Professional Documents
Culture Documents
Kaise Battery series are Top terminal VRLA AGM battery for General use. With advanced
manufacturing technique and industry scale, KBL series delivers high energy density and high 12 V 40Ah AGM 10 years
voltage capacity tech design life
reliability performance, highly suited for UPS systems, security and alarm systems,
telecommunication, utilities, emergency light systems, CATV and other backup applications.
Technical Specifications
Nominal Voltage (V) 12 (6 cells per unit)
Designed Floating Life (25°C) 10 Years
Nominal Capacity (25°C) 40 Ah @ 20HR-rate (to 1.80Vpc)
Dimension (mm) L196 x W165 x H170 x TH170
Approx. Weight 12.8 kg (28.2 lbs)
Terminal Type Female Copper Insert M6 (torque 6~8N.m)
Internal Resistance Approx. 0.0095 Ohm (fully charged @ 20°C)
Max. Charge Current 9.5A
Max. Discharge Current (5S) 400A
Short Circuit Current 1250A
Self Discharge Approx. 3% per month @ 25°C
Discharge: -20~55°C
Ambient Temperature Charge: -20 ~ 50 °C
Storage: -20~45°C
Float Charge Voltage 13.6V/block @25°C (-3mV/cell/ C) Complied standards
• IEC 60896-21/22
Equalize and cycle Use Charge Voltage 14.4V/block @25°C
• GB/T19638
Container Material ABS (UL94-V0 optional) • JIS C8704
• BS6290 part 4
Battery Dimensions
197mm 165mm
TERMINAL DIMENSION
16mm
M6mm
5mm
170mm
2.17
Voltage
Current
Charge
Charge
Charge
100
10
Capacity (%)
8 80
Life(years)
o
5C
6 60
o
4
40 C o
30 C 20 oC
40
2
20
0
20 25 30 35 40 45 50 0 0 2 4 6 8 10 12 14 16 18 20
Temperature ( C ) o
Storage time:months
80
Float Life (%)
80
Capacity (%)
2.25V/cell
60
60
40
40
Test Procedure:
Temp:20~25
Discharge :0.25CA 20
20 Cut-off Voltage:1.75V/cell
End of life:≤60% of nominal capacity
0
0 -20 -10 0 10 20 30 40 50
2.10 2.20 2.30 2.40 2.50
Temperature (° C)
Float Voltage (V/cell)
Discharge Current I (A) I ≤ 0.08C 0.08C ≤ I < 0.2C 0.2C ≤ I < 0.6C 0.6C ≤ I < 1.0C I ≥ 1.0C
Final of Voltage ≥ 1.85Vpc ≥ 1.80Vpc ≥ 1.75Vpc ≥ 1.70Vpc ≥ 1.60Vpc