You are on page 1of 44

Sunday, April 08, 2018, 06:07 PM

PAGE NO. 1

****************************************************
* *
* STAAD.Pro V8i SELECTseries6 *
* Version 20.07.11.33 *
* Proprietary Program of *
* Bentley Systems, Inc. *
* Date= APR 5, 2018 *
* Time= 13:10:24 *
* *
* USER ID: *
****************************************************

1. STAAD SPACE
INPUT FILE: E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.STD
2. START JOB INFORMATION
3. ENGINEER DATE 01-APR-18
4. END JOB INFORMATION
5. INPUT WIDTH 79
6. UNIT METER KG
7. JOINT COORDINATES
8. 1 0 0 0; 2 2.42 -2.42 0; 3 0.625082 -0.625082 0; 4 1.52254 -1.52254 0
9. 5 0 0 0.6; 6 2.42 -2.42 0.6; 7 0.625082 -0.625082 0.6; 8 1.52254 -1.52254 0.6
10. 9 0 0 1.2; 10 2.42 -2.42 1.2; 11 0.625082 -0.625082 1.2
11. 12 1.52254 -1.52254 1.2; 13 0 0 1.8; 14 2.42 -2.42 1.8
12. 15 0.625082 -0.625082 1.8; 16 1.52254 -1.52254 1.8; 17 0 0 2.4
13. 18 2.42 -2.42 2.4; 19 0.625082 -0.625082 2.4; 20 1.52254 -1.52254 2.4
14. 21 0 0 3; 22 2.42 -2.42 3; 23 0.625082 -0.625082 3; 24 1.52254 -1.52254 3
15. 25 0 0 3.6; 26 2.42 -2.42 3.6; 27 0.625082 -0.625082 3.6
16. 28 1.52254 -1.52254 3.6; 29 0 0 4.2; 30 2.42 -2.42 4.2
17. 31 0.625082 -0.625082 4.2; 32 1.52254 -1.52254 4.2; 33 0 0 4.8
18. 34 2.42 -2.42 4.8; 35 0.625082 -0.625082 4.8; 36 1.52254 -1.52254 4.8
19. 37 0 0 5.4; 38 2.42 -2.42 5.4; 39 0.625082 -0.625082 5.4
20. 40 1.52254 -1.52254 5.4; 41 0 0 6; 42 2.42 -2.42 6; 43 0.625082 -0.625082 6
21. 44 1.52254 -1.52254 6
22. MEMBER INCIDENCES
23. 5 2 6; 6 3 7; 7 4 8; 12 6 10; 13 7 11; 14 8 12; 19 10 14; 20 11 15; 21 12 16
24. 26 14 18; 27 15 19; 28 16 20; 33 18 22; 34 19 23; 35 20 24; 40 22 26; 41 23 27
25. 42 24 28; 47 26 30; 48 27 31; 49 28 32; 54 30 34; 55 31 35; 56 32 36; 61 34 38
26. 62 35 39; 63 36 40; 68 38 42; 69 39 43; 70 40 44
27. ELEMENT INCIDENCES SHELL
28. 77 9 5 7 11; 78 11 7 8 12; 79 12 8 6 10; 80 13 9 11 15; 81 15 11 12 16
29. 82 16 12 10 14; 83 17 13 15 19; 84 19 15 16 20; 85 20 16 14 18; 86 21 17 19 23
30. 87 23 19 20 24; 88 24 20 18 22; 89 25 21 23 27; 90 27 23 24 28; 91 28 24 22 26
31. 92 29 25 27 31; 93 31 27 28 32; 94 32 28 26 30; 95 33 29 31 35; 96 35 31 32 36
32. 97 36 32 30 34; 98 37 33 35 39; 99 39 35 36 40; 100 40 36 34 38
33. 101 41 37 39 43; 102 43 39 40 44; 103 44 40 38 42; 104 5 1 3 7; 105 7 3 4 8
34. 106 8 4 2 6
35. ELEMENT PROPERTY
36. 77 TO 106 THICKNESS 0.1
37. DEFINE MATERIAL START
38. ISOTROPIC CONCRETE

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 1 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 2

39. E 2.21467E+009
40. POISSON 0.17
41. DENSITY 2402.62
42. ALPHA 1E-005
43. DAMP 0.05
44. TYPE CONCRETE
45. STRENGTH FCU 2.81228E+006
46. END DEFINE MATERIAL
47. MEMBER PROPERTY AMERICAN
48. 6 7 13 14 20 21 27 28 34 35 41 42 48 49 55 56 62 63 69 70 PRIS YD 0.25 ZD 0.25
49. 5 12 19 26 33 40 47 54 61 68 PRIS YD 0.4 ZD 0.5
50. CONSTANTS
51. MATERIAL CONCRETE ALL
52. SUPPORTS
53. 1 TO 44 ELASTIC MAT DIRECT Y SUBGRADE 35150 PRINT

JOINT INFLUENCE AREA


----- --------------

1 0.132600
2 0.190380
3 0.322980
4 0.380760
5 0.265200
6 0.380760
7 0.645959
8 0.761519
9 0.265200
10 0.380760
11 0.645959
12 0.761519
13 0.265200
14 0.380760
15 0.645959
16 0.761519
17 0.265200
18 0.380760
19 0.645959
20 0.761519
21 0.265200
22 0.380760
23 0.645959
24 0.761519
25 0.265200
26 0.380760
27 0.645959
28 0.761519
29 0.265200
30 0.380760
31 0.645959
32 0.761519
33 0.265200
34 0.380760
35 0.645959
36 0.761519
37 0.265200

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 2 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 3

38 0.380760
39 0.645959
40 0.761519
41 0.132600
42 0.190380
43 0.322980
44 0.380760
TOTAL 20.534380
54. LOAD 1 LOADTYPE DEAD TITLE BS
55. SELFWEIGHT Y -1 LIST 5 TO 7 12 TO 14 19 TO 21 26 TO 28 33 TO 35 40 TO 42 47 -
56. 48 TO 49 54 TO 56 61 TO 63 68 TO 70 77 TO 103
57. LOAD 2 LOADTYPE NONE TITLE BM
58. ELEMENT LOAD
59. 77 80 83 86 89 92 95 98 101 104 TRAP GX Y 0 748
60. 78 81 84 87 90 93 96 99 102 105 TRAP GX Y 748 1824
61. 79 82 85 88 91 94 97 100 103 106 TRAP GX Y 1824 2894
62. LOAD 3 LOADTYPE LIVE TITLE SURCHARGE
63. ELEMENT LOAD
64. 77 TO 106 PR GX 400
65. LOAD COMB 4 KONDISI KOSONG
66. 1 1.2 2 1.2 3 1.6
67. PERFORM ANALYSIS PRINT STATICS CHECK

P R O B L E M S T A T I S T I C S
-----------------------------------

NUMBER OF JOINTS 44 NUMBER OF MEMBERS 30


NUMBER OF PLATES 30 NUMBER OF SOLIDS 0
NUMBER OF SURFACES 0 NUMBER OF SUPPORTS 44

SOLVER USED IS THE OUT-OF-CORE BASIC SOLVER

ORIGINAL/FINAL BAND-WIDTH= 6/ 6/ 21 DOF


TOTAL PRIMARY LOAD CASES = 3, TOTAL DEGREES OF FREEDOM = 132
TOTAL LOAD COMBINATION CASES = 1 SO FAR.
SIZE OF STIFFNESS MATRIX = 3 DOUBLE KILO-WORDS
REQRD/AVAIL. DISK SPACE = 12.2/ 163525.7 MB

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 3 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 4

*WARNING- APPLIED SELFWEIGHT IS LESS THAN TOTAL WEIGHT OF ALL


STRUCTURAL ELEMENTS IN LOAD CASE 1 ALONG Y.
THIS COULD BE DUE TO SELFWEIGHT APPLIED TO SPECIFIC
LIST OF MEMBERS/PLATES/SOLIDS/SURFACES.
TOTAL UNFACTORED WEIGHT OF THE STRUCTURE = 9618.740 KG
TOTAL UNFACTORED WEIGHT OF THE STRUCTURE APPLIED = 9125.378 KG

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 1


LOADTYPE DEAD TITLE BS

CENTER OF FORCE BASED ON Y FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.156540401E+01
Y = -0.156540401E+01
Z = 0.314597562E+01

***TOTAL APPLIED LOAD ( KG METE ) SUMMARY (LOADING 1 )


SUMMATION FORCE-X = 0.00
SUMMATION FORCE-Y = -9125.38
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 28708.22 MY= 0.00 MZ= -14284.90

***TOTAL REACTION LOAD( KG METE ) SUMMARY (LOADING 1 )


SUMMATION FORCE-X = 0.00
SUMMATION FORCE-Y = 9125.38
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= -28708.22 MY= 0.00 MZ= 14284.90

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 1)


MAXIMUMS AT NODE
X = 0.00000E+00 0
Y = -1.26498E+00 38
Z = 0.00000E+00 0
RX= 3.36454E-06 1
RY= 0.00000E+00 0
RZ= -2.40424E-06 2

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 2


LOADTYPE NONE TITLE BM

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 4 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 5

CENTER OF FORCE BASED ON X FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.161316344E+01
Y = -0.161316344E+01
Z = 0.300000044E+01

***TOTAL APPLIED LOAD ( KG METE ) SUMMARY (LOADING 2 )


SUMMATION FORCE-X = 29741.08
SUMMATION FORCE-Y = 0.00
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 0.00 MY= 89223.25 MZ= 47977.22

***TOTAL REACTION LOAD( KG METE ) SUMMARY (LOADING 2 )


SUMMATION FORCE-X = -29741.08
SUMMATION FORCE-Y = 0.00
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 0.00 MY= -89223.25 MZ= -47977.22

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 2)


MAXIMUMS AT NODE
X = 0.00000E+00 0
Y = 0.00000E+00 0
Z = 0.00000E+00 0
RX= 0.00000E+00 0
RY= 0.00000E+00 0
RZ= 0.00000E+00 0

STATIC LOAD/REACTION/EQUILIBRIUM SUMMARY FOR CASE NO. 3


LOADTYPE LIVE TITLE SURCHARGE

CENTER OF FORCE BASED ON X FORCES ONLY (METE).


(FORCES IN NON-GLOBAL DIRECTIONS WILL INVALIDATE RESULTS)

X = 0.120999996E+01
Y = -0.120999996E+01
Z = 0.300000044E+01

***TOTAL APPLIED LOAD ( KG METE ) SUMMARY (LOADING 3 )


SUMMATION FORCE-X = 8213.75
SUMMATION FORCE-Y = 0.00
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 0.00 MY= 24641.26 MZ= 9938.64

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 5 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 6

***TOTAL REACTION LOAD( KG METE ) SUMMARY (LOADING 3 )


SUMMATION FORCE-X = -8213.75
SUMMATION FORCE-Y = 0.00
SUMMATION FORCE-Z = 0.00

SUMMATION OF MOMENTS AROUND THE ORIGIN-


MX= 0.00 MY= -24641.26 MZ= -9938.64

MAXIMUM DISPLACEMENTS ( CM /RADIANS) (LOADING 3)


MAXIMUMS AT NODE
X = 0.00000E+00 0
Y = 0.00000E+00 0
Z = 0.00000E+00 0
RX= 0.00000E+00 0
RY= 0.00000E+00 0
RZ= 0.00000E+00 0

************ END OF DATA FROM INTERNAL STORAGE ************

68. START CONCRETE DESIGN

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 6 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 7

69. CODE ACI


70. FC 1.75E+006 MEMB 77 TO 106
71. FYMAIN 2.4E+007 MEMB 77 TO 106
72. DESIGN ELEMENT ALL

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 7 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 8

ACI 318-11 ELEMENT DESIGN SUMMARY


=====================================

ELEMENT LONG. REINF MOM-X /LOAD TRANS. REINF MOM-Y /LOAD


(SQ.MM/MM) (KN-MM/MM) (SQ.MM/MM) (KN-MM/MM)

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
77 TOP : Longitudinal direction - Only minimum steel required.
77 BOTT: Longitudinal direction - Only minimum steel required.
77 TOP : Transverse direction - Only minimum steel required.
77 BOTT: Transverse direction - Only minimum steel required.
77 TOP : 0.200 0.00 / 0 0.200 0.00 / 0
BOTT: 0.200 0.00 / 4 0.200 0.00 / 3

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
78 TOP : Longitudinal direction - Only minimum steel required.
78 BOTT: Longitudinal direction - Only minimum steel required.
78 TOP : Transverse direction - Only minimum steel required.
78 BOTT: Transverse direction - Only minimum steel required.
78 TOP : 0.200 0.00 / 0 0.200 0.00 / 0
BOTT: 0.200 0.00 / 4 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
79 TOP : Longitudinal direction - Only minimum steel required.
79 BOTT: Longitudinal direction - Only minimum steel required.
79 TOP : Transverse direction - Only minimum steel required.
79 BOTT: Transverse direction - Only minimum steel required.
79 TOP : 0.200 0.00 / 0 0.200 0.00 / 0
BOTT: 0.200 0.00 / 4 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
80 TOP : Longitudinal direction - Only minimum steel required.
80 BOTT: Longitudinal direction - Only minimum steel required.
80 TOP : Transverse direction - Only minimum steel required.
80 BOTT: Transverse direction - Only minimum steel required.
80 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
81 TOP : Longitudinal direction - Only minimum steel required.
81 BOTT: Longitudinal direction - Only minimum steel required.
81 TOP : Transverse direction - Only minimum steel required.
81 BOTT: Transverse direction - Only minimum steel required.
81 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
82 TOP : Longitudinal direction - Only minimum steel required.
82 BOTT: Longitudinal direction - Only minimum steel required.
82 TOP : Transverse direction - Only minimum steel required.

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 8 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 9

82 BOTT: Transverse direction - Only minimum steel required.


82 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
83 TOP : Longitudinal direction - Only minimum steel required.
83 BOTT: Longitudinal direction - Only minimum steel required.
83 TOP : Transverse direction - Only minimum steel required.
83 BOTT: Transverse direction - Only minimum steel required.
83 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
84 TOP : Longitudinal direction - Only minimum steel required.
84 BOTT: Longitudinal direction - Only minimum steel required.
84 TOP : Transverse direction - Only minimum steel required.
84 BOTT: Transverse direction - Only minimum steel required.
84 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
85 TOP : Longitudinal direction - Only minimum steel required.
85 BOTT: Longitudinal direction - Only minimum steel required.
85 TOP : Transverse direction - Only minimum steel required.
85 BOTT: Transverse direction - Only minimum steel required.
85 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
86 TOP : Longitudinal direction - Only minimum steel required.
86 BOTT: Longitudinal direction - Only minimum steel required.
86 TOP : Transverse direction - Only minimum steel required.
86 BOTT: Transverse direction - Only minimum steel required.
86 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
87 TOP : Longitudinal direction - Only minimum steel required.
87 BOTT: Longitudinal direction - Only minimum steel required.
87 TOP : Transverse direction - Only minimum steel required.
87 BOTT: Transverse direction - Only minimum steel required.
87 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
88 TOP : Longitudinal direction - Only minimum steel required.
88 BOTT: Longitudinal direction - Only minimum steel required.
88 TOP : Transverse direction - Only minimum steel required.
88 BOTT: Transverse direction - Only minimum steel required.

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 9 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 10

88 TOP : 0.200 0.00 / 4 0.200 0.00 / 0


BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
89 TOP : Longitudinal direction - Only minimum steel required.
89 BOTT: Longitudinal direction - Only minimum steel required.
89 TOP : Transverse direction - Only minimum steel required.
89 BOTT: Transverse direction - Only minimum steel required.
89 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
90 TOP : Longitudinal direction - Only minimum steel required.
90 BOTT: Longitudinal direction - Only minimum steel required.
90 TOP : Transverse direction - Only minimum steel required.
90 BOTT: Transverse direction - Only minimum steel required.
90 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
91 TOP : Longitudinal direction - Only minimum steel required.
91 BOTT: Longitudinal direction - Only minimum steel required.
91 TOP : Transverse direction - Only minimum steel required.
91 BOTT: Transverse direction - Only minimum steel required.
91 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
92 TOP : Longitudinal direction - Only minimum steel required.
92 BOTT: Longitudinal direction - Only minimum steel required.
92 TOP : Transverse direction - Only minimum steel required.
92 BOTT: Transverse direction - Only minimum steel required.
92 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
93 TOP : Longitudinal direction - Only minimum steel required.
93 BOTT: Longitudinal direction - Only minimum steel required.
93 TOP : Transverse direction - Only minimum steel required.
93 BOTT: Transverse direction - Only minimum steel required.
93 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
94 TOP : Longitudinal direction - Only minimum steel required.
94 BOTT: Longitudinal direction - Only minimum steel required.
94 TOP : Transverse direction - Only minimum steel required.
94 BOTT: Transverse direction - Only minimum steel required.

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 10 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 11

94 TOP : 0.200 0.00 / 4 0.200 0.00 / 0


BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
95 TOP : Longitudinal direction - Only minimum steel required.
95 BOTT: Longitudinal direction - Only minimum steel required.
95 TOP : Transverse direction - Only minimum steel required.
95 BOTT: Transverse direction - Only minimum steel required.
95 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
96 TOP : Longitudinal direction - Only minimum steel required.
96 BOTT: Longitudinal direction - Only minimum steel required.
96 TOP : Transverse direction - Only minimum steel required.
96 BOTT: Transverse direction - Only minimum steel required.
96 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
97 TOP : Longitudinal direction - Only minimum steel required.
97 BOTT: Longitudinal direction - Only minimum steel required.
97 TOP : Transverse direction - Only minimum steel required.
97 BOTT: Transverse direction - Only minimum steel required.
97 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
98 TOP : Longitudinal direction - Only minimum steel required.
98 BOTT: Longitudinal direction - Only minimum steel required.
98 TOP : Transverse direction - Only minimum steel required.
98 BOTT: Transverse direction - Only minimum steel required.
98 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
99 TOP : Longitudinal direction - Only minimum steel required.
99 BOTT: Longitudinal direction - Only minimum steel required.
99 TOP : Transverse direction - Only minimum steel required.
99 BOTT: Transverse direction - Only minimum steel required.
99 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
100 TOP : Longitudinal direction - Only minimum steel required.
100 BOTT: Longitudinal direction - Only minimum steel required.
100 TOP : Transverse direction - Only minimum steel required.
100 BOTT: Transverse direction - Only minimum steel required.

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 11 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 12

100 TOP : 0.200 0.00 / 4 0.200 0.00 / 0


BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
101 TOP : Longitudinal direction - Only minimum steel required.
101 BOTT: Longitudinal direction - Only minimum steel required.
101 TOP : Transverse direction - Only minimum steel required.
101 BOTT: Transverse direction - Only minimum steel required.
101 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
102 TOP : Longitudinal direction - Only minimum steel required.
102 BOTT: Longitudinal direction - Only minimum steel required.
102 TOP : Transverse direction - Only minimum steel required.
102 BOTT: Transverse direction - Only minimum steel required.
102 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
103 TOP : Longitudinal direction - Only minimum steel required.
103 BOTT: Longitudinal direction - Only minimum steel required.
103 TOP : Transverse direction - Only minimum steel required.
103 BOTT: Transverse direction - Only minimum steel required.
103 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
104 TOP : Longitudinal direction - Only minimum steel required.
104 BOTT: Longitudinal direction - Only minimum steel required.
104 TOP : Transverse direction - Only minimum steel required.
104 BOTT: Transverse direction - Only minimum steel required.
104 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
105 TOP : Longitudinal direction - Only minimum steel required.
105 BOTT: Longitudinal direction - Only minimum steel required.
105 TOP : Transverse direction - Only minimum steel required.
105 BOTT: Transverse direction - Only minimum steel required.
105 TOP : 0.200 0.00 / 4 0.200 0.00 / 0
BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

FY: 235.358 MPA FC: 17.161 MPA COVER (TOP): 19.050 MM


COVER (BOTTOM): 19.050 MM TH: 100.000 MM
106 TOP : Longitudinal direction - Only minimum steel required.
106 BOTT: Longitudinal direction - Only minimum steel required.
106 TOP : Transverse direction - Only minimum steel required.
106 BOTT: Transverse direction - Only minimum steel required.

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 12 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 13

106 TOP : 0.200 0.00 / 4 0.200 0.00 / 0


BOTT: 0.200 0.00 / 3 0.200 0.00 / 4

***************************END OF ELEMENT DESIGN***************************

73. FC 1.75E+006 MEMB 5 TO 7 12 TO 14 19 TO 21 26 TO 28 33 TO 35 40 TO 42 -


74. 47 TO 49 54 TO 56 61 TO 63 68 TO 70
75. FYMAIN 2.4E+007 MEMB 5 TO 7 12 TO 14 19 TO 21 26 TO 28 33 TO 35 40 TO 42 47 -
76. 48 TO 49 54 TO 56 61 TO 63 68 TO 70
77. FYSEC 2.4E+007 ALL
78. DESIGN BEAM ALL

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 13 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 14

ACI 318-11 BEAM NO. 5 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 22. 453. NO NO


2 343. 2 - 12MM 0. 320. YES NO
3 343. 2 - 12MM 155. 600. NO YES

B E A M N O. 5 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 5 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 5 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 2J____________________ 600X 500X 400_____________________ 6J____


| |
||=========================================================================||
| 2No12 H 343. 0.TONo320H 343. 155.TO 600 |
| |
| 2No12 H 57. 22.TO 453 |
| ======================================================== |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 14 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 15

ACI 318-11 BEAM NO. 6 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 24. 401. NO NO


2 193. 2 - 12MM 0. 246. YES NO
3 193. 2 - 12MM 179. 600. NO YES

B E A M N O. 6 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.06 KNS Vc= 31.69 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.27 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 3J____________________ 600X 250X 250_____________________ 7J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 24612|H 193. 179.TO 600 | |
| 3*12c/c 97 | | | 3*12c/c 97 |
| 2No12 H 57. 24.TO 401| | |
| ================================================ |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 15 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 16

ACI 318-11 BEAM NO. 7 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 24. 401. NO NO


2 193. 2 - 12MM 0. 246. YES NO
3 193. 2 - 12MM 179. 600. NO YES

B E A M N O. 7 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.05 KNS Vc= 31.69 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.28 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 4J____________________ 600X 250X 250_____________________ 8J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 24612|H 193. 179.TO 600 | |
| 3*12c/c 97 | | | 3*12c/c 97 |
| 2No12 H 57. 24.TO 401| | |
| ================================================ |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 16 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 17

ACI 318-11 BEAM NO. 12 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 123. 452. NO NO


2 343. 2 - 12MM 0. 420. YES NO
3 343. 2 - 12MM 155. 600. NO YES

B E A M N O. 12 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 12 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 12 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 6J____________________ 600X 500X 400_____________________ 10J____


| |
||=========================================================================||
| 2No12 H 343. 0.TONo420H 343. 155.TO 600 |
| |
| 2No12 H 57. 123.TO 452 |
| =========================================== |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 17 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 18

ACI 318-11 BEAM NO. 13 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 174. 451. NO NO


2 193. 2 - 12MM 0. 396. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 13 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.21 KNS Vc= 31.69 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.13 KNS Vc= 31.69 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 7J____________________ 600X 250X 250_____________________ 11J____


| |
||=========================================================================||
| 2No12 H 193. 0.TO 396 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | 3*12c/c 97 |
| 2No12|H 57. 174.TO 451 | |
| ==================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 18 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 19

ACI 318-11 BEAM NO. 14 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 174. 451. NO NO


2 193. 2 - 12MM 0. 396. YES NO
3 193. 2 - 12MM 279. 600. NO YES

B E A M N O. 14 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.22 KNS Vc= 31.69 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.11 KNS Vc= 31.69 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 8J____________________ 600X 250X 250_____________________ 12J____


| |
||=========================================================================||
| 2No12 H 193. 0.TO 396 | 2No12 H 193.|279.TO 600 |
| 3*12c/c 97 | | 3*12c/c 97 |
| 2No12|H 57. 174.TO 451 | |
| ==================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 19 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 20

ACI 318-11 BEAM NO. 19 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 123. 452. NO NO


2 343. 2 - 12MM 0. 420. YES NO
3 343. 2 - 12MM 205. 600. NO YES

B E A M N O. 19 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 19 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 19 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 10J____________________ 600X 500X 400_____________________ 14J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 4202No12 H 343. 205.TO 600 |
| |
| 2No12 H 57. 123.TO 452 |
| =========================================== |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 20 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 21

ACI 318-11 BEAM NO. 20 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 20 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.16 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 11J____________________ 600X 250X 250_____________________ 15J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 21 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 22

ACI 318-11 BEAM NO. 21 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 21 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.16 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 12J____________________ 600X 250X 250_____________________ 16J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 22 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 23

ACI 318-11 BEAM NO. 26 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 73. 502. NO NO


2 343. 2 - 12MM 0. 370. YES NO
3 343. 2 - 12MM 205. 600. NO YES

B E A M N O. 26 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 26 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 26 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 14J____________________ 600X 500X 400_____________________ 18J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 3702No12 H 343. 205.TO 600 |
| |
| 2No12 H 57. 73.TO 502 |
| ======================================================= |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 23 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 24

ACI 318-11 BEAM NO. 27 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 27 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 15J____________________ 600X 250X 250_____________________ 19J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 24 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 25

ACI 318-11 BEAM NO. 28 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 28 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 16J____________________ 600X 250X 250_____________________ 20J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 25 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 26

ACI 318-11 BEAM NO. 33 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 73. 502. NO NO


2 343. 2 - 12MM 0. 370. YES NO
3 343. 2 - 12MM 205. 600. NO YES

B E A M N O. 33 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 33 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 33 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 18J____________________ 600X 500X 400_____________________ 22J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 3702No12 H 343. 205.TO 600 |
| |
| 2No12 H 57. 73.TO 502 |
| ======================================================= |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 26 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 27

ACI 318-11 BEAM NO. 34 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 34 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 19J____________________ 600X 250X 250_____________________ 23J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 27 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 28

ACI 318-11 BEAM NO. 35 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 35 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 20J____________________ 600X 250X 250_____________________ 24J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 28 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 29

ACI 318-11 BEAM NO. 40 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 73. 502. NO NO


2 343. 2 - 12MM 0. 370. YES NO
3 343. 2 - 12MM 205. 600. NO YES

B E A M N O. 40 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 40 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 40 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 22J____________________ 600X 500X 400_____________________ 26J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 3702No12 H 343. 205.TO 600 |
| |
| 2No12 H 57. 73.TO 502 |
| ======================================================= |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 29 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 30

ACI 318-11 BEAM NO. 41 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 41 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 23J____________________ 600X 250X 250_____________________ 27J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 30 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 31

ACI 318-11 BEAM NO. 42 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 42 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 24J____________________ 600X 250X 250_____________________ 28J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 31 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 32

ACI 318-11 BEAM NO. 47 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 73. 502. NO NO


2 343. 2 - 12MM 0. 370. YES NO
3 343. 2 - 12MM 205. 600. NO YES

B E A M N O. 47 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 47 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 47 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 26J____________________ 600X 500X 400_____________________ 30J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 3702No12 H 343. 205.TO 600 |
| |
| 2No12 H 57. 73.TO 502 |
| ======================================================= |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 32 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 33

ACI 318-11 BEAM NO. 48 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 48 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 27J____________________ 600X 250X 250_____________________ 31J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 33 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 34

ACI 318-11 BEAM NO. 49 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 49 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 28J____________________ 600X 250X 250_____________________ 32J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 34 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 35

ACI 318-11 BEAM NO. 54 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 73. 502. NO NO


2 343. 2 - 12MM 0. 370. YES NO
3 343. 2 - 12MM 205. 600. NO YES

B E A M N O. 54 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 54 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 54 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 30J____________________ 599X 500X 400_____________________ 34J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 3702No12 H 343. 205.TO 600 |
| |
| 2No12 H 57. 73.TO 502 |
| ======================================================= |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 35 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 36

ACI 318-11 BEAM NO. 55 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 55 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

___ 31J____________________ 599X 250X 250_____________________ 35J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 36 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 37

ACI 318-11 BEAM NO. 56 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 56 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

___ 32J____________________ 599X 250X 250_____________________ 36J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 37 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 38

ACI 318-11 BEAM NO. 61 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 72. 503. NO NO


2 343. 2 - 12MM 0. 370. YES NO
3 343. 2 - 12MM 205. 600. NO YES

B E A M N O. 61 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 61 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 61 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 34J____________________ 599X 500X 400_____________________ 38J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 3702No12 H 343. 205.TO 600 |
| |
| 2No12 H 57. 72.TO 503 |
| ======================================================= |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 38 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 39

ACI 318-11 BEAM NO. 62 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 62 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

AT END SUPPORT - Vu= 0.16 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

___ 35J____________________ 599X 250X 250_____________________ 39J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 39 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 40

ACI 318-11 BEAM NO. 63 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 124. 451. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 229. 600. NO YES

B E A M N O. 63 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

AT END SUPPORT - Vu= 0.17 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 113. MM

___ 36J____________________ 599X 250X 250_____________________ 40J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 |2No12 H 193. 229.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|124.TO 451 | |
| =========================================== |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 40 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 41

ACI 318-11 BEAM NO. 68 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 500. X 400. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 71. 554. NO NO


2 343. 2 - 12MM 0. 370. YES NO
3 343. 2 - 12MM 255. 600. NO YES

B E A M N O. 68 D E S I G N R E S U L T S - SHEAR

** LOCATION FOR DESIGN FOR SHEAR AT START OF MEMBER 68 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

** LOCATION FOR DESIGN FOR SHEAR AT END OF MEMBER 68 IS BEYOND


THE MIDPOINT OF MEMBER. DESIGN FOR SHEAR AND TORSION NOT PERFORMED.

___ 38J____________________ 600X 500X 400_____________________ 42J____


| |
||=========================================================================||
| 2No12 H 343. 0.TO 370 2No12 H 343. 255.TO 600 |
| |
| 2No12 H 57. 71.TO 554 |
| ============================================================== |
| |
|___________________________________________________________________________|
___________________ ___________________ ___________________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|___________________| |___________________| |___________________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 41 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 42

ACI 318-11 BEAM NO. 69 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 123. 552. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 329. 600. NO YES

B E A M N O. 69 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.22 KNS Vc= 31.71 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.11 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 39J____________________ 600X 250X 250_____________________ 43J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 | 2No12 H 193. 329.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|123.TO 552 | | |
| ======================================================= |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 42 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 43

ACI 318-11 BEAM NO. 70 DESIGN RESULTS


=============================================

LEN - 600. MM FY - 235. FC - 17. MPA, SIZE - 250. X 250. MMS

LEVEL HEIGHT BAR INFO FROM TO ANCHOR


(MM) (MM) (MM) STA END
_____________________________________________________________________

1 57. 2 - 12MM 123. 552. NO NO


2 193. 2 - 12MM 0. 346. YES NO
3 193. 2 - 12MM 329. 600. NO YES

B E A M N O. 70 D E S I G N R E S U L T S - SHEAR

AT START SUPPORT - Vu= 0.22 KNS Vc= 31.71 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

AT END SUPPORT - Vu= 0.11 KNS Vc= 31.70 KNS Vs= 0.00 KNS
Tu= 0.00 KN-MET Tc= 1.0 KN-MET Ts= 0.0 KN-MET LOAD 1
NO STIRRUPS ARE REQUIRED FOR TORSION.
REINFORCEMENT FOR SHEAR IS PER CL.11.5.5.1.
PROVIDE 12 MM 2-LEGGED STIRRUPS AT 97. MM C/C FOR 114. MM

___ 40J____________________ 600X 250X 250_____________________ 44J____


| |
||=========================================================================||
| 2No12 H 193. | 0.TO 346 | 2No12 H 193. 329.TO| 600 |
| 3*12c/c 97 | | | 3*12c/c 97 |
| |2No12 H 57.|123.TO 552 | | |
| ======================================================= |
| |
|___________________________________________________________________________|
_______________ _______________ _______________
| | | | | |
| oo | | oo | | oo |
| 2#12 | | 2#12 | | 2#12 |
| | | | | |
| | | 2#12 | | |
| | | oo | | |
| | | | | |
|_______________| |_______________| |_______________|

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 43 of 44


Sunday, April 08, 2018, 06:07 PM
STAAD SPACE -- PAGE NO. 44

********************END OF BEAM DESIGN**************************

79. END CONCRETE DESIGN


80. FINISH

*********** END OF THE STAAD.Pro RUN ***********

**** DATE= APR 5,2018 TIME= 13:10:28 ****

************************************************************
* For technical assistance on STAAD.Pro, please visit *
* http://selectservices.bentley.com/en-US/ *
* *
* Details about additional assistance from *
* Bentley and Partners can be found at program menu *
* Help->Technical Support *
* *
* Copyright (c) 1997-2015 Bentley Systems, Inc.
* http://www.bentley.com *
************************************************************

E:\Proyek 2018\Cilacap\Saluran Induk Alternatif A.anl Page 44 of 44