Professional Documents
Culture Documents
NF12-100
12V100Ah / 10hr rate
Battery Features
○ Compactness ○ Central gassing system
○ ETSI 19 inch / 23 inch and hinged front covers on
integration all models
○ Rackable standard ○ Fully tank formed plates
component ○ Low impurity electrolyte
○ High power to volume ratio ○ Multi-position usage
○ Modularity ○ Spill proof / leak proof Terminal Type: T14
○ Long life ○ ABS case and cover
○ Front connection and VO upon request
terminal access ○ Very high purity lead
Electrical Specification
Design floating Life @ 25° C (77° F) …………………… 12 years
Nominal Capacity @ 25° C /77° F
20 hour rate 5.29A to 1.75Vpc …………………… 105.8 Ah
10 hour rate 10.09A to 1.75Vpc …………………… 100.9 Ah
Internal Resistance
(Fully charged battery @ 25°C /77°F ) …………. 5mΩ Dimension & Weight
Max. Discharge Current @ 25°C /77°F ………….. 800 A (5S) Dimension (± 2mm) Weight
Charge Methods: Constant voltage charge @ 25° C /77° F Length Width Height Total Height (± 2%)
Cycle Use ……………………………………… 14.7 ~ 14.9V 395 mm 110 mm 286 mm 286 mm 32.1 kg
Max. Current ………………………………….. 25 A 15.6 inch 4.3 inch 11.3 inch 11.3 inch 70.8 lbs
Standby Use ………………………………….. 13.6 - 13.8V
Operating Temperature Range …………………… -30 ~ 50° C Typical Applications
Notes: battery voltage must be adjusted according to temperature. ○ Telecommunications ○ Power Utility ○ Data Center ○ UPS & EPS
Please refer to our recommendation.
Self-Discharge Certificates
3% of capacity declined per month @ 25° C (77° F).
Subject to revision without notice. Please contact our sales representatives for latest version.
Web: www.genergybattery.com 丨 Email: sales@genergybattery.com Version NO.20181101 Page 1 of 2
AGM Standby Use Battery > NF Series
NF12-100
12V100Ah / 10hr rate
Graphs
Charged
Voltage
Current
(V/ cell)
Constant Voltage Charging Characteristic (25° C)
( %) ( CA) ( V/ce ll)
120
2.17
20 0 .0 2 1 .8 3 1.33
CHARGING CURRENT
0 0 0
0 1 2 3 5 10 20 30 60 2 3 5 10 20 30
0 2 4 6 8 12 16 20 24 28 32
m in h
Cha rging Time ( hours )
Dis c ha rge Time
Temperature Effects On Float Life Cycle Service Life V.S. Depth Of Discharge
100% 100
Depth of discharge (%)
75%
80
33%
Design Li fe
60
40
7%
20
3%
100
2 .6
80 10° C
Chargi ng Voltage (V)
2 .5
Capaci ty (%)
60 20° C
2 .4
40° C 30° C
40
2 .3
Cy c le Us e
20
2 .2
St a ndby Us e
-10 0 10 20 30 40 50 60 0 3 6 9 12 15
0.1C A
80 80
Capacity (%)
20
20
0
0 4 6 8 10 12 -2 0 -1 0 0 10 20 30 40
Lif e (y e a r ) Ambie nt Te mpre t ure ( ° C)
Subject to revision without notice. Please contact our sales representatives for latest version.
Web: www.genergybattery.com 丨 Email: sales@genergybattery.com Version NO.20181101 Page 2 of 2