Professional Documents
Culture Documents
com
2V TUBULAR FLOODED SERIES BATTERY
The OPzS series is a traditional tubular plate flooded battery which offers 2V Tubular 20+ years
20+ years design life according to the standard IEC60896-11.With a new 150 Ah Flooded design life
design and technical improvement, it offers maximum efficiency and
reliability for the widest variety of applications. This series is highly suited
for all standby power applications that require the highest levels of reliability
and security.
SPECIFICATIONS
Nominal Voltage (V) 2
Designed Floating Life (20oC) 20+ Years
Nominal Capacity (20oC) 150 Ah @ C10 (to 1.80Vpc)
Demensions L103mm×W206mm×H409mm
Without electrolyte: 11.0Kg (24.2 lbs)
Approx. Weight
With electrolyte: 15.6Kg (34.4 lbs)
Diluted sulphuric acid of 1.240 g/cm3 (20°C)
Electrolyte Acid weight: 4.0Kg
Terminal Type Female Copper Insert M8 (torque:10~12N.m)
Internal Resistance Approx. 1.2mOhm (fully charged @ 20°C)
Max. Charge Current 30 A
Max. Discharge Current (5S) 1000 A
Short Circuit Current 2400 A
Self Discharge Approx. 4% per month @ 20°C
Discharge: -25~65°C
Ambient Temperature Charge: -20~65°C
Storage: -15~40°C
Complied standards
IEC 60896-11
Float Charge Voltage 2.23V @25oC (-3mV / oC/ cell) DIN40736
Equalize Charge Voltage 2.35V @25oC IEC61427
Eurobat guide, long life
Container Material SAN BS6290 part 4
UL1989
DIMENSIONS
20mm
108mm M8mm
103mm
354mm
7mm
409mm
206mm
TERMINAL DIMENSION
Copyright © 2015 BSB Power Company Limited. All rights reserved. 1/2
OPzS2-150 www.bsbpower.com
CHARACTERISTICS
Capacity
Current
Voltage
Charge
Charge
Charge
Charge Characteristic Discharge Characteristic (20OC)
2.17
(%) (CA) (V/Cell) Constant Charge At 0.15CA-2.40V (20oC)
110 2.00
Charge Charge
40 0.05 1.33
1.80
20 0.02
Charge Current 0 2 6 12 30 60 3 10 20
0 0 Min Hour
0 3 6 9 12 15 18
Time (hour)
100
20
2.23V/Cell
80
Capacity (%)
Life(years)
10
60 10oC
o o
40 C 20 C
40
5
20
0 0
2 4 6 8 10 12 14 16 18 20
10 20 30 40 50
o
Storage time : months
Temperature ( C )
6000
100
5000
80
Capacity (%)
Cycle life
4000
60
3000
40
2000
20
1000
0
0 -20 -10 0 10 20 30 40 50
10 20 30 40 50 60 70 80 90 100
Depth of discharge(%) Temperature (°C)
12.5
Shallow cycling at high state of charge
12.0
Shallow cycling at low state of charge
11.5
11.0
0 5 10 15 20 25 30 35 40 45 50 1 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100
Cycle times (cycles)
Long time discharge capacity for Solar & Wind applications Solar & Wind applications parameters settings
Over voltage disconnect: 2.47±0.01V/cell @ 25°C
Capacity C 24 C 48 C 72 C 100 C 120 C 240
(Ah) (Ah) (Ah) (Ah) (Ah) (Ah) Regulation/equalize voltage: 2.40±0.01V/cell @ 25°C
OPzS2-150 170 186 195 203 206 210 Array roconnection voltage: 2.23±0.005V/cell @ 25°C
Final Voltage 1.85 V Float voltage setting: 2.25±0.005V/cell @ 25°C
Low voltage alarm voltage: 1.95±0.005V/cell @ 25°C
Low voltage disconnect: 1.90±0.005V/cell @ 25°C
Load reconnect voltage: 2.09±0.01V/cell @ 25°C
Temp. compensate coefficienty: -4mV/cell/°C
Copyright © 2015 BSB Power Company Limited. All rights reserved. 2/2
Modify date:2017-05