Switchgear CBM

Activities

1
POWERING THE NATION
Switchgear Condition Monitoring Techniques
Maintenance Tests/Condition (Tier 1) Condition Indicator
Thermography 1
Ultrasonic Scanning 2
SF6 Gas Leakage Emission 3
Partial Discharge (TEV) 4
Breaker Wear Out (not implemented yet) 5
Operation and Maintenance Performance 6
Age 7

Maintenance Tests ( Tier 2) Maintenance Tests (Tier


Contact Resistance Interrupter
3)
Contact Resistance Busbar
Partial Discharge (HFCT)
Cable Insulation Resistance

Insulation Resistance (Main Circuit) SF6 Gas Monitoring (SF6


Insulation Resistance (Auxiliary Circuit) Breaker)
Insulation Resistance (Busbar)

Bushing Tan δ

Dielectric/Pressure Test (leakage current) Interrupter


2
Dielectric/Pressure Test (leakage current) Busbar

POWERING THE NATION Circuit Breaker Timing and Travel 2


Switchgear CBM Techniques

THERMOGRAPHIC INSPECTION

POWERING THE NATION 3


THERMOGRAPHIC INSPECTION
• Thermographic inspection is an effective condition monitoring
tool as:
 Problem detection is quick without interruption of service
 Prioritization for corrective actions
 Elimination of unscheduled power outages
 Improved safety by reducing risk of fire and/or injury

• Use of thermography can detect high contact resistance or


other loose parts.

POWERING THE NATION 4


THERMOGRAPHIC INSPECTION
• During thermographic inspections, the operator should be aware
of the approximate load on the breaker to help discriminate
between problem types
• Thermography can be applied at the time of commissioning and
in-service
• A good technique is to compare the readings between bushings
and between phases.
• Usually for metal clads, any difference of more than 10C between
phases or bushings should be questioned, especially if the circuit
breaker is operating below its rating.
• For direct scanning, obtain absolute temperature measurement
of the overheating component to determine if the component
5
has exceeded the electrical temperature ratings standard
POWERING THE NATION 5
CASE STUDY 1

Pre-repair - Loose connection creates excessive heat on cable end,


thus produce spike in thermal
6

POWERING THE NATION 6


CASE STUDY 1

Post-repairs – The thermal pattern is uniform


7

POWERING THE NATION 7


Switchgear Condition Monitoring Techniques
Maintenance Tests/Condition (Tier 1) Condition Indicator
Thermography 1
Ultrasonic Scanning 2
SF6 Gas Leakage Emission 3
Partial Discharge (TEV) 4
Breaker Wear Out (not implemented yet) 5
Operation and Maintenance Performance 6
Age 7

Maintenance Tests ( Tier 2) Maintenance Tests (Tier


Contact Resistance Interrupter
3)
Contact Resistance Busbar
Partial Discharge (HFCT)
Cable Insulation Resistance

Insulation Resistance (Main Circuit) SF6 Gas Monitoring (SF6


Insulation Resistance (Auxiliary Circuit) Breaker)
Insulation Resistance (Busbar)

Bushing Tan δ

Dielectric/Pressure Test (leakage current) Interrupter


8
Dielectric/Pressure Test (leakage current) Busbar

POWERING THE NATION Circuit Breaker Timing and Travel 8


Switchgear CBM Techniques

ULTRASONIC INSPECTION

POWERING THE NATION 9


Switchgear CBM activities
• Partial Discharge in Switchgear

• In electrical engineering, a partial discharge (PD) is a localised dielectric


breakdown of a small portion of a solid or liquid electrical insulation
system under high voltage stress.

• Partial discharges within an insulation system may or may not exhibit


visible discharges, and discharge events tend to be more sporadic in
nature than corona discharges.

– Internal Discharge
• Voids in insulation material
– Surface Discharge
• Surface Tracking
• Dry Banding
– Corona
• Usually revealed by a relatively steady glow or brush discharge in air 10

POWERING THE NATION 10


Switchgear CBM activities
• Partial Discharge in Switchgear

11

POWERING THE NATION 11


12

POWERING THE NATION 12


Limits for
Limits for TEV
Ultrasound
<20 dB < 1 dB

20-29 dB
> 1 dB

>29 dB

13

POWERING THE NATION 13


Switchgear CBM activities
• The ultrasonic sensors are piezoelectric crystals that convert sound energy
to electrical energy

• Ultrasonic sensors are either airborne or contact types

• Airborne ultrasonic sensors will work best when there is a clear and direct
air path from the sensor to the partial discharge site

• Contact type ultrasonic sensor pick up ultrasound appearing at the metal


surface and therefore work best when there is completely no air path
between the sensor and the partial discharge source

• Airborne ultrasonic sensors are typically narrow bandwidth with 40KHz


center frequency and 3dB bandwidth of ±1KHz

• The typical frequency response will be 100KHz center frequency and 3dB
bandwidth of ±20KHz
14

POWERING THE NATION 14


Switchgear CBM activities
Sound Samples

Corona

Tracking

Arcing

15

15
Switchgear Condition Monitoring Techniques
Maintenance Tests/Condition (Tier 1) Condition Indicator
Thermography 1
Ultrasonic Scanning 2
SF6 Gas Leakage Emission 3
Partial Discharge (TEV) 4
Breaker Wear Out (not implemented yet) 5
Operation and Maintenance Performance 6
Age 7

Maintenance Tests ( Tier 2) Maintenance Tests (Tier


Contact Resistance Interrupter
3)
Contact Resistance Busbar
Partial Discharge (HFCT)
Cable Insulation Resistance

Insulation Resistance (Main Circuit) SF6 Gas Monitoring (SF6


Insulation Resistance (Auxiliary Circuit) Breaker)
Insulation Resistance (Busbar)

Bushing Tan δ

Dielectric/Pressure Test (leakage current) Interrupter


16
Dielectric/Pressure Test (leakage current) Busbar

POWERING THE NATION Circuit Breaker Timing and Travel 16


Switchgear CBM Techniques

PARTIAL DISCHARGE (TEV)

17

POWERING THE NATION 17


Switchgear CBM activities
• Transient Earth Voltage (TEV)
•When a partial discharge occurs in the phase to earth insulation, a
small quantity of electrical charge is transferred capacitively from
the high voltage conductor system to the earthed metal cladding.
•Electromagnetic waves propagate away from the discharge site in
both directions.
•However an opening is required for the waves to propagate out to
generate transient earth voltage on the metal surface.

HV BUSBAR

DISCHARGE
EM WAVE

18
Earth Voltage wave
POWERING THE NATION 18
Switchgear CBM activities
• Transient Earth Voltage (TEV)
• The amplitude of the TEV measurement is a function of the
amplitude of the discharge and the attenuation of the
propagation path.
• The amplitude is displayed on the instrument, measured in
dBmV, hence the measurement is a relative indication only
• Method of measurement – using TEV probe, place flat onto
metallic surface of the switchgear and record the reading

19

POWERING THE NATION 19


Training using TEV equipment

20

POWERING THE NATION 20


Anomalies Detected

Fig 1: Hotspot on a cable termination at PPU Desa Fig 2: Tracking pada terminal kabel
Tun Razak 33kV Tx1 di PPU Pdg Menora

21

Fig 3 : 3T0 PDS - PMU Prai GIS Fig 4: Tracking on bus spout-PMU Fig 5: Tracking on cable-
21
Pandamaran PPU Midland Park
More anomalies

Cable termination Crack on VCB insulator Capacitance bushing

22

PDS
POWERING THE NATION Busbar 1122kV Rekahan VT
Switchgear Condition Monitoring Techniques
Maintenance Tests/Condition (Tier 1) Condition Indicator
Thermography 1
Ultrasonic Scanning 2
SF6 Gas Leakage Emission 3
Partial Discharge (TEV) 4
Breaker Wear Out (not implemented yet) 5
Operation and Maintenance Performance 6
Age 7

Maintenance Tests ( Tier 2) Maintenance Tests (Tier


Contact Resistance Interrupter
3)
Contact Resistance Busbar
Partial Discharge (HFCT)
Cable Insulation Resistance

Insulation Resistance (Main Circuit) SF6 Gas Monitoring (SF6


Insulation Resistance (Auxiliary Circuit) Breaker)
Insulation Resistance (Busbar)

Bushing Tan δ

Dielectric/Pressure Test (leakage current) Interrupter


23
Dielectric/Pressure Test (leakage current) Busbar

POWERING THE NATION Circuit Breaker Timing and Travel 23


Switchgear CBM Techniques

SF6 LEAKAGE DETECTION

24

POWERING THE NATION 24


25
SF6 Gas Leak Detector
POWERING THE NATION 25
SF6 Gas Leak Detection

• Measurement of gas leaks in ml/sec, gm/year and ppm.


• Rapid leak detection with response and clear down time < 1 sec after
saturation or exposure to 100% SF6 gas.
• Non-radioactive measurement and storage.
• High sensitivity (minimum detection sensitivity of 1x10-7 ml/sec).
• Audible alarm to alert gas leaks.
• Long extension hose (5m long) to reach and scan large and difficult to reach
areas.

26

26
POWERING THE NATION 26
SF6 Gas Leak Detection
What to Scan

• Scan along the welded joints.


• Scan around valve fittings and other fittings e.g. bushings, cable
connectors, etc.
• Scan around sealed removable covers.
• Scan around the bursting disc.
Frequency

• During switchgear installation.


• Once in 3-6 months if constant monitoring or surveillance is required
• Once a year if no anomalies are detected. This will provide data for
trending switchgear performance.

27

CIRED Dr Ghosh Ch. 4 27


POWERING THE NATION 27
Switchgear Condition Monitoring Techniques
Maintenance Tests/Condition (Tier 1) Condition Indicator
Thermography 1
Ultrasonic Scanning 2
SF6 Gas Leakage Emission 3
Partial Discharge (TEV) 4
Breaker Wear Out (not implemented yet) 5
Operation and Maintenance Performance 6
Age 7

Maintenance Tests ( Tier 2) Maintenance Tests (Tier


Contact Resistance Interrupter
3)
Contact Resistance Busbar
Partial Discharge (HFCT)
Cable Insulation Resistance

Insulation Resistance (Main Circuit) SF6 Gas Monitoring (SF6


Insulation Resistance (Auxiliary Circuit) Breaker)
Insulation Resistance (Busbar)

Bushing Tan δ

Dielectric/Pressure Test (leakage current) Interrupter


28
Dielectric/Pressure Test (leakage current) Busbar

POWERING THE NATION Circuit Breaker Timing and Travel 28


Switchgear CBM Techniques

CB TIMING TEST

29

POWERING THE NATION 29


Online Breaker Analyzer Test
1. To test the breaker in the energized state so that the performance of the first
trip can be analyzed. The magnitude, duration and shape of the coil current
captured by the test instrument is directly related to the mechanism and main
breaker contact operation and reveals how the breaker would have performed
should it be called upon to trip in a real situation after it has been put in
service for a long period of time.

2. To monitor the DC voltage drop during a trip operation when the trip coil is
Energized.

3. To analyze the trip performance of the main breaker contacts.

4. The close operation can also be analyzed in the same way.

30

POWERING THE NATION 30


Online Breaker Analyzer Test

31

POWERING THE NATION 31


Circuit Breaker Timing Test
Trip coil current analysis
C Linkage fully collapsed
u
rr
e
n
t
Plunger
Touches Trip
Hook

Trip Hook
Unlatches

Triggering of Trip Coil

Trip hook Linkage


unlatching Collapsing

Time ms
32

POWERING THE NATION 32


Off-Line Breaker Analyzer Test
• This is applicable to all circuit beaker types, e.g. oil, air, vacuum
and SF6
• This is conducted on a circuit breaker to determine if there are
any variations in timing synchronism or any mechanism
abnormalities
• Dependent on the circuit breaker type and the type of timing
equipment malfunctions of the following can be detected:
Time for breaker to trip free
Time for breaker to trip
Time for breaker to close
Synchronism of contacts and phases
Improper spring adjustment

33

POWERING THE NATION 33


Off-Line Breaker Analyzer Test

• Dependent on the circuit breaker type and the type of timing


equipment malfunctions of the following can be detected
(contd.):

Improper stop adjustments


Worn contacts
Excessive contact friction
Malfunctioning shock absorbers, buffers, or dashpots
Improper velocity through the arcing zone
Incorrect e.g., excessive rebound
Incorrect e.g., excessive unlatching friction
34

POWERING THE NATION 34


Off-Line Breaker Analyzer Test
• Most manufacturer’s instruction books contain limits and
recommendations on this important data and may recommend a
supplier for such instrumentation.
• When the timing or travel analysis is found to be outside of the
manufacturer’s limits, there will usually be a need for adjustments
to the mechanism.
• Whenever any maintenance, adjustment, or disassembly is
required, the timing tests should be repeated prior to re-
energization.
• Timing tests should be performed at normal mechanism conditions
e.g. pressure, and normal control voltage.
• Circuit breaker is designed to facilitate the mounting of an
electromechanical transducer to monitor instantaneous travel and
velocity. 35

POWERING THE NATION 35


Off-Line Breaker Analyzer Test
Test Procedure

• De-energize and isolate circuit breaker

• Set-up and connect the test instrument

• Conduct test
a) Breaker timing test for CLOSE-OPEN sequence.
b) Breaker timing test for OPEN-CLOSE sequence.
c) Breaker timing for OPEN-DELAY-CLOSE-OPEN sequence.
d) Breaker timing for CLOSE-OPEN-CLOSE sequence.

36

POWERING THE NATION 36


Off-Line Breaker Analyzer Test
Test Procedure

• Record or print out results

• Analyze results
a) Contact closing time.
b) Contact opening time.
c) Contact travel.
d) Contact chattering.
e) Trip coil Current Profile.
f ) Close coil Current Profile.

37

POWERING THE NATION 37


Off-Line Breaker Analyzer Test Set Up

38

38
POWERING THE NATION 38
Off-Line Breaker Analyzer Test Set Up

39

POWERING THE NATION 39


Off-Line Breaker Analyzer Test Set Up

40

POWERING THE NATION 40


Off-Line Breaker Analyzer Test Set Up

41

POWERING THE NATION 41


Circuit Breaker Timing Test Results
Timing Chart of Close-Open operation

42

POWERING THE NATION 42


Circuit Breaker Timing Test

The abnormalities in the above results may indicate the


following failure modes:

1) Weak auxiliary supply


2) Slow movement of the plunger
3) Inadequate force exerted on the trip hook
Sluggishness in the linkages
4) Jammed trip latch
5) Maladjusted Spring
6) Synchronism of interrupter
7) Maladjusted Spring
43

POWERING THE NATION 43


Circuit Breaker Timing Test
The profile for opening operation of a new circuit breaker

Coil Current Profile for Trip Operation

Opening time of interrupter from


close position

44

POWERING THE NATION 44


SUCCESS STORIES

45

POWERING THE NATION 45


PDTEV TEST RESULT PMU GONG BADAK (33kV) PANEL NO. 2HO – 20/10/2009

DOUBLE
CLICK HERE

17 dB
46

POWERING THE NATION 46


PMU GONG BADAK, TERENGGANU

Fig 5 – Presence of dry banding & surface tracking on the CT bushings ( Red phase )

47

POWERING THE NATION 47 Fig 6 – Presence of oxidation on cable terminals and earth switch ( yellow phase )
PMU GONG BADAK, TERENGGANU

Fig 7 – Surface tracking & partial discharge on PT ( l-r B,Y,R phases )

48

POWERING THE NATION 48


Fig 8 – Oxidation on red phase contact finger & red phase circuit spouts along with surface
tracking
UJIAN PDTEV+ PMU BATU
RAKIT (PANEL 33KV) PADA
27/9/09 & FINDING

49

POWERING THE NATION 49


Kesan Pengoksidaan Pada
Tulip Contact Red Phase

50

POWERING THE NATION 50


Kesan Tracking Pada Spout
Circuit Red Phase
51

POWERING THE NATION 51


U/S =25db , TEV = 29dbmV
Detected 27 Jan 2010

52

POWERING THE NATION Max52U/S =40db U/S Sound


Findings 04/02/2010

53

POWERING THE NATION 53


LESSON LEARNT

54

POWERING THE NATION 54


PMU PAKA TERENGGANU
ULTRASOUND & IR RESULTS FROM PMU PAKA

Panel No Date of Scanning Remarks


13 20 November 2008 Tracking on CB 5db (Done on 27/11/08)
11 20 November 2008 IR breaker problem
3 19 July 2008 Cable Mechanical Vibration (Done on
12/08/08)
1 20 November 2008 Cable tracking 3db (Done 28/11/08)
31 20 November 2008 Tracking on CB 4dB
Bus Section 20 November 2008 CB Mech Vibration 27dB
2 19 July 2008 Cable 1dB
20 November 2008 CB tracking 25dB (Done 26/11/08)
Cable 20 dB (Done 26/11/08)
6 20 November 2008 Cable <1dB (Done 26/11/08)
8 19 July 2008 Cable (Done 4/8/08)
10 19 July 2008 Cable tracking (Done 2/9/08)

55

POWERING THE NATION 55


PMU PAKA TERENGGANU

56

POWERING THE NATION 56


Fig 1. Front overview of affected 11kV Fig 2. Rear overview of affected 11kV
panels panels

57
Fig 3. Panel 31 & GCB truck – forced drawn Fig 4. Panel 31 & GCB truck – forced drawn
by Bomba to facilitate extinguishing of fire by Bomba to facilitate extinguishing of fire
POWERING THE NATION 57
Fig 7. Remnants of CB conducting arms after Fig 8. CB spouts with burnt through arcing holes.
withdrawal of GCB truck Circuit & Busbar Spout looks ok

Fig 9. Cable
compartment

58
Fig 10. VT compartment of panel 31
POWERING THE NATION 58
Flashover of 11kV AIS TAMCO VCB

Fig.1. Front Overview of 11kV panels in Fig.2. Rear Overview of 11kV panels

59

POWERING THE NATION 59


Flashover of 11kV AIS TAMCO VCB

60
Fig.3. Cable and CB compartment of panel 7
POWERING THE NATION 60
PMU DAMANSARA HEIGHTS

61

POWERING THE NATION 61


PMU DAMANSARA HEIGHTS

62

POWERING THE NATION 62