Professional Documents
Culture Documents
Ironing out
resonance
Ferroresonance prevention in MV voltage transformers
Wojciech Piasecki, Marek Florkowski, Marek Fulczyk,
Pentti Mahonen, Mariusz Luto, Wieslaw Nowak, Otto Preiss
Every engineer knows the phenomenon of resonance. Without it, there would
be no musical instruments, no radio-based communication and many natural
phenomena, ranging from the astronomical to the sub-atomic would not occur.
The occurrence is not always benign: Oscillations can reach amplitudes for
which the system was not designed, leading to damage and failure. In 1940 the
Tacoma Narrows Bridge in the USA collapsed spectacularly as the result of
undamped resonance. Resonance is also a frequent cause of malfunction in
electronic systems.
Grid reliability
flux ψ
allel and the series resonant circuits 1 . occur at various frequencies.
ng
operati
ns
In the series circuit, the equivalent im- In practice, ferroresonant oscillations
conditio
pedance is the sum of the impedances are initiated by momentary saturation
normal
of the individual components: of the core of the inductive element
as a a result of switching operations,
Ζ(ω) = jωL – j __
1 +R
s
for example. The effects of such reso- current i
ωC nance are further aggravated if damp-
ing is insufficient.
In the parallel resonant circuit the
3 Ungrounded MV network with three
equivalent admittance is the sum of
single-phase voltage transformers
the admittances of the individual com-
ponents:
Currents can occur that connected phase-to-ground.
exceed nominal values
Y(ω) = jωC – j __
1 + __
1 by orders of magnitude, R
ωL RP risking damage to the S
T
The resonance pulsation is VTs.
UN
C C C
ωr = 1 VT1 VT2 VT3
√LC In many cases of non-transient reso-
nance involving a saturated inductive
in both cases. At and near to this fre- element, some nodes in the equiva-
quency in the series circuit, voltages lent network circuit are electrically
4 The result of the ferroresonance in
across the capacitor and the induc- floating (or connected to the fixed
unprotected VT.
tance can reach values that exceed potential points through very high
the source voltage significantly. In the impedances). Such a situation is illus-
parallel circuit, it is the currents trated in the network of 3 .
through these components that are
similarly amplified. Such extreme val- Although ferroresonance can also be
ues can damage the equipment if no initiated in other situations (eg, capac-
remedial action is taken. itive coupling between parallel lines,
ferroresonance between the VT and
For known values of L and C, the the power transformer’s internal ca-
resonant frequency can be predicted. pacitance or single-phase disconnec-
Resonance-related hazards can be tion in grounded networks) the con-
avoided by maintaining an appropri- figuration shown in 3 reflects a typi-
ate safety margin from the power- cal unearthed distribution system with
supply frequency. single-pole VTs.
Grid reliability
Despite first publications on the fer- this day. No universally applicable thermal damage to the primary wind-
roresonance phenomenon appearing mitigation methods exist other than a ing if not appropriately damped 4 .
at the beginning of the 20th century, damping resistor connected to the
open-delta auxiliary windings of the The compact design of modern volt-
three individual VTs. age transformers and the high quality
The compact design of of the magnetic material (low losses)
modern voltage trans- Risk to equipment makes damping difficult. The resistive
formers and the high Under normal operating conditions,
the primary currents in the MV volt-
load must have a low value to dissi-
pate sufficient oscillation energy. Too
quality of the magnetic age transformers are typically well be- small a value, however, draws too
material (low losses) low 10mA. In ferroresonance, the core much power from the VT when a sus-
of the VT operates in the deep satura- tained zero-sequence voltage occurs
makes damping difficult. tion region and primary currents can (eg, due to a ground fault that is not
reach amp values. The two order of cleared), and so overloads the VT
no reliable criteria on the risk of fer- magnitude difference between normal thermally. Selecting the right resist-
roresonance have been formulated to and ferroresonant conditions leads to ance is therefore crucial.
5 Simulated and experimentally obtained primary VT current and neutral voltage for capacitance C within the hazardous range.
2.0 2.0
0 0
-2.0 -2.0
0 0.2 0.4 0.6 0.8 1.0 0 0.2 0.4 0.6 0.8 1.0
20 20
0 0
-20 -20
0 0.2 0.4 0.6 0.8 1.0 0 0.2 0.4 0.6 0.8 1.0
6 Simulated and experimentally obtained primary VT current and neutral voltage for capacitance C above the hazardous range.
500 500
0 0
-500 -500
0 0.2 0.4 0.6 0.8 1.0 0 0.2 0.4 0.6 0.8 1.0
2.0 2.0
0 0
-2.0 -2.0
0 0.2 0.4 0.6 0.8 1.0 0 0.2 0.4 0.6 0.8 1.0
Grid reliability
7 FerroTool for potential ferroresonance risk identification for particular network VT configuration.
VT type selection
Substation view
Link to VT manager
Analysis of potential ferroresonance models were inserted into an equiva- maximum damping resistance for dif-
To analyze the network conditions for lent network model with ungrounded ferent VT types and voltage levels.
which ferroresonance is initiated in voltage sources and line-to-ground To make full use of these results in
particular VT types, simulations were capacitances. A worst-case analysis of practical applications, software tools
performed using dedicated transient the unloaded network was performed were implemented for the fast identifi-
to determine the capacitance range in cation of potential ferroresonance.
FerroTool contains a data- which hazardous ferroresonance oc- FerroTool 7 contains a database map-
curs. Including the auxiliary windings ping VTs to their parameters, includ-
base mapping VTs to their and damping resistors in the models ing hazardous capacitance ranges and
parameters, including helped identify the optimal resistor suggested damping resistances. The
hazardous capacitance values. tool calculates equivalent capacitance
values for substations based on the
ranges and suggested Simulation results were verified exper- line characteristics to permit fast
damping resistances. imentally. 5 shows a switching re- analysis of the risk of ferroresonance.
sponse with ferroresonant oscillation
simulation software (PSpice,
ATP/EMTP). Simulating transient re-
and 6 shows a response without.
Computer simulations and
sponses to switching events involved FerroTool and FerroSim experiments show that in
making models of various VT types, The simulations identified the haz- many cases the resistance
based on magnetic parameters. These ardous capacitance range and the
needed to damp ferrores-
onant oscillations is very
8 Predefined circuit model and stimulus. small. Such a resistor
eA
would, however, draw too
RS LS iA ipA
t=0
Um much current from the VT
Rp
uA C
k:1 in the case of a network
i(ψA) Overvoltage factor
kov=Um/Em asymmetry.
eB
FerroTool is supported by the FerroSim
RS LS iB ipB
Em dedicated software for simulating a
t=0 Rp network response to switching tran-
Voltage
k:1
uB C t0 sients 8 . As the topology of the circuit
i(ψB) Rt is predefined, the user interface is kept
0
Time very simple 9 .
eC RS LS iC ipC
VT Guard: New
SmartLoad: Newferroresonance
ferroresonance
t=0 Rp
k:1 prevention concept
prevention concept
uC C phase A Computer simulations and experi-
i(ψC)
phase B ments show that in many cases the
phase C resistance needed to damp ferroreso-
nant oscillations is very small (< 20 W).
Grid reliability
9 User interface of the FerroSim and exemplary results showing the primary VT currents and the neutral voltage.