﺑﻪ ﺻﻮﺭﺕ ﺛﺎﺑﺖ‬
‫ﺭﻭﺷﻦ ﺑﺎﻗﻲ ﻣﻲ ﻣﺎﻧﺪ‪.‬‬
‫ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ ‪ STOP‬ﻓﺸﺮﺩﻩ ﺷﻮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺷﺪﻩ ﻭﻟﻲ ﺩﺳﺘﮕﺎﻩ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ‪،‬‬
‫ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ ‪ STOP‬ﻣﺠﺪﺩﺍ" ﻓﺸﺮﺩﻩ ﺷﻮﺩ ﻭ ﭘﺲ ﺍﺯ ﺁﻥ ﺑﻪ ﻣﺪﺕ ‪ 5‬ﺩﻗﻴﻘﻪ ﻫﻴﭻ ﺩﻛﻤﻪ ﺍﻱ ﻓﺸﺮﺩﻩ‬
‫ﻧﺸﻮﺩ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻃﻮﺭ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬
‫ﺯﻣﺎﻧﻲ ﻛﻪ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺩﺭ ﺣﺎﻝ ﻛﺎﺭ ﺍﺳﺖ ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ ‪ RUN‬ﻓﺸﺮﺩﻩ ﺷﻮﺩ ‪ LED‬ﺯﺭﺩ ﺭﻧﮓ‬
‫ﺳﻨﻜﺮﻭﻧﺎﻳﺰﺭ ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﻚ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻛﺮﺩ ﻭ ﺩﺳﺘﮕﺎﻩ ﺣﺎﻟﺖ ﺳﻨﻜﺮﻭﻥ ﺑﻮﺩﻥ ﮊﻧﺮﺍﺗﻮﺭ ﺑﺎ ﺑﺎﺱ‬
‫ﺑﺎﺭ ﺭﺍ ﭼﻚ ﺧﻮﺍﻫﺪ ﻛﺮﺩ ‪ ،‬ﭼﻨﺎﻧﭽﻪ ﺑﺎﺱ ﺑﺎﺭ ﺑﺮﻕ ﺩﺍﺭ ﻧﺒﺎﺷﺪ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﺎ‬
‫ﺳﻴﮕﻨﺎﻝ ‪ Dead Bus Enable‬ﻓﻌﺎﻝ ﻧﻤﻮﺩ ﭼﻨﺎﻧﭽﻪ ﺑﺎﺱ ﺑﺎﺭ ﻓﻌﺎﻝ ﺑﺎﺷﺪ ﻭ ﺗﻤﺎﻡ ﺣﺎﻟﺘﻬﺎﻱ ﺳﻨﻜﺮﻭﻥ‬
‫ﻣﻮﺟﻮﺩ ﺑﺎﺷﺪ) ‪ (∆v, ∆f, ∆θ‬ر ون  ل  و ‪ LED‬زرد &ن دا‪ "#‬رو! ‬
‫ﻥ‪.‬‬
‫ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ ‪ STOP‬ﻓﺸﺮﺩﻩ ﺷﻮﺩ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻏﻴﺮ ﻓﻌﺎﻝ ﺷﺪﻩ ﻭ ‪ LED‬ﺁﻥ‬
‫)‪ (Synchronized‬ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ‪ .‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ﻭ ﺑﺎ ﻓﺸﺎﺭ‬
‫ﺩﺍﺩﻥ ﻣﺠﺪﺩ ﺩﻛﻤﻪ ‪ STOP‬ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬
‫ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺯﻣﺎﻥ ﺩﺍﺭ ﻧﺒﻮﺩﻩ ﻭ ﺗﺎ ﺯﻣﺎﻧﻲ ﻛﻪ ﺷﺮﺍﻳﻂ ﺳﻨﻜﺮﻭﻥ ﺗﺤﻘﻖ ﻳﺎﺑﺪ ﺍﻳﻦ ﻋﻤﻞ ﺍﺩﺍﻣﻪ‬
‫ﻣﻲ ﻳﺎﺑﺪ ﻭ ﺍﻳﻦ ﻋﻤﻞ ﺑﻪ ﺻﻮﺭﺕ ﺩﺳﺘﻲ ﻭ ﻳﺎ ﺍﺯ ﻃﺮﻳﻖ ﺳﻴﮕﻨﺎﻝ ‪ Remote Start‬ﺧﺎﺗﻤﻪ ﻣﻲ ﻳﺎﺑﺪ‪.‬‬
‫ﭼﻨﺎﻧﭽﻪ ﺩﺭ ﻫﺮ ﺣﺎﻟﺘﻲ ﺍﺯ ﺣﺎﻟﺘﻬﺎﻱ ﻛﺎﺭﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎﻳﻲ ﺍﺗﻔﺎﻕ ﺍﻓﺘﺪ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻏﻴﺮ‬
‫ﻓﻌﺎﻝ ﺷﺪﻩ ﻭ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺧﺎﻣﻮﺵ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ‪ LED‬ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎﻱ ﻣﺮﺑﻮﻃﻪ ﺑﻪ ﻃﻮﺭ ﺩﺍﺋﻢ‬
‫ﺭﻭﺷﻦ ﻣﻲ ﻣﺎﻧﺪ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺗﺎ ﺯﻣﺎﻧﻲ ﻛﻪ ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎ ﺑﻮﺳﻴﻠﻪ ﺩﻛﻤﻪ ‪ STOP‬ﺑﺮﻃﺮﻑ ﻧﺸﻮﺩ ﺧﺎﻣﻮﺵ‬
‫ﻧﺨﻮﺍﻫﺪ ﺷﺪ‪.‬‬
‫ﻭﺭﻭﺩﻱ‪ (9) Remote Start‬ﻫﻤﻴﺸﻪ ﻓﻌﺎﻝ ﺑﻮﺩﻩ ﻭ ﻧﻴﺎﺯﻱ ﺑﻪ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻧﺪﺍﺭﺩ‪ .‬ﺣﺎﻟﺖ‬
‫‪ Remote Start‬ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﺎ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﺩﻳﺎﮔﺮﺍﻡ ﺯﻳﺮ ﺑﺮﺭﺳﻲ ﻧﻤﻮﺩ‪.‬‬

‫‪14‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪-6‬ﺩﻳﮕﺮ ﺧﺼﻮﺻﻴﺎﺕ ‪:‬‬


‫‪ : 6-1‬ﻋﻤﻠﮑﺮﺩ ﺑﻪ ﺻﻮﺭﺕ ‪Remote Start‬‬
‫ﺩﺳﺘﮕﺎﻩ ﺍﻣﻜﺎﻥ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ‪ Remote Start‬ﺭﺍ ﺑﻪ ﻛﺎﺭﺑﺮ ﻣﻲ ﺩﻫﺪ ‪ .‬ﻭﺭﻭﺩﻱ‪Remote Start‬‬
‫)‪ (9‬ﻫﻤﻴﺸﻪ ﻓﻌﺎﻝ ﺑﻮﺩﻩ ﻭ ﻧﻴﺎﺯﻱ ﺑﻪ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻧﺪﺍﺭﺩ‪ .‬ﻭ ﺳﻴﮕﻨﺎﻝ ‪ Remote Start‬ﺑﻪ ﻭﺭﻭﺩﻱ‬
‫ﺷﻤﺎﺭﻩ ‪ 9‬ﻣﺘﺼﻞ ﻣﻲ ﮔﺮﺩﺩ‪ .‬ﻭﺭﻭﺩﻱ ‪ Remote Start‬ﻫﻤﻴﺸﻪ ﺑﻪ ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ ﻣﺘﺼﻞ ﻣﻲ ﮔﺮﺩﺩ ﻭ‬
‫ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﺣﺎﻟﺖ )ﻣﺼﺮﻑ ﺻﻔﺮ( ﺩﺭ ﺣﺎﻟﺖ ﺑﻴﻜﺎﺭﻱ ﺩﺳﺘﮕﺎﻩ ﻭﻟﺘﺎﮊ ﻣﻲ ﺑﺎﻳﺴﺘﻲ ﺑﻪ ﺍﻳﻦ ﺗﺮﻣﻴﻨﺎﻝ ﻣﺘﺼﻞ‬
‫ﺷﺪﻩ ﺗﺎ ﺩﺳﺘﮕﺎﻩ ﺍﺯ ﺣﺎﻟﺖ ﺧﺎﻣﻮﺵ ﺑﻪ ﺣﺎﻟﺖ ﻋﻤﻠﻴﺎﺗﻲ ﺗﻐﻴﻴﺮ ﺣﺎﻟﺖ ﺩﻫﺪ‪.‬‬

‫ﻫﺸﺪﺍﺭ‬
‫ﺑﻪ ﻫﻴﭻ ﻋﻨﻮﺍﻥ ﻭﻟﺘﺎﮊﻱ ﺑﺎﻻﺗﺮ ﺍﺯ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺑﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻣﺘﺼﻞ ﻧﻨﻤﺎﻳﻴﺪ ﺩﺭ ﻏﻴﺮ ﺍﻳﻦ‬
‫ﺻﻮﺭﺕ ﺧﺴﺎﺭﺕ ﺟﺪﻱ ﺑﻪ ﺍﻳﻦ ﺩﺳﺘﮕﺎﻩ ﻭﺍﺭﺩ ﺧﻮﺍﻫﺪ ﺁﻣﺪ‪.‬‬

‫ﺳﻴﮕﻨﺎﻝ ‪ Remote Start‬ﻣﻌﺎﺩﻝ ﺳﻪ ﺑﺎﺭ ﻓﺸﺮﺩﻥ ﺩﻛﻤﻪ ‪ RUN‬ﻣﻲ ﺑﺎﺷﺪ ﻭ ﺑﻪ ﻣﻌﻨﺎﻱ ﺯﻳﺮ ﺍﺳﺖ ‪:‬‬
‫‪ -‬ﺭﻭﺷﻦ ﺷﺪﻥ ﺩﺳﺘﮕﺎﻩ‬
‫‪ -‬ﺭﻭﺷﻦ ﺷﺪﻥ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ‬

‫‪15‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﭼﻨﺎﻧﭽﻪ ﺑﺨﻮﺍﻫﻴﻢ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﻳﻚ ﺑﺎﺱ ﺑﻲ ﺑﺮﻕ ﻣﺘﺼﻞ ﻧﻤﺎﻳﻴﻢ ﺍﻳﻦ ﻋﻤﻞ ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﺎ ﺳﻴﮕﻨﺎﻝ‬
‫‪ Dead Bus Enable‬ﺍﻧﺠﺎﻡ ﺩﺍﺩ ﻭ ﭼﻨﺎﻧﭽﻪ ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﺑﺎﺱ ﺑﺮﻕ ﺩﺍﺭ ﻣﺘﺼﻞ ﺷﻮﺩ ﺍﺑﺘﺪﺍ ﻋﻤﻞ‬
‫ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺍﻧﺠﺎﻡ ﮔﺸﺘﻪ ﻭ ﭘﺲ ﺍﺯ ﺍﻳﻨﻜﻪ ﻛﻠﻴﻪ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺳﻨﻜﺮﻭﻥ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺧﻮﺩ ﺑﺎﺷﻨﺪ‬
‫ﺩﺳﺘﮕﺎﻩ ﺑﻪ ﺑﺎﺱ ﺑﺮﻕ ﺩﺍﺭ ﻣﺘﺼﻞ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫‪ : 6-2‬ﺳﻨﻜﺮﻭﻥ ﭼﻚ‬
‫ﺍﻳﻦ ﺩﺳﺘﮕﺎﻩ ﺣﺎﻟﺖ ﺳﻨﻜﺮﻭﻥ ﺭﺍ ﺩﺭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﻭ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ‬
‫ﺷﺪﻩ ﺑﺎﺷﻨﺪ ﭼﻚ ﻛﺮﺩﻩ ﻭ ‪ LED‬ﻣﺮﺑﻮﻃﻪ ﺑﻪ ﺻﻮﺭﺕ ﭼﺸﻤﻚ ﺯﻥ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪ ،‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ‬
‫‪LED‬ﻫﺎﻱ ﺳﻨﻜﺮﻭﻧﺴﻜﻮﭖ ﺭﻭﺷﻦ ﺷﺪﻩ ﻭ ﻣﻘﺪﺍﺭ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﻧﺸﺎﻥ‬
‫ﻣﻲ ﺩﻫﺪ‪.‬‬
‫ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺗﻮﺳﻂ ﻛﻨﺘﺮﻟﺮ ﻣﺘﺸﻜﻞ ﺍﺯ ﺍﺭﺯﻳﺎﺑﻲ ﺷﺮﻭﻁ ﺫﻳﻞ ﺩﺭ ﺧﻼﻝ ﺳﻴﻜﻞ ﻫﺎﻱ ﻛﺎﺭﻱ‬
‫ﻣﺘﻮﺍﻟﻲ ﺑﺎﺱ ﺑﺎﺭ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ ﻣﻲ ﺑﺎﻳﺴﺘﻲ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺗﻮﺳﻂ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ‪ P-004‬ﻭ ‪ P-005‬ﺑﺎﺷﺪ‪.‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ ﻣﻲ ﺑﺎﻳﺴﺘﻲ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺗﻮﺳﻂ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ‪ P-006‬ﻭ ‪P-007‬‬
‫ﺑﺎﺷﺪ‪.‬‬
‫‪ -‬ﺍﺧﺘﻼﻑ ﻓﺮﻛﺎﻧﺲ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭﺑﻴﺶ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-039‬‬
‫ﻧﺒﺎﺷﺪ‪.‬‬
‫‪ -‬ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﺑﻴﺶ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‪P-040‬‬
‫ﻧﺒﺎﺷﺪ‪.‬‬
‫‪ -‬ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﺑﻴﺶ ﺍﺯ ﻣﺤﺪﻭﺩﻩ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-041‬‬
‫ﻧﺒﺎﺷﺪ‪.‬‬
‫ﭼﻨﺎﻧﭽﻪ ﺣﺎﻟﺘﻬﺎﻱ ﻣﺘﻮﺍﻟﻲ ﺑﺎﻻ ﺩﺭ ﺷﺮﺍﻳﻂ ﻛﺎﺭﻱ ﺳﻴﻜﻞ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﻫﺎﻱ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺑﺎﺷﻨﺪ‬
‫ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺳﺮﻳﻌﺎ" ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﭼﻨﺎﻧﭽﻪ ﺣﺎﻟﺘﻬﺎﻱ ﻣﺘﻮﺍﻟﻲ ﺳﻴﻜﻞ ﻛﺎﺭﻱ ﺑﺎﺱ ﺑﺎﺭ ﺩﺭ ﻣﺤﺪﻭﺩﻩ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺫﻛﺮ ﺷﺪﻩ ﻧﺒﺎﺷﺪ ﺭﻟﻪ‬
‫ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﺳﺮﻳﻌﺎ" ﻏﻴﺮ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫‪16‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻫﺸﺪﺍﺭ‬
‫ﭘﻴﺸﻨﻬﺎﺩ ﻣﻲ ﺷﻮﺩ ﻛﻪ ﺍﺯ ﻛﻨﺘﺎﻛﺘﻮﺭ ﻭ ﻛﻠﻴﺪﻫﺎﻱ ﺑﺎ ﻗﻄﻊ ﻭ ﻭﺻﻞ ﺳﺮﻳﻊ ﺍﺳﺘﻔﺎﺩﻩ ﺷﻮﺩ‪.‬‬

‫‪ : 6-3‬ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ‬

‫ﺳﻴﺴﺘﻢ ﻗﺎﺑﻠﻴﺖ ﺗﻄﺒﻴﻖ ﺑﺎ ﻫﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﻳﺎ ﺩﻣﺎ ﺭﺍ ﺩﺍﺭﺍﺳﺖ ‪ .‬ﺑﻪ ﻃﻮﺭ ﻛﻠﻲ ﻣﺸﺨﺼﻪ ﺳﻨﺴﻮﺭﻫﺎﻱ‬
‫ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﺩﺭ ﺩﺍﺧﻞ ﺣﺎﻓﻈﻪ ﻛﻨﺘﺮﻟﺮ ﺛﺒﺖ ﺷﺪﻩ ﺍﺳﺖ ﻭ ﺍﺯ ﺭﻭﻱ ﻟﻴﺴﺖ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪.‬‬
‫ﺳﻨﺴﻮﺭﻫﺎﻱ ﻏﻴﺮ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺰ ﻣﻤﮑﻦ ﺍﺳﺖ ﺑﺎ ﻭﺍﺭﺩ ﻛﺮﺩﻥ ﻣﺸﺨﺼﺎﺕ ﺁﻧﻬﺎ ﺩﺭ ﺟﺪﻭﻝ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ‬
‫ﺑﺎﺷﻨﺪ ‪.‬‬

‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ‪:‬‬


‫ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ (P-019‬ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪ .‬ﻧﻮﻉ ﺳﻨﺴﻮﺭﻫﺎﻱ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﻋﺒﺎﺭﺗﻨﺪ‬
‫ﺍﺯ ‪:‬‬
‫‪ : 0‬ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭﺩﺭ ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﺗﻌﻴﻴﻦ ﻣﻲ ﮔﺮﺩﺩ‪ ،‬ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ )‪ P-131‬ﻭ ‪. ( P-142‬‬
‫‪VDO 0-7bars (10-180 ohms) : 1‬‬
‫‪VDO 0-10bars (280-20 ohms) : 2‬‬
‫‪DATCON 0-7bars (240-33 ohms) : 3‬‬
‫‪DATCON 0-10bars (240-33 ohms) : 4‬‬
‫‪DATCON 0-7bars (0-90 ohms) : 5‬‬
‫‪DATCON 0-10bars (0-90 ohms) : 6‬‬
‫‪DATCON 0-7bars (75-10 ohms) : 7‬‬

‫‪17‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ‪:‬‬
‫ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-020‬ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﺍﺳﺖ ‪ .‬ﺍﻧﻮﺍﻉ ﺳﻨﺴﻮﺭﻫﺎﻱ ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ ﻋﺒﺎﺭﺗﻨﺪ‬
‫ﺍﺯ ‪:‬‬
‫‪ : 0‬ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ‪ P-143‬ﻭ‪ P-154‬ﻗﺎﺑﻞ ﺍﻧﺘﺨﺎﺏ‬
‫ﺍﺳﺖ‪.‬‬
‫‪VDO : 1‬‬
‫‪DATCON DAH Type : 2‬‬
‫‪DATCON DAL Type : 3‬‬

‫‪ : 6-4‬ﻋﻤﻞ ﮔﺮﻡ ﻛﺮﺩﻥ ﻣﻮﺗﻮﺭ‬


‫ﺩﺭ ﺧﺼﻮﺹ ﻣﻮﺗﻮﺭﻫﺎﻳﻲ ﻛﻪ ﺑﺪﻭﻥ ﮔﺮﻡ ﻛﻦ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﻭ ﻳﺎ ﮔﺮﻡ ﻛﻦ ﺁﻧﻬﺎ ﺧﺮﺍﺏ ﺷﺪﻩ ‪ ،‬ﺑﻬﺘﺮ‬
‫ﺍﺳﺖ ﻛﻪ ﻗﺒﻞ ﺍﺯ ﮔﺮﻡ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﻭ ﺭﺳﻴﺪﻥ ﺑﻪ ﺣﺮﺍﺭﺕ ﻣﻄﻠﻮﺏ ﺑﺎﺭ ﺑﻪ ﻣﻮﺗﻮﺭ ﺍﻋﻤﺎﻝ ﻧﮕﺮﺩﺩ ﺍﺯ ﺍﻳﻦ‬
‫ﺭﻭ ﻛﻨﺘﺮﻟﺮ ﺩﻭ ﺣﺎﻟﺖ ﻛﺎﺭﻱ ﺯﻳﺮ ﺭﺍ ﺟﻬﺖ ﮔﺮﻡ ﻛﺮﺩﻥ ﻣﻮﺗﻮﺭ ﺍﻧﺠﺎﻡ ﻣﻲ ﺩﻫﺪ‪:‬‬
‫‪ -1‬ﺗﺎﻳﻤﺮﮔﺮﻡ ﻛﻦ‬
‫ﺍﻳﻦ ﺣﺎﻟﺖ ﻛﺎﺭﻱ ﺑﺎ ﺗﻨﻈﻴﻢ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-037‬ﺑﻪ ﻣﻘﺪﺍﺭ ‪ 0‬ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﻣﻮﺗﻮﺭ ﺑﺎ ﻣﻘﺪﺍﺭ‬
‫ﺯﻣﺎﻥ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-029‬ﮔﺮﻡ ﺷﺪﻩ ﻭ ﺳﭙﺲ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬

‫‪ -2‬ﻛﻨﺘﺮﻝ ﺣﺮﺍﺭﺕ ﻭ ﺗﺎﻳﻤﺮ ﮔﺮﻡ ﻛﻦ‬


‫ﺍﻳﻦ ﺣﺎﻟﺖ ﻛﺎﺭﻱ ﺑﺎ ﺗﻨﻈﻴﻢ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-037‬ﺑﻪ ﻣﻘﺪﺍﺭ ‪ 1‬ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﺍﺑﺘﺪﺍ ﻣﻮﺗﻮﺭ ﺑﺎ‬
‫ﻣﻘﺪﺍﺭ ﺯﻣﺎﻥ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-029‬ﮔﺮﻡ ﺷﺪﻩ ﻭ ﺳﭙﺲ ﻫﻤﭽﻨﺎﻥ ﺍﺩﺍﻣﻪ ﺑﻪ ﻛﺎﺭ ﺩﺍﺩﻩ ﺗﺎ ﺯﻣﺎﻧﻲ‬
‫ﻛﻪ ﻣﻘﺪﺍﺭ ﺣﺮﺍﺭﺕ ﺁﺏ ﺑﻪ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‪ P-022‬ﺑﺮﺳﺪ‪ .‬ﺩﺭ ﺍﻳﻦ ﺣﺎﻟﺖ ﺭﻟﻪ‬
‫ﺳﻨﻜﺮﻭﻥ ﭼﻚ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ‪ ،‬ﺍﻳﻦ ﺣﺎﻟﺖ ﻣﻲ ﺗﻮﺍﻧﺪ ﺑﻪ ﻋﻨﻮﺍﻥ ﭘﺸﺘﻴﺒﺎﻥ ﮔﺮﻡ ﻛﻦ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺑﺎﺷﺪ ﻭ‬
‫ﭼﻨﺎﻧﭽﻪ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺑﻪ ﺍﻧﺪﺍﺯﻩ ﻛﺎﻓﻲ ﮔﺮﻡ ﺑﺎﺷﺪ ﺍﻳﻦ ﺣﺎﻟﺖ ﺑﻪ ﻃﻮﺭ ﺍﺗﻮﻣﺎﺗﻴﻚ ﺣﺬﻑ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫‪18‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ : 6-5‬ﻧﻤﺎﻳﺸﮕﺮ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ‬


‫ﺍﻳﻦ ‪ LED‬ﺟﻬﺖ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺩﻭﺭﻩ ﺍﻱ ﺳﺎﺯﮔﺎﺭ ﺑﺎ ﮐﺎﺭﮐﺮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭﻃﺮﺍﺣﻲ ﺷﺪﻩ‬
‫ﺍﺳﺖ ‪.‬‬
‫ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺩﻭﺭﻩ ﺍﻱ ﺑﺮﺍﺳﺎﺱ ﺭﺳﻴﺪﻥ ﺑﻪ ﺯﻣﺎﻥ ﺧﺎﺻﻲ ﺑﺮﺍﻱ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻃﺮﺍﺣﻲ ﺷﺪﻩ‬
‫ﺍﺳﺖ )ﺑﻪ ﻋﻨﻮﺍﻥ ﻣﺜﺎﻝ ‪ 200‬ﺳﺎﻋﺖ ( ‪.‬‬
‫ﺍﻣﺎ ﺍﮔﺮ ﻣﻴﺰﺍﻥ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻛﺎﻣﻞ ﻧﺸﺪﻩ ﺑﺎﺷﺪ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺑﺎ ﺭﺳﻴﺪﻥ ﺑﻪ ﺣﺪ ﺯﻣﺎﻧﻲ ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ‬
‫)ﻣﺜﻼ ‪ 12‬ﻣﺎﻩ ( ‪.‬‬

‫ﺗﻮﺟﻪ ‪ LED :‬ﻣﺮﺑﻮﻁ ﺑﻪ ﺳﺮﻭﻳﺲ ﺩﻭﺭﻩ ﺍﻱ ﺗﺎﺛﻴﺮﻱ ﺩﺭ ﻋﻤﻠﮑﺮﺩ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ‬
‫ﺩﺍﺷﺖ ‪.‬‬

‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﻗﺎﺑﻠﻴﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﻪ ﺩﻭ ﺻﻮﺭﺕ ‪ ،‬ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻭ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺗﻌﻤﻴﺮﺍﺕ‬
‫ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺭﺍ ﺩﺍﺭﺍ ﻣﻲ ﺑﺎﺷﺪ ‪ .‬ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ (P-044‬ﺑﺎ‬
‫ﻣﺮﺣﻠﻪ ﻫﺎﻱ ‪ 50‬ﺳﺎﻋﺘﻪ ﺍﺳﺖ ﻭ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﻧﻴﺰ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ )‪ (P-045‬ﺑﺎ‬
‫ﻣﺮﺣﻠﻪ ﻫﺎﻱ ‪ 1‬ﻣﺎﻫﻪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺍﺳﺖ ‪ .‬ﺍﮔﺮ ﻫﺮ ﻳﮏ ﺍﺯ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﮔﻔﺘﻪ ﺷﺪﻩ ﺑﺎ ﻋﺪﺩ ﺻﻔﺮ ﺑﺮﻧﺎﻣﻪ‬
‫ﺭﻳﺰﻱ ﺷﻮﻧﺪ ﺍﻳﻦ ﺑﻪ ﺁﻥ ﻣﻌﻨﻲ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ﮐﻪ ﺍﺯ ﺁﻥ ﭘﺎﺭﺍﻣﺘﺮﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﺷﻮﺩ ‪ .‬ﺑﻪ ﻋﻨﻮﺍﻥ ﻣﺜﺎﻝ ﺍﮔﺮ‬
‫ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻪ ﺩﺍﺭﻱ ﺑﺮﺍﺑﺮ ﺻﻔﺮ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ ‪ ،‬ﺑﻪ ﺍﻳﻦ ﻣﻌﻨﻲ ﺍﺳﺖ ﮐﻪ ﺳﻴﺴﺘﻢ‬
‫ﻓﻘﻂ ﺑﺮ ﺍﺳﺎﺱ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﭘﺎﺳﺦ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ﻭ ﻫﻤﭽﻨﻴﻦ ﺍﮔﺮ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻧﻴﺰ ﺻﻔﺮ‬
‫ﺷﻮﺩ ﺍﻳﻦ ﺑﻪ ﻣﻌﻨﻲ ﺍﺳﺖ ﮐﻪ ﻧﻤﺎﻳﺸﮕﺮ ‪ Service Request‬ﻏﻴﺮ ﻓﻌﺎﻝ ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺣﺪ ﺯﻣﺎﻧﻲ ﻳﺎ ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺑﻪ ﭘﺎﻳﺎﻥ ﺑﺮﺳﺪ ‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪Service‬‬
‫‪ Request‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﺧﻮﺍﻫﺪ ﻧﻤﻮﺩ ‪.‬‬
‫ﺑﺮﺍﻱ ﺧﺎﻣﻮﺵ ﺷﺪﻥ ﺍﻳﻦ ‪ LED‬ﻭ ‪ Reset‬ﺗﻌﻤﻴﺮﺍﺕ ﺩﻭﺭﻩ ﺍﻱ ﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﺩﻭ ﺩﮐﻤﻪ ‪Lamp‬‬
‫‪ Test‬ﻭ ‪ Alarm Mute‬ﺭﺍ ﺑﺮﺍﻱ ﻣﺪﺕ ‪ 5‬ﺛﺎﻧﻴﻪ ﺑﻪ ﺻﻮﺭﺕ ﻫﻤﺰﻣﺎﻥ ﻧﮕﻪ ﺩﺍﺭﻳﺪ ‪ .‬ﻧﻤﺎﻳﺸﮕﺮ ﺑﺎﻻﻳﻲ‬
‫ﻋﺒﺎﺭﺕ " ‪ " SER‬ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪.‬‬

‫‪19‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺯﻣﺎﻥ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﻭ ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﻣﺤﺪﻭﺩﻩ ﺯﻣﺎﻧﻲ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺫﺧﻴﺮﻩ ﻣﻲ ﺷﻮﻧﺪ ﻭ‬
‫ﺑﺎ ﻗﻄﻊ ﺑﺮﻕ ﺳﻴﺴﺘﻢ ﭘﺎﮎ ﻧﺨﻮﺍﻫﻨﺪ ﺷﺪ ‪.‬‬
‫ﺯﻣﺎﻥ ﺑﺎﻗﻲ ﻣﺎﻧﺪﻩ ﺑﺮﺍﻱ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﻭﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺩﺭ ﻣﻨﻮﻱ ﺁﻣﺎﺭﻱ ‪ ،‬ﺑﺎ ﻧﮕﻪ‬
‫ﺩﺍﺷﺘﻦ ﺩﮐﻤﻪ ‪ Menu‬ﺑﻪ ﻣﺪﺕ ‪ 1‬ﺛﺎﻧﻴﻪ ‪ ،‬ﻗﺎﺑﻞ ﻣﺸﺎﻫﺪﻩ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫ﺑﺎ ﻓﺸﺮﺩﻥ ﻛﻠﻴﺪ ‪ Menu‬ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ ﺗﻮﺳﻂ ﻧﻤﺎﻳﺸﮕﺮ " ‪) " Hts‬ﺑﺮ ﺣﺴﺐ ﺳﺎﻋﺖ(‬
‫ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ‪ ،‬ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ 3 ،‬ﺭﻗﻢ ﺍﻭﻝ ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ‬
‫ﻣﻮﺗﻮﺭ ﻭ ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻣﺠﺪﺩ ﻛﻠﻴﺪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ " ‪) " Hts‬ﺑﺮ ﺣﺴﺐ ﺳﺎﻋﺖ( ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﻲ‬
‫ﺷﻮﺩ ﻭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ‪ 3‬ﺭﻗﻢ ﺁﺧﺮ ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ‬
‫ﺧﻮﺍﻫﻨﺪ ﺩﺍﺩ‪.‬‬
‫ﺑﺎ ﻓﺸﺮﺩﻥ ﻛﻠﻴﺪ ‪ Menu‬ﺯﻣﺎﻥ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺗﻮﺳﻂ ﻧﻤﺎﻳﺸﮕﺮ ﺑﺮﺍﻱ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻧﻤﺎﻳﺸﮕﺮ " ‪ttS‬‬
‫" ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪ ، ،‬ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ 3 ،‬ﺭﻗﻢ ﺍﻭﻝ ﺭﻭﺯﻫﺎﻱ‬
‫ﺑﺎﻗﻴﻤﺎﻧﺪﻩ ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﻭ ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻣﺠﺪﺩ ﻛﻠﻴﺪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ " ‪) " ttS‬ﺑﺮ ﺣﺴﺐ ﺳﺎﻋﺖ(‬
‫ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﻭ ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ‪ 3‬ﺭﻗﻢ ﺁﺧﺮ ﺭﻭﺯﻫﺎﻱ‬
‫ﺳﺮﻭﻳﺲ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﻨﺪ ﺩﺍﺩ‪.‬‬

‫‪ : -6-6‬ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ‬


‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮﺩﺍﺭﺍﻱ ﺳﺎﻋﺖ ﻛﺎﺭ ﻣﻮﺗﻮﺭ ﺑﻮﺩﻩ ﮐﻪ ﻏﻴﺮ ﻗﺎﺑﻞ ﭘﺎﮎ ﮐﺮﺩﻥ ﺍﺳﺖ ﺳﺎﻋﺖ ﮐﺎﺭ ﻣﻮﺗﻮﺭ ﺩﺭ‬
‫ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﻧﮕﻪ ﺩﺍﺭﻱ ﻣﻲ ﺷﻮﺩ ﻭ ﺑﺎ ﻗﻄﻊ ﺑﺮﻕ ﻧﻴﺰ ﭘﺎﮎ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺳﺎﻋﺖ ﮐﺎﺭ ﻣﻮﺗﻮﺭ ﺩﺭ ﻣﻨﻮﻱ ﺁﻣﺎﺭﻱ ﺗﻮﺳﻂ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﺑﻪ ﻣﺪﺕ ‪ 1‬ﺛﺎﻧﻴﻪ‪ ،‬ﻗﺎﺑﻞ‬
‫ﻣﺸﺎﻫﺪﻩ ﺍﺳﺖ ‪.‬‬
‫ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ ‪ Menu‬ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ "‪ "EnH‬ﺭﺍ ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﺪ ﺩﺍﺩ ﻛﻪ ﻧﺸﺎﻧﮕﺮ‬
‫ﺳﺎﻋﺖ ﮐﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭﻣﻲ ﺑﺎﺷﺪ ‪ ، ،‬ﺯﻣﺎﻧﻲ ﻛﻪ ﻛﻠﻴﺪ ‪ Menu‬ﺭﻫﺎ ﻣﻲ ﺷﻮﺩ ﻧﻤﺎﻳﺸﮕﺮ ‪ 3 ،‬ﺭﻗﻢ ﺍﻭﻝ‬
‫ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﻣﻮﺗﻮﺭ ﺭﺍ ﻧﺸﺎﻥ ﻣﻲ ﺩﻫﺪ ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻣﺠﺪﺩ ﻛﻠﻴﺪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ"‪ "EnH‬ﺭﺍ‬
‫ﻧﻤﺎﻳﺶ ﺧﻮﺍﻫﻨﺪ ﺩﺍﺩ ﻭ ﺑﺎ ﺭﻫﺎ ﻛﺮﺩﻥ ﻛﻠﻴﺪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ ‪ 3‬ﺭﻗﻢ ﺁﺧﺮ ﺳﺎﻋﺖ ﻛﺎﺭﻛﺮﺩ ﺭﺍ ﻧﻤﺎﻳﺶ‬
‫ﺧﻮﺍﻫﺪ ﺩﺍﺩ ‪.‬‬

‫‪20‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ : 6-5‬ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ‬
‫ﻛﻨﺘﺮﻟﺮ ﺍﻣﻜﺎﻥ ‪ Programming‬ﻭ ‪ Monitoring‬ﺭﺍ ﺍﺯ ﺍﺭﺗﺒﺎﻁ ﺑﺎ ﻣﻮﺩﻡ ﺍﻳﺠﺎﺩ ﻣﻲ ﻛﻨﺪ‪ .‬ﺩﺭ‬
‫ﺑﺮﻧﺎﻣﻪ ﺑﺮﺍﻱ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﮐﺮﺩﻥ ﻭ ﻣﻮﻧﻴﺘﻮﺭﻳﻨﮓ ﺍﺯ ﻣﻮﺩﻡ ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫ﺍﮔﺮ ﺍﺯ ﻣﻮﺩﻡ ﺍﺳﺘﻔﺎﺩﻩ ﺷﻮﺩ ‪ ،‬ﭘﺎﺭﺍﻣﺘﺮ )‪ ( P-043‬ﺑﺎﻳﺪ ﺑﺮﺍﺑﺮ ﺑﺎ ‪ 1‬ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ ‪ ،‬ﺩﺭ ﻏﻴﺮ ﺍﻳﻦ‬
‫ﺻﻮﺭﺕ ﻣﻤﮑﻦ ﺍﺳﺖ ﺧﻄﺎ ﺍﺗﻔﺎﻕ ﺑﻴﺎﻓﺘﺪ ‪.‬‬

‫‪Remote Monitoring And Programming : 6-6‬‬

‫ﺟﻬﺖ ‪ Down Load‬ﺑﺮﻧﺎﻣﻪ ‪ Monitoring‬ﻭ ‪ Programming‬ﺑﻪ ﺳﺎﻳﺖ ﺷﺮﮐﺖ ﻣﺮﺍﺟﻌﻪ‬


‫ﻧﻤﺎﻳﻴﺪ ‪WWW.DATAKOM.COM.tr :‬‬
‫ﺍﻳﻦ ﻧﺮﻡ ﺍﻓﺰﺍﺭ ﺍﻣﻜﺎﻥ ﺩﻳﺪﻥ ﻭ ﺛﺒﺖ ﺗﻤﺎﻣﻲ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺭﺍ ﺑﻪ ﻛﺎﺭﺑﺮ ﻣﻲ ﺩﻫﺪ ‪.‬‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺭﺍ ﻣﻲ ﺗﻮﺍﻥ ﺑﻪ ﺻﻮﺭﺕ ﮔﺮﺍﻓﻴﻜﻲ ﻣﻮﺭﺩ ﺗﺠﺰﻳﻪ ﻭ ﺗﺤﻠﻴﻞ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻭ‬
‫ﻫﻤﭽﻨﻴﻦ ﻗﺎﺑﻠﻴﺖ ﺁﻧﻬﺎ ﻧﻴﺰ ﻭﺟﻮﺩ ﺩﺍﺭﺩ‪.‬‬
‫ﺍﻳﻦ ﻧﺮﻡ ﺍﻓﺰﺍﺭ ﻫﻤﭽﻨﻴﻦ ﺍﻣﮑﺎﻥ ﺗﻨﻈﻴﻢ ﻭ ﺫﺧﻴﺮﻩ ﺗﻤﺎﻡ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﺭﺍ ﺍﺯ ﻃﺮﻳﻖ ‪ PC‬ﺑﻪ ﺩﺍﺧﻞ ﻛﻨﺘﺮﻟﺮ ﻭ‬
‫ﺑﺎﻟﻌﻜﺲ ﺭﺍ ﺩﺍﺭﺍ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬

‫‪ – 7‬ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺁﻣﺎﺭﻱ‬

‫ﻛﻨﺘﺮﻟﺮ ﻳﮏ ﺳﺮﻱ ﺍﺯ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎﻱ ﺍﻓﺰﺍﻳﺸﻲ ﻏﻴﺮ ﻗﺎﺑﻞ ﺭﻳﺴﺖ ﺭﺍ ﺑﺮﺍﻱ ﺛﺒﺖ ﺑﺮﺧﻲ ﺍﺯ ﻭﻗﺎﻳﻊ ﻓﺮﺍﻫﻢ‬
‫ﻣﻲ ﺁﻭﺭﺩ ﻛﻪ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ ‪:‬‬
‫‪ -‬ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ‬
‫‪ -‬ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺭﻭﺷﻦ ﺷﺪﻥ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﻧﻤﻲ‬ ‫ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮ ﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﺫﺧﻴﺮﻩ ﻣﻲ ﺷﻮﻧﺪ ﻭ ﺩﺭ ﺻﻮﺭﺕ ﻗﻄﻊ ﺑﺮﻕ ﺍﺯ ﺑﻴﻦ‬
‫ﺭﻭﻧﺪ ‪.‬‬
‫ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﻱ ﺁﻣﺎﺭﻱ ﺗﻨﻬﺎ ﺍﺯ ﻃﺮﻳﻖ ‪ PC‬ﻗﺎﺑﻞ ﻧﻤﺎﻳﺶ ﻫﺴﺘﻨﺪ ﻭ ﺩﺳﺘﺮﺳﻲ ﺑﻪ ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﻓﻘﻂ‬
‫ﺩﺭ ﺻﻮﺭﺕ ﮐﺎﺭ ﺑﺎ ﻧﺮﻡ ﺍﻓﺰﺍﺭ ﺍﻣﮑﺎﻥ ﭘﺬﻳﺮ ﺍﺳﺖ ﻭ ﻣﺸﺎﻫﺪﻩ ﺍﻳﻦ ﺷﻤﺎﺭﻧﺪﻩ ﻫﺎ ﺩﺭ ﻛﻨﺘﺮﻟﺮ ﺍﻣﮑﺎﻥ ﭘﺬﻳﺮ‬
‫ﻧﻤﻲ ﺑﺎﺷﺪ ‪.‬‬
‫‪21‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -8‬ﻧﮕﻬﺪﺍﺭﻱ‬

‫ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺑﺎﺯ ﻧﮑﻨﻴﺪ‬


‫ﻗﺴﻤﺖ ﻗﺎﺑﻞ ﺗﻌﻤﻴﺮﻱ ﺩﺭ ﺩﺍﺧﻞ ﺁﻥ ﻭﺟﻮﺩ ﻧﺪﺍﺭﺩ ‪.‬‬

‫ﺩﺭ ﺻﻮﺭﺕ ﻧﻴﺎﺯ ﺑﺮﺍﻱ ﺗﻤﻴﺰ ﮐﺮﺩﻥ ﺁﻥ ﺍﺯ ﭘﺎﺭﭼﻪ ﻧﻤﺪﺍﺭ ﺍﺳﺘﻔﺎﺩﻩ ﮐﻨﻴﺪ ﻭ ﺍﺯ ﻣﻮﺍﺩ ﺷﻴﻤﻴﺎﻳﻲ ﺍﺳﺘﻔﺎﺩﻩ‬
‫ﻧﮑﻨﻴﺪ ‪.‬‬

‫‪ – 9‬ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻛﻨﺘﺮﻟﺮ‬

‫ﺍﺯ ﺣﺎﻟﺖ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺩﺭ ﺗﻨﻈﻴﻢ ﺗﺎﻳﻤﺮﻫﺎ ‪ ،‬ﺗﻌﺮﻳﻒ ﺣﺪﻭﺩ ﮐﺎﺭ ﺳﻴﺴﺘﻢ ﻭ ﭘﻴﮑﺮﺑﻨﺪﻱ ﺳﻴﺴﺘﻢ ﺍﺳﺘﻔﺎﺩﻩ‬
‫ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫ﺑﺮﺍﻱ ﻭﺍﺭﺩ ﺷﺪﻥ ﺑﻪ ﺍﻳﻦ ﺣﺎﻟﺖ ﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﺩﮐﻤﻪ ‪ Menu‬ﺭﺍ ﺑﺮﺍﻱ ﻣﺪﺕ ‪ 5‬ﺛﺎﻧﻴﻪ ﻧﮕﻪ ﺩﺍﺭﻳﺪ ‪،‬‬
‫ﺑﺮﺍﻱ ﺍﻳﻦ ﻛﺎﺭ ﻻﺯﻡ ﺍﺳﺖ ﮐﻪ ﻭﺭﻭﺩﻱ ‪) Program Lock‬ﺗﺮﻣﻴﻨﺎﻝ ‪ (24‬ﺑﺎﺯ ﺑﺎﺷﺪ ‪ .‬ﺍﮔﺮ ﻭﺭﻭﺩﻱ‬
‫ﻣﺮﺑﻮﻃﻪ ﺯﻣﻴﻦ ﺷﻮﺩ ﺍﺟﺎﺯﻩ ﺗﻐﻴﻴﺮﺍﺕ ﻏﻴﺮ ﻣﺠﺎﺯ ﺩﺭ ﻣﻘﺎﺩﻳﺮ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺩﺍﺩﻩ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ﺍﺯ ﺍﻳﻨﺮﻭ‬
‫ﺗﻮﺻﻴﻪ ﻣﻲ ﺷﻮﺩ ﮐﻪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﺭﺍ ﺣﺘﻤﺎ ﺑﻪ ﺯﻣﻴﻦ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫ﺣﺎﻟﺖ ‪ Program‬ﺗﺎﺛﻴﺮﻱ ﺩﺭ ﻋﻤﻠﮑﺮﺩ ﻛﻨﺘﺮﻟﺮ ﻧﺪﺍﺭﺩ ﺍﺯ ﺍﻳﻨﺮﻭﻣﻲ ﺗﻮﺍﻥ ﺩﺭ ﻣﻮﺍﻗﻌﻲ ﮐﻪ ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﺩﺭﺣﺎﻝ ﮐﺎﺭ ﺍﺳﺖ ﻭﺍﺭﺩ ﺍﻳﻦ ﺣﺎﻟﺖ ﺷﺪ ﻭ ﻣﻘﺎﺩﻳﺮ ﺭﺍ ﺗﻐﻴﻴﺮ ﺩﺍﺩ ‪.‬‬

‫ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺍﺭﺩ ﺣﺎﻟﺖ ‪ Program‬ﻣﻲ ﺷﻮﺩ ﭼﻨﺎﻧﭽﻪ ﺩﻛﻤﻪ ‪ Menu‬ﻓﺸﺮﺩﻩ ﺷﻮﺩ‬
‫ﻧﻤﺎﻳﺸﮕﺮ ﺷﻤﺎﺭﻩ ﭘﺎﺭﺍﻣﺘﺮ ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ﻭ ﺑﺎ ﺭﻫﺎ ﺷﺪﻥ ﺩﻛﻤﻪ ‪ Menu‬ﻧﻤﺎﻳﺸﮕﺮ ﻣﻘﺪﺍﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫ﺭﺍ ﻧﻤﺎﻳﺶ ﻣﻲ ﺩﻫﺪ ﻭ ﺍﻭﻟﻴﻦ ﺷﻤﺎﺭﻩ ﺑﺮﻧﺎﻣﻪ ”‪ “000‬ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫ﻫﺮ ﺑﺎﺭ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﺩﮐﻤﻪ ‪ Menu‬ﺳﺒﺐ ﺭﻓﺘﻦ ﺑﻪ ﭘﺎﺭﺍﻣﺘﺮ ﺷﻤﺎﺭﻩ ﺑﻌﺪ ﻣﻲ ﺷﻮﺩ ‪ .‬ﺑﺎ ﻓﺸﺎﺭ ﺩﺍﺩﻥ ﻭ ﻧﮕﻪ‬
‫ﺩﺍﺷﺘﻦ ﺩﮐﻤﻪ ‪ Menu‬ﺑﺎﻋﺚ ﺍﻓﺰﺍﻳﺶ ﺑﺎ ﮔﺎﻡ ‪ 10‬ﺗﺎﻳﻲ ﺩﺭ ﺷﻤﺎﺭﻩ ﭘﺎﺭﺍﻣﺘﺮ ﻣﻲ ﺷﻮﺩ ‪ .‬ﺑﻌﺪ ﺍﺯ ﺭﺳﻴﺪﻥ‬
‫ﺑﻪ ﺁﺧﺮﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺩﻭﺑﺎﺭﻩ ﺍﻭﻟﻴﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫‪22‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﺑﺮﺍﻱ ﺍﻓﺰﺍﻳﺶ ﻭ ﻛﺎﻫﺶ ﻣﻘﺪﺍﺭ ﻳﮏ ﭘﺎﺭﺍﻣﺘﺮ ﺍﺯ ﺩﮐﻤﻪ ﻫﺎﻱ  ﻭ  ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﺪ ‪ .‬ﺑﺮﺍﻱ ﺍﻓﺰﺍﻳﺶ ‪/‬‬
‫ﻛﺎﻫﺶ ﻣﻘﺪﺍﺭ ﻳﮏ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺎ ﮔﺎﻡ ‪ 10‬ﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﺩﮐﻤﻪ ﻫﺎﻱ  ﻭ  ﺭﺍ ﻓﺸﺎﺭ ﺩﺍﺩﻩ ﻭ ﻧﮕﻪ‬
‫ﺩﺍﺭﻳﺪ ‪.‬‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺑﺮﻧﺎﻣﻪ ﺩﺭ ﺣﺎﻓﻈﻪ ﻏﻴﺮﻓﺮﺍﺭ ﺳﻴﺴﺘﻢ ﻧﮕﻬﺪﺍﺭﻱ ﻣﻲ ﺷﻮﻧﺪ ﺍﺯ ﺍﻳﻨﺮﻭ ﺑﺎ ﻗﻄﻊ ﺑﺮﻕ ﺍﻳﻦ ﻣﻘﺎﺩﻳﺮ‬
‫ﺣﻔﻆ ﺧﻮﺍﻫﻨﺪ ﺷﺪ ‪.‬‬
‫ﺑﺮﺍﻱ ﺧﺮﻭﺝ ﺍﺯ ﺣﺎﻟﺖ ‪ Progarm‬ﮐﺎﻓﻲ ﺍﺳﺖ ﮐﻪ ﻳﮑﻲ ﺍﺯ ﺩﮐﻤﻪ ﻫﺎﻱ ﺗﻐﻴﻴﺮﺣﺎﻟﺖ ﺭﺍ ﻓﺸﺎﺭ ﺩﻫﻴﺪ‬
‫ﻭ ﻳﺎ ﻛﻠﻴﺪﻫﺎﻱ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺑﻪ ﻣﺪﺕ‪ 1‬ﺩﻗﻴﻘﻪ ﺩﺳﺖ ﻧﺰﻧﻴﺪ ‪.‬‬

‫ﺟﺪﻭﻝ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﻭﺍﺣﺪ‬ ‫ﺗﻨﻈﻴﻢ‬ ‫ﺷﺮﺡ‬
‫ﻛﺎﺭﺧﺎﻧﻪ‬
‫ﻧﺴﺒﺖ ﺗﺒﺪﻳﻞ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﺟﺮﻳﺎﻥ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ‬
‫‪0‬‬ ‫ﺟﺮﻳﺎﻥ ﺍﻭﻟﻴﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ‬ ‫‪A‬‬ ‫‪500‬‬
‫ﻣﻲ ﺷﻮﺩ ‪ .‬ﻫﻤﻪ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ ﻫﺎﻱ ﺟﺮﻳﺎﻥ ﻣﻲ ﺑﺎﻳﺴﺖ ﺩﺍﺭﺍﻱ‬
‫ﻧﺴﺒﺖ ﺗﺒﺪﻳﻞ ﻳﻜﺴﺎﻥ ﺑﺎﺷﻨﺪ‪ .‬ﺛﺎﻧﻮﻳﻪ ﺗﺮﺍﻧﺲ ﺟﺮﻳﺎﻥ ﺑﺎﻳﺪ ‪ 5‬ﺁﻣﭙﺮ‬
‫ﺑﺎﺷﺪ ‪ .‬ﺑﺮﺍﻱ ﻣﻘﺎﺩﻳﺮ ﺑﺎﻻﻱ ‪ 990‬ﺁﻣﭙﺮ ‪ %10‬ﻣﻘﺪﺍﺭ ﺣﻘﻴﻘﻲ ﺭﺍ‬
‫ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﺎﻳﻴﺪ ‪ ،‬ﺍﻳﻦ ﻣﻘﺎﺩﻳﺮ ﺑﻪ ﺻﻮﺭﺕ ﻛﻴﻠﻮ ﺁﻣﭙﺮ ﻧﻤﺎﻳﺶ‬
‫ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺭﻧﺞ ﻧﻤﺎﻳﺶ ﻣﻘﺎﺩﻳﺮ ﺟﺮﻳﺎﻥ ﻭ ﺗﻮﺍﻥ ﺍﮐﺘﻴﻮ ﺭﺍ‬


‫ﻣﺸﺨﺺ ﻣﻲ ﮐﻨﺪ‬
‫‪1‬‬ ‫ﻣﻤﻴﺰ ﺍﻋﺸﺎﺭﻱ ﺑﺮﺍﻱ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮ‬
‫‪0‬‬
‫‪000-999 : 0‬‬
‫ﺟﺮﻳﺎﻥ‬
‫‪0.00-9.99 : 1‬‬
‫‪00.0-99.9 : 2‬‬

‫ﺍﮔﺮ ﻣﻘﺪﺍﺭ ﺟﺮﻳﺎﻥ ﺍﺯ ﺍﻳﻦ ﺣﺪ ﺩﺭ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ‬


‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-024‬ﺑﺎﻻﺗﺮ ﺭﻭﺩ ﭘﻴﻐﺎﻡ ‪ OverLoad‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ‬
‫ﻣﺤﺪﻭﺩﻳﺖ ﺍﺿﺎﻓﻪ ﺟﺮﻳﺎﻥ‬ ‫‪A‬‬ ‫‪500‬‬
‫‪2‬‬ ‫ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻤﻲ ﺑﺎﻳﺪ ﻣﻄﺎﺑﻖ ﺑﺎ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ‬
‫)‪( Over Current‬‬
‫ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-000‬ﺑﺎﺷﺪ‪.‬‬

‫‪23‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﻭﺍﺣﺪ‬ ‫ﺗﻨﻈﻴﻢ‬ ‫ﺷﺮﺡ‬
‫ﻛﺎﺭﺧﺎﻧﻪ‬
‫ﺍﮔﺮ ﻣﻘﺪﺍﺭ ﺗﻮﺍﻥ ﺍﺯ ﺍﻳﻦ ﺣﺪ ﺩﺭ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫‪ P-024‬ﺑﺎﻻﺗﺮ ﺭﻭﺩ ﭘﻴﻐﺎﻡ ‪ OverLoad‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ‬
‫‪3‬‬ ‫ﻣﺤﺪﻭﺩﻳﺖ ﺍﺿﺎﻓﻪ ﺗﻮﺍﻥ‬ ‫‪KW‬‬ ‫‪350‬‬
‫ﺷﺪ ‪ .‬ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻤﻲ ﺑﺎﻳﺪ ﻣﻄﺎﺑﻖ ﺑﺎ ﻣﻘﺪﺍﺭ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-000‬ﺑﺎﺷﺪ‪.‬‬
‫‪4‬‬ ‫ﻣﺤﺪﻭﺩﻩ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ‬ ‫‪V‬‬ ‫‪100‬‬ ‫ﭼﻨﺎﻧﭽﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﺑﺎﺱ ﺑﺎﺭ ﭘﺎﻳﻴﻦ ﺗﺮ ﺍﺯ ﺣﺪ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺑﺎﺷﺪ‬
‫ﺑﺪﻳﻦ ﻣﻌﻨﺎﺳﺖ ﻛﻪ ﺑﺎﺱ ﺑﺎﺭ ﺑﺪﻭﻥ ﺑﺮﻕ ﺍﺳﺖ ‪.‬‬
‫‪5‬‬ ‫ﻣﺤﺪﻭﺩﻩ ﺑﺎﻻﻱ ﻭﻟﺘﺎﮊ ﺑﺎﺱ ﺑﺎﺭ‬ ‫‪V‬‬ ‫‪500‬‬ ‫ﭼﻨﺎﻧﭽﻪ ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﺑﺎﺱ ﺑﺎﺭ ﺑﺎﻻ ﺗﺮ ﺍﺯ ﺣﺪ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺑﺎﺷﺪ‬
‫ﺑﺪﻳﻦ ﻣﻌﻨﺎﺳﺖ ﻛﻪ ﺑﺎﺱ ﺑﺎﺭ ﺑﺪﻭﻥ ﺑﺮﻕ ﺍﺳﺖ ‪.‬‬
‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻳﮑﻲ ﺍﺯ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ‬
‫ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ )ﺩﺭ ﺷﺮﺍﻳﻄﻲ ﮐﻪ ﺯﻳﺮ ﺑﺎﺭ ﺍﺳﺖ( ‪ ،‬ﺁﻻﺭﻡ‬
‫‪6‬‬ ‫ﺣﺪ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪V‬‬ ‫‪180‬‬
‫ﻭﻟﺘﺎﮊ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﻳﮑﻲ ﺍﺯ ﻓﺎﺯﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﻻﻱ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ‬


‫ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ) ﺩﺭ ﺷﺮﺍﻳﻄﻲ ﮐﻪ ﺯﻳﺮ ﺑﺎﺭ ﺍﺳﺖ ( ‪ ،‬ﺁﻻﺭﻡ‬
‫‪7‬‬ ‫ﺣﺪ ﺑﺎﻻﻱ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪V‬‬ ‫‪270‬‬
‫ﻭﻟﺘﺎﮊ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ‪ ،‬ﻭ ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬


‫ﺑﺮﺳﺪ ‪ ،‬ﺁﻻﺭﻡ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ‬
‫‪8‬‬ ‫ﺁﻻﺭﻡ ﺣﺪ ﭘﺎﻳﻴﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬ ‫‪Hz‬‬ ‫‪30‬‬
‫ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪ .‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺗﻨﻬﺎ ﺩﺭ ﺯﻣﺎﻧﻲ ﮐﻪ ﻣﻮﺗﻮﺭ ‪Run‬‬
‫ﺍﺳﺖ ﻭ ﺑﻌﺪ ﺍﺯ ‪ Delay Time‬ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-023‬‬
‫ﺗﻌﻴﻴﻦ ﻣﻲ ﮔﺮﺩﺩ ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺯﻳﺮ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬


‫ﺑﺮﺳﺪ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺍﻳﻦ‬
‫ﻫﺸﺪﺍﺭ ﭘﺎﻳﻴﻦ ﺭﻓﺘﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ‬
‫‪Hz‬‬ ‫‪40‬‬ ‫ﺍﺧﻄﺎﺭ ﺑﻌﺪ ﺍﺯ ﺗﺎﺧﻴﺮﻱ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺗﻌﻴﻴﻦ‬
‫ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫‪9‬‬ ‫ﻣﻲ ﮔﺮﺩﺩ ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪.‬‬

‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﻻﻱ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ‬


‫ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫‪Hz‬‬ ‫‪54‬‬
‫‪10‬‬ ‫ﻫﺸﺪﺍﺭ ﺑﺎﻻﺭﻓﺘﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺍﺯ‬
‫ﻭ ﺍﻳﻦ ﺍﺧﻄﺎﺭ ﺑﻌﺪ ﺍﺯ ﺗﺎﺧﻴﺮﻱ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺗﻌﻴﻴﻦ‬
‫ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫ﻣﻲ ﮔﺮﺩﺩ ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ‬

‫‪24‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﻭﺍﺣﺪ‬ ‫ﺗﻨﻈﻴﻢ‬ ‫ﺷﺮﺡ‬
‫ﻛﺎﺭﺧﺎﻧﻪ‬
‫ﺍﮔﺮ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﺑﺎﻻﻱ ﺣﺪ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺳﺪ ‪ ،‬ﺁﻻﺭﻡ ‪ Speed‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ‬
‫‪11‬‬ ‫ﺁﻻﺭﻡ ﺑﺎﻻﺭﻓﺘﻦ ﻓﺮﮐﺎﻧﺲ ﮊﻧﺮﺍﺗﻮﺭ ﺍﺯ‬ ‫‪Hz‬‬ ‫‪57‬‬ ‫ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪ .‬ﺍﻳﻦ ﺁﻻﺭﻡ ﺗﻨﻬﺎ ﺩﺭ ﺯﻣﺎﻧﻲ ﮐﻪ ﻣﻮﺗﻮﺭ‬
‫ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬ ‫‪ Run‬ﺍﺳﺖ ﻭ ﺑﻌﺪ ﺍﺯ ﺗﺎﺧﻴﺮﻱ ﮐﻪ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P-023‬ﺗﻌﻴﻴﻦ‬
‫ﻣﻲ ﮔﺮﺩﺩ ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫ﺍﮔﺮ ﻭﻟﺘﺎﺯ ﺑﺎﻃﺮﻱ ﺑﻪ ﺯﻳﺮ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬
‫ﻫﺸﺪﺍﺭ ﭘﺎﻳﻴﻦ ﺁﻣﺪﻥ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺍﺯ‬
‫‪12‬‬ ‫ﺑﺮﺳﺪ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ‪ Battery‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫‪V‬‬ ‫‪9.0‬‬
‫ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬

‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺑﻪ ﺑﺎﻻﻱ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬


‫ﻫﺸﺪﺍﺭ ﺑﺎﻻﺭﻓﺘﻦ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺍﺯ‬ ‫‪V‬‬ ‫‪31.0‬‬
‫‪13‬‬ ‫ﺑﺮﺳﺪ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Battery‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﻣﻘﺪﺍﺭ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫ﺍﮔﺮ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺑﻪ ﺑﺎﻻﻱ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ‬
‫ﺁﻻﺭﻡ ﺑﺎﻻﺭﻓﺘﻦ ﻭﻟﺘﺎﮊ ﺑﺎﻃﺮﻱ ﺍﺯ ﻣﻘﺪﺍﺭ‬
‫‪14‬‬ ‫ﺑﺮﺳﺪ ‪ ،‬ﺁﻻﺭﻡ ‪ Battery‬ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ‬
‫‪V‬‬ ‫‪33.0‬‬
‫ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫ﺭﺍ ﻣﺘﻮﻗﻒ ﻣﻲ ﮐﻨﺪ ‪.‬‬

‫ﺍﮔﺮ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺩﺭ ﺁﻧﺎﻟﻮﮒ ﻭﺭﻭﺩﻱ ﺑﻪ‬


‫‪15‬‬ ‫ﺯﻳﺮ ﺍﻳﻦ ﺣﺪ ﺑﺮﺳﺪ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪Oil Pressure‬‬
‫ﻫﺸﺪﺍﺭﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬ ‫‪Bar‬‬ ‫‪1.5‬‬
‫ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻓﻘﻂ ﻭﻗﺘﻲ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫ﮐﻪ ﻣﻮﺗﻮﺭ ‪ Run‬ﺑﺎﺷﺪ ﻭ ﺯﻣﺎﻥ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-023‬‬
‫ﺳﭙﺮﻱ ﺷﺪﻩ ﺑﺎﺷﺪ‪.‬‬
‫ﺍﮔﺮ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺩﺭ ﺁﻧﺎﻟﻮﮒ ﻭﺭﻭﺩﻱ ﺑﻪ‬
‫ﺯﻳﺮ ﺍﻳﻦ ﺣﺪ ﺑﺮﺳﺪ ‪ ،‬ﺁﻻﺭﻡ ﻣﺮﺑﻮﻁ ﺑﻪ ‪Oil Pressure‬‬
‫‪16‬‬ ‫ﺁﻻﺭﻡ ﭘﺎﻳﻴﻦ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬ ‫ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﺍﻳﻦ ﻭﺭﻭﺩﻱ ﻓﻘﻂ ﻭﻗﺘﻲ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫‪Bar‬‬ ‫‪1.0‬‬
‫ﮐﻪ ﻣﻮﺗﻮﺭ ‪ Run‬ﺑﺎﺷﺪ ﻭ ﺯﻣﺎﻥ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫‪ P-023‬ﺳﭙﺮﻱ ﺷﺪﻩ ﺑﺎﺷﺪ ‪.‬‬

‫ﺍﮔﺮ ﺩﻣﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺗﻮﺳﻂ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺁﻧﺎﻟﻮﮒ ﺍﺯ‬
‫‪C‬‬ ‫‪90‬‬ ‫ﺩﻣﺎﻱ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮ ﺍﺯ ﻣﻘﺪﺍﺭ ﺗﻌﺮﻳﻒ ﺷﺪﻩ‬
‫‪17‬‬ ‫ﻫﺸﺪﺍﺭ ﺑﺎﻻ ﺑﻮﺩﻥ ﺩﻣﺎﻱ ﺁﺏ‬
‫ﺷﻮﺩ ‪ ،‬ﻫﺸﺪﺍﺭ ﻣﺮﺑﻮﻁ ﺑﻪ ‪ High Temp‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ‬
‫ﺷﺪ ‪.‬‬

‫‪25‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﻭﺍﺣﺪ‬ ‫ﺗﻨﻈﻴﻢ‬ ‫ﺷﺮﺡ‬
‫ﻛﺎﺭﺧﺎﻧﻪ‬
‫ﺍﮔﺮ ﺩﻣﺎﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺗﻮﺳﻂ ﻭﺭﻭﺩﻱ ﺁﻧﺎﻟﻮﮒ ﺍﺯ‬
‫ﺩﻣﺎﻱ ﺗﻨﻈﻴﻢ ﺷﺪﻩ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮ ﺷﻮﺩ ‪ ،‬ﺁﻻﺭﻡ ﻣﺮﺑﻮﻁ ﺑﻪ‬
‫‪18‬‬ ‫ﺁﻻﺭﻡ ﺑﺎﻻ ﺑﻮﺩﻥ ﺩﻣﺎﻱ ﺁﺏ‬ ‫‪C‬‬ ‫‪98‬‬
‫‪ High Temp‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ‬
‫ﺧﻮﺍﻫﺪ ﮐﺮﺩ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ‬
‫‪ : 0‬ﺳﻨﺴﻮﺭ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺴﺖ ﻭ ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ‪ P-131‬ﺗﺎ ‪ P-142‬ﺗﻌﻴﻴﻦ‬
‫ﻣﻲ ﮔﺮﺩﺩ ‪.‬‬
‫‪-‬‬ ‫‪1‬‬
‫‪VDO 0-7bars (10-180 ohms) : 1‬‬
‫‪19‬‬ ‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ‬
‫‪VDO 0-10bars (280-20 ohms) : 2‬‬
‫‪DATCON 0-7bars (240-33 ohms) : 3‬‬
‫‪DATCON0-10bars (240-33 ohms) : 4‬‬
‫‪DATCON 0-7bars (0-90 ohms) : 5‬‬
‫‪DATCON 0-10bars (0-90 ohms) : 6‬‬
‫‪DATCON 0-7bars (75-10 ohms) : 7‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎﻱ ﺁﺏ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ‬


‫‪ : 0‬ﺳﻨﺴﻮﺭ ﺍﺳﺘﺎﻧﺪﺍﺭﺩ ﻧﻴﺴﺖ ﻭ ﻣﺸﺨﺼﺎﺕ ﺳﻨﺴﻮﺭ ﺩﺭ ﺟﺪﻭﻝ‬
‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻭ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ‪ P-143‬ﻭ ‪ P-154‬ﺗﻌﻴﻴﻦ‬
‫‪20‬‬ ‫ﺍﻧﺘﺨﺎﺏ ﻧﻮﻉ ﺳﻨﺴﻮﺭ ﺩﻣﺎﻱ ﺁﺏ‬ ‫‪-‬‬ ‫‪1‬‬ ‫ﻣﻲ ﮔﺮﺩﺩ ‪.‬‬
‫‪VDO : 1‬‬
‫‪DATCON DAH type : 2‬‬
‫‪DATCON DAL type : 3‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺎﻋﺚ ﻣﺤﺪﻭﺩ ﻛﺮﺩﻥ ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ ﻭ ﺑﺮﻕ ﺷﻬﺮﺑﻪ‬
‫ﻛﻤﻚ ﻳﻚ ﺑﺎﺯﻩ ﻛﻨﺘﺮﻟﻲ ﺟﻬﺖ ﺟﻠﻮﮔﻴﺮﻱ ﺍﺯ ﺧﻄﺎﻱ‬
‫ﺍﺣﺘﻤﺎﻟﻲ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬
‫‪21‬‬ ‫ﻭﻟﺘﺎﮊ ﻫﻴﺴﺘﺮﻳﺰﻳﺲ‬ ‫‪V‬‬ ‫‪8‬‬ ‫ﺑﺮﺍﻱ ﻣﺜﺎﻝ ﻫﻨﮕﺎﻣﻲ ﻛﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺭﺩ ﭘﺎﺭﺍﻣﺘﺮ‪P_004‬‬
‫ﺑﻪ ﻋﻨﻮﺍﻥ ﺣﺪ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﻣﻲ ﺷﻮﺩ ﻭ ﺩﺭ ﻫﻨﮕﺎﻡ‬
‫ﻗﻄﻊ ﺑﺮﻕ ﺷﻬﺮ ﺟﻤﻊ ﺩﻭ ﭘﺎﺭﺍﻣﺘﺮ ‪ P_004+P_021‬ﺑﻪ ﻋﻨﻮﺍﻥ‬
‫ﺣﺪ ﭘﺎﻳﻴﻦ ﻭﻟﺘﺎﮊ ﺩﺭ ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﻣﻲ ﺷﻮﺩ ‪ .‬ﺗﻮﺻﻴﻪ ﻣﻲ ﺷﻮﺩ‬
‫ﻣﻘﺪﺍﺭ ‪ 8‬ﺑﺮﺍﻱ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺩﺭﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﻮﺩ‬

‫‪26‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﻭﺍﺣﺪ‬ ‫ﺗﻨﻈﻴﻢ‬ ‫ﺷﺮﺡ‬
‫ﻛﺎﺭﺧﺎﻧﻪ‬
‫‪22‬‬ ‫ﺣﺮﺍﺭﺕ ﮔﺮﻡ ﻛﻦ ﻣﻮﺗﻮﺭ‬ ‫‪ºC‬‬ ‫‪50‬‬ ‫ﭼﻨﺎﻧﭽﻪ ﻧﻴﺎﺯ ﺑﺎﺷﺪ ﻣﻮﺗﻮﺭ ﺑﺪﻭﻥ ﺑﺎﺭ ﻛﺎﺭ ﻛﺮﺩﻩ ﺗﺎ ﺑﻪ ﺣﺮﺍﺭﺕ‬
‫ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺑﺮﺳﺪ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺗﻌﻴﻴﻦ ﻛﻨﻨﺪﻩ ﻣﻘﺪﺍﺭ ﺣﺮﺍﺭﺕ‬
‫ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮﻱ ﺭﺍ ﺗﻌﺮﻳﻒ ﻣﻲ ﮐﻨﺪ ﮐﻪ ﺑﻌﺪ ﺍﺯ‬
‫‪23‬‬ ‫ﺗﺎﻳﻤﺮ ﺗﺎﺧﻴﺮ‬ ‫‪Sec‬‬ ‫‪8‬‬
‫‪ Run‬ﺷﺪﻥ ﻣﻮﺗﻮﺭ‪،‬ﺩﺭ ﺁﻥ ﺯﻣﺎﻥ ‪ Fault‬ﻫﺎ ﻓﻌﺎﻝ ﻧﻤﻲ ﺷﻮﻧﺪ ‪.‬‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺯﻣﺎﻥ ﺗﺎﺧﻴﺮﻱ ﺍﺳﺖ ﮐﻪ ﺩﺭ ﺻﻮﺭﺕ ﺗﺠﺎﻭﺯ ﮐﺮﺩﻥ‬


‫ﺗﺎﻳﻤﺮﺗﺎﺧﻴﺮﺍﺿﺎﻓﻪ ﺟﺮﻳﺎﻥ) ‪Over‬‬ ‫ﺟﺮﻳﺎﻥ ﻭ ﺗﻮﺍﻥ ﺍﮐﺘﻴﻮ ﺍﺯ ﺣﺪﻭﺩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ) ‪ P-002‬ﻭ‬
‫‪24‬‬ ‫‪ ، (Current‬ﺍﺿﺎﻓﻪ ﺗﻮﺍﻥ ﻭ‬ ‫‪ (P-003‬ﻻﺯﻡ ﺍﺳﺖ ﺳﭙﺮﻱ ﺷﻮﺩ ﺗﺎ ﺁﻻﺭﻡ ﻇﺎﻫﺮ ﮔﺮﺩﺩ ‪.‬‬
‫ﻓﺮﮐﺎﻧﺲ‬ ‫‪Sec‬‬ ‫‪3‬‬ ‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﺮﺍﻱ ﺣﺪﻭﺩ ﻓﺮﮐﺎﻧﺲ )‪ P-008‬ﻭ ‪ (P-011‬ﻭ‬
‫ﻇﺎﻫﺮ ﺷﺪﻥ ﺁﻻﺭﻡ ‪ Speed Fault‬ﻧﻴﺰ ﺻﺎﺩﻕ ﺍﺳﺖ‪.‬‬

‫‪25‬‬ ‫‪Not Used‬‬


‫ﺯﻣﺎﻥ ﺑﻴﻦ ﻓﻌﺎﻝ ﺷﺪﻥ ﺷﻴﺮ ﺳﻮﺧﺖ ﻭ ﺍﺳﺘﺎﺭﺕ ﻣﻮﺗﻮﺭ ‪ ،‬ﺩﺭ ﺍﻳﻦ‬
‫‪26‬‬ ‫ﺯﻣﺎﻥ ﭘﻴﺶ ﮔﺮﻡ ﻛﻦ‬ ‫‪Sec‬‬ ‫‪1‬‬
‫ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﺭﻟﻪ ﻣﺮﺑﻮﻁ ﺑﻪ ﭘﻴﺶ ﮔﺮﻡ ﻛﻦ ﺩﺭ ﺻﻮﺭﺕ ﻓﻌﺎﻝ‬
‫ﺑﻮﺩﻥ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺮﺑﻮﻃﻪ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ‪.‬‬

‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻣﺸﺨﺺ ﻣﻲ ﮐﻨﺪ ‪ .‬ﺩﺭ ﺻﻮﺭﺕ ﺭﻭﺷﻦ‬


‫ﺷﺪﻥ ﮊﻧﺮﺍﺗﻮﺭ ‪ ،‬ﺍﺳﺘﺎﺭﺕ ﺑﻪ ﺻﻮﺭﺕ ﺍﺗﻮﻣﺎﺗﻴﮏ ﻗﺒﻞ ﺍﺯ ﺑﻪ ﭘﺎﻳﺎﻥ‬
‫ﺯﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ‬ ‫‪Sec‬‬ ‫‪6‬‬
‫‪27‬‬ ‫ﺭﺳﻴﺪﻥ ﺍﻳﻦ ﺯﻣﺎﻥ ﻗﻄﻊ ﻣﻲ ﺷﻮﺩ‬

‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻓﺎﺻﻠﻪ ﺯﻣﺎﻧﻲ ﺑﻴﻦ ﺩﻭ ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻣﺸﺨﺺ‬


‫‪28‬‬ ‫ﺯﻣﺎﻥ ﺑﻴﻦ ﺍﺳﺘﺎﺭﺕ ﻫﺎ‬ ‫‪Sec‬‬ ‫‪10‬‬
‫ﻣﻲ ﮐﻨﺪ ‪.‬‬
‫‪29‬‬ ‫ﺗﺎﻳﻤﺮ ﮔﺮﻡ ﻛﻦ ﻣﻮﺗﻮﺭ‬ ‫‪Sec‬‬ ‫‪3‬‬ ‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺟﻬﺖ ﮔﺮﻡ ﻛﺮﺩﻥ ﻣﻮﺗﻮﺭ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﻣﻘﺪﺍﺭ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ‪. P-037‬‬
‫‪30‬‬ ‫‪Not Used‬‬

‫ﺑﺎﺯﻩ ﺯﻣﺎﻧﻲ ﻛﺎﺭﻛﺮﺩ ﺑﺪﻭﻥ ﺑﺎﺭ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻣﻨﻈﻮﺭﺧﻨﮏ ﺷﺪﻥ‬


‫ﺯﻣﺎﻥ ﺧﻨﻚ ﺷﺪﻥ‬ ‫‪Min‬‬ ‫‪1.0‬‬
‫‪31‬‬ ‫ﻣﻮﺗﻮﺭ ‪ ،‬ﺑﻌﺪ ﺍﺯ ﺑﺮﮔﺸﺖ ﺑﺮﻕ ﺷﻬﺮ ﻭ ﺍﻧﺘﻘﺎﻝ ﺑﺎﺭ ﺑﻪ ﺑﺮﻕ ﺷﻬﺮ ‪.‬‬
‫‪32‬‬ ‫‪Not Used‬‬
‫‪33‬‬ ‫‪Not Used‬‬

‫‪27‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﻭﺍﺣﺪ‬ ‫ﺗﻨﻈﻴﻢ‬ ‫ﺷﺮﺡ‬
‫ﻛﺎﺭﺧﺎﻧﻪ‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮﻳﻦ ﺣﺪ ﺯﻣﺎﻥ ﺭﺍ ﺑﺮﺍﻱ ﺗﻮﻗﻒ ﻣﻮﺗﻮﺭ ﺗﻌﻴﻴﻦ‬
‫ﻣﻲ ﮐﻨﺪ ‪ .‬ﺩﺭ ﻃﻮﻝ ﺍﻳﻦ ﺯﻣﺎﻥ ﺭﻟﻪ ﺧﺮﻭﺟﻲ ‪ Stop‬ﻓﻌﺎﻝ‬
‫‪34‬‬ ‫ﺗﺎﻳﻤﺮ ﺧﺎﻣﻮﺵ ﺷﺪﻥ‬ ‫‪Sec‬‬ ‫‪10‬‬ ‫ﺧﻮﺍﻫﺪ ﺷﺪ ‪) .‬ﺍﻟﺒﺘﻪ ﺍﮔﺮ ﺑﻪ ﻭﺳﻴﻠﻪ ﺑﺮﻧﺎﻣﻪ ﺗﻌﺮﻳﻒ ﺷﻮﺩ( ﺍﮔﺮ‬
‫ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﻣﺘﻮﻗﻒ ﻧﺸﻮﺩ ‪ ،‬ﺁﻻﺭﻡ‬
‫‪ Stop Fail‬ﻇﺎﻫﺮ ﺧﻮﺍﻫﺪ ﺷﺪ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻴﺸﺘﺮﻳﻦ ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻣﺸﺨﺺ‬
‫‪35‬‬ ‫ﺗﻌﺪﺍﺩ ﺩﻓﻌﺎﺕ ﺍﺳﺘﺎﺭﺕ‬ ‫‪-‬‬ ‫‪3‬‬
‫ﻣﻲ ﮐﻨﺪ ‪.‬‬
‫ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﻣﺪﺕ ﺯﻣﺎﻧﻲ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ ﮐﻪ ﺧﺮﻭﺟﻲ‬
‫‪ Horn‬ﺩﺭ ﻃﻮﻝ ﺁﻥ ﻓﻌﺎﻝ ﺧﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫‪36‬‬ ‫ﺗﺎﻳﻤﺮ ﺁﮊﻳﺮ‬ ‫‪Sec‬‬ ‫‪10‬‬
‫ﺍﮔﺮ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ‪ 0‬ﺑﺎﺷﺪ ﺑﻪ ﻣﻌﻨﻲ ﻧﺎﻣﺤﺪﻭﺩ ﺑﻮﺩﻥ ﻣﺪﺕ ﺯﻣﺎﻥ‬
‫ﺁﮊﻳﺮ ﻣﻲ ﺑﺎﺷﺪ‪.‬‬
‫ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺭﻭﺵ ﮔﺮﻡ ﻛﺮﺩﻥ ﻣﻮﺗﻮﺭ ﺗﻌﻴﻴﻦ ﻣﻲ ﺷﻮﺩ ﻭ‬
‫‪-‬‬ ‫‪0‬‬ ‫ﺩﻳﺰﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺗﺎ ﺯﻣﺎﻧﻲ ﻛﻪ ﻣﻮﺗﻮﺭ ﮔﺮﻡ ﻧﺸﻮﺩ ﻗﺎﺑﻠﻴﺖ ﭘﺬﻳﺮﻓﺘﻦ‬
‫ﺑﺎﺭ ﺭﺍ ﻧﺪﺍﺭﺩ‪.‬‬
‫‪37‬‬ ‫ﻧﻮﻉ ﮔﺮﻡ ﻛﻦ ﻣﻮﺗﻮﺭ‬ ‫‪ : 0‬ﻣﻮﺗﻮﺭ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﺯﻣﺎﻥ ﺗﺎﻳﻤﺮ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫‪ P-029‬ﮔﺮﻡ ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫‪ : 1‬ﻣﻮﺗﻮﺭ ﺗﺎ ﻣﺤﺪﻭﺩﻩ ﻣﻘﺪﺍﺭ ﺩﻣﺎﻱ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ ‪P-‬‬
‫‪ 022‬ﮔﺮﻡ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﻳﺎ ﺣﺪﺍﻗﻞ ﺩﺭ ﺯﻣﺎﻥ ﺗﻌﻴﻴﻦ ﺷﺪﻩ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-029‬ﮔﺮﻡ ﺧﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫‪ : 0‬ﻭﺭﻭﺩﻱ ﺷﺎﺭﮊ ﻫﺸﺪﺍﺭ ﺩﻫﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ ﻧﺴﺎﺯﺩ‬


‫‪38‬‬ ‫ﻭﺭﻭﺩﻱ ‪ Charge‬ﺁﻻﺭﻡ‬ ‫‪-‬‬ ‫‪0‬‬
‫‪ : 1‬ﻭﺭﻭﺩﻱ ﺷﺎﺭﮊ ‪ Alarm‬ﺩﻫﺪ ﻭ ﻣﻮﺗﻮﺭ ﺭﺍ ﻣﺘﻮﻗﻒ ﺳﺎﺯﺩ ‪.‬‬

‫ﭼﻨﺎﻧﺠﻪ ﺍﺧﺘﻼﻑ ﻓﺮﻛﺎﻧﺲ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬


‫‪39‬‬ ‫ﺍﺧﺘﻼﻑ ﻓﺮﻛﺎﻧﺲ‬ ‫‪HZ‬‬ ‫‪1‬‬
‫ﺑﺎﻻﻱ ﻣﺤﺪﻭﺩﻩ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﺍﻧﺠﺎﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ‪.‬‬

‫‪40‬‬ ‫ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ‬ ‫‪V‬‬ ‫‪10‬‬ ‫ﭼﻨﺎﻧﺠﻪ ﺍﺧﺘﻼﻑ ﻭﻟﺘﺎﮊ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ ﺑﺎﻻﻱ‬
‫ﻣﺤﺪﻭﺩﻩ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﺍﻧﺠﺎﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ‬

‫‪41‬‬ ‫ﺍﺧﺘﻼﻑ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ‬ ‫‪deg .‬‬ ‫‪5‬‬ ‫ﭼﻨﺎﻧﺠﻪ ﺍﺧﺘﻼﻑ ﺯﺍﻭﻳﻪ ﻓﺎﺯﻱ ﺑﻴﻦ ﺑﺎﺱ ﺑﺎﺭ ﻭ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﺑﺎﻻﻱ ﻣﺤﺪﻭﺩﻩ ﺗﻌﻴﻴﻦ ﺷﺪﻩ ﻋﻤﻞ ﺳﻨﻜﺮﻭﻥ ﺍﻧﺠﺎﻡ ﻧﺨﻮﺍﻫﺪ ﺷﺪ‬

‫‪28‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪Pgm‬‬ ‫‪Definition‬‬ ‫‪Unit‬‬ ‫‪Std.val‬‬ ‫‪Description‬‬
‫ﻧﺎﻡ ﭘﺎﺭﺍﻣﺘﺮ‬ ‫ﻭﺍﺣﺪ‬ ‫ﺗﻨﻈﻴﻢ‬ ‫ﺷﺮﺡ‬
‫ﻛﺎﺭﺧﺎﻧﻪ‬
‫ﭼﻨﺎﻧﭽﻪ ﻣﻘﺪﺍﺭ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﺗﻮﺍﻥ ﺍﻛﺘﻴﻮ ﻓﺎﺯ ‪ U‬ﮊﻧﺮﺍﺗﻮﺭ‬
‫ﻣﻨﻔﻲ ﺑﺎﺷﺪ ﻭ ﺑﺎﻻﻱ ﺯﻣﺎﻥ ﻣﺤﺪﻭﺩﻩ ﺗﻌﺮﻳﻒ ﺷﺪﻩ ﺩﺭ ﭘﺎﺭﺍﻣﺘﺮ‬
‫‪KW‬‬ ‫‪ P-024‬ﺑﺮﻭﺩ ﺍﻋﻼﻡ ﺧﻄﺎﻱ ‪ Reverse Power‬ﺍﻧﺠﺎﻡ‬
‫‪42‬‬ ‫ﻣﺤﺪﻭﺩﻩ ﺗﻮﺍﻥ ﻣﻌﻜﻮﺱ‬ ‫‪0‬‬
‫ﺧﻮﺍﻫﺪ ﺷﺪ‪ .‬ﻣﻘﺪﺍﺭ ﺗﻮﺍﻥ ﻭﺍﺭﺩ ﺷﺪﻩ ﺑﺎﻳﺪ ﺑﺮﺣﺴﺐ ﻣﺸﺨﺼﻪ‬
‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-000‬ﻭﺍﺭﺩ ﮔﺮﺩﺩ ﻭ ﭼﻨﺎﻧﭽﻪ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮ ﺑﻪ ﻣﻘﺪﺍﺭ‬
‫ﺻﻔﺮ ﺗﻨﻈﻴﻢ ﮔﺮﺩﺩ ﻋﻤﻞ ﭼﻚ ﻛﺮﺩﻥ ‪Reverse Power‬‬
‫ﻏﻴﺮ ﻓﻌﺎﻝ ﻣﻲ ﮔﺮﺩﺩ ‪.‬‬
‫‪ : 0‬ﻣﻮﺩﻡ ﻣﺘﺼﻞ ﻧﻴﺴﺖ ‪ .‬ﺍﺯ ﭘﻮﺭﺕ ﺳﺮﻳﺎﻝ ﺑﺮﺍﻱ ﺍﺗﺼﺎﻝ ﺑﻪ ‪PC‬‬
‫ﺍﺗﺼﺎﻝ ﻣﻮﺩﻡ‬ ‫‪-‬‬ ‫‪0‬‬
‫‪43‬‬ ‫ﺍﺳﺘﻔﺎﺩﻩ ﻣﻲ ﺷﻮﺩ ‪.‬‬
‫‪ : 1‬ﻣﻮﺩﻡ ﻣﺘﺼﻞ ﺍﺳﺖ ‪.‬‬
‫‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Service Request‬ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ‬
‫ﺍﻳﻦ ﺯﻣﺎﻥ ﺍﺯ ﺁﺧﺮﻳﻦ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ‬
‫‪44‬‬ ‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ‬ ‫‪Hours‬‬ ‫‪200‬‬
‫ﺷﺪ ‪.‬‬
‫)ﺳﺎﻋﺖ ﮐﺎﺭﮐﺮﺩ ﻣﻮﺗﻮﺭ(‬
‫ﺩﺭ ﺻﻮﺭﺕ ﺍﻧﺘﺨﺎﺏ ﻋﺪﺩ ‪ 0‬ﻧﻴﺎﺯ ﺑﻪ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ‬
‫ﺑﺮﺍﻱ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ ﺑﻮﺩ ‪.‬‬
‫‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Service Request‬ﺑﻌﺪ ﺍﺯ ﺳﭙﺮﻱ ﺷﺪﻥ‬
‫ﺍﻳﻦ ﺯﻣﺎﻥ ﺍﺯ ﺁﺧﺮﻳﻦ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ ﺭﻭﺷﻦ ﺧﻮﺍﻫﺪ ﺷﺪ‬
‫ﻣﺪﺕ ﺯﻣﺎﻥ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ‬
‫‪45‬‬ ‫‪Month‬‬ ‫‪6‬‬ ‫ﺩﺭ ﺻﻮﺭﺕ ﺍﻧﺘﺨﺎﺏ ﻋﺪﺩ ‪ 0‬ﻧﻴﺎﺯ ﺑﻪ ﺗﻌﻤﻴﺮﺍﺕ ﻭ ﻧﮕﻬﺪﺍﺭﻱ‬
‫)ﻣﺎﻫﺎﻧﻪ(‬
‫ﺑﺮﺍﻱ ﮊﻧﺮﺍﺗﻮﺭ ﻧﺨﻮﺍﻫﺪ ﺑﻮﺩ‬
‫‪46‬‬ ‫‪Not Used‬‬
‫‪47‬‬ ‫‪Not Used‬‬
‫‪48‬‬ ‫‪Not Used‬‬
‫‪49‬‬ ‫‪Not Used‬‬
‫‪50‬‬ ‫‪Not Used‬‬

‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-051‬ﻭ ‪ P-052‬ﻋﻤﻠﻴﺎﺕ ﻣﺨﺘﻠﻒ ﺭﺍ ﺑﺮﺍﻱ ﺭﻟﻪ ﻫﺎﻱ ﺧﺮﻭﺟﻲ ﺗﻌﺮﻳﻒ ﻣﻴﻨﻤﺎﻳﻨﺪ ‪ .‬ﺍﻳﻦ‬
‫ﻛﻨﺘﺮﻟﺮ ‪ 5‬ﺭﻟﻪ ﺧﺮﻭﺟﻲ ﺩﺍﺭﺩ ﻭ ‪ 2‬ﻋﺪﺩ ﺍﺯ ﺁﻧﻬﺎ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻫﺴﺘﻨﺪ ‪ .‬ﺭﻟﻪ ﻫﺎﻳﻲ ﮐﻪ ﻋﻤﻠﻴﺎﺕ ﺛﺎﺑﺖ‬
‫ﺩﺍﺭﻧﺪ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ ‪ Start ، Fuel‬ﻭ ﺭﻟﻪ ﺳﻨﻜﺮﻭﻥ ﭼﻚ ‪.‬‬

‫‪29‬‬
DKG217 ‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

. ‫ﻓﺎﻧﮑﺸﻦ ﻫﺎﻱ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﺑﺮﺍﻱ ﺭﻟﻪ ﻫﺎﻱ ﺧﺮﻭﺟﻲ ﺩﺭ ﺷﮑﻞ ﺯﻳﺮ ﻧﺸﺎﻥ ﺩﺍﺩﻩ ﺷﺪﻩ ﺍﺳﺖ‬

‫ﻟﻴﺴﺖ ﻓﺎﻧﻜﺸﻦ ﻫﺎﻱ ﺭﻟﻪ ﺍﻱ‬


Program Description Std 00 Fuel 24 Oil Sender Alarm
25 Temp Sender Alarm
51 1 ‫ﻋﻤﻠﮑﺮﺩ ﺭﻟﻪ‬ 01 01 Horn 26 Speed Alarm
52 2 ‫ﻋﻤﻠﮑﺮﺩ ﺭﻟﻪ‬ 03 02 Start 27 Start Fail Alarm
03 Stop 28 Change Alarm
04 - 29 OverLoad Alarm
05 - 30 Voltage Alarm
06 Choke 31 Battery High Alarm
07 Preheat 32 Oil Switch Warning
08 Alarm 33 Temp Switch Warn.
09 Warnning 34 -
10 Alarm+Warnning 35 -
11 - 36 Emerg Stop Warn.
12 - 37 Spare-1 Warning
13 - 38 -
14 Check Synch. 39 -
15 - 40 Oil Sender Warning
16 Oil Switch Alarm 41 Temp Sender Warn.
17 Temp Switch Alarm 42 Speed Warning
18 Level Switch Alarm 43 -
19 - 44 Change Warning
20 Emerg.Stop alarm 45 Battery Low Warning
21 Spare-1 alarm 46 -
22 - 47 Battery High Warn.
23 -

. ‫ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﺭﺍ ﺑﺮ ﻋﻬﺪﻩ ﺩﺍﺭﻧﺪ‬P-088 ‫ ﺗﺎ‬P-053 ‫ﭘﺎﺭﺍﻣﺘﺮﻫﺎﻱ ﺷﻤﺎﺭﻩ‬
: ‫ﺍﻣﻜﺎﻧﺎﺕ ﻭﺭﻭﺩﻱ ﻫﺎﻱ ﺩﻳﺠﻴﺘﺎﻝ ﻗﺎﺑﻞ ﺑﺮﻧﺎﻣﻪ ﺭﻳﺰﻱ ﻋﺒﺎﺭﺗﻨﺪ ﺍﺯ‬
Operation -(‫ ﻫﺸﺪﺍﺭ ﻭ ﻏﻴﺮﻩ‬، ‫ ﻋﻤﻠﻴﺎﺕ ﺑﺮ ﺭﻭﻱ ﻭﺭﻭﺩ ﺳﻴﮕﻨﺎﻝ ﺑﻪ ﺳﻴﺴﺘﻢ )ﺁﻻﺭﻡ‬-
Fault Monitoring – ‫ ﺩﺭﻧﻈﺮ ﮔﺮﻓﺘﻦ ﺳﻴﮕﻨﺎﻟﻬﺎﻱ ﺧﻄﺎ‬-
Latching – ‫ ﻗﻔﻞ ﺷﺪﻥ ﺑﺮ ﺭﻭﻱ ﺳﻴﮕﻨﺎﻝ ﺧﻄﺎ‬-
Switching – (Bat- ‫ ﻭ‬Bat+) ‫ ﭘﻼﺭﻳﺘﻪ‬-
(NC,NO) ‫ ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬-
Response Delay – ‫ ﺗﺎﺧﻴﺮ ﺩﺭ ﭘﺎﺳﺨﮕﻮﻳﻲ‬-
30
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫ﻭﺭﻭﺩﻱ )‪ (Switch‬ﮐﻢ ﺑﻮﺩﻥ ﻓﺸﺎﺭ ﺭﻭﻏﻦ )‪(Low Oil Pressure Switch‬‬
‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : 0‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪53‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : 2‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : 3‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : 0‬ﻫﻤﻴﺸﻪ‬
‫‪54‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪1‬‬
‫‪ : 1‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : 2‬ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : 0‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪55‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪1‬‬
‫‪ : 1‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪ : 0‬ﻧﺮﻣﺎﻟﻲ ‪Open‬‬
‫‪56‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : 1‬ﻧﺮﻣﺎﻟﻲ ‪Close‬‬
‫‪ : 0‬ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ‬
‫‪57‬‬ ‫ﺳﻮﺋﻴﭽﻴﻨﮓ‬ ‫‪0‬‬
‫‪ : 1‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ‬

‫‪ : 0‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪58‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪1‬‬
‫‪ : 1‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ 4‬ﺛﺎﻧﻴﻪ(‬

‫ﻭﺭﻭﺩﻱ )ﺳﻮﺋﻴﭻ( ﺩﻣﺎﻱ ﺑﺎﻻﻱ ﺁﺏ )‪(High Temprature Switch‬‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : 0‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪59‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : 2‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : 3‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : 0‬ﻫﻤﻴﺸﻪ‬
‫‪60‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : 1‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : 2‬ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : 0‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪61‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪1‬‬
‫‪ : 1‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪ : 0‬ﻧﺮﻣﺎﻟﻲ ‪Open‬‬
‫‪62‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : 1‬ﻧﺮﻣﺎﻟﻲ ‪Close‬‬
‫‪ : 0‬ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ‬
‫‪63‬‬ ‫ﺳﻮﺋﻴﭽﻴﻨﮓ‬ ‫‪0‬‬
‫‪ : 1‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ‬
‫‪ : 0‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪64‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪1‬‬
‫‪ : 1‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ 4‬ﺛﺎﻧﻴﻪ(‬
‫‪31‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫ﻭﺭﻭﺩﻱ ﻓﻌﺎﻝ ﻛﺮﺩﻥ ﺑﺎﺱ )‪(Dead Bus Enable‬‬
‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : 0‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪65‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪3‬‬
‫‪) Warning : 2‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : 3‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : 0‬ﻫﻤﻴﺸﻪ‬
‫‪66‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : 1‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : 0‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪67‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪0‬‬
‫‪ : 1‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪ : 0‬ﻧﺮﻣﺎﻟﻲ ‪Open‬‬
‫‪68‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : 1‬ﻧﺮﻣﺎﻟﻲ ‪Close‬‬
‫‪ : 0‬ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ‬
‫‪69‬‬ ‫ﺳﻮﺋﻴﭽﻴﻨﮓ‬ ‫‪0‬‬
‫‪ : 1‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ‬
‫‪ : 0‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪70‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪1‬‬
‫‪ : 1‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ 4‬ﺛﺎﻧﻴﻪ(‬

‫ﻭﺭﻭﺩﻱ ‪Emergency Stop‬‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : 0‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪71‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : 2‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : 3‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : 0‬ﻫﻤﻴﺸﻪ‬
‫‪72‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : 1‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : 2‬ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : 0‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪73‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪0‬‬
‫‪ : 1‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪ : 0‬ﻧﺮﻣﺎﻟﻲ ‪Open‬‬
‫‪74‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : 1‬ﻧﺮﻣﺎﻟﻲ ‪Close‬‬
‫‪ : 0‬ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ‬
‫‪75‬‬ ‫‪Switching‬‬ ‫‪0‬‬
‫‪ : 1‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ‬
‫‪ : 0‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪76‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪0‬‬
‫‪ : 1‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ 4‬ﺛﺎﻧﻴﻪ(‬

‫‪32‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫ﻭﺭﻭﺩﻱ ﺫﺧﻴﺮﻩ ﺧﻄﺎ ) ‪(Spare-1 Fault‬‬
‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬
‫‪ : 0‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪77‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪0‬‬
‫‪) Warning : 2‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : 3‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : 0‬ﻫﻤﻴﺸﻪ‬
‫‪78‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : 1‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : 2‬ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : 0‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪79‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪0‬‬
‫‪ : 1‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪ : 0‬ﻧﺮﻣﺎﻟﻲ ‪Open‬‬
‫‪80‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : 1‬ﻧﺮﻣﺎﻟﻲ ‪Close‬‬
‫‪ : 0‬ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ‬
‫‪81‬‬ ‫‪Switching‬‬ ‫‪0‬‬
‫‪ : 1‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ‬
‫‪ : 0‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪82‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪1‬‬
‫‪ : 1‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ 4‬ﺛﺎﻧﻴﻪ(‬

‫ﻭﺭﻭﺩﻱ ﻗﻔﻞ ﺑﺮﻧﺎﻣﻪ‬


‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Std‬‬

‫‪ : 0‬ﺁﻻﺭﻡ )ﻣﻮﺗﻮﺭ ﻣﺘﻮﻗﻒ ﺧﻮﺍﻫﺪ ﺷﺪ ﻭ ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬


‫‪83‬‬ ‫ﻋﻤﻠﮑﺮﺩ‬ ‫‪3‬‬
‫‪) Warning : 2‬ﺭﻟﻪ ‪ Horn‬ﻋﻤﻞ ﺧﻮﺍﻫﺪ ﮐﺮﺩ(‬
‫‪ : 3‬ﻋﻤﻞ ﻧﺨﻮﺍﻫﺪ ﮐﺮﺩ‬
‫‪ : 0‬ﻫﻤﻴﺸﻪ‬
‫‪84‬‬ ‫ﻧﻤﺎﻳﺶ ‪Fault‬‬ ‫‪0‬‬
‫‪ : 1‬ﺑﻌﺪ ﺍﺯ ﺯﻣﺎﻥ ‪Hold Off‬‬
‫‪ : 2‬ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩﺍﺷﺖ‬
‫‪ : 0‬ﻗﻔﻞ ﺷﻮﺩ‬
‫‪85‬‬ ‫ﻗﻔﻞ ﺷﺪﻥ‬ ‫‪0‬‬
‫‪ : 1‬ﻗﻔﻞ ﻧﺸﻮﺩ‬
‫‪ : 0‬ﻧﺮﻣﺎﻟﻲ ‪Open‬‬
‫‪86‬‬ ‫ﻧﻮﻉ ﮐﻨﺘﺎﮐﺖ‬ ‫‪0‬‬
‫‪ : 1‬ﻧﺮﻣﺎﻟﻲ ‪Close‬‬
‫‪ : 0‬ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ‬
‫‪87‬‬ ‫‪Switching‬‬ ‫‪0‬‬
‫‪ : 1‬ﻣﺜﺒﺖ ﺑﺎﻃﺮﻱ‬
‫‪ : 0‬ﺗﺎﺧﻴﺮ ﻧﺪﺍﺭﺩ‬
‫‪88‬‬ ‫ﺗﺎﺧﻴﺮ ﭘﺎﺳﺨﮕﻮﻳﻲ‬ ‫‪0‬‬
‫‪ : 1‬ﺗﺎﺧﻴﺮ ﺩﺍﺭﺩ )‪ 4‬ﺛﺎﻧﻴﻪ(‬
‫‪33‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﺍﻳﻦ‬ ‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-089‬ﺗﺎ ‪ P-100‬ﻣﺸﺨﺼﺎﺕ ﺍﻫﻢ‪ -‬ﺑﺎﺭ ﺳﻨﺴﻮﺭ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ ‪.‬‬
‫ﻣﺸﺨﺼﺎﺕ ﺣﺪﺍﮐﺜﺮ ﺩﺭ ‪ 6‬ﻧﻘﻄﻪ ﺗﻌﻴﻴﻦ ﻣﻲ ﮔﺮﺩﺩ ‪ .‬ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﺍﻓﺰﺍﻳﺶ‬
‫ﺍﻫﻢ ﺍﺯ ﭘﺎﻳﻴﻦ ﺑﻪ ﺑﺎﻻ ﻭﺍﺭﺩ ﺷﻮﻧﺪ ‪ .‬ﺑﺮﺍﻱ ﻧﻘﺎﻃﻲ ﮐﻪ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﺷﻮﻧﺪ ﺑﺎﻳﺪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ‬
‫ﺷﻮﺩ ‪ .‬ﻣﺸﺨﺼﺎﺕ ﺯﻳﺮ ﻣﺸﺨﺼﺎﺕ ﻳﮏ ﺳﻨﺴﻮﺭ ﺍﺳﺖ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ ﻧﻤﻮﻧﻪ ﻭ ﻣﺜﺎﻝ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ‬
‫ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ‪.‬‬

‫‪0.0 bar…..240 ohms‬‬


‫‪1.0 bar ….. 218 ohms‬‬
‫‪5.0 bar ….. 183 ohms‬‬
‫‪10.0 bar ….. 103 ohms‬‬

‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Unit‬‬ ‫‪Value‬‬

‫‪89‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪1‬‬ ‫‪ohms‬‬ ‫‪103‬‬


‫‪90‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪1‬‬ ‫‪bar‬‬ ‫‪10.0‬‬
‫‪91‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪2‬‬ ‫‪ohms‬‬ ‫‪153‬‬
‫‪92‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪2‬‬ ‫‪bar‬‬ ‫‪5.0‬‬
‫‪93‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪3‬‬ ‫‪ohms‬‬ ‫‪218‬‬
‫‪94‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪3‬‬ ‫‪bar‬‬ ‫‪1.0‬‬
‫‪95‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪4‬‬ ‫‪ohms‬‬ ‫‪240‬‬
‫‪96‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪4‬‬ ‫‪bar‬‬ ‫‪0.0‬‬
‫‪97‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪5‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪98‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪5‬‬ ‫‪bar‬‬ ‫‪0.0‬‬
‫‪99‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪6‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪100‬‬ ‫ﻓﺸﺎﺭ ﻧﻘﻄﻪ ‪6‬‬ ‫‪bar‬‬ ‫‪0.0‬‬

‫‪34‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-101‬ﺗﺎ ‪ P-112‬ﻣﺸﺨﺼﺎﺕ ﺍﻫﻢ‪ -‬ﺩﺭﺟﻪ ﺳﻨﺴﻮﺭ ﺩﻣﺎ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ ‪ .‬ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ‬
‫ﺣﺪﺍﮐﺜﺮ ﺩﺭ ‪ 6‬ﻧﻘﻄﻪ ﺗﻌﻴﻴﻦ ﻣﻲ ﮔﺮﺩﺩ ‪ .‬ﺍﻳﻦ ﻣﺸﺨﺼﺎﺕ ﻣﻲ ﺑﺎﻳﺴﺖ ﺑﻪ ﺻﻮﺭﺕ ﺍﻓﺰﺍﻳﺶ ﺍﻫﻢ ﺍﺯ ﭘﺎﻳﻴﻦ‬
‫ﺑﻪ ﺑﺎﻻ ﻭﺍﺭﺩ ﺷﻮﻧﺪ ‪ .‬ﺑﺮﺍﻱ ﻧﻘﺎﻃﻲ ﮐﻪ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﺷﻮﻧﺪ ﺑﺎﻳﺪ ﻣﻘﺪﺍﺭ ﺻﻔﺮ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﺷﻮﺩ ‪ .‬ﻣﺸﺨﺼﺎﺕ‬
‫ﺯﻳﺮ ﻣﺸﺨﺼﺎﺕ ﻳﮏ ﺳﻨﺴﻮﺭ ﺍﺳﺖ ﮐﻪ ﺑﻪ ﺻﻮﺭﺕ ﻧﻤﻮﻧﻪ ﻭ ﻣﺜﺎﻝ ﺩﺭ ﺍﻳﻦ ﭘﺎﺭﺍﻣﺘﺮﻫﺎ ﻗﺮﺍﺭ ﺩﺍﺩﻩ ﻣﻲ‬
‫ﺷﻮﺩ ‪.‬‬

‫‪38 C ….. 342 ohm‬‬


‫‪82 C ….. 71 ohm‬‬
‫‪104 C ….. 40 ohm‬‬
‫‪121 C ….. 30 ohm‬‬

‫‪Prog‬‬ ‫‪Description‬‬ ‫‪Unit‬‬ ‫‪Value‬‬

‫‪101‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪1‬‬ ‫‪ohms‬‬ ‫‪30‬‬


‫‪102‬‬ ‫ﺩﻣﺎﻱ ﻧﻘﻄﻪ ‪1‬‬ ‫‪C‬‬ ‫‪121‬‬
‫‪103‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪2‬‬ ‫‪ohms‬‬ ‫‪40‬‬
‫‪104‬‬ ‫ﺩﻣﺎﻱ ﻧﻘﻄﻪ ‪2‬‬ ‫‪C‬‬ ‫‪104‬‬
‫‪105‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪3‬‬ ‫‪ohms‬‬ ‫‪71‬‬
‫‪106‬‬ ‫ﺩﻣﺎﻱ ﻧﻘﻄﻪ ‪3‬‬ ‫‪C‬‬ ‫‪82‬‬
‫‪107‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪4‬‬ ‫‪ohms‬‬ ‫‪342‬‬
‫‪108‬‬ ‫ﺩﻣﺎﻱ ﻧﻘﻄﻪ ‪4‬‬ ‫‪C‬‬ ‫‪38‬‬
‫‪109‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪5‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪110‬‬ ‫ﺩﻣﺎﻱ ﻧﻘﻄﻪ ‪5‬‬ ‫‪C‬‬ ‫‪0‬‬
‫‪111‬‬ ‫ﻣﻘﺎﻭﻣﺖ ﻧﻘﻄﻪ ‪6‬‬ ‫‪ohms‬‬ ‫‪0‬‬
‫‪112‬‬ ‫ﺩﻣﺎﻱ ﻧﻘﻄﻪ ‪6‬‬ ‫‪C‬‬ ‫‪0‬‬

‫‪35‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﭘﺎﺭﺍﻣﺘﺮ ‪ P-113‬ﺗﺎ ‪ P-118‬ﺗﻨﻈﻴﻤﺎﺕ ﺗﺎﺭﻳﺦ ﻭ ﺯﻣﺎﻥ ﺭﺍ ﺗﻌﻴﻴﻦ ﻣﻲ ﮐﻨﺪ ‪.‬‬


‫‪pgm‬‬ ‫‪Definiton‬‬ ‫‪Unit‬‬ ‫‪Std Val‬‬ ‫‪Description‬‬
‫‪113‬‬ ‫ﺳﺎﻝ‬ ‫‪-‬‬ ‫‪00-99‬‬ ‫ﺩﻭ ﺭﻗﻢ ﺁﺧﺮ ﻣﺮﺑﻮﻁ ﺑﻪ ﺳﺎﻝ ﺟﺎﺭﻱ‬
‫‪114‬‬ ‫ﻣﺎﻩ‬ ‫‪-‬‬ ‫‪01-12‬‬ ‫ﻣﺎﻩ ﺟﺎﺭﻱ‬
‫‪115‬‬ ‫ﺗﺎﺭﻳﺦ‬ ‫‪-‬‬ ‫‪01-31‬‬ ‫ﺭﻭﺯ ﺟﺎﺭﻱ ﻣﺎﻩ‬
‫‪116‬‬ ‫ﺭﻭﺯ‬ ‫‪-‬‬ ‫‪0-6‬‬ ‫ﺭﻭﺯ ﺟﺎﺭﻱ ﻫﻔﺘﻪ ) ‪ =0‬ﺩﻭﺷﻨﺒﻪ ‪ =1 ،‬ﺳﻪ ﺷﻨﺒﻪ‪ =2 ،‬ﭼﻬﺎﺭ ﺷﻨﺒﻪ‪،‬‬
‫‪=3‬ﭘﻨﺞ ﺷﻨﺒﻪ ‪ =4 ،‬ﺟﻤﻌﻪ‪ =5 ،‬ﺷﻨﺒﻪ ‪ =6 ،‬ﻳﻜﺸﻨﺒﻪ(‬
‫‪117‬‬ ‫ﺳﺎﻋﺖ‬ ‫‪-‬‬ ‫‪00-23‬‬ ‫ﺳﺎﻋﺖ ﺭﻭﺯ ﺟﺎﺭﻱ‬
‫‪118‬‬ ‫ﺩﻗﻴﻘﻪ‬ ‫‪-‬‬ ‫‪00-59‬‬ ‫ﺩﻗﻴﻘﻪ ﺭﻭﺯ ﺟﺎﺭﻱ‬

‫‪ -11‬ﺭﻓﻊ ﻋﻴﺐ‬

‫ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎﮊ ‪ AC‬ﻳﺎ ﻓﺮﮐﺎﻧﺲ ﻧﻤﺎﻳﺶ ﺩﺍﺩﻩ ﺷﺪﻩ ﺩﺭﺳﺖ ﻧﻴﺴﺖ ‪:‬‬ ‫•‬
‫‪ -‬ﺍﺗﺼﺎﻝ ﺑﺪﻧﻪ ﻣﻮﺗﻮﺭ ﺑﻪ ﺯﻣﻴﻦ ﺭﺍ ﭼﮏ ﮐﻨﻴﺪ ‪) .‬ﺍﻳﻦ ﺁﻳﺘﻢ ﺿﺮﻭﺭﻱ ﺍﺳﺖ( ﺑﺮﺍﻱ ﺁﺯﻣﺎﻳﺶ ﺍﻳﻦ‬
‫ﺍﻣﺮ ﺗﺮﻣﻴﻨﺎﻝ ‪ BAT-‬ﻭ ﺗﺮﻣﻴﻨﺎﻝ ﻧﻮﻝ ﺭﺍ ﺑﻪ ﻳﻜﺪﻳﮕﺮ ﺍﺗﺼﺎﻝ ﺩﺍﺩﻩ ﻭ ﭼﻚ ﻛﻨﻴﺪ ﻛﻪ ﺍﻳﺮﺍﺩ‬
‫ﺑﺮﻃﺮﻑ ﻣﻲ ﺷﻮﺩ‪.‬‬
‫‪ -‬ﻣﻴﺰﺍﻥ ﺧﻄﺎ ﺩﺭ ﺧﻮﺍﻧﺪﻥ ﻣﻘﺎﺩﻳﺮ ﺑﺮﺍﻱ ﮐﻨﺘﺮﻟﺮ ﺑﺮﺍﺑﺮ ‪ -/+ 3‬ﺍﺳﺖ ‪.‬‬
‫‪ -‬ﺍﮔﺮ ﻭﻗﺘﻲ ﮊﻧﺮﺍﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ‪ ،‬ﺧﻄﺎ ﺩﺭ ﺧﻮﺍﻧﺪﻥ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻣﺸﺎﻫﺪﻩ ﺷﻮﺩ ‪،‬‬
‫ﺍﻳﻦ ﺧﻄﺎ ﻣﻤﮑﻦ ﺍﺳﺖ ﻣﺮﺑﻮﻁ ﺑﻪ ﺷﺎﺭﮊﺭ)ﺩﻳﻨﺎﻡ( ﻳﺎ ﺭﮔﻮﻻﺗﻮﺭ ﻭﻟﺘﺎﮊ ﺑﺎﺷﺪ ‪ .‬ﺍﺗﺼﺎﻝ ﺷﺎﺭﮊﺭ ﺭﺍ‬
‫ﺍﺯ ﻣﻮﺗﻮﺭ ﺟﺪﺍ ﮐﻨﻴﺪ ﻭ ﭼﮏ ﮐﻨﻴﺪ ﮐﻪ ﺁﻳﺎ ﺧﻄﺎ ﺑﺮﻃﺮﻑ ﺷﺪﻩ ﻳﺎ ﺧﻴﺮ ‪.‬‬
‫‪ -‬ﺍﮔﺮ ﻫﻨﮕﺎﻣﻲ ﮐﻪ ﺑﺮﻕ ﺷﻬﺮ ﻭﺟﻮﺩ ﺩ ﺍﺭﺩ ﺧﻄﺎ ﺩﺭ ﻣﻘﺎﺩﻳﺮ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﺷﺪﻩ ﻭﺟﻮﺩ ﺩﺍﺷﺖ ‪،‬‬
‫ﺷﺎﺭﮊﺭ )ﺩﻳﻨﺎﻡ( ﻣﻤﮑﻦ ﺍﺳﺖ ﺩﭼﺎﺭ ﻣﺸﮑﻞ ﺷﺪﻩ ﺑﺎﺷﺪ ‪.‬‬

‫ﻣﻘﺎﺩﻳﺮ ‪ Cosφ‬ﻭ ﻳﺎ ‪ KW‬ﻣﻨﻔﻲ ﻫﺴﺘﻨﺪ ﺑﺎ ﻭﺟﻮﺩ ﺍﻳﻨﻜﻪ ﻗﺮﺍﺋﺖ ﺟﺮﻳﺎﻥ ﺻﺤﻴﺢ ﺍﺳﺖ ‪.‬‬ ‫•‬
‫‪ -‬ﭘﻼﺭﻳﺘﻪ ‪ CT‬ﻫﺎ ﺩﺭﺳﺖ ﻣﺘﺼﻞ ﻧﺸﺪﻩ ﺍﻧﺪ ‪ .‬ﭘﻼﺭﻳﺘﻪ ‪ CT‬ﻫﺎ ﺭﺍ ﺗﺼﺤﻴﺢ ﻧﻤﺎﻳﻴﺪ‪.‬‬
‫ﺧﺮﻭﺟﻲ ﻫﺎﻱ ﺗﺮﺍﻧﺴﻔﻮﺭﻣﺮﻫﺎﻱ ﺟﺮﻳﺎﻥ ﺭﺍ ﺩﺭ ﺻﻮﺭﺗﻲ ﮐﻪ ﺍﺯ ﺁﻧﻬﺎ ﺍﺳﺘﻔﺎﺩﻩ ﻧﻤﻲ ﮐﻨﻴﺪ ‪ ،‬ﺍﺗﺼﺎﻝ ﮐﻮﺗﺎﻩ‬
‫ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫‪36‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫ﻫﻨﮕﺎﻣﻲ ﻛﻪ ﻓﺮﻣﺎﻥ ﺭﻭﺷﻦ ﺷﺪﻥ ﻣﻮﺗﻮﺭ ﺩﺍﺩﻩ ﻣﻲ ﺷﻮﺩ ﺳﻠﻮﻧﻮﺋﻴﺪ ﺳﻮﺧﺖ ﻓﻌﺎﻝ ﺷﺪﻩ ﺍﻣﺎ‬ ‫•‬
‫ﻣﻮﺗﻮﺭ ﺭﻭﺷﻦ ﻧﻤﻲ ﺷﻮﺩ ﻭ‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressuer‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﻣﻲ ﻛﻨﺪ‪:‬‬
‫‪ -‬ﻭﺭﻭﺩﻱ ‪ Oil Pressure‬ﻛﻨﺘﺮﻟﺮ ﺑﺎ ﻭﻟﺘﺎﮊ ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ ﺗﻐﺬﻳﻪ ﻧﮕﺮﺩﻳﺪﻩ‪.‬‬
‫‪ Oil Pressure Switch -‬ﻭﺻﻞ ﻧﻴﺴﺖ ‪.‬‬
‫‪ -‬ﺳﻴﻢ ‪ Oil Pressure Switch‬ﻗﻄﻊ ﺷﺪﻩ ﺍﺳﺖ ‪.‬‬
‫‪ Oil Pressure Switch -‬ﺧﺮﺍﺏ ﻣﻲ ﺑﺎﺷﺪ ‪.‬‬
‫‪ -‬ﻛﻨﺘﺎﻛﺖ ‪ Oil Pressure Switch‬ﺑﺎ ﺗﺎﺧﻴﺮ ﺑﺴﺘﻪ ﻣﻲ ﺷﻮﺩ ‪ .‬ﺩﺭ ﺻﻮﺭﺕ ﺑﺴﺘﻪ ﺑﻮﺩﻥ ﺍﻳﻦ‬
‫ﻛﻨﺘﺎﻛﺖ ﻛﻨﺘﺮﻟﺮ ﺍﺳﺘﺎﺭﺕ ﻣﻲ ﺷﻮﺩ ‪ Oil Pressure Switch .‬ﺑﺎﻳﺪ ﺗﻌﻮﻳﺾ ﮔﺮﺩﺩ ‪.‬‬

‫ﻣﻮﺗﻮﺭ ﺑﻌﺪ ﺍﺯ ﻭﻗﻮﻉ ﺍﻭﻟﻴﻦ ﺍﺳﺘﺎﺭﺕ ﺭﻭﺷﻦ ﻧﻤﻲ ﺷﻮﺩ ‪ ،‬ﻛﻨﺘﺮﻟﺮ ﺩﻭﺑﺎﺭﻩ ﺍﺳﺘﺎﺭﺕ ﻧﻤﻲ ﺯﻧﺪ ﻭ‬ ‫•‬
‫‪ LED‬ﻣﺮﺑﻮﻁ ﺑﻪ ‪ Oil Pressure‬ﺷﺮﻭﻉ ﺑﻪ ﭼﺸﻤﮏ ﺯﺩﻥ ﻛﺮﺩﻩ ﺍﺳﺖ‪:‬‬

‫‪ -‬ﻛﻨﺘﺎﻛﺖ ‪ Oil Pressure Switch‬ﺑﺎ ﺗﺎﺧﻴﺮ ﺑﺴﺘﻪ ﻣﻲ ﺷﻮﺩ ‪ .‬ﻣﺎﺩﺍﻣﻴﻜﻪ ﻛﻨﺘﺮﻟﺮ ﻭﺟﻮﺩ‬
‫ﻛﻨﺘﺎﻛﺖ ﻓﺸﺎﺭ ﺭﻭﻏﻦ ﺭﺍ ﺩﺭ ﻭﺭﻭﺩﻱ ﺗﺸﺨﻴﺺ ﺩﺍﺩﻩ ﺍﺳﺖ ﻓﺮﻣﺎﻥ ﺍﺳﺘﺎﺭﺕ ﺩﺍﺩﻩ ﻧﻤﻲ ﺷﻮﺩ‪.‬‬

‫‪ -‬ﺩﺭﺻﻮﺭﺗﻲ ﮐﻪ ‪ Oil Pressure Switch‬ﺑﺴﺘﻪ ﺷﻮﺩ ‪،‬ﻛﻨﺘﺮﻟﺮ ﺍﺳﺘﺎﺭﺕ ﺧﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﭘﺲ‬


‫‪ Oil Pressure Switch‬ﺑﺎﻳﺪ ﺗﻌﻮﻳﺾ ﮔﺮﺩﺩ ‪.‬‬

‫ﻣﻮﺗﻮﺭ ﺍﺳﺘﺎﺭﺕ ﺯﺩﻩ ﻭ ﺭﻭﺷﻦ ﻣﻲ ﺷﻮﺩ ﻭﻟﻲ ﺁﻻﺭﻡ ‪ Start Fail‬ﻓﻌﺎﻝ ﺷﺪﻩ ﻭ ﺳﭙﺲ ﻣﻮﺗﻮﺭ‬ ‫•‬
‫ﺧﺎﻣﻮﺵ ﻣﻲ ﺷﻮﺩ‪.‬‬
‫‪ -‬ﻭﻟﺘﺎﮊ ﻓﺎﺯ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﻛﻨﺘﺮﻟﺮ ﻣﺘﺼﻞ ﻧﺸﺪﻩ ‪ ،‬ﻣﻘﺪﺍﺭ ﻭﻟﺘﺎﮊ ‪ AC‬ﺑﻴﻦ ﺗﺮﻣﻴﻨﺎﻝ ‪ U‬ﻭ ﻧﻮﻝ ﮊﻧﺮﺍﺗﻮﺭ ﺭﺍ ﺩﺭ‬
‫ﭘﺸﺖ ﻛﻨﺘﺮﻟﺮ ﺩﺭ ﺣﺎﻟﻲ ﻛﻪ ﻣﻮﺗﻮﺭ ﺭﻭﺷﻦ ﺍﺳﺖ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻧﻤﺎﻳﻴﺪ‪ .‬ﺍﻣﻜﺎﻥ ﺳﻮﺧﺘﻦ ﻣﺤﺎﻓﻆ ﻓﺎﺯ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﻭﺟﻮﺩ ﺩﺍﺭﺩ‪ .‬ﺍﻣﻜﺎﻥ ﻗﻄﻊ ﺷﺪﻥ ﺳﻴﻢ ﻓﺎﺯ ﺍﺯ ﻛﻨﺘﺮﻟﺮ ﻭﺟﻮﺩ ﺩﺍﺭﺩ‪ .‬ﭼﻨﺎﻧﭽﻪ ﻫﻤﻪ ﺍﺭﺗﺒﺎﻃﺎﺕ‬
‫ﺻﺤﻴﺢ ﺑﺎﺷﺪ ﻛﻠﻴﻪ ﻓﻴﻮﺯﻫﺎ ﺭﺍ ﻗﻄﻊ ﻧﻤﻮﺩﻩ ﻭ ﺳﭙﺲ ﻣﺠﺪﺩﺍ" ﻓﻴﻮﺯﻫﺎ ﺭﺍ ﺑﻪ ﺗﺮﺗﻴﺐ ﺍﺯ ﻓﻴﻮﺯ ﺗﻐﺬﻳﻪ ‪ DC‬ﻭ‬
‫ﺩﺭ ﺍﻧﺘﻬﺎ ﻓﻴﻮﺯ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ‪.‬‬

‫‪37‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫• ﻛﻨﺘﺮﻟﺮ ﺑﻪ ﮐﻨﺪﻱ )ﺩﻳﺮ( ﺍﺳﺘﺎﺭﺕ ﺭﺍ ﻗﻄﻊ ﻣﻲ ﮐﻨﺪ ‪:‬‬


‫‪ -‬ﻭﻟﺘﺎﮊ ﮊﻧﺮﺍﺗﻮﺭ ﺑﻪ ﮐﻨﺪﻱ ﺍﻓﺰﺍﻳﺶ ﭘﻴﺪﺍ ﻣﻲ ﮐﻨﺪ ‪ ،‬ﻫﻤﭽﻨﻴﻦ ﺟﻤﻊ ﻭﻟﺘﺎﮊﻫﺎﻱ ﮊﻧﺮﺍﺗﻮﺭ ﺯﻳﺮ ‪20‬‬
‫ﻭﻟﺖ ﺍﺳﺖ ‪ .‬ﻛﻨﺘﺮﻟﺮﺍﺣﺘﻴﺎﺝ ﺑﻪ ﺣﺪﺍﻗﻞ ‪ 20‬ﻭﻟﺖ ﺑﺮﺍﻱ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻓﺮﮐﺎﻧﺲ ﺩﺍﺭﺩ ﻭ ﺍﺳﺘﺎﺭﺕ‬
‫ﮊﻧﺮﺍﺗﻮﺭ ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﻋﺪﻡ ﺷﻨﺎﺳﺎﻳﻲ ﻓﺮﮐﺎﻧﺲ ﻗﻄﻊ ﻧﺨﻮﺍﻫﺪ ﺷﺪ ‪ .‬ﺑﺮﺍﻱ ﺍﺟﺘﻨﺎﺏ ﺍﺯ ﺍﻳﻦ ﻭﺿﻌﻴﺖ‬
‫ﺗﻨﻬﺎ ﺭﺍﻩ ﺍﺳﺘﻔﺎﺩﻩ ﺍﺯ ﻳﮏ ﺭﻟﻪ ﮐﻤﮑﻲ ﺍﺳﺖ ‪ .‬ﺑﻮﺑﻴﻦ ﺍﻳﻦ ﺭﻟﻪ ﺑﺎﻳﺪ ﺑﻴﻦ )‪ Battery(-‬ﻭ ﺗﺮﻣﻴﻨﺎﻝ‬
‫‪ D+‬ﻣﺮﺑﻮﻁ ﺑﻪ ﺷﺎﺭﮊﺭ ﻣﺘﻨﺎﻭﺏ ﻗﺮﺍﺭ ﮔﻴﺮﺩ ‪ .‬ﮐﻨﺘﺎﮐﺖ ‪ Normaly Close‬ﺍﻳﻦ ﺭﻟﻪ ﺑﺎﻳﺪ ﺑﻪ‬
‫ﺻﻮﺭﺕ ﺳﺮﻱ ﺑﻪ ﺧﺮﻭﺟﻲ ﺍﺳﺘﺎﺭﺕ ﻛﻨﺘﺮﻟﺮ ﻣﺘﺼﻞ ﮔﺮﺩﺩ ‪.‬‬

‫• ﻛﻨﺘﺮﻟﺮ ﻛﺎﺭ ﻧﻤﻲ ﻛﻨﺪ ‪:‬‬


‫‪ -‬ﻭﻟﺘﺎﮊ ‪ DC‬ﻣﺮﺑﻮﻁ ﺑﻪ ﺗﻐﺬﻳﻪ ﻛﻨﺘﺮﻟﺮ )ﺗﺮﻣﻴﻨﺎﻝ ﻫﺎﻱ ‪ 11‬ﻭ ‪ (12‬ﺭﺍ ﺍﻧﺪﺍﺯﻩ ﮔﻴﺮﻱ ﻧﻤﺎﻳﻴﺪ ‪ .‬ﻫﻤﻪ‬
‫ﻓﻴﻮﺯﻫﺎ ﺭﺍ ‪ OFF‬ﮐﻨﻴﺪ ﺳﭙﺲ ﻫﻤﻪ ﻓﻴﻮﺯﻫﺎ ﺭﺍ ‪ ON‬ﮐﻨﻴﺪ ‪ .‬ﺍﺯ ﻣﻨﺒﻊ ﺗﻐﺬﻳﻪ ‪ DC‬ﺷﺮﻭﻉ ﮐﻨﻴﺪ ﻭ‬
‫ﺩﻭﺑﺎﺭﻩ ﻛﻨﺘﺮﻟﺮ ﺭﺍ ﺗﺴﺖ ﮐﻨﻴﺪ ‪.‬‬

‫• ﻛﻨﺘﺮﻟﺮ ﻭﺍﺭﺩ ﺣﺎﻟﺖ ‪ Programming‬ﻧﻤﻲ ﺷﻮﺩ ‪:‬‬


‫‪ -‬ﻭﺭﻭﺩﻱ ﻗﻔﻞ ‪ Programming‬ﻣﺎﻧﻊ ﺍﺯ ﻭﺭﻭﺩ ﮐﻨﺘﺮﻟﺮ ﺑﻪ ﺍﻳﻦ ﺣﺎﻟﺖ ﻣﻲ ﺷﻮﺩ ‪ .‬ﻗﺒﻞ ﺍﺯ‬
‫ﺗﻐﻴﻴﺮﺍﺕ ‪ ،‬ﻭﺭﻭﺩﻱ ﻗﻔﻞ ﺑﺮﻧﺎﻣﻪ ﺭﺍ ﺍﺯ ﻣﻨﻔﻲ ﺑﺎﻃﺮﻱ ﺟﺪﺍ ﻧﻤﺎﻳﻴﺪ ‪ .‬ﻓﺮﺍﻣﻮﺵ ﻧﮑﻨﻴﺪ ﮐﻪ ﺍﻳﻦ‬
‫ﺍﺗﺼﺎﻝ ﺭﺍ ﺑﺮﺍﻱ ﺟﻠﻮﮔﻴﺮﻱ ﺍﺯ ﻭﺍﺭﺩ ﺷﺪﻥ ﺑﻪ ﺣﺎﻟﺖ ‪ ، Program‬ﺩﻭﺑﺎﺭﻩ ﻭﺻﻞ ﻧﻤﺎﻳﻴﺪ ‪.‬‬

‫‪38‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬

‫‪ -12‬ﺍﻋﻼﻡ ﺗﻄﺎﺑﻖ ﻫﺎ‬


‫ﺍﻳﻦ ﻛﻨﺘﺮﻟﺮ ﺍﺯ ﺩﺳﺘﻮﺭﺍﻟﻌﻤﻞ ‪ EU‬ﭘﻴﺮﻭﻱ ﻣﻲ ﮐﻨﺪ‬
‫‪ 73/23/EEC -‬ﻭ ‪(Low Voltage) 93/68/EEC‬‬
‫‪ 89/336/EEC -‬ﻭ ‪ 92/31/EEC‬ﻭ ‪93/68/EEC‬‬
‫ﻣﺂﺧﺬ ﻗﺎﻧﻮﻧﻲ ﻣﺮﺑﻮﻁ ﺑﻪ ‪: Refrence‬‬
‫‪EN 61010 -‬‬
‫‪EN50081-2 -‬‬
‫‪EN50082-2 -‬‬
‫ﻧﺸﺎﻥ ‪ ، CE‬ﻧﺸﺎﻥ ﻣﻲ ﺩﻫﺪ ﮐﻪ ﺍﻳﻦ ﺗﻮﻟﻴﺪ ‪ Safty‬ﻫﺎ ‪ ،‬ﺳﻼﻣﺖ ﻣﺤﻴﻂ ﻭ ﺣﻔﺎﻇﺖ ﻣﺸﺘﺮﻱ‬
‫ﻣﻮﺭﺩ ﻧﻴﺎﺯ ﺍﺭﻭﭘﺎ ﺭﺍ ﺗﺎﻣﻴﻦ ﻣﻴﮑﻨﺪ ‪.‬‬

‫‪ -13‬ﻣﺸﺨﺼﺎﺕ ﻓﻨﻲ‬

‫‪39‬‬
‫ﺭﺍﻫﻨﻤﺎﻱ ﻧﺼﺐ ﻛﻨﺘﺮﻟﺮ ‪DKG217‬‬ ‫ﺷﺮﻛﺖ ﺩﺭﻧﺎ ﻣﻬﺮ‬
‫‪ -14‬ﺩﻳﺎﮔﺮﺍﻡ ﻧﺼﺐ‬

‫‪40‬‬