You are on page 1of 2

HVAC GRILLE SCHEDULE

MOUTH PROPOSED FLOWBAR


S.no LEVEL GRILLE TYPE SIZE QUANTITY FLOW RATE(L/S) LOCATION REVISED GRILLE SIZE AS PER RFI RESPONSE (CCEC01-RCA-RFI-05-00021) MODEL LPS CFM NOZZLE LENGTH (FT) CFM/FT Type PD (Pa) NC Throw (m) RAL NUMBER
CONNECTION LENGTH (MM)
1 GROUND FLOOR SUPPLY GRILLE 940x254 14 588/441 JET DIFFUSER - DETAIL-7 ( 01-712) SIZE TO BE PROPOSED BY SUPPLIER TBF-AA 6", 4 nozzle Supply 106 41 19.5 7047
2 GROUND FLOOR RETURN GRILLE 550x250 8 298 PRAYER HALL (01.11) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 9 18 - 9016 - STANDARD WHITE
3 GROUND FLOOR RETURN GRILLE 600x250 6 398 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 14 25 - 9016 - STANDARD WHITE
4 GROUND FLOOR SUPPLY GRILLE 940x254 8 618 JET DIFFUSER - DETAIL-7 ( 01-712) SIZE TO BE PROPOSED BY SUPPLIER TBF-AA 6", 4 nozzle Supply 118 43 19.8 7047
MULTI-PURPOSE
5 GROUND FLOOR RETURN GRILLE 700x300 8 476 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 10 21 - 9016 - STANDARD WHITE
6 GROUND FLOOR SUPPLY GRILLE 2000x200 1 611 HH. LOUNGE NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 13.7 9016 - STANDARD WHITE
7 GROUND FLOOR RETURN GRILLE 1700x200 1 525 (01.13) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 5 14 - 9016 - STANDARD WHITE
8 GROUND FLOOR SUPPLY GRILLE 150x100 1 42 HH. DRESS FLOWBAR SIZE (ROOM WIDTH- 2795mm) FL-10-HT 42 0 600 1.968 0 Supply 23 17 4.3 STANDARD BLACK
9 GROUND FLOOR RETURN GRILLE 150x100 1 27 (01.12) SEPARATE FLOWBARS FOR SUPPLY AND RETURN FL-10-HT 27 0 600 1.968 0 Return 11 13 - STANDARD BLACK
10 GROUND FLOOR SUPPLY GRILLE 150x100 1 21 HH. WC (01.12A) FLOWBAR SIZE (ROOM WIDTH- 1490mm) FL-10-HT 21 0 600 1.968 0 Supply 5 10 3 STANDARD BLACK
11 GROUND FLOOR SUPPLY GRILLE 1000x200 2 337 OPEN OFFICE NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 7 12 10.7
9016 - STANDARD WHITE
(01.16)
12 GROUND FLOOR RETURN GRILLE 850x200 2 247 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 5 14 - 9016 - STANDARD WHITE
13 GROUND FLOOR SUPPLY GRILLE 250x200 1 52 VESTIBULE NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 4 10 5.3 9016 - STANDARD WHITE
14 GROUND FLOOR RETURN GRILLE 250x200 1 43 (01.18) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 3 9 - 9016 - STANDARD WHITE
15 GROUND FLOOR SUPPLY GRILLE 250x200 1 48 VESTIBULE NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 4 10 5.3 9016 - STANDARD WHITE
16 GROUND FLOOR RETURN GRILLE 250x200 1 40 (01.21) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 3 9 - 9016 - STANDARD WHITE
17 GROUND FLOOR SUPPLY GRILLE 950x200 1 303 MEETING NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 14 9016 - STANDARD WHITE
18 GROUND FLOOR RETURN GRILLE 750X200 1 222 (01.25) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 5 14 - 9016 - STANDARD WHITE
19 GROUND FLOOR SUPPLY GRILLE 900x200 1 264 NORTH ENTRY NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 13.4 9016 - STANDARD WHITE
20 GROUND FLOOR RETURN GRILLE 800x200 1 221 (01.27) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 4 14 - 9016 - STANDARD WHITE
21 GROUND FLOOR SUPPLY GRILLE 1000x200 1 327 CLASS 1 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 7 12 10.7 9016 - STANDARD WHITE
22 GROUND FLOOR RETURN GRILLE 650x200 1 202 (01.31) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 6 14 - 9016 - STANDARD WHITE
23 GROUND FLOOR SUPPLY GRILLE 1400x200 1 459 CLASS 2 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 7 12 12.6 9016 - STANDARD WHITE
24 GROUND FLOOR RETURN GRILLE 1100x200 1 308 (01.33) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 5 14 - 9016 - STANDARD WHITE
25 GROUND FLOOR SUPPLY GRILLE 600x200 1 210 WMS.WC2 (01.35) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 8 12 12.1 9016 - STANDARD WHITE
26 GROUND FLOOR SUPPLY GRILLE 100x100 1 24 WC VEST (01.35A) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 16 15 5.8 9016 - STANDARD WHITE
27 GROUND FLOOR SUPPLY GRILLE 100x100 1 22 WC VEST (01.36A) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 16 15 5.8 9016 - STANDARD WHITE
28 GROUND FLOOR SUPPLY GRILLE 1100x200 1 344 IMMA/MENS NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 11.5 9016 - STANDARD WHITE
29 GROUND FLOOR RETURN GRILLE 1100x200 1 392 (01.08) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 5 14 - 9016 - STANDARD WHITE
30 GROUND FLOOR SUPPLY GRILLE 1500x200 1 469 ABLUTION (01.06) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 12.9 9016 - STANDARD WHITE
31 GROUND FLOOR SUPPLY GRILLE 1500x200 1 411 WMS.WC1 (01.02) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 12.9 9016 - STANDARD WHITE
32 GROUND FLOOR SUPPLY GRILLE 2000x200 1 603 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 13.7
ENTRY (01.01) 9016 - STANDARD WHITE
33 GROUND FLOOR RETURN GRILLE 1900x200 1 456 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 4 13 - 9016 - STANDARD WHITE
34 GROUND FLOOR SUPPLY GRILLE 1800x200 2 564 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 6 12 13.9 9016 - STANDARD WHITE
CAFÉ (01.40)
35 GROUND FLOOR RETURN GRILLE 350x200 2 81 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 4 12 - 9016 - STANDARD WHITE
36 GROUND FLOOR SUPPLY GRILLE 1400x200 1 451 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 7 12 12.6 9016 - STANDARD WHITE
MULTI-FUNCTION
37 GROUND FLOOR RETURN GRILLE 1400x200 1 375 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 4 14 - 9016 - STANDARD WHITE
38 GROUND FLOOR EXHAUST GRILLE 150x100 1 35 HH WC (01.12A) FLOWBAR SIZE (ROOM WIDTH- 1490mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
39 GROUND FLOOR EXHAUST GRILLE 700x80 1 35 OFFICE WC (01.14) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING FL-10-HT 25 0 600 1.968 0 Exhaust 9 13 - STANDARD BLACK
40 GROUND FLOOR EXHAUST GRILLE 150x150 1 25 JAN (01.22) PROPOSED CEILING DIFFUSER WITH SIZE OF 150x150 350RH-TG Exhaust 4 13 - 7047
41 GROUND FLOOR EXHAUST GRILLE 150x150 1 30 TRASH (01.20) PROPOSED CEILING DIFFUSER WITH SIZE OF 150x150 350RH-TG Exhaust 4 13 - 7047
42 GROUND FLOOR EXHAUST GRILLE 700x80 1 25 SHOWER 2 (01.36) FLOWBAR SIZE (ROOM WIDTH- 1585mm) FL-10-HT 25 0 600 1.968 0 Exhaust 9 13 - STANDARD BLACK
43 GROUND FLOOR EXHAUST GRILLE 200x150 1 155 WMS WC 2 (01.35) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 59 39 - 9016 - STANDARD WHITE
44-A GROUND FLOOR EXHAUST GRILLE 700x80 2 35 WMS WC 2 (01.35) FLOWBAR SIZE (ROOM WIDTH- 855mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
44-B GROUND FLOOR EXHAUST GRILLE 700x80 1 35 WMS WC 2 (01.35)-AD FLOWBAR SIZE (ROOM WIDTH- 1765mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
45 GROUND FLOOR EXHAUST GRILLE 150x100 1 30 WC VEST (01.35A) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 10 14 - 9016 - STANDARD WHITE
46 GROUND FLOOR EXHAUST GRILLE 150x100 1 30 WC VEST (01.36A) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 10 14 - 9016 - STANDARD WHITE
47 GROUND FLOOR EXHAUST GRILLE 550x200 1 427 CAFE (01.40) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 29 35 - 9016 - STANDARD WHITE
48 GROUND FLOOR EXHAUST GRILLE 150X100 1 35 WC (01.41) FLOWBAR SIZE (ROOM WIDTH- 2325mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
49-A GROUND FLOOR EXHAUST GRILLE 700x80 5 35 WMS WC 1 (01.02) FLOWBAR SIZE (ROOM WIDTH- 845mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
49-B GROUND FLOOR EXHAUST GRILLE 700x80 2 35 WMS WC 1 (01.02) FLOWBAR SIZE (ROOM WIDTH- 835mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
49-C GROUND FLOOR EXHAUST GRILLE 700x80 1 35 WMS WC 1 (01.02)-AD FLOWBAR SIZE (ROOM WIDTH- 1695mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
50 GROUND FLOOR EXHAUST GRILLE 250x150 1 240 WMS WC 1 (01.02) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust > 80 > 45 - 9016 - STANDARD WHITE
51 GROUND FLOOR EXHAUST GRILLE 700X80 1 30 SHOWER 1 (01.03) FLOWBAR SIZE (ROOM WIDTH- 1525mm) FL-10-HT 30 0 600 1.968 0 Exhaust 15 13 - STANDARD BLACK
52 GROUND FLOOR EXHAUST GRILLE 700x80 1 10 JAN (01.04) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 2 7 - 9016 - STANDARD WHITE
53 GROUND FLOOR EXHAUST GRILLE 250x200 1 165 SHOES 1 (01.05) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 3 9 - 9016 - STANDARD WHITE
54 GROUND FLOOR EXHAUST GRILLE 250x200 1 165 SHOES 2 (01.07) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 3 9 - 9016 - STANDARD WHITE
55 GROUND FLOOR EXHAUST GRILLE 700x80 1 35 MENS WC (01.10) FLOWBAR SIZE (ROOM WIDTH- 1870mm) FL-10-HT 35 0 600 1.968 0 Exhaust 20 14 - STANDARD BLACK
56 GROUND FLOOR SUPPLY DIFFUSER 600x600 2 300x300 100 FURN STORAGE NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING TDCS-TG Supply 4 4 2.2 7047
57 GROUND FLOOR RETURN DIFFUSER 600x600 2 300x300 87 (01.24) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING TDCR-TG Return 4 4 - 7047
58 GROUND FLOOR SUPPLY DIFFUSER 600x600 1 300x300 255 RECEIVING NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING TDCS-TG Supply 4 4 2.2 7047
59 GROUND FLOOR RETURN DIFFUSER 600x600 1 300x300 234 (01.19) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING TDCR-TG Return 4 4 - 7047
60 GROUND FLOOR SUPPLY DIFFUSER 600x600 1 300x300 202 COPY NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING TDCS-TG Supply 4 4 2.2 7047
61 GROUND FLOOR RETURN DIFFUSER 600x600 1 300x300 195 (01.15) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING TDCR-TG Return 4 4 - 7047
62 GROUND FLOOR SUPPLY DIFFUSER 600x600 1 150x100 21 OFFICE WC (01.14) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING TDCS-TG Supply 4 4 2.2 7047
63-A GROUND FLOOR SUPPLY DIFFUSER 300x300 1 80 ELEC (01.09) OMITTED TDCS-TG Supply 7 7 2.6
64-A GROUND FLOOR RETURN DIFFUSER 300x300 1 80 ELEC (01.09) OMITTED TDCR-TG Return 9 7 -
65-A GROUND FLOOR SUPPLY DIFFUSER 600x600 1 91 ELEC (01.23) OMITTED TDCS-TG Supply 4 4 2.2
66-A GROUND FLOOR RETURN DIFFUSER 600x600 1 91 ELEC (01.23) OMITTED TDCR-TG Return 4 4 -
63-B GROUND FLOOR SUPPLY GRILLE 200x100 1 45 FLOWBAR SIZE (ROOM WIDTH- 3065mm) FL-10-HT 45 0 600 1.968 0 Supply 25 19 4.3 STANDARD BLACK
OFFICE MTG (01.17A)
64-B GROUND FLOOR RETURN GRILLE 200x100 1 17 SEPARATE FLOWBARS FOR SUPPLY AND RETURN FL-10-HT 17 0 600 1.968 0 Return 4 13 - STANDARD BLACK
65-B GROUND FLOOR SUPPLY GRILLE 300x150 1 143 FLOWBAR SIZE (ROOM WIDTH- 3875mm) FL-10-HT 143 0 1400 4.592 0 Supply 50 32 7.9 STANDARD BLACK
MGRS OFFICE (01.17)
66-B GROUND FLOOR RETURN GRILLE 300x150 1 124 SEPARATE FLOWBARS FOR SUPPLY AND RETURN FL-10-HT 124 0 1200 3.936 0 Return 55 35 - STANDARD BLACK
67 BASEMENT SUPPLY GRILLE 150x100 1 8 EMR NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHD-TG Supply 2 7 1.8 9016 - STANDARD WHITE
68 BASEMENT RETURN GRILLE 150x100 1 8 (B. 19) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Return 10 14 - 9016 - STANDARD WHITE
69 BASEMENT FRESH AIR GRILLE 950x750 1 5627 STAIR 2 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHF-TG Supply > 51 > 49 > 34 9016 - STANDARD WHITE
70 BASEMENT FRESH AIR GRILLE 150x100 1 14 CORRIDOR (B.34) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHF-TG Supply 3 8 3 9016 - STANDARD WHITE
71 BASEMENT FRESH AIR GRILLE 150x100 1 22 CORRIDOR (B.35) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHF-TG Supply 3 8 3 9016 - STANDARD WHITE
72 BASEMENT FRESH AIR GRILLE 250x150 1 105 PREP. KITCHEN (B. 05) OMITTED 300SHF-TG Supply 11 18 8.4
73 BASEMENT FRESH AIR GRILLE 100x100 1 12 SECURITY (B.07) OMITTED 300SHF-TG Supply 3 10 3.9
74 BASEMENT FRESH AIR GRILLE 150x150 1 45 CORRIDOR (B. 04) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHF-TG Supply 6 10 6.4 9016 - STANDARD WHITE
75 BASEMENT FRESH AIR GRILLE 150x100 1 17 CORRIDOR (B.13) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHF-TG Supply 3 8 3 9016 - STANDARD WHITE
76 BASEMENT FRESH AIR GRILLE 100x100 1 12 BMS ENGR (B. 16) OMITTED 300SHF-TG Supply 3 10 3.9
77 BASEMENT FRESH AIR GRILLE 150x150 1 42 CORRIDOR (B.17) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 300SHF-TG Supply 6 10 6.4 9016 - STANDARD WHITE
78 BASEMENT EXHAUST GRILLE (EF-04) 200 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust > 80 > 45 -
79 BASEMENT EXHAUST GRILLE (EF-03) 1000 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 56 47 -
80 BASEMENT EXHAUST GRILLE (EF-01) 1150x1150 1 1150 STAIR 2 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 60 49 - 9016 - STANDARD WHITE
81 BASEMENT EXHAUST GRILLE (EF-02) 135 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 19 24 -
82 BASEMENT EXHAUST GRILLE (EF-05) 427 NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 28 34 -
83 BASEMENT EXHAUST GRILLE 150x100 1 35 STORAGE (B.02) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 10 14 - 9016 - STANDARD WHITE
84 BASEMENT EXHAUST GRILLE 150x100 1 35 STORAGE (B.03) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 10 14 - 9016 - STANDARD WHITE
85 BASEMENT EXHAUST GRILLE 200x150 1 65 STORAGE (B.27) NO CHANGE - SIZE REMAINS THE SAME AS PER IFC DRAWING 350RH-TG Exhaust 59 39 - 9016 - STANDARD WHITE
86 BASEMENT EXHAUST GRILLE 150x100 1 150x100 40 JANITOR (B.20) PROPOSED CEILING DIFFUSER WITH SIZE OF 600x600 350RH-TG Exhaust 10 14 - 9016 - STANDARD WHITE
87 BASEMENT EXHAUST GRILLE 150x150 1 150x150 45 TRASH (B.21) PROPOSED CEILING DIFFUSER WITH SIZE OF 600x600 350RH-TG Exhaust 4 13 - 9016 - STANDARD WHITE
88 BASEMENT EXHAUST GRILLE 700x80 1 35 WC (B.22) NO CHANGE - SAME AS IFC DRAWING 350RH-TG Exhaust 2 7 - 9016 - STANDARD WHITE
89 BASEMENT EXHAUST GRILLE 600x600 1 1000 PREP. KITCHEN (B.05) NEWELY ADDED - PROPOSED SIZE TO BE CONFIRMED 7047
90 BASEMENT SUPPLY DIFFUSER 600x600 2 300x250 295 PROPOSED SIZE IS ACCEPTED AS 600x600 TDCS-TG Supply 4 4 2.2 7047
PREP. KITCHEN (B.05)
91 BASEMENT RETURN DIFFUSER 600x600 2 300x250 295 PROPOSED SIZE IS ACCEPTED AS 600x600 TDCR-TG Return 4 4 - 7047
92 BASEMENT SUPPLY DIFFUSER 600x600 1 300x200 189 PROPOSED SIZE IS ACCEPTED AS 600x600 TDCS-TG Supply 4 4 2.2 7047
BMS ENGINNER (B.16)
93 BASEMENT RETURN DIFFUSER 600x600 1 300x200 189 PROPOSED SIZE IS ACCEPTED AS 600x600 TDCR-TG Return 4 4 - 7047
94 BASEMENT SUPPLY DIFFUSER 300x300 1 400x250 72 PROPOSED CEILING DIFFUSER WITH SIZE OF 600x600 TDCS-TG Supply 7 7 2.6 7047
SECURITY ROOM (B.07)
95 BASEMENT RETURN DIFFUSER 300x300 1 400x250 72 PROPOSED CEILING DIFFUSER WITH SIZE OF 600x600 TDCR-TG Return 9 7 - 7047
96 BASEMENT SUPPLY DIFFUSER 300x300 1 150x150 63 PROPOSED CEILING DIFFUSER WITH SIZE OF 600x600 TDCS-TG Supply 7 7 2.6 7047
LOCKERS ROOM (B.23)
97 BASEMENT RETURN DIFFUSER 300x300 1 150x150 63 PROPOSED CEILING DIFFUSER WITH SIZE OF 600x600 TDCR-TG Return 9 7 - 7047
98 BASEMENT SUPPLY GRILLE 400x200 1 339 PROPOSED SIZE IS ACCEPTED AS 400x200 300SHD-TG Supply 41 34 15.3 9016 - STANDARD WHITE
99 BASEMENT RETURN GRILLE 400x200 1 339 IDF ROOM (B.14) PROPOSED SIZE IS ACCEPTED AS 400x200 350RH-TG Return 36 36 - 9016 - STANDARD WHITE
100 BASEMENT SUPPLY GRILLE 700x300 1 1093 PROPOSED SIZE IS ACCEPTED AS 700x300 300SHD-TG Supply 57 43 27.4 9016 - STANDARD WHITE
101 BASEMENT RETURN GRILLE 700x300 1 1093 TELECOM (B.11) PROPOSED SIZE IS ACCEPTED AS 700x300 350RH-TG Return 10 21 - 9016 - STANDARD WHITE
102 BASEMENT SUPPLY GRILLE 200x150 1 86 PROPOSED SIZE IS ACCEPTED AS 200x150 300SHD-TG Supply 21 20 7.9 9016 - STANDARD WHITE
103 BASEMENT RETURN GRILLE 200x150 1 86 AV (B.10) PROPOSED SIZE IS ACCEPTED AS 200x150 350RH-TG Return 59 39 - 9016 - STANDARD WHITE
104 BASEMENT SUPPLY GRILLE 500x200 1 434 PROPOSED SIZE IS ACCEPTED AS 500x200 300SHD-TG Supply 42 36 17.3 9016 - STANDARD WHITE
105 BASEMENT RETURN GRILLE 500x200 1 434 SEC EQPM (B.08) PROPOSED SIZE IS ACCEPTED AS 500x200 350RH-TG Return 37 38 - 9016 - STANDARD WHITE
106 BASEMENT SUPPLY GRILLE 200x150 1 106 PROPOSED SIZE IS ACCEPTED AS 200x150 300SHD-TG Supply 21 20 7.9 9016 - STANDARD WHITE
107 BASEMENT RETURN GRILLE 200x150 1 106 ELEC (B.28) PROPOSED SIZE IS ACCEPTED AS 200x150 350RH-TG Return 59 39 - 9016 - STANDARD WHITE
108 BASEMENT SUPPLY GRILLE 200x150 1 80 PROPOSED SIZE IS ACCEPTED AS 200x150 300SHD-TG Supply 21 20 7.9 9016 - STANDARD WHITE
109 BASEMENT RETURN GRILLE 200x150 1 80 UPS (B.29) PROPOSED SIZE IS ACCEPTED AS 200x150 350RH-TG Return 59 39 - 9016 - STANDARD WHITE
110 BASEMENT SUPPLY GRILLE 500x200 1 434 PROPOSED SIZE IS ACCEPTED AS 500x200 300SHD-TG Supply 42 36 17.3 9016 - STANDARD WHITE
111 BASEMENT RETURN GRILLE 500x200 1 434 CBS ROOM PROPOSED SIZE IS ACCEPTED AS 500x200 350RH-TG Return 37 38 - 9016 - STANDARD WHITE
112 BASEMENT EXHAUST GRILLE 150x100 1 12 SUMP PUMP ROOM (B.01) PROPOSED SIZE IS ACCEPTED AS 150x100 350RH-TG Exhaust 10 14 - 9016 - STANDARD WHITE
113 BASEMENT EXHAUST GRILLE 150x100 1 112 CBS ROOM PROPOSED SIZE IS ACCEPTED AS 150x100 350RH-TG Exhaust 10 14 - 9016 - STANDARD WHITE
114 BASEMENT FRESH AIR GRILLE 150x100 1 112 CBS ROOM NEWELY ADDED - PROPOSED SIZE TO BE CONFIRMED 300SHF-TG Supply 3 8 3 9016 - STANDARD WHITE

Notes:
1. Throw is given at isothermal terminal velocity 0.25 m/s.
3. Fresh air grille performance is based on without filter.
4. Supply Square diffuser performance is based on without opposed blade damper.
5. Square diffuser performance is based on standard neck sizes.
6. Performance for grille based on zero degree deflection.