You are on page 1of 5

UNDERSTANDING FERRORESONANCE

Marta Val Escudero (1), Ivan Dudurych (2), Miles Redfern (3)
(1) ESB International, Ireland. (2) ESB National Grid, Ireland. (3) University of Bath, UK.

ABSTRACT

This paper presents a ferroresonant experience involving inductive Voltage Transformers (VTs) in a 400kV substation.
The origin of the phenomena, the conditions under it may become sustained and its effects on plant equipment are
discussed. A very comprehensive analysis is performed using time domain simulations with ATP. Simulation results
reproduced satisfactorily the ferroresonant events recorded during the field tests in the 400kV substation. A number of
mitigation options are discussed.
Keywords: Ferroresonance, Non-Linear Dynamics, Inductive Voltage Transformers, Circuit Breaker Grading
Capacitors, Power System Modelling, ATP/EMTP.

INTRODUCTION normal steady-state condition to jump into another


stable operation point with very high currents and/or
The term ferroresonance can be found in technical voltages. Another significant characteristic of a
literature dating as far back as 1920 (P. Boucherot) [1] ferroresonant oscillation is the presence of highly
referring to an oscillating phenomenon between a non- distorted voltage and current waveforms.
linear inductance and a capacitor. Since then a large
number of papers have been published describing the From an operational point of view, ferroresonant
phenomenon, proposing analytical methods or reporting oscillations can represent a hazard to the plant
experienced cases. Despite the extensive literature, equipment integrity. Large currents and/or voltages may
ferroresonance still remains widely unknown and is overheat the transformer primary winding and might,
feared by Power Systems Operators as it seems to occur eventually, cause insulation breakdown. The large
randomly, possibly resulting in the catastrophic voltage oscillations (temporary or sustained) can also
destruction of plant equipment. This general lack of cause severe stresses on the insulation of all the
knowledge means that ferroresonance is normally equipment connected to the same circuit. Surge arresters
overlooked at the planning and design stages or, on the are the typical victims due to their low TOV
contrary, held responsible for “inexplicable” equipment capabilities. Additionally, maloperation of protection
failures. relays may also occur due to the highly distorted
waveforms measured by the instrument transformers.
For ferroresonance to occur, the following elements The systems engineer’s challenge is to predict whether
must be present: ferroresonance can arise in a particular circuit and to
1. A non-linear inductance. This appears in a determine a good operational safety margin.
transformer ferromagnetic core.
2. A capacitance. This can appear in the form of Ferroresonance can happen at any voltage level with the
voltage grading capacitors in HV circuit breakers, appropriate combination of capacitance, non-linear
conductor inter-phase capacitances, capacitance to inductance and low losses. Studies and field experience
ground of cables and long lines, series capacitors or have shown that certain power system configurations
shunt capacitor banks. are more susceptible to ferroresonance than others. The
3. Low Losses. These are present in very lightly loaded most frequent cases are listed below:
transformers combined with modern low losses • Voltage Transformers energized through grading
magnetic cores. capacitors of open circuit breakers.
4. A voltage or current source. • Voltage Transformers connected to an isolated or
resonant neutral system (distribution networks).
In linear circuits, resonance occurs when the capacitive • Power Transformers energized in only one or two
reactance equals the inductive reactance at the circuit phases.
source frequency, resulting in large currents and
• Lightly loaded Power Transformers connected to a
voltages. Unlike linear resonance, ferroresonance is not
cable network with low short circuit power.
so easy to predict. Due to the non-linearity, several
• Single phase switching (fuse blowing) in distribution
steady state solutions may exist for a particular
networks.
excitation and range of circuit parameters.
Ferroresonant systems are very sensitive to initial Depending on their frequency content, steady-state
conditions: remanent flux in the magnetic cores, ferroresonant oscillations are normally classified as:
switching instant, circuit losses and charge in the
capacitances are the key variables that determine the 1. Harmonic ferroresonance: periodic waveforms with
steady state response. It is possible that a system a frequency multiple of the power system frequency.
disturbance cause the circuit that was operating in a
2. Fundamental ferroresonance: periodic waveforms frequency spectrum of the recorded ferroresonant
with the same period as the power system. waveforms which shows a predominant fundamental
3. Sub-harmonic ferroresonance: periodic waveforms frequency component and a number of decaying odd
with a period multiple of the power system period. harmonics (3, 5, 7 and 9). Such frequency spectrum is
4. Quasi-periodic ferroresonance: non-periodic typical of fundamental frequency ferroresonant modes.
waveforms with a discontinuous frequency
spectrum. A very unusual loud noise combined with high voltage
5. Chaotic ferroresonance: non-periodic waveforms readings prompted the local operator to isolate the
with a continuous frequency spectrum. 400kV busbar within seconds, which terminated the
ferroresonant oscillation. This quick reaction prevented
the catastrophic failure of the VTs. It is evident that in
FERRORESONANCE EXPERIENCED IN 400KV this instance the damping resistor (0.5 ) connected
SUBSTATION across the tertiary windings failed to suppress the
ferroresonant oscillations. A negative experience with
Switching operations performed during the
open delta damping resistors was also reported in [3],
commissioning of a new 400kV substation in Ireland
where resistance values as low as 0.1 failed to
inadvertently drove two single-phase Voltage
suppress ferroresonance.
Transformers (VTs) into a sustained ferroresonant state.
Figure 1 shows the single-line diagram of the line bay Similar ferroresonant incidents involving wound
involved in the incident. Of especial importance is the Voltage Transformers and Circuit Breaker grading
VT location, in the bay side of the line disconnector capacitors in HV substations have been reported in [3]
(DL). to [9]. The described steady-state ferroresonant modes
400kV Busbar
were always of fundamental or sub-harmonic nature. A
DA CB P1 CT P2 DL very interesting case is described in [6] where chaotic
400kV oscillations were observed for about 700ms before the
Line system jumped into a steady state, fundamental
VT frequency ferroresonant mode, with very similar
DEM DE waveforms to those shown in Figure 3.
Figure 1 – 400kV Line Bay

Following a “live test” consisting on the energization of ANALYSIS OF FERRORESONANCE


the VT’s from busbars with DL open, the line VT’s EXPERIENCED IN 400KV SUBSTATION
were de-energized by opening the line circuit breaker. A
ferroresonant circuit was formed upon opening the The non-linear inductance of the VTs makes a rigorous
circuit breaker with the busbar disconnector (DA) mathematical analysis of the phenomena very complex.
closed and the line disconnector (DL) open. Far from Due to limitations in numerical methods required to
being de-energized, the VT’s remained fed via the solve non-linear differential equations and the
circuit breaker grading capacitors, which had been complexity of our three phase system we decided to use
previously overlooked. Sustained overvoltages of 2p.u. time-domain simulations to study the ferroresonant
were recorded in two phases. Additionally, very loud phenomena. This method, however, only gives us the
noise was reported by local operators. circuit response for a particular set of parameters or
initial conditions and it can not provide any indication
After this first ferroresonant experience, and in of the system behaviour under slightly different
accordance to VT manufacturer recommendations, a conditions. In order to estimate the risk of
damping resistor of 0.5 was connected across the open ferroresonance for a particular configuration with
delta tertiary windings. The purpose of the resistor was confidence, a very large number of simulations will be
to introduce enough losses in the circuit that should required. With the purpose of reducing the computation
damp out the ferroresonant oscillations. Further burden, a preliminary simplified analysis was performed
switching operations were performed to assess its as described below.
effectiveness.
The 400kV line bay shown in Figure 1, having DA
The first two tests performed with the damping resistors closed and CB and DL open, was represented as the
resulted in some initial quasi-periodic oscillations that single-phase circuit displayed in Figure 5, ignoring
died out in about six cycles (see Figure 2), evolving into inter-phase capacitances. In this diagram Cg is the
a “normal” steady state response with power frequency Circuit Breaker grading capacitance (600pF); CS is the
voltages of 0.5pu. The third switching test, however, circuit phase-to-ground capacitance, including
produced a completely different response. Recorded conductors, VT, CT and CB stray capacitances (460pF);
waveforms are included in Figure 3. It can be seen that R is an equivalent resistance representing the VT core
the resonant condition also initiated as a quasi-periodic losses and it’s resistive load; and L is the non-linear
oscillation but, after near 300ms, it jumped into a inductance of the VT. Applying Thevenin’s theorem
sustained ferroresonant state with voltages reaching and ignoring losses, the previous circuit can be
2p.u. in two phases. Depicted in Figure 4 is the represented as shown in Figure 6. The fundamental
frequency steady-state solution of the circuit can be • Sub-harmonic ferroresonance (m = 1/2, 1/3, …) is
obtained by solving equation (1) with m=1, which more likely to occur as |E’+VC’| turns anticlockwise
graphical solution is depicted in Figure 7. and the non-linear saturation curve |VL| turns flatter.
r
r I The two curves can intercept for a wide range of
E = VL( m) (1)
capacitances and sub-harmonic frequencies. The
m 0C higher the circuit capacitance, the lower the frequency
VL( m) = m 0 (2) sustained ferroresonance can occur at.
For the system parameters under study, the circuit
presents up to three possible states at power frequency, With a piece-wise linear approximation of the VT’s
as shown in Figure 7. Points 1 and 3 represent stable magnetizing curve, a range of circuit capacitances can
solutions whereas “point 2” corresponds to a transient, lead to sustained ferroresonance at m-th sub-harmonic
instable solution. Instability of “point 2” can be frequency (m = 1/2, 1/3, …):
demonstrated by slightly increasing the current, which 1 1 (3)
< m <
2 2
will result in |E’+VC’| exceeding |VL| and, in turn, will 0 Llinear C 0 Lsaturated C
force the current to increase further. If, on the other
hand, the current is reduced, |VL| will be greater than 2.5
2.0
|E’+VC’|. The source will not be able to supply the 1.5
1.0
0.5
voltage deficit, forcing the current to drop further. 0.0 VR
-0.5
-1.0
It is interesting to note that this simple graphical -1.5
-2.0
-2.5
analysis can be used to reproduce with high accuracy 2.5
2.0
1.5
the two recorded responses during field tests: “point 1” 1.0
0.5
corresponds to the “normal response” recorded in 0.0
-0.5
VS
Figure 2 and “point 3” corresponds to the ferroresonant -1.0
-1.5
state recorded in Figure 3. It should be mentioned that -2.0
-2.5
2.5
the fundamental frequency component of recorded 2.0
1.5
1.0
ferroresonant voltages (as shown in Figure 4) is slightly 0.5
0.0
lower than the predicted value due to the simplifications -0.5 VT
-1.0
made in the analysis, in particular neglecting losses. -1.5
-2.0
-2.5
2.5
The previous graphical analysis can be extended to 2.0
1.5
1.0
study the possibility of sustained ferroresonance at 0.5
VN
0.0
different frequencies: -0.5
-1.0
• Harmonic ferroresonance (m = 2, 3, 4, …) is not likely -1.5
-2.0
to arise as the “m-th” harmonic produces a flatter -2.5
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200

|E’+VC’| characteristic and a steeper non-linear Time (ms)

characteristic |VL|. The two curves will only intercept Figure 3 – Recorded voltages (p.u.) during the third
if unrealistically high m-harmonic e.m.f. is applied. switching operation
2.0
1.5 1.6
1.0
0.5 VR 1.4
0.0
-0.5 1.2
-1.0
-1.5 1.0
-2.0
2.0
1.5 0.8
1.0
0.5 0.6
0.0 VS
-0.5 0.4
-1.0
-1.5 0.2
-2.0
2.0
1.5 0.0
1.0
0 50 100 150 200 250 300 350 400 450
0.5 Frequency (Hz)
0.0 VT
-0.5 Figure 4 – Frequency spectrum of recorded
-1.0
-1.5
-2.0
ferroresonant voltages
2.0
1.5
1.0
0.5 VN
0.0
-0.5
Cg
-1.0
-1.5
-2.0 E CS R L
0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200
Time (ms)

Figure 2 – Recorded voltages (p.u.) during the first


switching operation
Figure 5 – Single-Phase ferroresonant circuit
FIELD MEASUREMTS VS SIMULATION
RESULTS
C = C g + CS
Cg Simulation results of the switching operation leading to
E =E L sustained ferroresonance are shown in Figure 8, which
Cg + CS compare well with recorded waveforms shown in Figure
3. Shape and amplitude of the sustained ferroresonant
overvoltages are reproduced with very good accuracy.
Figure 6 –Simplified equivalent of ferroresonant circuit The quasi-periodic oscillations prior to the steady-state
2.5 V [pu]
ferroresonant condition (from 200 ms to 500 ms in
2.0 2 Figure 3) were almost impossible to replicate, although
1.5 simulated waveforms also displayed a quasi-periodic
1.0 behaviour. We suggest that this is due to a random
0.5
1
combination of parameters such as switching time, pre-
0.0
I [Amps] switching voltage, remnant magnetization and power
-0.25 -0.20 -0.15 -0.10 -0.05 -0.50.00 0.05 0.10 0.15 losses, the latter being variable during high saturation in
|E’+VC’| -1.0 the magnetic cores.
2.50

|VL|
-1.5 [V]

1.25
-2.0
3
-2.5
VR 0.00

Figure 7 – Graphical solution of Ferroresonant Circuit -1.25

(Fundamental Frequency) -2.50

2.50
0.0 0.2 0.4 0.6 0.8 [s] 1.0

[V]

1.25

ATP/EMTP MODEL OF THE 400KV STATION VS 0.00

As an extension of the previous graphical analysis,


-1.25

time-domain simulations were performed with the


-2.50
0.0 0.2 0.4 0.6 0.8 [s] 1.0
2.50

purpose of better understanding the factors influencing 1.25


[V]

the occurrence of ferroresonance and in order to VT 0.00

evaluate methods for mitigating or avoiding system


-1.25

overvoltages. The line bay shown in Figure 1 was


modelled in detail using the ATP/EMTP software.
-2.50
0.0 0.2 0.4 0.6 0.8 [s] 1.0
2.50

Preliminary simulations indicate that an accurate 1.25

representation of the Voltage Transformers is essential VN 0.00

for the study of ferroresonance. The three voltage


-1.25

transformers were represented as three single-phase


three-winding transformers, with their tertiary winding
-2.50
0.0 0.2 0.4 0.6 0.8 [s] 1.0

connected in open-delta and closed through a 0.5 Figure 8 – Simulation results of ferroresonant condition
resistor, as in the field tests. The magnetic behaviour of MITIGATION OPTIONS
the core was represented by its saturation curve, derived
from the no-load V-I curve supplied by the A review of literature reveals a wide range of remedial
manufacturer. The hysteretic behaviour of the steel core actions for mitigating ferroresonance in HV substations:
plays an important role since it imposes additional switched resistors connected to “Y” secondary windings
losses that are crucial for the stability of a ferroresonant [3], damping resistors permanently connected across
state. It has been reported in [11] that the equivalent open-delta windings [12], air-core reactors connected in
iron-core losses of a 245kV gas-insulated VT can parallel with the HV winding [6], series combination of
increase to four times its nominal value when working a resistor and a saturable reactor in the secondary
in a high saturated region. Some attempts have been winding [9], replacement of inductive VTs by capacitive
made to represent deep saturated iron core losses using VTs [6], revised switching procedures [6], closing
dynamic resistors that take flux levels into account [5] grounding switches upon detection of ferroresonance
or as a function of the amplitude and shape of the [10], use of VTs with higher saturation level or
oscillation [9]. The main difficulty when trying to installing primary neutral resistors.
implement any of those dynamic models is the lack of
measurements to validate them. Furthermore, it has Mitigation options investigated in our analysis are
been suggested in [2] that single-phase transformers are briefly discussed below:
not very sensitive to core losses representation and, 1. 0.5 damping resistor in the open delta winding
therefore, it is acceptable to use a linear resistor with a was not effective in suppressing ferroresonance.
value as close as possible to nominal voltage. As Lower resistance values were not practical due to
hysteresis measuremets were not available for the VTs thermal limitations in the secondary windings.
under study, we represented iron core losses by a 2. 50M resistor connected across the HV winding
lumped linear resistor of 182M (293W at 400kV). could suppress ferroresonance. This solution,
however, would imply extra losses of 28 MWh per frequency and sub-harmonic (period 3, 6, 9 etc)
year. ferroresonant modes as the station capacitance is varied.
3. 50 resistor connected across the “Y” secondary No chaotic behaviour has been detected yet. Ongoing
can successfully quench resonance. Consideration work is aimed to identifying all possible ferroresonant
should be given to the effect of this added load on modes and understanding their periodic behaviour. This
the operation of protection relays connected to the work will be presented in a publication in the near
same winding. future.
4. 1 MVAR air-core reactor connected across the HV
winding avoids the occurrence of ferroresonance. REFERENCES
5. Optical transformer technology is a promising
1. Boucherot, “Existence de deux régimes en ferro-
emerging alternative that eliminates the concern for
résonance,” R.G.E., pp. 827-828, Dec. 10, 1920.
ferroresonance. Further operating experience is
required, however, before they can be generally 2. Slow Transients Task Force of the IEEE Working
installed in HV plants. Group on Modelling and Analysis of System Transients
6. Capacitive VTs were not an option as fast line Using Digital Programs. Modelling and Analysis
discharge is essential for the autorecloser scheme. Guidelines for Slow Transients – Part III: The Study of
7. VT relocation to the “line side” of DL was Ferroresonance, IEEE Trans. on Power Delivery. Vol
considered. The permanent connection of the 95km 15, No 1. January 2000.
long line capacitance (1.05 microF) prevents 3. Yunge Li, Wei Shi, Rui Qin and Jilin Yang: A
ferrroresonance from happening. Field tests Systematical Method for Suppressing Ferroresonance at
performed with DL closed confirmed this result. Neutral-Grounded Substations, IEEE Trans. on Power
8. Interlocking scheme to prevent the series Delivery, Vol. 18, No 3, pp 1009-1014, July 2003.
connection of the VTs with the CB grading 4. Z. Emin, B.A.T. Al Zahawi, Y. K. Tong: Voltage
capacitors when DL is open and DA is closed. Transformer Ferroresonance in 275kV Substation, IEE
9. VTs with higher saturation knee are under High Voltage Engineering Symposium Procs., August
consideration for future installations. 1999.
5. Z. Emin, Y. K. Tong: Ferroresonance Experience in
CONCLUSIONS UK: Simulations and Measurements, Procs. of the 4-th
A ferroresonant experience involving inductive VTs in a International Conference on Power System Transients,
400kV substation has been presented in this paper. Key Rio de Janeiro, June 24-28, 2001.
factors affecting the phenomenon have been analysed 6. D. A. Jacobson, D. R. Swatek, R. W. Mazur:
and discussed. These include substation capacitance, Mitigating Potential Transformer Ferroresonance in a
circuit breaker grading capacitance, VT magnetizing 230kV Converter Station, Computer Analysis of
characteristic and circuit losses. It has been Electric Power System Transients: Selected Readings.
demonstrated that fundamental and sub-harmonic IEEE Press. pp 359-365, 1997.
ferroresonance are possible for a range of substation 7. D. Ray Crane, G. W. Walsh: Large Mill Power
capacitances. Attention must be paid to this issue when Outages caused by Potential Transformer
performing busbar extensions or bay alterations that Ferroresonance, IEEE Trans. on Industry Applications,
could modify the equivalent circuit capacitance. A very Vol 24, No 4, pp 635-640, July/August 1988.
comprehensive analysis was carried out using time
domain simulations with the ATP version of EMTP. 8. S. R. Sagardia, A. Morched: Potential Transformer
Simulation results duplicated reasonably well the Failure due to Ferroresonance, Procs. of the 2nd
ferroresonant events recorded in the 400kV substation. International Conference on Power System Transients,
Digital time-domain simulations as well as field tests Seattle, pp 191-196, June 22-26, 1997.
demonstrated the chaotic nature of ferroresonance: 9. N. Janssens, V. Vanderstockt, H. Denoel, P. A.
small variations in the model parameters or initial Monflis: Elimination of Temporary Overvoltages due to
conditions lead to completely different solutions. Ferroresonance of Voltage Transformers: Design and
During the course of the studies a number of methods Testing of a Damping System. CIGRE paper 33-204.
for suppressing ferroresonance were evaluated including Procs. of the CIGRE 1990 session.
revised switching procedures (interlocking), VT 10. P. Bornard, V. Collet Billon, C. Kieny: Protection of
relocation, adding circuit losses and detuning the circuit EHV Power Systems against Ferroresonance, Procs.
by installing a shunt reactor. CIGRE paper 34-103. Procs. of the CIGRE 1990
session.
Although some understanding has been gained on the
ferroresonant phenomenon, many aspects require further 11. D. A. N. Jacobson, R. W. Menzies: Investigation of
research such as its transient behaviour and the “jump Station Service Transformer Ferroresonance in
mechanism”. A deterministic approach does not apply Manitoba Hydro’s 230-kV Dorsey Converter Station,
to a ferroresonant circuit, where more than one steady Procs. of the 4-th International Conference on Power
state are possible. Further work is taking place in the System Transients, Rio de Janeiro, June 24-28, 2001.
use of chaos theory and non-linear dynamical methods. 12. P. Ferracci: Ferroresonance, Cahier technique no
Preliminary analysis have revealed fundamental 190. Groupe Schneider. 1998

You might also like