Professional Documents
Culture Documents
7PA22/23/26/27/30
Auxiliary Relays for Various Applications
Technical data
Switching contacts
Continuous current 10 A
Overload capability 80 A/200 ms
150 A/10 ms
Switching current/voltage 40 A/0.5 s/110 V DC
Breaking capacity for 105 operating cycles
Non-inductive Inductive, 20 ms
1 contact 2 contacts 1 contact 2 contacts
in series in series
V DC A A A A
24 6.6 12.7 3.2 6.0
60 2.6 4.9 1.4 2.7
125 1.2 2.2 0.6 1.1
LSP2457-afp.tif
220 0.6 1.1 0.3 0.6
Technical data
7PA22
While the auxiliary voltage is being sup-
Fast-acting lockout relay plied to the SET coil, the reset pushbutton
Description must not remain pushed longer than 20 s.
Auxiliary voltage
24 V DC 1
60 V DC 2
110 V DC 3
220 V DC 4
125 V DC 5
30 V DC 6
Socket
without socket 0
with flush-mounting socket 7XP9010-1 1
15
Auxiliary voltage
24 V DC 1
60 V DC 2
110 V DC 3
220 V DC 4
125 V DC 5
30 V DC 6
Socket
without socket 0
with flush-mounting socket 7XP9011-1 1
15
Auxiliary voltage
24 /30 V DC 1
60 V DC 2
110/125 V DC 3
220 V DC 4
Standard, 20 ms 0
Fast, 10 ms 1
Socket
without socket 0
with flush-mounting socket 7XP9010-0 1
15
Technical data
7PA27 Monostable relay
Rated voltages and consumption
Description
VN Voltage Consumption
The monostable 7PA27 is a fast-acting relay range
with four changeover contacts and is V DC V DC
plugged into a mounting frame equipped
24/30 19 - 33 ≤ 3.5 W
with a plug-in socket (type 7XP9011) with Peak: ≤ 25 W
screw-type terminals at the rear. 60 48 - 66
110/125 88 - 137
220 176 - 242
Auxiliary voltage
24 /30 V DC 1
60 V DC 2
110/125 V DC 3
220 V DC 4
Socket
without socket 0
with flush-mounting socket 7XP9011-0 1
15
7PA30
Trip circuit supervision
Description
The 7PA30 relay is equipped with green
LED and two changeover contacts. It is ap-
plied for trip circuit supervision in the open
and close position of the circuit-breaker. It
monitors the trip circuit, the trip coil and
the proper state of the fuses and mini cir-
cuit-breakers of the circuit.
Functions
The 7PA30 indicates a trip circuit failure
with a time delay of 150 ms.
The relay is always in an energized condi-
tion, regardless of the position of the cir-
cuit-breaker (open/close).
In the event of actuation of the relay, its
unassigned contacts can be used for:
– Blocking the circuit-breaker connection
– Issuing the trip command to another
c.-b. upstream or to a second trip coil of Fig. 15/7 Connection diagram
the same c.-b. Switching contacts shown without
– Local or remote signaling auxiliary power supply in the relay
Auxiliary voltage
24 V DC 1
60 V DC 2
110 / 125 V DC 3
220 V DC 4
30 V DC 6
Socket
15 without socket 0
with flush-mounting socket 7XP9011-0 1