Professional Documents
Culture Documents
www.elsevier.com/locate/engstruct
Abstract
The paper is devoted to stone masonry structures in view of possible improvement of their dynamic-seismic resistance and durability. Many
existing structures and large models were investigated by the authors in the framework of national and international research projects. The
investigation of a large stone masonry model, tested on the shaking table, had as main purpose the evaluation of the behaviour of new and
rehabilitated masonry structures reinforced with polymer grids produced in the European Union. The test plan consisted of the following parts:
tests of individual material properties; seismic tests of a masonry model reinforced with polymer grids inserted horizontally in prescribed bed
joints; seismic tests of a masonry model reinforced on parts of a wall surface by vertical polymer grids bonded with fibre-reinforced plaster.
The paper presents the selected representative results and synthesis of obtained data. The polymer grids and fibre mortars enhance the seismic
resistance of stone masonry structures. They contribute also to the durability of historical and other stone masonry structures, especially in cases
of vertical polymer grids combined with fibre lime–cement plaster.
c 2007 Elsevier Ltd. All rights reserved.
Keywords: Seismic vulnerability; Retrofitting; Upgrading; Fibre mortars; Polymer grids; Stone masonry; Seismic tests; Seismic resistance
Fig. 1. Deterioration of stones in lower part of defensive walls — the medieval castle. The detail is on the right.
Fig. 2. Example of the old stone masonry building under repair — left; ruins of an old stone masonry structure — right.
Fig. 3. Limestone used for static tests. The end of diagram shows an atypical start of failure due to local crushing of stone (force control mode of compression test).
Table 3
Properties of mortars and polymer grid
4. Limestone masonry model tested on the shaking table Fig. 4. Dimensions of the stone masonry model in plan.
A large, nearly 30 tons heavy, 3D asymmetrical model of The original stone masonry model was not plastered. The
a structure made of natural stone masonry, reinforced with weak lime–cement mortar had a compression strength of
polymer grids, was built and tested on a shaking table in two 0.85–1.0 MPa. The limestone used has mean compression
phases: In the first phase the masonry received polymer grid strength of 67 MPa and Young’s modulus of 37 GPa, higher
reinforcement only in horizontal bed layers. After a series than that of concrete. These characteristics correspond to the
of tests involving seismic loading, and when a reasonable low strength limestone, as shown in Table 2.
damage level was reached, the model was repaired by externally The measurement points on the model were chosen to
bonding the polymer grid with special screws and a fibre monitor the essential absolute accelerations and chosen relative
lime–cement plaster. Then it was tested again in the second displacements. The scheme of the model with the position
phase with increasing seismic loading. The test campaign ran of the measurement points is in Fig. 5. Design and drawings
on the LNEC Lisbon 3D shaking table. An alternative of were elaborated in University of Bucharest, after consulting
the model, without any reinforcement and representing the and agreement of design with ICA SAS Bratislava and LNEC
original historical stone masonry structure, was not built and Lisbon. The model was built and tested in the laboratories of
tested because of available financial sources. However, such LNEC Lisbon (Fig. 6).
research has been executed on large brick masonry models, Before starting the tests, preliminary calculations of the
with the further retrofitting only by vertical polymer grids and natural frequencies were carried out in ICA SAS Bratislava and
fibre lime–cement plaster [16,18,19,24,25]. The results can be LNEC Lisbon, applying a number of finite element calculation
extrapolated also for stone masonry structures. codes and different degrees of FE mesh refinement. Results
The stone masonry model was designed as an asymmetrical of calculations showed the space effect in natural modes with
structure with two windows on the east side, a door on the significant out-off-plane deformation of walls. The apparent
south side, one window on the west side, a solid wall on the modulus of elasticity used in these calculations was E m =
north side and an indent in the north-west corner. No floor slab 2100 MPa, and the Poisson’s ratio ν as equal to 0.1. The
was provided. The lintels above the opening were replaced by estimate of E m was based on experience with other masonry
application of a single strip of polymer grid in the mortar layer. structures, previously analysed and tested. Fig. 7 illustrates
The model was built in full scale 1:1, dimensions in plan were shapes of the first five natural vibration modes. Calculated
4010 × 3580 mm, its height was 3600 mm. The thickness of and experimental values of respective natural frequencies are
the walls was 240 mm. The dimensions of the model in plan are given in Table 4 for the original model and, in Table 5 for the
given in Fig. 4. repaired one. ρ is the considered unit mass, d is the thickness
2198 E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205
Fig. 6. One-storey stone masonry model before tests: (a) Original model — grids only in prescribed bed joints; (b) Repairing procedure; (c) Repaired model —
added vertical grids inside of plaster. The thickness of repaired walls increased to app. 32 cm, due to the rough surface of stone masonry walls.
Fig. 7. Calculated natural modes of vibration of the original stone masonry model.
E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205 2199
Table 4
Calculated and experimental values of natural frequencies — original model
Mode j 0 1 2 3 4 5
Down — means parking position of the shaking table; up — means ready for operation position of the shaking table.
Table 5
Calculated and experimental values of natural frequencies — repaired model
Mode j 0 1 2 3 4 5
Fig. 8. Cracks in the original stone masonry model: (a) south side; (b) east side. Solid (blue) lines are cracks after the transport. (For interpretation of the references
to colour in this figure legend, the reader is referred to the web version of this article.)
(c) Series of ambient (like white noise) excitation in one for directions x and y, respectively. The related input
direction x or y, respectively; Records and analysis results accelerograms along with their 5% response spectra are in
were obtained by similar methods used in the sweep sine Fig. 14 — left.
tests. Sampling frequency f s = 400 Hz. During impact tests, only accelerations were recorded.
(d) Seismic tests with simultaneous earthquake excitation in Remaining tests included also measurements of relative
two directions (x, y); The earthquake input started from displacements — “strains” above openings on east and south
low level of earthquake intensity and it was successively sides of the model. The acceleration records of seismic response
increasing up to the significant appearance of cracks in in representative points on the model (Fig. 5) and input
masonry. Earthquake like response time histories were motion of the shaking table allow the calculation of model
recorded with sampling frequency f s = 400 Hz. Maximum to shaking table relative deflection time histories. Deflections
seismic input acceleration (equivalent of PGA — peak give also information on out-of-plane vibration of walls. It
ground acceleration) reached values 0.36g and 0.34g, was confirmed that polymer grids in bed joints supported the
2200 E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205
Fig. 9. Cracks on the most damaged parts of the walls: the original stone masonry model after shaking table tests. 0.02g (1) — means the first sweep sine test in x
direction.
Table 6
Key values of the seismic response of stone masonry model (original and repaired)
Exp. natural frequency Estimated damping Maximum input Maximum top rel. displ. Maximum top abs. Estimated max. base shear (kN)
(Hz) ratio acc. (g) (mm) acc. (g)
Stone masonry model 1:1, original, only grids above openings (m tot = 34.8 t), the seismic input based on Herceg Novi earthquake 2D x, y (polymer
grids in bed joints)
f 1x = 8.31 0.05 0.359 S-16.72; N-18.74 S-1.211; N-1.033 127.6
f 1y = 11.84 0.05 0.339 E-26.20; W-10.39 E-0.780; W-1.003 101.4
f 1θ z = 23.80 0.05 – –
Stone masonry model 1:1, repaired (m tot = app.42 t), the seismic input based on Herceg Novi earthquake 2D x, y (polymer grids in bed joints and
vertical polymer grids inside of fibre lime–cement plaster)
f 1x = 8.41 0.05 1.29 S-9.72; N-8.14 S-1.866; N-1.763 249.2
f 1y = 11.46 0.05 1.04 E-13.61; W-13.47 E-2.187; W-1.735 289.37
f 1θ z = 24.46 – – – – –
integrity, however, they gave the allowance for comparatively Phase 2 — shaking table tests of the repaired model with
high out-of-plane deflection amplitudes (Fig. 10 and Table 6). vertical grids and fibre plaster. The sequence of tests was
In the majority of existing old structures, the wooden floor slightly different from phase 1, and it was as follows:
systems are comparatively flexible. Wooden floors influence (a) Impact tests of model with acting force in chosen points
the dynamic response and behaviour both in plane and out- of upper part of model near A7, A29, A9, A10; Response
of-plane. This can also bring some stability problems [13–15]. time histories were recorded with sampling frequency f s =
The partial help is coming from polymer grids in bed joints, as 2000 Hz:
they support by friction the individual disconnected stones. The (b) Series of ambient (like white noise) excitation in one
substantial improvement can be reached by using of vertical direction x or y, respectively; used sampling frequency
grids. f s = 400 Hz.
E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205 2201
Fig. 10. Time histories of horizontal relative deflections — the original stone masonry model. Achieved maximum seismic input: PGA xS = 0.359g; PGA yE =
0.339g.
Fig. 11. Cracks on the most damaged parts of the walls: the repaired stone masonry model after shaking table tests.
2202 E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205
Fig. 12. Cracks in the repaired stone masonry model: (a) south side; (b) east-north corner.
Fig. 13. Time histories of horizontal relative deflections — the repaired stone masonry model. Achieved maximum seismic input: PGA xS = 1.290g; PGA yE =
1.040g.
(c) Seismic tests with simultaneous earthquake excitation in The seismic response of the repaired model was different
two directions (x, y); The earthquake input started from than that of the original model. Fig. 13 shows the respective
low level of earthquake intensity, and it was successively horizontal relative deflections of the repaired model against
increasing up to the limit of shaking table. Used sampling the shaking table. The out-off-plane vibration of walls nearly
frequency f s = 400 Hz. Maximum input acceleration disappeared (Table 6).
achieved values 1.29g and 1.04g for directions x and y, In Table 7 presented vector extremes Acc xy, Vel xy mean
respectively. The corresponding input accelerograms along maximum values of space vectors of seismic inputs verified in
with their 5% response spectra are in Fig. 14 — right. time domain. Critical frequencies Crit f A were calculated under
(d) Repeated series of ambient (like white noise) excitation in assumption that maximum acceleration and maximum velocity
one direction x or y, respectively; used sampling frequency are bounded nearly as in harmonic vibration. Critical ranges of
f s = 400 Hz. frequency Crit f B were determined on the basis of calculated
The pattern of cracks indicates that the damage of repaired acceleration response spectra and represent the range of natural
model was accumulated in the lower parts of walls, near the frequencies at which maximum local stresses in the structure
base plate (Figs. 11 and 12). can be expected (Fig. 14).
E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205 2203
Fig. 14. Time histories and response spectra of actual extreme seismic inputs: left — the last test of the original model; right — the last test of the repaired model.
Table 7
Seismic input extremes — achieved during the tests of original and repaired stone masonry model
Required max acc. Acc x (g) Acc y (g) Acc z (g) Acc x y (g) Vel x (mm/s) Vel y (mm/s) Vel z (mm/s) Vel x y (mm/s)
Original model f s = 400 Hz; f p = 0.8 Hz;
0.25g 0.359g 0.338g – 0.359g 158.853 181.383 – 192.652
Crit f A (Hz) 3.528 2.908 2.912
Crit f B (Hz) 2–5 2–5
Original, measured quantities were accelerations. Corre- either on the secant modulus approach or on the ideal
sponding velocities were calculated using the numerical step in- elastic–plastic nonlinear model [15,22]. The allowable space
tegration procedure. The integration was applied together with for a dynamic resistance capacity is thus determined by the
the Butterworth high-pass filter. The sampling frequency f s was natural frequencies and damping variation and the strength
given from measurements, the cut-off frequency f p was chosen and displacement limits. However, the tested models reached
to be sufficiently low in comparison with the frequency con- their ultimate state through the limit strength and integrity. It
tent of records. The selection of filter was verified by Matlab should be understood that the integrity of masonry structure
Toolbox procedures. and its components does not mean the monolithic state without
It can be seen from Table 7 that differences between any crack. The cracks are allowed but limited. The main
the unidirectional seismic input maximum and the space achievement of the presented retrofitting (also upgrading)
vector seismic input maximum are slightly less than those procedure is in the redistribution of stresses and in the
recommended in standards. This is valid for all tests and prevention of collapse.
is partially influenced by the used seismic input, mass and The response of a structure is a product of global and
dimensions of the model, and the shaking table properties. local stress–strain states resulting from the interaction of
natural modes/frequencies and seismic input properties in
5. Limits of the dynamic resistance of original and repaired time and space [6,17,20]. It can happen that the response
stone masonry to unidirectional seismic excitation is higher than that one
to multicomponent excitation, and/or one mode response can
Each presented and tested model configuration has its overrun multimodal response. The more detailed verification is
dynamic resistance limits. The same concerns existing old needed, if the structure is susceptible to a sudden initiation of
stone masonry structures. The development of cracks and local and/or global damage.
partial damage decrease values of natural frequencies and The relation of maximum seismic response and maximum
consequently influence the seismic response time history. seismic input can but need not be influenced by varying
The analytical estimate of the resistance can be based natural frequencies. The changes of natural frequencies and
2204 E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205
Fig. 15. Application of polymer grids combined with fibre lime–cement mortar/plaster in stone masonry structures.
total mass can be less important, and the main player is the box” behaviour of the repaired model and a very high seismic
integrity of a structure. Therefore, the response of repaired resistance. The achieved PGA was more than 1g. The observed
model exhibited smaller increments of absolute accelerations mechanisms of dynamic response have opened the door for
and relative deflections in comparison with the response of practical applications in stone masonry structures, either new
original model (Fig. 13 and Table 6). or repaired.
Table 6 gives the review of achieved seismic response The practical use of the retrofitting procedure is intercon-
extremes during the original and repaired model tests. Global nected with the requirements on the service properties and the
limits, usually presented by the total base shear force versus appearance of a structure (Fig. 15). Thus, for new/old structures
top relative displacement relationship, are not fully compatible there exist options:
with local stresses of a system. Especially, this must be
(a) only fibre lime–cement mortar — new and partially old
taken into account when analysing the original stone model
structures;
behaviour. The acceleration response ratio (maximum response
(b) horizontal polymer grids + fibre lime–cement mortar —
acceleration to PGA) recorded variation only about two or
new and partially old structures;
fewer (Fig. 14). This phenomenon suggests the effect of large
(c) vertical polymer grids + fibre lime–cement plaster — any
masses and dimensions of tested stone masonry models.
new and old structures;
The acceptable integrity was observed already during the
(d) both horizontal and vertical polymer grids + fibre
original model tests. After repair, the critical regions have
lime–cement mortar/plaster — new structures.
changed the position. The dissipation of energy has run
near the base mat corners and only slight cracks appeared The horizontal grids in chosen bed joints of old stone
throughout the model. In general, the very good integrity masonry can be considered for the repair of ruins and upper
and the excellent increase of the seismic resistance capacity parts of defensive walls. However, in the other parts it means
underline the behaviour of the repaired model. using the rather tedious technique of lateral inserting of grids,
combined with the mortar injection.
6. Discussion on intervention measures
7. Conclusions
The results have shown remarkably progressive information.
The overall behaviour of reinforced stone masonry model In this paper few aspects of material properties and the
has discovered several important features. Originally fragile seismic response estimate of stone masonry structures are
composition of stone units and mortar after introduction of depicted. The composite system of a plain stone masonry
horizontal grids has changed the behaviour into nearly “flexible structure presents the nonlinear dynamic response, which is
one”. The seismic response of the original model included accompanied with the damping increase and reversible or
contribution of large deformation of walls in out-of-plane irreversible changes of stiffness. The local and total failure can
direction, resembling the behaviour of shells. Even, what is appear suddenly as the result of extensive vibration and a low
important, the integrity of walls near openings has remained in resistance capacity. The vulnerability can be mitigated by the
acceptable limits and no collapse appeared. The achieved PGA proper choice of upgrading materials and their combination. In
was 0.36g. The second phase of tests presented nearly “stiff the analysis, the apparent masonry modulus of elasticity in the
E. Juhásová et al. / Engineering Structures 30 (2008) 2194–2205 2205
range of E m = 1000–2000 MPa and Poisson’s ratio ν = 0.1 seismic vulnerability of the building stock, NSE Lisbon, April 1, 2001.
seem to be appropriate for the assessment of initial natural Lisbon: LNEC; 2001. p. 15–56.
[8] Colombo A, Negro P. Advanced materials for strengthening, rehabilita-
frequencies and modes of vibration. The tools, which are
tion and repair of structures. experimental activities in ELSA. In: Pro-
used in the nonlinear response analysis, should be reasonably ceedings of the workshop mitigation of seismic risk support to recently
selected to estimate the stone masonry structure resistance affected European countries. Ispra: JRC EC; 2000. 5/1–7.
capacity. If ductility is supposed to be beneficial, the cracks can [9] EN 1990: 2002 Eurocode. Basis of structural design. Brussels: CEN.
be accepted, provided that neither loss of structure integrity nor [10] EN 1996-1-1: 2005 Eurocode 6. Design of masonry structures. Part 1-
instability can appear. The proper detailing and the appropriate 1: Common rules for reinforced and unreinforced masonry structures.
Brussels: CEN.
measures for increasing the total resistance capacity are key [11] EN 1998-1: 2004 Eurocode 8. Design of structures for earthquake
design and execution activities in the construction industry. resistance. Part 1: General rules, seismic actions and rules for buildings.
The described technology of retrofitting underlines the Brussels: CEN.
integrity role in the enhanced dynamic resistance capacity of [12] EN 1998-3: 2005 Eurocode 8. Design of structures for earthquake
resistance. Part 3: Assessment and retrofitting of buildings. Brussels:
stone and other masonry structures. The fibre lime–cement
CEN.
plaster even participates on the durability increasing. It [13] Griffith MC, Magenes G, Melis G, Picchi L. Evaluation of out-off-plane
is proved the high efficiency of polymer grids and fibre stability of unreinforced masonry walls subjected to seismic excitation.
lime–cement mortars at acceptable costs. This supports using of Journal of Earthquake Engineering 2003;7(1):141–69.
similar interventions in existing structures including historical [14] Javed M, Naeem Khan K, Penna A, Magenes G. Behaviour of masonry
structures during the Kashmir 2005 earthquake. In: Proceedings of the 1st
ones. Mentioned measures have wider field of applications.
European conference on earthquake engineering and seismology. 2006.
Not only safety aspects related to natural earthquake disasters Paper 1077.
or terrorist hazards, but also protection against undesirable [15] Juhásová E. Seismic effects on structures. Amsterdam: Elsevier; 1991.
transport effects and settlements can be reasonably and [16] Juhásová E. Experimental investigation of technical interventions to
conveniently solved by the presented intervention procedures. reduce seismic vulnerability of old existing buildings. Bratislava: ICA
SAS; 1996.
[17] Juhásová E, Coelho E, Bairrao R, Costa A, Virsta A, Sofronie R.
Acknowledgements Enhancing the performances of natural stone masonry. In: Proceedings
of IASS 2005 conference. vol. 2. Cluj-Napoca; 2005. p. 959–66.
The research was mainly funded by European Commission [18] Juhásová E, Hurák M, Zembaty Z. Assessment of seismic resistance of
in the framework of ECOLEADER Project HPRI-CT-2002- masonry structures including boundary conditions. Soil Dynamics and
00182 and partially by VEGA Projects 2/4078/24 and Earthquake Engineering 2002;22(9–12):1193–7.
[19] Juhásová E, Pezzoli P, Da Rin EM, Sofronie R, Zembaty Z. Resistance
2/7114/27. The financial support is gratefully acknowledged.
of brick building model with arches before and after retrofitting.
In: Proceedings of the 11th European conference on earthquake
References engineering. Rotterdam: Balkema; 1998. Paper 180.
[20] Juhásová E, Sofronie R, Juhás M. The key role of structure integrity and
[1] Abrams DP. Performance-based engineering concepts for unreinforced new materials. In: Proceedings of the conference building for European
masonry building structures. Progress in Structural Engineering and future, vol. 1. Brussels: ECCREDI; 2004. p. 527–44.
Materials 2001;1:48–56. [21] Krstevska L. Development and application of non-Linear micro models
[2] Aničić D, Fajfar P, Petrović B, Szavits-Nossan A, Tomažević M. for evaluation of seismic behaviour of rc frames infilled with plain and
Earthquake engineering. Beograd: Gradevinska knjiga; 1990. reinforced masonry. University of Skopje reports. Skopje: IZIIS; 2002.
[3] Bairrao R, Bursi O, Carydis P, Magonette G, Mouzakis H, Tirelli D, [22] Paulay T, Priestley MJN. Seismic design of reinforced concrete and
et al. Benchmark testing and performance comparison of shaking tables masonry buildings. New York: John Wiley & Sons; 1992.
and reaction walls. In: Proceedings of the 13th world conference on [23] Severn R, Juhásová E, Franchioni G, Popa G, Sofronie R. Mitigation of
earthquake engineering. Vancouver: UBC; 2004. Paper 441. seismic risk by composing of masonry structures. In: Proceedings of the
[4] Bairrao R, Falcao Silva MJ, Juhásová E, Campos Costa A, Coelho workshop mitigation of seismic risk support to recently affected European
E. Shaking table tests of an asymmetrical limestone building. In: countries. Ispra: JRC EC; 2000. 22/1–7.
Proceedings of the 1st European conference on earthquake engineering [24] Sofronie R. Performances in seismic strengthening of masonry.
and seismology. 2006. Paper 636. In: Proceedings of the 13th world conference on earthquake engineering.
[5] Coburn A, Spence R. Earthquake protection. London: John Wiley & Sons; Vancouver: UBC; 2004. Paper 182.
2002. [25] Sofronie R, Juhásová E, Greening P. Seismic strengthening of masonry.
[6] Coelho E, Campos Costa A. Seismic testing and vulnerability assessment. SECED Newsletter 2003;16(4):6–7.
In: Proceedings of the Portuguese–US workshop on seismic behaviour of [26] STN 73 0031: 1989 Civil Engineering Structures and Foundations. Basic
masonry structures. 2004. rules for analysis. Prague: VUNM.
[7] Coias e Silva V. Technical feasibility of the national programme for [27] ISO DIS 13823 General Principles on the Design of Structures for
reducing the seismic vulnerability of the building stock. In: Reducing the Durability. Draft 2006. Geneva: ISO.