Professional Documents
Culture Documents
Response Analysis of Plus Shaped Tall Building With Different Bracing Systems Under Wind Load Dr. Ritu Raj
Response Analysis of Plus Shaped Tall Building With Different Bracing Systems Under Wind Load Dr. Ritu Raj
Base shear at 0 degree was higher than 30 degree and 60o degree angles of attack in both
cases i.e. windward side and leeward side of the building. However, at 0o wind incidence
angle, cross bracing exhibited maximum base shear at windward side (7462.84 kN) while V
bracing exhibited maximum base shear at leeward side (12480.57 kN). At 30o and 60o wind
incidence angles, single diagonal bracing system exhibited maximum value of base shear at
both windward and leeward positions of the building. For windward position of the building
(column A), V bracing system showed minimum values of base shear at all angles of attack
with least value of base shear being 4722.85 kN at 30o angle of attack, whereas for leeward
position of the building (column B), isolated condition (without any bracing system) showed
minimum values of base shear at all angles of attack with least value of base shear as
5685.17 kN at 60o angle of attack.
Base moment was seen to be maximum at 0-degree angle of wind attack for both columnA
(windward position) and Column B (Leeward position), as observed in Figures 4 and 5. It was gauged
that base moment (My) in an isolated condition was maximum at 60 degree angle of attack for
column-A (windward position) and at 30 degree angle of attack for Column B (Leeward position).
At all angles of attack, Inverted V bracing showed minimum values of My at windward position and
maximum values of My at leeward position while V bracing showed maximum values of My at
windward position and minimum values of My at leeward position.
Numerical values obtained for twisting moment were negligible in all conditions as compared to
corresponding values of base moment about Y-axis. It was hence concluded that a section designed
for maximum axial force or base moment is safe and can take care of the twisting moment.
Therefore, there is no need to design the section of a column separately for twisting moment.
Deflection in isolated condition was seen to be maximum at all angles of attack with highest value of
deflection as 161.46 mm at leeward position and 0o wind incidence angle. For both i.e. leeward and
windward positions of the building, inverted V bracing had the minimum value of deflection at all
angles of attack with least value of 42.35 mm at 60o wind incidence angle at windward position. At
windward position, reduction of sway by 44.8%, 46.33% and 18.29% while at leeward position,
reduction of sway by 41.37%, 48.61% and 53.17% at 0o , 30o and 60o wind incidence angles
respectively was observed due to Inverted V bracing
Conclusion:
1.Single diagonal bracing system reflected lesser axial force values. The axial force values
show a very slow decrease from bottom to 30% height of the building and then a rapid
decrease to the top.
2. Twisting moment was observed to be negligible in all systems, except in the case of
inverted V-bracing system for column B (Leeward position) at 60-degree angle of attack.
3. It was concluded that, at 0-degree, 30 degree and 60-degree angle of wind attack, V and
inverted V-bracing systems gave comparable values with minimum sway of 67%, 50% and
54% respectively.
3 authors: 1,727
Matin Alaghmanda
Shahid Beheshti Universit
Farid Abdolhossein Pour
16PUBLICATIONS52CITATIONS
Illinois Institute of Technology
SEE PROFIL
Jamshid Mohammad
Illinois Institute of Technolog
84PUBLICATIONS722CITATIONS
SEE PROFIL
OPTIMIZATION METHOD:
In the proposed method of design, the optimization process is considered on the
workbench and works in two steps, simultaneously; first, in the process of the CFD
simulation and second, in the process of the structural design and analysis. In the
first step, models have to be optimized to find a model with the minimum wind
impact and in the second step; the structural systems and elements have to be
optimized to obtain the lowest weight of the structure of the models.
1 author:
Özgür A
Eskişehir Technical University
67 PUBLICATIONS 367 CITATIONS
SEE PROFIL
1. The type of the building affects the ISDR limit specified by TBEC (2018) considerably. The ISDR
limit for steel buildings is half of the ISDR limit for RC buildings. On the other hand, considering
the effective flexural rigidities for the RC sections increases the displacement demands of RC
buildings with the implementation of TBEC (2018).
2. TBEC (2018) enforces to reduce the ISDR limit to its half when the infill walls interact with the
neighboring structural components. This requirement enforces the structural engineer to design
much stiffer buildings. Otherwise, the infill walls should be separated from the structural
components with sufficient gap inbetween. Separation of infill walls will require additional details
to prevent their out-of-plane failure and to fulfill thermal and sound insulation.
3. Smaller ISDR limits were calculated for buildings constructed at soft soil sites especially if the
fundamental period of the building is in the range of 0-0.6 seconds.
Rob J. Smit
Aru
9 PUBLICATIONS 265 CITATIONS
SEE PROFIL
c/ Core building – interstorey drift can be lower d/ Example of building with high
than panel deformation interstorey drift and low panel
deformation
American Standards
Similarly, tests by Freeman (1977) on plasterboard partitions indicated that first cracks
would occur around H/300 to H/400. The paper also discusses how partitions may
effect the overall damping and stiffness of the building.
One of the most comprehensive reviews of the drifts is published by the Council of
Tall Buildings and Urban Habitat (1980) includes a study of the state of the art in the
1970s. Limits for interstorey drift from literature range from H/333 to H/666. Note
that the latter is based upon a wind pressure of 958 Pa (20 lb/ft2) at 30m height,
rather than a specific return period. Most of the drift values in this book refer to those
in common usage, but little mention is made of physical testing. A later study by ASCE
(Ellingwood et al 1986) shown in table 4 compiled the results of various tests to
ascertain the effect of drift on damage to non-structural components. As can be seen,
the critical point where damage becomes visible would appear to be H/500 to H/300.
Of course, the above has focussed on determining a deflection limit for a defined wind
event, ie a deterministic approach. In reality, a probabilistic approach is more realistic,
although not practical in normal building design. Reid and Turkstra (1981) reviewed
this process and concluded the most important variable was the damage limitation
threshold (ie the drift limit!) The other conclusion that can be drawn from their work
is rather simple – flexible buildings are more likely to suffer damage if not detailed
correctly. This is a sliding scale and not based on a single number.
Examples of buildings which have been designed outside of “normal” drift limits are
given in Taranth (2009) The SRZ tower in Dubai (265m high office building, designed by
Lemessuirier Consultants) did not meet a limit of H/500 in design, and this
requirement was relaxed owing to the nature of the deflection (bending rather than
shear). The same argument was applied to the Al Bateen Towers in Dubai (204m). See
table 2.
Another building designed (but not built) with high drifts is the 600m Chicago Spire.
While the drifts are not reported publicly (Burns et al, 2008) the first natural period is
– 18 seconds. This is an indication of a very flexible building which could not meet
traditional deflection limits.
Total building drift
Much of the older literature (CTBUH, 1980) focused on total building drift limits,
discussing occupant comfort and dynamics. At that time, the use of damping to
control building dynamics was in its infancy, as was the understanding of the
sensitivity of building occupants to lateral movement. A survey of engineers in
Boston, Ma indicated that total building drifts used in the 1970s was between H/1000
and H/200, with the majority using a limit of H/400. Two companies reported that
buildings designed with a limit of H/200 had performed adequately in the past,
although no details are given.
A key point to note that in the 1970s US design practice, there was no fixed deflection
criteria. This remains true in today’s practice.
Accommodate movements
In many case, non-structural items can be designed to accommodate deflections.
Items which can be designed for this are cladding panels, partitions, lift cables, services
etc.. As has been discussed previously, overall deflection limits and interstorey drift
limits can in general be a crude measure the functional requirements, and specific
‘performance based’ approaches offer greater flexibility and make more sense
particularly for very tall buildings. In seismic zones construction details are modified to
permit greater movement than normal without damage to cladding and fit-out. .