You are on page 1of 8

594 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 29, NO.

3, SEPTEMBER 2014

Brushless Three-Phase Synchronous Generator


Under Rotating Diode Failure Conditions
Mohamed Salah, Khmais Bacha, Abdelkader Chaari, and Mohamed El Hachemi Benbouzid, Senior Member, IEEE

Abstract—In brushless excitation systems, the rotating diodes


can experience open- or short-circuits. For a three-phase syn-
chronous generator under no-load, we present theoretical devel-
opment of effects of diode failures on machine output voltage.
Thereby, we expect the spectral response faced with each fault
condition, and we propose an original algorithm for state monitor-
ing of rotating diodes. Moreover, given experimental observations
of the spectral behavior of stray flux, we propose an alternative
technique. Laboratory tests have proven the effectiveness of the
proposed methods for detection of fault diodes, even when the
generator has been fully loaded. However, their ability to distin-
guish between cases of diodes interrupted and short-circuited, has
been limited to the no-load condition, and certain loads of specific
natures.
Fig. 1. Typical architecture of brushless synchronous generators.
Index Terms—Alternators, brushless machines, fault detection,
fault diagnosis, monitoring, spectral analysis.
pm Number of pair–poles related to the main generator.
ϕnf Phase shifting related to the nth excitation coil current.
NOMENCLATURE ψa Permanent flux embraced by stator phase a.
R Resistance of the excitation coil.
α Instantaneous angle of the rectifier input voltage. ρ±i;ν Maximal amplitude related to the frequency ωi;ν ±
.
An nth Fourier series coefficient. U Maximal line to line input voltage of the rectifier bridge.
β Additional phase shifting due to short-circuit condition. uf Instantaneous output voltage of the rectifier bridge.
ea emf induced in stator phase a under no-load condition. vj jth rectifier input voltage.
± ± ±
E1;1 Normalized amplitude of the frequency ω1;1 . ξ Amplitudes ratio related to sidebands ω1;1 .
Eν Maximal amplitude related to the νth harmonic of ea .
Hn nth harmonic of fundamental frequency ωm . I. INTRODUCTION
if Instantaneous excitation coil current.
OST systems of electrical energy production are based
If
K
L
DC component of the excitation coil current.
±
Ratio of characteristic defect frequencies ω1;1
Inductance of the excitation coil.
. M on three-phase synchronous generators. According to
their excitation technique, these generators can be classified
Maf Mutual inductance linking excitation coil and phase a. into brushed and brushless machines.
Mν Maximal amplitude related to the νth harmonic of Maf . A brushless excitation system is provided by an auxiliary
Ω Mechanical speed. synchronous generator (exciter) mechanically coupled to the
ωe Fundamental frequency of the rectifier input voltage. end of the main alternator’s shaft. This exciter is with stationary
ωH±
Prevailing sideband components under intact bridge. field coils and rotating armature. A diodes bridge, mounted
±
ωi;ν Sideband frequencies. on a plate attached to the rotor, allows rectifying the ac input
ωm Fundamental frequency of the main output voltage. voltage of its armature. Therefore, the excitation coil of the
pe Number of pair–poles related to the exciter. main generator will be fed by a dc field current. By means of an
automatic voltage regulator (AVR), the exciter field current is
autoadjusted for regulating the generator’s output voltage level,
faced to load variations (see Fig. 1).
Manuscript received June 2, 2013; revised November 18, 2013 and February Due to ageing phenomenon and to process’s continuous
10, 2014; accepted March 12, 2014. Date of publication April 9, 2014; date of
current version August 18, 2014. Paper no. TEC-00316-2013. regime, rectifier diodes can fail either open- or short-circuit
M. Salah, K. Bacha, and A. Chaari are with the University of Tunis, Unit of Re- (see Fig. 2).
search in Control, Monitoring and Reliability of the Systems, Higher School of While under interrupted diode condition (ID), the alternator
Sciences and Techniques of Tunis, Tunis 1008, Tunisia (e-mail: mohamed.
salah.isetgf@gmail.com; khmais-bacha@voila.fr; nabile.chaari@yahoo.fr). can operate safely with limited transient capability, subjected
M. E. H. Benbouzid is with the University of Brest, EA 4325 LBMS, Brest to condition of short-circuited diode (SD), the exciter becomes
29231, France (e-mail: m.benbouzid@ieee.org). extremely overloaded and the alternator can no longer run se-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. curely. If such condition is prolonged, the AVR as well as the
Digital Object Identifier 10.1109/TEC.2014.2312173 exciter windings can be damaged [1].
0885-8969 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
SALAH et al.: BRUSHLESS THREE-PHASE SYNCHRONOUS GENERATOR UNDER ROTATING DIODE FAILURE CONDITIONS 595

In addition, we suppose that all diodes’ switching is ideal. The


current’s transfer from one diode to another will be assumed to
be instantaneous.

A. Case of Intact Bridge


Due to the bridge’s symmetrical structure, rectified voltage
uf is a dc component with tiny ac ripple (six pulses during each
input voltage cycle).
For π/6 ≤ α ≤ π/2, the expression of uf will be given by
Fig. 2. Rotating Diodes bridge.
uf (α) = U. cos(α − π/3). (3)
To compute the expression of the excitation coil current, we
For a long time, the development of appropriate approaches expand uf into Fourier series. By taking into account the effects
for early detection of diode faults was a task of interesting re- of the impedance (R, L), we can write
search for the scientific community. The main idea was based  ∞

on the implementation of a search coil into the exciter stator 
k
if (α) = If 1 + (−1) A6k . cos(6kα) (4)
slots. Through spectral analysis of the induced electromotive
k =1
force (EMF), many authors, e.g., [2] have proposed the am-
plitudes monitoring of the second and of the sixth harmonics. where If = 3U/(πR), tan(ϕkf ) = k.Lωe /R, and
Unfortunately, most of the synchronous generators are not al- −2
ready equipped with an incorporated search coil. In addition, A6k = cos(ϕ6k
f ). (5)
36k 2 − 1
the integration of such sensor into an existing stator winding ar-
rangement is not always practical. To overcome this drawback, Because k.Lωe >> R, we can write
other works were focused on the harmonic analysis of the ex- cos(ϕkf ) ≈ cos(ϕ1f )/k. (6)
citer field current. The main proposed indicators have dealt on
ratio monitoring of the fundamental component regarding the dc Thereby, (5) gives
level [1], as well as on the amplitude oversight of the component −1
A6k = cos(ϕ1f ). (7)
related to twice rated frequency [3]. In [4], other authors have 3k(36k 2 − 1)
suggested to measure the brushless transfer characteristic, given
On the other hand, the flux embraced by the stator coil a is
by the ratio of the generator’s output voltage and the exciter field
given by
current.
On the other hand, many diagnosis techniques based on ma- ψa (t) = Maf (t).if (t). (8)
chine’s models [5]–[9] and control algorithms [10], [11] have
Due to discrete character of stator winding distribution, the
been suggested. Recently, via voltage-behind-reactance formu-
mutual inductance in (8) may be expressed by
lation of the stator and the field windings, the model proposed
in [12] has proven its applicability in an excitation failure case 
+∞

study. Maf (t) = Mν . cos(νωm t), ν = 1, 3, 5... (9)


ν =1
On the basis of spectral analysis of the generator output volt-
age, we are going to suggest an original algorithm for monitoring where
the state of rotating diodes. An alternative based on the stray flux ωm = pm Ω. (10)
will be also proposed. The efficiency of both techniques will be
experimentally discussed according to the load condition. Time derivation of (8) using (4) and (9) gives
 ∞


+∞ 
k ± ±
II. FAULTS EFFECTS ON THE GENERATOR’S INDUCED EMF ea (t) = Eν . sin(νωm t) + (−1) ρ6k ;ν . sin(ω6k ;ν t)
ν =1 k =1
In the following study, the machine under investigation is no- (11)
loaded, and is driven at its rated speed Ω. Thereby, there is no where Eν = νpm ΩIf Mν , and
magnetic interaction between the generator’s stator coils.  
1 i.pe
For simplification purpose, we neglect the saturation phenom- ρ±
i;ν = ± 1 Ai (12)
2 ν.pm
ena and coil-damping effects. The rectifier bridge is supposed
±
to be supplied by balanced voltages given by ωi;ν = (i.pe ± ν.pm ) Ω. (13)
√ As shown by the previous equation, besides the fundamental fre-
vj (α) = (U/ 3). sin [α − 2π(j − 1)/3] , j = 1, 2, 3 (1)
quency ωm and its odd harmonics, the EMF spectrum includes
±
other sidebands ω6k ;ν . The prevailing components are obtained
where
for k = ν = 1:
±
α = ωe t, ωe = pe Ω. (2) ωH = 6.ωe ± ωm . (14)
596 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 29, NO. 3, SEPTEMBER 2014

Fig. 3. Rectified voltage under ID condition. Fig. 4. Rectified voltage under SD condition.

TABLE I
TABLE II
EXPRESSIONS OF THE RECTIFIED VOLTAGE UNDER ID CONDITION
EXPRESSIONS OF THE RECTIFIED VOLTAGE UNDER SD CONDITION

±
For ω < 6ωe − ωm , sidebands ωH cannot be observed.

B. Case of Interrupted Diode


Under such fault condition, the rectified voltage waveform
is cyclic with main frequency ωe (see Fig. 3). Its analytical
expressions are reported in Table I. For k = 0, ν = 1, and ω < 6ωe − ωm , the outstanding side-
By following a similar reasoning as of Section III-A, we can band frequencies characterizing the fault occurrence are given
deduce the expression of the excitation coil current: by
⎡ ∞ ⎤
 ±
ω1;1 = (pe ± pm )Ω. (18)
k +1 I D
⎢ 1 + (−1) A 2k +1 sin((2k + 1)α) ⎥
ID 5If ⎢
⎢ k =0 ⎥

if (α) =
6 ⎢⎣ ∞ ⎥

C. Case of Short-Circuited Diode
+ (−1)k AI2kD cos(2kα) Fig. 4 shows the rectified voltage related to the SD condition.
k =1 Its waveform consists of a transient component which disap-
(15)
pears when α = 4π/3, followed by a permanent cyclic wave
where
with main frequency ωe (see Table II).
ID −π
A1 = √ cos(ϕ1f ) Fourier transformation of the transient component gives
5 3
. (16) U  √ √ 
n
AI D = −2 2 cos(2nπ/3) + (−1) + 2 cos(ϕ1 ) UfS D (ω) = − (5π + 3 3) + (11 3π + 21)j . (19)
n = 1 5n(n2 − 1) f 48ω

Thus, the expression of the induced EMF becomes Far from the moment of the fault occurrence, the excitation coil
⎡ ⎤ is supplied by the cyclic component. Fourier series expansion
 ∞
k ID± ± gives
⎢sin(νωm t)+ (−1) ρ2k ;ν sin(ω2k ;ν t)⎥
⎡ ⎤
5 ⎢ ⎥
+∞
ID
ea (t) = Eν⎢
k =1 ⎥. 1 + Asd
1 cos(α + β1 )
⎢ ∞
 ⎥ ⎢
6 ν =1 ⎣
k ID± ± ⎦ ⎢ +
∞
 sd  ⎥

+ (−1) ρ2k +1;ν cos(ω2k +1;ν t) ⎢ A cos(2kα + β ) ⎥
If 2k 2k
k =0 iSf D (α) = √ ⎢⎢ k =1

⎥ (20)
(17) 2 3⎢ ∞ ⎥
This previous equation shows that ID condition involves an ⎣   sd ⎦
+ A2k +1 cos((2k + 1)α)
amplitude modulation of the induced EMF’s wave. k =1
SALAH et al.: BRUSHLESS THREE-PHASE SYNCHRONOUS GENERATOR UNDER ROTATING DIODE FAILURE CONDITIONS 597

where Given the previous statements, we can deduce that the am-
k plitudes ratios (ξ0I D and ξ0S D ) related to unloaded generator
tan(β1 ) = π/2, tan(β2k ) = 2k(−1) (21)
condition (UGC), and the frequencies ratio K are bound by the
and comparison expression given by

SD
A1 = − π + 4 cos(ϕ1f ) ξ0S D << ξ0I D < K.
2
(26)


√4   Thus, the monitoring of the ratio ξ0 range can be an efficient
AS D = − 1 + 4k 2 cos kπ cos(ϕ1 ) indicator to distinguish between open- and short-circuit diode
2k
k(4k 2 − 1) 3 f
failures.
 
  (k − 1)π By loading the generator under fault condition, the effect of
− 2k − (−1) k
+ 1 cos
the rotating zero-sequence component on the ratio ξ will be cer-
AS D = 3
cos(ϕ1f ).
2k +1 tainly altered. Hence, the expression given by (26) can no longer
2k(k + 1)(2k + 1)
(22) be guaranteed especially in case of short circuit. This prediction
Accordingly, the expression of the induced EMF becomes will be verified experimentally for various load natures.
⎡ ⎤
sin(νωt) + ρS1;νD ± sin(ω1;ν ±
t + β1 )
⎢  III. USEFULNESS OF THE MAGNETIC STRAY FLUX
⎢ ∞  SD± ⎥⎥
+∞ ⎢ + ρ sin(ω ±
t + β ) ⎥ From a design standpoint, electrical machines include two
1 ⎢ 2k ;ν 2k ;ν 2k ⎥
eSa D (t) = √ Eν .⎢ k =1 ⎥. different circuits. Whereas the electric circuit (coils) ensures
2 3 ν =1 ⎢ ⎥
⎢  ∞   ⎥ the currents flow, the magnetic circuit is the main pathway for
⎣ ± ± ⎦
+ ρS2kD+1;ν sin(ω2k +1;ν t) channeling magnetic fluxes. The physical phenomena involving
k =1 the two circuits’ parameters are basically governed by electro-
(23)
magnetism laws. A circulating current through an electric circuit
As shown by (17) and (23), both diode failure cases have the
(field coils) produces a magnetic field (vector quantity). At dif-
same frequency signature. Thus, the distinguishing between
ferent points in space, the properties of this vector are given
fault conditions (ID or SD) remains ambiguous.
by means of Biot–Savart law [13]. The measurement (inner
vectors product) of the quantity of magnetic field that crosses
D. Distinguishing Between Fault Conditions
perpendicularly an opened surface (electric circuit) gives rise
For both cases of diode failures, the rise in amplitude of to the magnetic flux which is a not null scalar. In accordance
±
characteristic sidebands ω1;1 , derives from the presence of fre- with Faraday’s law, the time variation of this magnetic flux pro-
quencies ωk ;ν with k = v = 1, and all other components |ωk−;ν |
± duces a boundary EMF (generator mode) tending to drive cur-
such that k = 2λpm + 1 and ν = 2λpe ∓ 1, or k = 2λpm − 1 rent through the concerned circuit (armature coils). On the other
and ν = 2λpe ± 1, where λ = 1, 2, 3 . . . hand, in the presence of a magnetic field, a current-carrying wire
Accordingly to (17) and to (23), by disregarding all effects due endures a Laplace force (macroscopic form of Lorenz force).
to (k, v) = (1, 1) we can expect that the normalized amplitudes Consequently, an electromagnetic torque may be produced (mo-
± tor mode).
of sidebands ω1;1 will be given by
Because of the inherent machine dissymmetry, the limited
ID± (pe ± pm ) S D ± (pe ± pm )  2 relative permeability of the magnetic circuit, and the effects of
E1;1 = , E1;1 = π + 4. (24)
2pm 2πpm the air-gap length, a portion of the magnetic flux will radiate
Previous expression shows thatthese amplitudes are slightly outside of the machine’s frame. This stray flux does not partic-
SD± ID±

more accentuated in case of SD E1;1 − E1;1 ≈ 1.5 dB . ipate in the process of generating of useful outputs. However,
In addition, it seems that the amplitudes ratio defined by it has the particularity to provide useful information about the
+ − phenomena that occur inside the machine. Indeed, when a fault
ξ = E1;1 /E1;1 is closely equal to the frequencies ratio K =
+ −
ω1;1 /ω1;1 : occurs into stator or rotor windings, harmonics distribution into
the air gap will be altered. Consequently, the stray flux will cer-
ξ = K. (25) tainly undergo these changes. A simple search coil placed near
the machine’s frame will retrieve an image of this stray flux
However, due to fault conditions, the currents flowing into the
(time derivative). Therefore, by spectral analysis of the EMF
exciter armature becomes unbalanced. It follows the emergence
induced at the coil terminals, we can detect a possible failure in
of a rotating zero-sequence component. Given that condition,
the machine circuits [14].
the rotational speed Ω and its harmonics will be reflected into
the EMF spectrum. Therefore, the expression given (25) cannot
be strictly respected. The ratio ξ will tend to be lesser than the IV. EXPERIMENTAL RESULTS
ratio K. The brushless machine under investigation is a 4-kVA, 380-V,
While this unbalance effect remains relatively moderate for 50-Hz, four-pole generator with 14-pole exciter.
ID faults, it is very significant in case of faults of SD nature. For three diode conditions (intact bridge, ID, and SD),
Indeed, under SD condition, the unbalance level will be more experimental tests have been conducted under UGC as
intensified because of the exciter windings overload. well as under fully loaded generator condition (FGC), with
598 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 29, NO. 3, SEPTEMBER 2014

Fig. 7. Output voltage spectra: intact–SD for no-load generator.


Fig. 5. Laboratory test bench.

Fig. 6. Output voltage spectra: intact–ID for no-load generator.


Fig. 8. Stray flux spectra: intact–ID for no-load generator.

various load natures. The output voltage, and EMF at coil ter-
minals, were acquired at 25-kHz sampling rate, and recorded
for 10 s (see Fig. 5). As predicted by the theoretical study,
characteristic sidebands and their ratio worth, respectively,
− +
ω1;1 = 125 Hz, ω1;1 = 225 Hz, and K = 1.8 (5.1 dB).

A. No-Load Generator
±
For the ID fault condition, an amplitude rise of sidebands ω1;1
is clearly observed (see Fig. 6), as expected by (17).
This same spectral fault signature is also observed when the
generator is running under SD condition (see Fig. 7). How-
ever, due to the significant effect of the rotating zero-sequence
component, this spectral response is marked by the presence of
additional harmonics related to the rotational frequency. More-
over, whereas under ID condition the amplitudes ratio ξ0I D is
Fig. 9. Stray flux spectra: intact–SD for no-load generator.
closely equal to the ratio K(ξ0I D = 5.16 dB), under SD condi-
tion this ratio falls to about half (ξ0S D = −0.4 dB ≈ 53%.K).
These experimental results confirm the comparison expression
given by (26). when the generator runs under SD condition. In addition, for
On the other hand, the spectral responses of the stray flux to this particular fault condition, a clear increase in amplitude is
both diode failure cases are given in Figs. 8 and 9. also observed for the second harmonic (+13.5 dB), against the
For both conditions, these spectra are characterized by an am- decrease (−7.9 dB) of the third-harmonic’s amplitude. These
plitude rise, observed especially for the fourth, sixth, and ninth experimental results confirm the usefulness of the stray flux for
harmonics. However, this augmentation is much accentuated health assessment of the machine circuits.
SALAH et al.: BRUSHLESS THREE-PHASE SYNCHRONOUS GENERATOR UNDER ROTATING DIODE FAILURE CONDITIONS 599

Fig. 10. Output voltage spectra: intact–ID for balanced resistive full load.
Fig. 12. Stray flux: intact–ID for balanced resistive full load.

Fig. 11. Output voltage spectra: intact–SD for balanced resistive full load.
Fig. 13. Stray flux: intact–SD for balanced resistive full load.

B. Balanced Resistive Load (3%) lagging (0.73) load, and nonlinear load (six-pulse diodes
Regardless of fault condition, when the generator supplies rectifier).
balanced resistive load, we see that spectra of output voltage When the generator runs under ID condition, experimental
± results have shown that the gradual decrease of the ratio ξ I D
are always characterized by the presence of sidebands ω1;1 .
However, we note a moderate reduction in their amplitude ratios. by loading effect, remains always respected. Upon reaching the
ID
Under FGC, this ratio reaches about 85%K (3.73 dB) for ID FGC, the minimum value (ξm in = 76%.K) is observed for the
condition (see Fig. 10), against 42%K (−2.4 dB) under SD case of balanced lagging load.
condition (see Fig. 11). From these experimental results, we can For the cases of resistive load, regardless of balancing state,
extend the validity of the comparison expression given by (26) the downtrend of this ratio has been still observed even for
SD
to cover the FGC with balanced resistive load. the SD fault condition. The minimum value (ξm in 1 = 39%.K)
On the other hand, for both diode failure cases, we remark was observed by reaching the FGC. The clause expected by
that all characteristic harmonics of stray flux spectra (H4, H6, expression (26) remains always respected.
and H9) that were already observed under UGC are also affected Rather, in cases of lagging and of nonlinear loads the ratio
in amplitude. In order not to lose view, we shall merely track ξ S D has exhibited contrary behavior. Indeed, since we have
solely the behavior of the sixth harmonic. Regardless the fault loaded the generator, this ratio has undergone a sudden leap to
SD
condition, by loading the generator we note a progressive in- reach values greater than K(ξm in 2 = 115%.K). A progressive
crease in amplitude for this particular frequency. Under FGC, it increase was then observed. Upon reaching the FGC, the max-
SD
reaches about +5 dB for the ID condition (see Fig. 12), against imum value (ξm ax = 183%.K) was encountered in the case of
+17.9 dB for the SD condition (see Fig. 13). balanced lagging load. The expression expected by (26) is no
longer respected.
Regarding the spectral response of the stray flux, the experi-
C. Unbalanced, Lagging, and Nonlinear Loads mental tests have shown that the amplitude rise of H6 that has
Further tests were performed on the generator when it sup- characterized the occurrence of diode faults, remains always
plies nonideal loads. Four cases were studied: unbalanced observed irrespective of the nature and the level of the load. On
(3%) resistive load, balanced lagging (0.73) load, unbalanced the other hand, for the cases of resistive and nonlinear loads,
600 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 29, NO. 3, SEPTEMBER 2014

TABLE III
RATIO ξ/K (%) FOR SIDEBANDS ω 1±, 1

TABLE IV
H6 AMPLITUDE INCREASE (%) OF THE STRAY FLUX

the outstanding rise for the H6 amplitude remains specific to the


SD condition. However, for the lagging loads this characteristic
behavior is no longer guaranteed regardless of the state of load
balancing. The H6 amplitude rise remains moderate as it has
been encountered under ID condition.
Fig. 14. Monitoring algorithm based on output voltage.
V. PROPOSED DIAGNOSIS TECHNIQUES
From previous theoretical predictions and experimental ob- augmentation does not exceeding 100%. In contrast, under SD
servations, we are going to suggest two diagnosis techniques condition, this augmentation is well above (except for lagging
that may contribute to the state of the art for health assessment loads). Based on these experimental observations, the amplitude
of the rotating diodes. monitoring of the six harmonic can be an alternative for diode
health assessment. Besides the efficiency of this technique in
detecting diode faults, it has the particularity to be efficient for
A. Main Output Voltage
discrimination of the failure nature for resistive loads as well as
By exploring the output voltage spectral response, we have for the studied nonlinear load. However, it cannot be adopted in
observed that the occurrence of a diode failure was marked by cases of lagging loads.
±
an amplitude rise of sidebands ω1;1 . Furthermore, regardless of
the nature of investigated loads, the ID condition was, exclu- VI. CONCLUSION
sively, characterized by belonging of the amplitude ratio to the
range delimited by ξm ID ID For many load conditions, the proposed algorithm arising
in = 76%.K, and ξ0 = 100%.K (see
Table III). from output voltage analysis, has proven ability for distinguish-
On the basis of aforementioned statements, we propose the ing between two diode failure cases. However, further efforts
monitoring algorithm given by Fig. 14. need to be devoted to explain the behavior of the spectral re-
Despite the proven efficiency of this algorithm for the detec- sponse when the generator supplies lagging and nonlinear loads.
tion of diode failures regardless the load nature, its ability to Due to the low cost of the flux sensor, the alternative tech-
distinguish between conditions of ID and SD cannot be guaran- nique can be an excellent alternative for condition monitoring of
teed for other cases of nonideal loads that were not studied in rotating diodes. However, its ability to classify the diode fault
this paper. remains limited to cases of resistive-, and of nonlinear loads.
In this paper, we have limited our analysis to the behavior of
the sixth harmonic. To extend the classification ability of this
B. Stray Flux
algorithm for covering cases of lagging loads, the exploration
As mentioned earlier, the observed rise in amplitude for the of other frequency components, seems to be promising.
sixth harmonic of the stray flux, involves the occurrence of a
diode fault. For all load conditions studied, the levels of these REFERENCES
increases are reported in Table IV.
[1] M. G. McArdle and D. J. Morrow, “Noninvasive detection of brushless
By analyzing the variation boundaries of these data, we real- exciter rotating diode failure,” IEEE Trans. Energy Convers., vol. 19,
ize that the ID condition is still characterized by an amplitude no. 2, pp. 378–383, Jun. 2004.
SALAH et al.: BRUSHLESS THREE-PHASE SYNCHRONOUS GENERATOR UNDER ROTATING DIODE FAILURE CONDITIONS 601

[2] X.-Y. Li, “A microprocessor-based fault monitor for rotating rectifiers of Khmais Bacha was born in Tunis, Tunisia, in 1975.
brushless ac exciters using a pattern-recognition approach,” in Proc. IEEE He received the B.Sc., M.Sc., Ph.D., and “Habilita-
Instrum. Meas. Tech. Conf., 1994, pp. 394–397. tion à Diriger des Recherches” degrees in electrical
[3] J. Sottile, F. C. Trutt, and A. W. Leedy, “Condition monitoring of brushless engineering from the Higher School of Sciences and
three-phase synchronous generators with stator windings or rotor circuit Techniques of Tunis, Tunisia, in 1998, 2001, 2008,
deterioration,” IEEE Trans. Ind. Appl., vol. 42, no. 5, pp. 1209–1215, and 2013, respectively.
Sep./Oct. 2006. Since 2004, he has been an Assistant then an As-
[4] T. D. Batzel, D. C. Swanson, and J. F. Defenbaugh, “Predictive diagnostics sociate Professor at the Electrical Engineering De-
for the main field winding and rotating rectifier assembly in the brushless partment, National Institute of Applied Sciences and
synchronous generator,” in Proc. IEEE Symp. Diagnostics Elect. Ma- Technology of Tunis, Tunisia. His current research in-
chines, Power Electron. Drives Conf., 2003, pp. 349–354. terests include fault diagnosis in induction machines
[5] V. Ruuskanen, M. Niemela, J. Pyrhonen, S. Kanerva, and J. Kaukonen, and power transformer.
“Modelling the brushless excitation system for a synchronous machine,”
IET Elect. Power Appl., vol. 3, no. 3, pp. 231–239, May 2009.
[6] K. Veszpremi, I. Schmidt, and M. Hunyar, “Optimal operation of the
rotating transformer brushless excitation of synchronous machine,” in
Proc. IEEE Int. Symp. Ind. Electron. Conf., 2003, pp. 627–632.
[7] T. Zouaghi and M. Poloujadoff, “Modeling of polyphase brushless ex-
citer behavior for failing diode operation,” IEEE Trans. Energy Convers.,
vol. 13, no. 3, pp. 214–220, Sep. 1998. Abdelkader Chaari was born in Sfax, Tunisia, in
[8] Y. Li and C. Zhang, “Simulation of harmonic armature reaction in syn- 1957. He received the M.Sc., Ph.D., and “Habilita-
chronous brushless excitation,” in Proc. Artif. Intell. Manage. Sci. Elec- tion à Diriger des Recherches” degrees in electri-
tron. Commerce Conf., 2011, pp. 4304–4306. cal engineering from the “Ecole Normale Superieure
[9] M. Shahnazari and A. Vahedi, “Improved dynamic average modelling of de l’Enseignement Technique de Tunis,” Tunisia, in
brushless excitation system in all rectification modes,” IET Elect. Power 1982, 1986, and 2008, respectively.
Appl., vol. 4, no. 8, pp. 657–669, Sep. 2010. Since 1982, he has been with the Higher School
[10] S. Feng, X. Jianbo, W. Guoping, and X. Yong-hong, “Study of brushless of Sciences and Techniques of Tunis, Tunisia, as an
excitation system parameters estimation based on improved genetic al- Assistant Professor. Currently, he is a Director of the
gorithm,” in Proc. Elect. Utility Deregulation Restruct. Power Technol. research unit: control, monitoring and reliability of
Conf., 2008, pp. 915–919. the systems (C3S). His main research interests in-
[11] W. Na, “A feedforward controller for a brushless excitation system during clude the identification and control of nonlinear systems, robust estimation and
the diode open circuit fault operation,” in Proc. IEEE Power Energy Soc. robust filtering.
Gen. Meet., 2011, pp. 1–4.
[12] A. M. Cramer, B. P. Loop, and D. C. Aliprantis, “Synchronous machine
model with voltage-behind-reactance formulation of stator and field wind-
ings,” IEEE Trans. Energy Convers., vol. 27, no. 2, pp. 391–402, Jun.
2012.
[13] M. Salah, K. Bacha, and A. Chaari, “Comparative investigation of diagno-
sis media for induction machine mechanical unbalance fault,” ISA Trans.,
vol. 52, no. 6, pp. 888–899, Nov. 2013. Mohamed El Hachemi Benbouzid (SM’98) was
[14] H. Henao, C. Demian, and G.-A. Capolino, “A frequency-domain detec- born in Batna, Algeria, in 1968. He received the B.Sc.
tion of stator winding faults in induction machines using an external flux degree in electrical engineering from the University
sensor,” IEEE Trans. Ind. Appl., vol. 39, no. 5, pp. 1272–1279, Sep./Oct. of Batna, Algeria, in 1990, the M.Sc. and Ph.D. de-
2003. grees in electrical and computer engineering from the
National Polytechnic Institute of Grenoble, France, in
1991 and 1994, respectively, and the “Habilitation à
Diriger des Recherches” degree from the University
of Picardie “Jules Verne,” Amiens, France, in 2000.
After receiving the Ph.D. degree, he joined the Pro-
fessional Institute of Amiens, University of Picardie
Mohamed Salah was born in El-Guettar, Tunisia, in Jules Verne, where he was an Associate Professor of electrical and computer
1972. He received the B.Sc. and Aggregation degrees engineering. Since September 2004, he has been with the “Institut Universitaire
in electrical engineering from the “Ecole Normale de Technologie” of Brest, University of Brest, France, where he is a Professor of
Superieure de l’Enseignement Technique de Tunis,” electrical engineering. His main research interests and experience include anal-
Tunisia, in 1995 and 1996, respectively. ysis, design, and control of electric machines, variable-speed drives for traction,
Since 1995, he joined the secondary school Ibn propulsion, renewable energy applications, and fault diagnosis of electric ma-
Rached of Gafsa, Tunisia, as a Technical Trainer. In chines. He is an Associate Editor of four IEEE TRANSACTIONS.
1997, he joined the high institute of technological
studies of Gafsa Tunisia, as a Technologist then a
Master Technologist (2010). From 1999 to 2002, he
was the Head of the Electrical Engineering Depart-
ment of this institute, then the Director of studies and trainings. From 2007 to
2011, he was its Director. Since 2004, he is a member of the unit of research in
control, monitoring and reliability of the systems at the High School of Sciences
and Techniques of Tunis, Tunisia. His current research interests include fault
diagnosis in induction machines and synchronous generators.

You might also like