85001-0560 - Reflective Beam Detector
85001-0560 - Reflective Beam Detector
EC-50R/-100R Reflector
MEA
Test Station
Overview Operation
The EC-50R/-100R comprises a transmitter and receiver in a Alarm Threshold: Alarm thresholds of 25%, 35% and 50%
single enclosure and is usually installed between 19 inches and obscuration can be selected to suit the environment, with 25%
24 inches below the ceiling. The transmitter emits an invisible the most sensitive setting. The factory default setting is 35 percent
infrared light beam that is reflected via a prism mounted directly and is used for most typical applications. If the received infrared
opposite and with a clear line of sight. The reflected infrared light signal reduces to below the selected threshold for approximately
is detected by the receiver and analyzed. Smoke in the beam path 10 seconds, the fire relay is activated.
will reduce the received infrared light proportionally to the density
Fire Alarm: There are two modes to the operation of the fire
of the smoke. The detector analyzes this attenuation or obscura-
relay. Auto reset mode will reset the fire relay 5 seconds after the
tion of light and acts accordingly. Detectors are typically mounted
received infrared signal has recovered to a level above the Alarm
within ±30 feet (9.14 m) of a potential fire source. Consult your
threshold. Latching mode holds the fire relay active indefinitely
Authority Having Jurisdiction for spacing requirements specific to
after an Alarm condition has occurred. To clear the latched mode,
your locality.
power must be removed from the Detector for a minimum of 5
seconds.
Trouble Alarm: If the infrared beam is obscured rapidly to a level
Standard Features of 90% or greater for approximately 10 seconds, the Trouble relay
• Coverage: 50R range 15 -160 ft (4.6 - 48.8 m); is activated. Typical causes of trouble include an object being
100R range 160- 330 ft (48.8 - 100 m) placed in the beam path, transmitter failure, loss of the prism, or
• Microprocessor controlled sudden misalignment of the detector. The Trouble relay will reset
within 2 seconds of the trouble being cleared.
• Automatic drift compensation
Automatic Gain Control (AGC): The Detector monitors long
• Simple alignment term degradation of signal strength caused by component aging
• Selectable alarm thresholds or build up of dirt on optical surfaces. By comparing the received
infrared signal against a standard every 15 minutes, the detec-
• 24 Vdc operating voltage tor automatically compensates for signal differences of less than
• Latching or non-latching operation 0.7dB/hour. When the detector is showing AGC fault, detector is
still capable of generating an alarm, and will display both Alarm
• Low current consumption
and Trouble indications.
• Optional Ground Level Test Station
(102 mm)
reflector placed at the opposite end of the detection zone. The
4”
reflector.
signal is reflected back to the receiver where it is analyzed for fire
and trouble. The EC-50R/-100R must be positioned correctly to
4"
Single
(102 mm)
minimize the detection time. The maximum lateral distance either reflector
side of the beam is found to be typically 30 feet (9.1 m) for satis-
factory detection under flat ceilings, providing a total area cover- 8" (204 mm) 0.34"
(10 mm)
0.34"
(10 mm)
age of 19,800 square feet (60 feet x 330 feet), or 1844 square EC-100R detectors should be
metres (18.3 x 100.6 m). mounted between 160 and 330 feet
(102 mm)
(102 mm)
4”
4”
Smoke stratification may be overcome by mounting multiple beam (48.8 and 100.6 m) from a group of
4" 4"
(102 mm) (102 mm)
beam below the heat layer and into the smoke layer. (102 mm)
(102 mm)
4”
4”
Detection time will be longer in a building with a peaked roof if a
fire occurs at the fringes of the protected area. If in doubt conduct 4"
(102 mm)
4"
(102 mm)
Detector Spacing
Single Detector Ceiling Multiple Detectors
19 to 24 inches L
C L
C
(483 to 610 mm)
(209.55 mm)
8.25"
Zone Wiring
POWER
SUPPLY
Zone Wiring
10.2 to 30 Volts DC (RED)
EC-50R/-100R 0V (BLACK)
Fire Relay
NO (YELLOW)
COM (BLUE)
Trouble Relay
COM (WHITE)
4.5"
End of Line Resistor (114.3 mm)
NC (GREEN)
Test Station
Ground Level Test Station 2.75" (69.85 mm) 1.5" (38.1 mm)
COMMON
CONN. 8-WAY CONNECTOR
8 CONNECTIONS
WHITE
7
BLUE TEST
B
YELLOW
A
YELLOW
RUN
BLACK
EC-50R / EC-100R
BLUE
CABLE ASSY.
RED
APPROX 3 FT.
GROUND LEVEL C B A
TEST STATION Ø 0.2
TO BE LOCATED D FIXING HOLES
0.5" (12.7 mm)
WITHIN 330 FT. OF GROUND LEVEL
THE JUNCTION BOX. TEST STATION (LLT)
0.34"
Reflector (10 mm)
Detector Installation
Install the detector to a secure surface not subject to movement or
vibration. Use the template provided to mark and install four fixing
points. Secure the rear mounting plate to the four fixing points
through the keyholes on the plate.
When installing the detector on a wall supported with wood studs,
(102 mm)
4"
(102 mm)