Performance Supplement
• Engineering Information
• Air Performance
• Sound Performance
®
April
2016
Table of Contents
Engineering Data
Motor Starting Torque ..................................................................................... 3
V-Belt Drives ................................................................................................... 3
Wheel Moments of Inertia ............................................................................... 3
Fan RPM Limitations ....................................................................................... 3
Effects of Air Density ...................................................................................... 4
Effect of Installation on Performance ............................................................ 5
Sound Performance Testing .........................................................................6-7
Sample Fan Selection .................................................................................8-9
2
®
Engineering Data
Motor Starting Torque USF-400 Moments of Inertia (lb-ft2)
When selecting a motor for a centrifugal fan, the motor must be Moments of inertia are shown for steel wheels. Aluminum wheels
capable of driving the fan at operating speed and also capable of are one-third of the value shown.
accelerating the fan wheel, shaft and drive to the operating speed.
Steel Backward Inclined Steel Airfoil
The fan performance tables and curves in this catalog show the Centrifugal Wheels Centrifugal Wheels
Fan Size
brake horsepower required to operate the fan once it is brought to
operating speed. For applications requiring a large air volume at a Class I Class II Class I Class II
low static pressure, the BHP required at the fan’s operating RPM 7-10 1.0 1.0 — —
may not be sufficient to initially start the fan. If the time required to 12 1.5 1.8 — —
bring the fan to speed is excessive, the motor winding insulation 13 2.1 2.5 — —
can be damaged due to excessive temperature rise and the life of 15 3.5 3.7 — —
the motor seriously affected. 16 5.3 6.3 — —
For a belt drive fan, the required motor starting torque capability 18 8.9 10.2 9.8 11.1
can be expressed by the following formula: 20 12.4 14.2 13.3 20.1
22 22.4 22.4 24.0 24.0
( )
2 2 FRPM 2 24 31.8 34.4 33.3 33.3
WR M = WR F x x (1.1) 27 46.0 49.8 49.7 49.7
MRPM
30 71.8 87.3 78.4 88.8
2 33 103 125 113 144
WR M = The moment of inertia that the motor must2 be 36 179 200 183 230
capable of turning at the motor shaft, lb-ft
40 300 333 303 372
2 44 434 541 432 530
WR F = The moment of inertia of the fan wheel, lb-ft2 49 663 821 741 816
3
®
Engineering Data
Effect of Air Density – Temperature and Elevation
Ratings in the fan performance tables and curves of this catalog are based on standard air (clean, dry air with a density of 0.075 pounds per
cubic foot, barometric pressure at sea level of 406.75 inches wg, temperature of 70°F). Selecting a fan to operate at conditions other than
standard air requires an adjustment to both static pressure and brake horsepower.
One cubic foot of air has a constant volume regardless of temperature or elevation. However, air density changes with non-standard
temperature or elevation. Therefore, when selecting a fan to operate at a non-standard air density using standard air density tables and
curves, corrections must be made to parameters affected by air density. These parameters are static pressure and brake horsepower.
For example, a size
30 USF 400-BI centrifugal Dry Air Density Correction Factor (I-P)
fan is to deliver 13,000 cfm Multiply Standard Air Density, 0.075 lbm / ft3 by the Factor to obtain Density at Condition pb
at 4.85 inches wg static Sea
pressure. Elevation is 2000 Altitude, (Z) ft. -1000 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Level
feet, temperature is 150°F. in. Hg 31.02 29.92 28.85 27.82 26.82 25.84 24.89 23.98 23.09 22.22 21.39 20.58
Barometric Pressure
The 4.85 inches wg static ( pb ) in. wg 421.71 406.75 392.21 378.20 364.61 351.29 338.37 326.00 313.90 302.07 290.79 279.78
pressure refers to the static
-40 1.309 1.262 1.217 1.174 1.131 1.090 1.050 1.012 0.974 0.937 0.902 0.868
pressure at the operating air
density, in this case at 2000 0 1.195 1.152 1.111 1.071 1.033 0.995 0.959 0.924 0.889 0.856 0.824 0.793
feet, 150°F. Intuitively, we 40 1.099 1.060 1.022 0.986 0.950 0.915 0.882 0.850 0.818 0.787 0.758 0.729
realize that at higher than
70 1.037 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688
standard elevations and
temperatures, air density 100 0.981 0.946 0.913 0.880 0.848 0.817 0.787 0.759 0.730 0.703 0.677 0.651
will be lower than standard. Temperature °F, (t) 150 0.901 0.869 0.838 0.808 0.779 0.750 0.723 0.696 0.670 0.645 0.621 0.598
Therefore, we must determine 200 0.832 0.803 0.774 0.747 0.720 0.693 0.668 0.644 0.620 0.596 0.574 0.552
what static pressure at
standard air density will 250 0.774 0.746 0.720 0.694 0.669 0.645 0.621 0.598 0.576 0.554 0.534 0.513
equate to 4.85 inches wg 300 0.723 0.697 0.672 0.648 0.625 0.602 0.580 0.559 0.538 0.518 0.498 0.480
static pressure at our 350 0.678 0.654 0.631 0.608 0.586 0.565 0.544 0.524 0.505 0.486 0.468 0.450
operating density. Since
standard air density is greater 400 0.639 0.616 0.594 0.573 0.552 0.532 0.513 0.494 0.475 0.458 0.440 0.424
than operating air density in Adapted from AMCA Standard 99-09, section 0200, Charts and Tables, with written permission from Air Movement and
this case, we would expect Control Association International, Inc.
the corrected static pressure
to be greater than the operating static pressure.
The accompanying table gives air density correction factors for non-standard temperatures and elevations.
The example below shows the relationship of fan performance at sea level and at 2000 ft. elevation and 150°F.
Example:
The following example shows how to properly select the fan described above:
1. Since the air volume delivered by the fan is not affected by density, airflow remains 16,500 cfm.
2. Determine correction factor from chart for an elevation of 2000 feet and air temperature of 150°F. The correction factor is 0.808.
3. Divide the specified operating static pressure by the correction factor to determine the standard air density equivalent static pressure.
Corrected static pressure = 4.85 inches wg ÷ 0.808 = 6.0 inches wg static pressure.
4. Refer to the fan performance table for a 30 USF 400. At 13,000 cfm and 6.0 inches wg static pressure:
Fan RPM = 1400, BHP = 17.02
5. 1400 Fan RPM is required to produce the desired performance.
6. Since the horsepower selected refers to standard air
density, this must be corrected to reflect actual BHP at
the lighter operating air. Standard Air 70°F, Sea Level
Operating BHP = Standard BHP x 0.808, or 17.02 x 0.808 Correct Air 150°F, Altitude of 2000 ft. 30 USF-400-BI
8
= 13.75 BHP.
17.02 Bhp
18 18
If a fan is selected to operate at high temperatures, the 7
Air, 1400 RPM
Standard
motor must be of sufficient horsepower to handle the 16 6.0 in. wg
fan at start-up is 0°F. For 0°F and 2000 feet elevation, the air 12
5
12
density correction factor is 1.071
10 4
BHP at 0°F = 17.02 x 1.071 = 18.24, therefore, a 20 hp motor
9
is required. 8 Ai
r,
Bh
p
3 a rd
nd
S ta p
6 Bh 6
r,
Ai
ed
2 ct
rre
4 Co
3
1
2
0 0 0
0 5 10 15 20 25
Volume (cfm x 1000)
0 5 10 15 20 25 30 35 40
3
Volume (m /hr x 1000)
4
®
Engineering Data
Effect of Installation on Performance Inlet Spin
Ratings presented in the performance tables and curves of this Rot Turning Rot
a Vanes a
catalog were derived from tests made in accordance with AMCA
tio
tio
Standard 210 — “Laboratory Methods of Testing Fans for Ratings.”
n
The AMCA test procedure utilizes an open inlet and a straight
outlet duct to assure maximum static regain.
Any installation with inlet or discharge configurations that deviate
from this standard may result in reduced fan performance.
Restricted or unstable flow at the fan inlet can cause pre-rotation
of incoming air or uneven loading of the fan wheel yielding large POOR GOOD
system losses and increased sound levels. Free discharge or
turbulent flow in the discharge ductwork will also result in system
effect losses. Inlet spin is a frequent cause of reduced fan performance. The
change in fan performance is a function of the intensity of spin
Static pressure losses due to inlet and discharge conditions can and not easily defined. The best solution is proper duct design and
be expressed in terms of system effect factors. The static pressure airflow patterns.
for selection of the fans equals the system static pressure plus the
system effect factor.
Discharge Duct Turns
Some common inlet and discharge conditions which affect fan
performance are:
t
Ro
One
fan
wheel
diameter
POOR
have one fan wheel diameter between the fan inlet and the wall.
System effect Curve #3 depicts the pressure loss for one-half
wheel diameter clearance.
Duct turns located near the fan discharge should always be in the
direction of the fan rotation.
Fan performance is reduced when duct turns are made immediately
off the fan discharge. To achieve cataloged fan performance there
should be at least three equivalent duct diameters of straight
ductwork between the fan discharge and any duct turns. Curve #4
shows the system effect factor for two diameters of straight
ductwork and Curve #2 for one diameter.
Free or abrupt discharge into a plenum results in a reduction in fan
performance. The effect of static regain in discharge is not realized.
System effect Curve #2 depicts the pressure loss for free or abrupt System Effect Factor Curves
discharge.
Additional information on system effect factors can be found
in AMCA Publication 201 — “Fans and Systems” and ASHRAE
Handbooks.
Inlet Duct Turns
1.2
diameter
0.8
1
0.6 e
rv
Turning Cu 2
Vanes rve
Cu 3
GOOD POOR 0.4 rve
Cu
ve 4
Cur
Installation of a duct turn or elbow too close to the fan inlet 0.2
reduces fan performance because the air is loaded unevenly into
the fan wheel. To achieve full fan performance there should be at 0.0
least one fan wheel diameter between the turn or elbow and the fan 0 5 10 15 20 25 30 35 40 45
inlet. Curve #1 shows the system effect factor when less than one
diameter is provided. Note: Use of an inlet box in lieu of a turn or Outlet Velocity (FPM x 100)
elbow significantly reduces system effect.
5
®
Sound Performance Testing
AMCA Licensed Ratings
Sound tests were conducted in Greenheck Fan Corporation’s AMCA Accredited sound laboratory in accordance with AMCA Standard
300. Inlet and outlet sound ratings comply with AMCA Publication 311, qualifying these models to bear the AMCA Seal for Sound and
Air Performance. The sound power levels published here can be compared directly with those of other similarly rated fans, or used as a
baseline to determine sound levels in occupied spaces.
The sound data in this brochure is the result of extensive testing, which included both inlet and outlet sound tests on single-width
centrifugal fans. Typically, fan manufacturers publish only inlet sound for single-width fans. The assumption they make is that outlet sound
is identical to inlet sound. Sound data based on this assumption is simply not accurate enough for today’s sound sensitive installations.
This assumption also ignores duct end corrections for outlet sound.
Test Methods
AMCA Standard 300 clearly defines methods used to test fans in a reverberant sound test room. The reverberant room is specifically
designed to allow sound waves to be dispersed evenly throughout the room. The walls have a hard surface that reflects sound and are
positioned to prevent resonances which could result in quiet areas within the room.
Sound power cannot be directly measured. The test method is based on a Reference Sound Source (RSS) substitution for determining fan
sound power. The RSS is a laboratory calibrated device which has a known sound power output level. The test fan is installed as shown
below. The RSS is energized and the sound pressure levels in the reverberant room are recorded. The fan is then operated without the RSS
and the fan sound pressure levels are recorded for various points of operation. Since the sound power levels of the RSS are known, the
substitution method is used to determine the sound power levels of the fan. This method is illustrated in the following example.
Test Setups
The illustrations show where the sound levels were measured with respect to the fan. Inlet sound was tested as in Figure 2 of AMCA
Standard 300 and outlet sound was tested as in Figure 3. Inlet and outlet sound were determined in the same inlet and outlet configurations
as the air tests. (Installation Type B - Free Inlet, Ducted Outlet).
Reference Reference
Airfl
Sound Sound
ow
Source Source
Reverberant ow Reverberant
Room Airfl Room
Fan
Fan
Microphone Microphone
Path Path
Figure 2: Figure 3:
AMCA Standard 300 - Fan Inlet Sound Testing AMCA Standard 300 - Fan Outlet Sound Testing
Installation Type B: Free Inlet, Ducted Outlet Installation Type B: Free Inlet, Ducted Outlet
(Ratings include the effects of duct end correction)
6
®
Sound Performance Testing
Tolerance and Application
The certification process in AMCA Standard 311 calls for a precertification test to verify original test results. Check tests are also required
every three (3) years for each model licensed. Test data must agree with the published sound power within the following tolerance levels:
Octave Band 1 2 3 4 5 6 7 8
Center Frequency (Hz) 63 125 250 500 1000 2000 4000 8000
Tolerance +6 +3 +3 +3 +3 +3 +3 +3
These tolerance levels are a good indication of the variance that could occur from one fan or test setup to another. Once installed however,
there are many other factors that can affect the sound power generated by a fan.
The lower frequencies (below 125 Hz) are greatly affected by vibration. Fan wheel balance, motor balance, drive alignment, etc., all affect
the vibration level of the fan and can increase sound power in the 1st and 2nd octaves. When ducts are not properly isolated from the fan,
these vibrations can be transmitted into the ducts, which can generate additional low frequency sound.
Sound power generated by a fan can also be influenced by system effects. System effects are pressure losses caused by inlet or outlet
restrictions, or other conditions causing non-uniform airflow at the inlet or discharge of a fan (see AMCA Publication 201). Examples include
inlet or outlet elbows too close to a fan, restricted inlets and fan accessories. While system effects can prevent fans from reaching their
designed air performance, they can also result in increased sound power levels. Typically, system effects cause pressure fluctuations
which influence the lower frequencies. Poor inlet conditions can also greatly increase sound levels at the blade pass frequency (BPF). The
blade pass frequency refers to how often a blade or wheel fin passes a stationary location of the housing and can be calculated using the
following equation:
7
®
Sample
Fan Selection
Fan Selection
Procedure
The purpose of this page is to demonstrate the manual centrifugal fan selection process. This page also contains helpful
tips to check your fan selection, as well as a step-by-step set of instructions on how to use this manual to properly select a
centrifugal fan.
An important point to remember when manually selecting a centrifugal fan is that more than one fan is available to meet
the desired performance (CFM and Ps). Selection criteria such as unit size, efficiency, speed, outlet velocity, horsepower, or
construction material may also dictate which fan is chosen.
36 USF-400 - BI
12
A The Outlet Area is used 20 25 30 40 50
RPM
HP
VE
71
CUR
10
7.66 ft2
OV = A
TEM
Outlet Area
OA 0.71 m2 1 12
SYS
15 6 7 ⁄2 00
HIS
Maximum BHP at a given RPM (RPM/381)3
FT
10
B 5 51
TO
B The Maximum BHP can Maximum KW at a given RPM (RPM/420)3 10 4
EF
90
EL
3 0
TH
be calculated for a given C Maximum RPM 1371
TO
750
CT
5 2
fan RPM along the fan
LE
RPM x 9.56 ft/min. 600
SE
Tip Speed
T
NO 450
RPM x 0.049 m/s
curve. Imperial data - Metric data
0 0
0
DO
5 10 15 20 25 30 35 40 45
Volume (cfm x 1000)
C The maximum fan RPM 0 20 40 60
for each fan class is Volume (m3/hr x 1000)
Performance certified is for model USF 400-BI, Installation Type B: free inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Power rating (Bhp) does not include transmission losses.
STEP 1
Enter the performance table with the desired CFM and Ps. Obtain the fan RPM, BHP Sound.
EXAMPLE
For this example, we will use 23,000 cfm at 3.0 Ps. This gives us a fan RPM of 1002, requiring 18.16 Bhp.
NOTE: If your specific fan selection is not at standard air (70°F), refer to air density correction factor table found on
page 4. LwiA and LwoA are the A-weighted sound power levels for the fan inlet and outlet, respectively, at the selected
performance. For this example, inlet sound is 92 dBA and the outlet sound is 95 dBA.
8
®
Notes
9
®
Notes
10
®
06 USF-200/300
4.5
11 34
⁄ 1
RPM
HP
10 4.0 Density 0.075 lb/ft3
Density 1.2 kg/m3
12
⁄
9
3.5
10.5 in.
Wheel Diameter
E
33
8 71
CURV
267 mm 3.0
STEM
7
0.63 ft2
Outlet Area 2.5
IS SY
6
0.06 m2 ¼ 283
0
F TH
5 2.0
(RPM/3629)3
O
Maximum BHP at a given RPM
LEFT
4
Maximum KW at a given RPM (RPM/4001)3 1.5 229
0
THE
3
TO
Maximum RPM 3371 1.0
CT
1750
2
ELE
RPM x 2.75 ft/min.
TS
0.5
Tip Speed 1 1210
NO
RPM x 0.014 m/s
O
D 670
0 0.0
0 1 2 3 4 5 6 7
Imperial data - Metric data
Volume (cfm x 100)
0 1 2 3 4 5 6 7 8 9 10 11
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA
Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet,
Ducted outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
11
®
07 USF-200/300
6
1 11⁄2
14 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
5
12 34
⁄
10.5 in.
Wheel Diameter 33
267 mm 10 4
71
E
Static Pressure (in. wg)
URV
1
⁄2
0.63 ft2
C
Outlet Area
TEM
8
0.06 m2 3
28
30
SYS
13
⁄
HIS
Maximum BHP at a given RPM (RPM/3099)3 6
FT
¼
(RPM/3417)3
TO
22
Maximum KW at a given RPM 2 90
EF
EL
4
Maximum RPM 3371
TH
17
TO
50
1
CT
RPM x 2.75 ft/min. 2
LE
Tip Speed
SE
121
T 0
RPM x 0.014 m/s DO
NO
670
0 0
0 2 4 6 8 10 12
Imperial data - Metric data
Volume (cfm x 100)
0 5 10 15 20
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA
Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet,
Ducted outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
12
®
08 USF-200/300
6
1 11⁄2
14 RPM
HP
34
⁄ Density 0.075 lb/ft3
Density 1.2 kg/m3
5
12
10.5 in.
Wheel Diameter 33
267 mm 10 4
12
⁄ 71
VE
CUR
0.63 ft2
Outlet Area
TEM
8
0.06 m2
13
⁄
3 28
SYS
30
¼
(RPM/3242)3
HIS
Maximum BHP at a given RPM 6
FT
Maximum KW at a given RPM (RPM/3574)3
TO
2 229
EF
0
4
EL
Maximum RPM 3371
TH
TO
175
1 0
CT
RPM x 2.75 ft/min. 2
LE
Tip Speed
SE
121
T 0
RPM x 0.014 m/s DO
NO
670
0 0
0 2 4 6 8 10 12 14 16
Imperial data - Metric data
Volume (cfm x 100)
0 5 10 15 20 25
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA
Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet,
Ducted outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
13
®
10 USF-200/300
6
1 11⁄2 2 3
14 RPMHP
HP
Density 0.075 lb/ft3
34
Density 1.2 kg/m3
5 ⁄
12
10.5 in.
Wheel Diameter
33
267 mm 10
71
4
0.63 ft2
E
Outlet Area
RV
8
0.06 m2
CU
3
28
13
⁄
40
EM
ST
Maximum BHP at a given RPM (RPM/2649)3 6
SY
¼
IS
Maximum KW at a given RPM (RPM/2921)3 2
TH
23
OF
00
4
FT
Maximum RPM 3371
LE
17
E
70
TH
1
TO
2
RPM x 2.75 ft/min. CT
Tip Speed SE
LE
12
50
RPM x 0.014 m/s DO N
OT 70
0
0 0
0 5 10 15 20 25 30
Imperial data - Metric data
Volume (cfm x 100)
0 10 20 30 40 50
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the requirements of the AMCA
Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet,
Ducted outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
14
®
12 USF-200/300
7
2 3
RPM
16 HP
11⁄2 Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14
12.25 in.
Wheel Diameter 5 32
311 mm 12 1 74
VE
Static Pressure (in. wg)
CUR
0.86 ft2 10 4 3
⁄4
Outlet Area
TEM
0.08 m2 28
00
SYS
8
3
HIS
1
⁄2
Maximum BHP at a given RPM (RPM/2347)3
FT
(RPM/2588)3 23
TO
6
Maximum KW at a given RPM 1
⁄3 00
EF
2 ¼
EL
Maximum RPM 3274
TH
4 18
00
TO
CT
1
RPM x 3.21 ft/min.
LE
2 130
Tip Speed
SE
0
T
RPM x 0.016 m/s DO
NO
0 0
0 5 10 15 20 25 30 35
Imperial data - Metric data
Volume (cfm x 100)
0 10 20 30 40 50
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
15
®
13 USF-200/300
7
2 3 5
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14 11⁄2
13.5 in.
Wheel Diameter 5
343 mm 12 29
70
VE
Static Pressure (in. wg)
CUR
1
1.05 ft2 10 4
TEM
Outlet Area
0.10 m2 25
SYS
34 ⁄ 00
8
S
3
THI
Maximum BHP at a given RPM (RPM/1997)3
OF
1
⁄2 21
Maximum KW at a given RPM (RPM/2202)3 6 00
EFT
2
EL
13 ⁄
TH
Maximum RPM 2970 4 17
00
TO
CT
1
RPM x 3.53 ft/min.
LE
2 120
SE
Tip Speed 0
T
RPM x 0.018 m/s NO 800
DO
0 0
0 5 10 15 20 25 30 35 40 45
Imperial data - Metric data
Volume (cfm x 100)
0 10 20 30 40 50 60 70
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
16
®
15 USF-200/300
7
3 5
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
2
14
15 in.
Wheel Diameter 5
381 mm 12
VE
11⁄2
26
Static Pressure (Pa x 100)
74
CUR
Static Pressure (in. wg)
1.29 ft2
M
10 4
STE
Outlet Area
0.12 m2 1 23
00
S SY
8
THI
3
(RPM/1675)3
3
⁄4
Maximum BHP at a given RPM
OF
19
(RPM/1847)3
00
EFT
6
Maximum KW at a given RPM 1
⁄2
EL
2
TH
1
⁄3
Maximum RPM 2674 4 15
TO
00
CT
LE
1
RPM x 3.93 ft/min. 110
SE
2 0
Tip Speed
OT
900
RPM x 0.020 m/s DO
N
0 0
0 1 2 3 4 5 6
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
17
®
16 USF-200/300
7
3 5
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14
16.5 in.
Wheel Diameter 5
2
24
419 mm 12
31
Static Pressure (Pa x 100)
URV
Static Pressure (in. wg)
C
1.57 ft2 10
11⁄2
TEM
4
Outlet Area 21
0.15 m2 00
SYS
8 1
HIS
3
Maximum BHP at a given RPM (RPM/1429)3
T
OF
3
⁄4
Maximum KW at a given RPM (RPM/1576)3 6 17
EFT
00
EL
2 12
⁄
TH
Maximum RPM 2431 4 14
00
TO
CT
1
LE
RPM x 4.32 ft/min. 2
11
00
SE
Tip Speed
T
O
RPM x 0.022 m/s DO
N 800
0 0
0 1 2 3 4 5 6 7
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
18
®
18 USF-200/300
7
3 5 71⁄2
RPM
16 HP
Density 0.075 lb/ft3
6 2 Density 1.2 kg/m3
14
18.25 in.
Wheel Diameter 5 11⁄2 20
99
464 mm 12
RVE
1.92 ft2 10 4
CU
Outlet Area 1 18
0.18 m2
M
00
STE
8
SY
34
⁄
3
Maximum BHP at a given RPM (RPM/1330)3
HIS
15
FT
00
Maximum KW at a given RPM (RPM/1330)3 6
TO
2
EF
EL
Maximum RPM 2099 4 12
00
TH
TO
1
T
RPM x 4.78 ft/min. 900
EC
2
Tip Speed
EL
S
T
RPM x 0.024 m/s DO
NO 600
0 0
0 1 2 3 4 5 6 7 8
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10 12
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
19
®
20 USF-200/300
7
3 5 71⁄2
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14
20 in. 2
19
Wheel Diameter 5 15
508 mm 12
E
Static Pressure (in. wg)
11⁄2
URV
2.3 ft2 10
17
C
4 00
Outlet Area
TEM
0.21 m2
SYS
1
8
3
HIS
Maximum BHP at a given RPM (RPM/1035)3 14
FT
00
(RPM/1141)3
TO
6
Maximum KW at a given RPM
EF
12
2 ⁄
EL
11
Maximum RPM 1915
TH
4 00
TO
CT
1
RPM x 5.24 ft/min.
LE
2 800
SE
Tip Speed NO
T
RPM x 0.027 m/s DO
0 0
0 2 4 6 8 10
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10 12 14 16
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
20
®
22 USF-200/300
7
5 71⁄2 10
RPM
16 HP
3 Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14
22.25 in.
Wheel Diameter 5 17
565 mm 12 22
VE
CUR
2.85 ft2 10 4
Outlet Area 15
TEM
11⁄2
0.26 m2 00
SYS
8
3 1
HIS
Maximum BHP at a given RPM (RPM/867)3 13
00
FT
(RPM/956)3 6
TO
Maximum KW at a given RPM
EF
2 11
00
EL
12
⁄
Maximum RPM 1722
TH
4
TO
90
0
CT
1
RPM x 5.83 ft/min.
LE
2 700
Tip Speed
SE
T
RPM x 0.030 m/s NO
DO
0 0
0 2 4 6 8 10 12
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10 12 14 16 18 20
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
21
®
24 USF-300
16 5 71⁄2 10
RPM
6 HP
3
Density 0.075 lb/ft3
14 Density 1.2 kg/m3
5
24.5 in. 12
Wheel Diameter 15
70
622 mm 2
VE
Static Pressure (in. wg)
10 4
CUR
3.45 ft2 11⁄2
Outlet Area
TEM
0.32 m2 8
13
00
SYS
3
HIS
Maximum BHP at a given RPM (RPM/750)3
FT
6 11
(RPM/827)3
00
TO
3
⁄4
Maximum KW at a given RPM 2
EF
EL
4 90
Maximum RPM 1570
TH
0
TO
CT
1 70
RPM x 6.41 ft/min.
LE
2 0
SE
Tip Speed NO
T
RPM x 0.033 m/s DO
0 0
0 2 4 6 8 10 12 14 16
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20 25
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
22
®
27 USF-300
7
5 71⁄2 10 15
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14 14
3
27 in. 25
Wheel Diameter 5
686 mm 12
RVE
4.19 ft2 10 4
2 50
Outlet Area
CU
0.39 m2
EM
11⁄2 11
ST
8 00
SY
3
Maximum BHP at a given RPM (RPM/629)3
HIS
FT
Maximum KW at a given RPM (RPM/693)3 6
TO
3
⁄4 90
0
2
EF
EL
Maximum RPM 1425 4
TH
70
TO
0
1
RPM x 7.07 ft/min.
T
EC
2 L
Tip Speed OT
SE 500
RPM x 0.036 m/s DO
N
0 0
0 2 4 6 8 10 12 14 16 18
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20 25 30
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings
Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)
do not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
23
®
30 USF-300
7
5 71⁄2 10 15
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14 12
30 in. 79
Wheel Diameter 5
762 mm 12 3
VE
Static Pressure (in. wg)
11
50
CUR
5.17 ft2 10 4
Outlet Area
TEM
0.48 m2 2
SYS
10
8 00
3
HIS
Maximum BHP at a given RPM (RPM/527)3 11⁄2
FT
(RPM/581)3 6
TO
Maximum KW at a given RPM 85
0
EF
2
EL
34
⁄
Maximum RPM 1279
TH
4 70
0
TO
CT
1
RPM x 7.85 ft/min. 55
LE
2 0
Tip Speed
SE
T
RPM x 0.040 m/s DO
NO 400
0 0
0 5 10 15 20 25
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20 25 30 35 40
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings
Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)
do not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
24
®
33 USF-300
7
71⁄2 10 15 20
RPM
16 HP
5 Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14 11
63
33 in.
Wheel Diameter 5
838 mm 12
V E
Static Pressure (Pa x 100)
CUR
Static Pressure (in. wg)
3
10
6.26 ft2 00
EM
10 4
Outlet Area
YST
0.58 m2
SS
2
8
THI
3 85
0
Maximum BHP at a given RPM (RPM/445)3
OF
11⁄2
EFT
Maximum KW at a given RPM (RPM/491)3 6
EL
2 1 70
0
TH
Maximum RPM 1163 4
TO
CT
550
LE
1
RPM x 8.64 ft/min.
SE
2
Tip Speed
T
400
O
N
RPM x 0.044 m/s DO
0 0
0 5 10 15 20 25 30
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40 50
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings
Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)
do not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
25
®
36 USF-300
7 10 15 20 25
71⁄2
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
10
14 51
36.5 in. 5
Wheel Diameter 5
VE
Static Pressure (Pa x 100)
CUR
92
5
7.66 ft2 10 4
TEM
Outlet Area 3
0.71 m2
SYS
800
8
S
THI
3
Maximum BHP at a given RPM (RPM/376)3 2
OF
Maximum KW at a given RPM (RPM/415)3 6
EFT
11⁄2 675
EL
2
TH
Maximum RPM 1051 4 550
TO
CT
1
LE
RPM x 9.56 ft/min. 2 425
SE
Tip Speed
T
NO
RPM x 0.049 m/s DO
0 0
0 5 10 15 20 25 30 35
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40 50
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings
Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)
do not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
26
®
40 USF-300
7
10 15 20 25
RPM
16 HP
71⁄2 Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14
40.25 in.
Wheel Diameter 5
93
1022 mm 12
6
5
RVE
9.31 ft2
CU
10 4
Outlet Area 82
0
M
0.86 m2
STE
8 3
SY
3
(RPM/321)3
HIS
Maximum BHP at a given RPM 71
0
FT
Maximum KW at a given RPM (RPM/354)3 6 2
TO
EF
2 60
0
EL
Maximum RPM 936 4
TH
50
TO
0
T
1
EC
RPM x 10.54 ft/min. 2 400
EL
Tip Speed NO
T
S
300
RPM x 0.054 m/s DO
0 0
0 5 10 15 20 25 30 35 40
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40 50 60
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings
Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)
do not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
27
®
44 USF-300
7
15 20 25 30 40
RPM
16 10 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14
44.5 in. 71⁄2 84
Wheel Diameter 5 7
1130 mm 12
RVE
11.38 ft2 10 4 5 75
CU
0
Outlet Area
1.06 m2
M
STE
8
SY
65
3
Maximum BHP at a given RPM (RPM/271)3 0
HIS
3
FT
Maximum KW at a given RPM (RPM/299)3 6
TO
55
0
EF
2
EL
Maximum RPM 847 4
TH
45
TO
0
CT
1
RPM x 11.65 ft/min.
LE
2 350
Tip Speed T
SE
RPM x 0.059 m/s DO
NO
0 0
0 1 2 3 4 5
Imperial data - Metric data
Volume (cfm x 10000)
0 1 2 3 4 5 6 7 8
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings
Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)
do not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
28
®
49 USF-300
7
15 20 25 30 40
RPM
16 HP
Density 0.075 lb/ft3
6 Density 1.2 kg/m3
14 10
49 in.
Wheel Diameter 5 76
1245 mm 12 9
RVE
13.8 ft2 10 4
Outlet Area
CU
67
5
1.28 m2
TEM
5
8
YS
3
(RPM/231)3
S
Maximum BHP at a given RPM 57
HIS
5
FT
Maximum KW at a given RPM (RPM/255)3 6 3
TO
2
EF
47
5
EL
Maximum RPM 769 4
TH
TO
37
1 5
T
RPM x 12.83 ft/min.
EC
2 L
Tip Speed T
SE 275
RPM x 0.065 m/s DO
NO
0 0
0 1 2 3 4 5 6
Imperial data - Metric data
Volume (cfm x 10000)
0 2 4 6 8 10
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA publication 211 and comply with the requirements of the AMCA Certified Ratings
Program. The AMCA Certified Ratings Seal applies to air performance ratings only. Performance certified is for installation type B: Free inlet, Ducted outlet. Power rating (BHP/kW)
do not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories).
29
®
18 USF-400 - AF
12
5 71⁄2 10 15
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
18.25 in. 30
Wheel Diameter 01
464 mm 20 8
3
RVE
27
00
1.92 ft2
CU
Outlet Area
M
m2
STE
0.18 15 6
2
SY
23
11⁄2 01
HIS
Maximum BHP at a given RPM (RPM/1348)3
FT
(RPM/1486)3 20
TO
Maximum KW at a given RPM 10 4 1 00
EF
EL
3
⁄4
Maximum RPM 3001
TH
1
160
⁄2
TO
0
5 2 1⁄3
T
130
EC
RPM x 4.78 ft/min. 0
EL
Tip Speed NO
T
S
0 0
0 2 4 6 8 10
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10 12 14 16
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
30
®
20 USF-400 - AF
12
71⁄2 10 15
RPM
HP
Density 0.075 lb/ft3
5 Density 1.2 kg/m3
25 10
20 in. 27
34
Wheel Diameter
508 mm 20 8
VE
3 24
2.3 ft2 00
UR
Outlet Area
MC
0.21 m2 15 6
STE
2 20
SY
86
Maximum BHP at a given RPM (RPM/1157)3
HIS
11⁄2
FT
Maximum KW at a given RPM (RPM/1276)3 10 4
TO
17
1 00
EF
EL
Maximum RPM 2734 3
⁄4
TH
140
1 0
2 ⁄2
TO
5
CT
RPM x 5.24 ft/min. 13 ⁄ 110
LE
0
Tip Speed T
SE
800
RPM x 0.027 m/s DO
NO
0 0
0 2 4 6 8 10 12
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
31
®
22 USF-400 - AF
12
71⁄2 10 15 20
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
24
22.25 in. 5 59
Wheel Diameter
565 mm 20 8
E
22
URV
00
2.85 ft2
C
Outlet Area
TEM
0.26 m2 15 6
3
SYS
18
85
(RPM/969)3
HIS
Maximum BHP at a given RPM 2
FT
Maximum KW at a given RPM (RPM/1068)3
TO
10 4 11⁄2 16
00
EF
EL
1
Maximum RPM 2459
TH
130
34
⁄ 0
TO
5 2 110
CT
RPM x 5.83 ft/min. 0
LE
Tip Speed
SE
T 800
RPM x 0.030 m/s DO
NO
0 0
0 2 4 6 8 10 12 14 16
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20 25
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
32
®
24 USF-400 - AF
12
10 15 20
RPM
HP
Density 0.075 lb/ft3
71⁄2
Density 1.2 kg/m3
25 10
24.5 in.
Wheel Diameter
622 mm 20 8 5
22
08
RVE
Static Pressure (in. wg)
CU
3.45 ft2 20
Outlet Area
M
00
STE
0.32 m2 15 6
SY
3
HIS
Maximum BHP at a given RPM (RPM/824)3 16
FT
94
TO
(RPM/908)3
2
Maximum KW at a given RPM 10 4
EF
11⁄2
EL
140
0
TH
Maximum RPM 2208 1
TO
120
34
⁄ 0
CT
5 2
100
LE
RPM x 6.41 ft/min. 0
SE
Tip Speed NO
T
RPM x 0.033 m/s DO
700
0 0
0 2 4 6 8 10 12 14 16 18
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20 25 30
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
33
®
27 USF-400 - AF
12
15 20 25
RPM
10
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
27 in. 71⁄2
Wheel Diameter 20
686 mm 20 8
04
VE
Static Pressure (in. wg)
CUR
4.19 ft2 5
Outlet Area
TEM
17
0.39 m2 15 6
50
SYS
HIS
Maximum BHP at a given RPM (RPM/701)3 3 15
37
FT
(RPM/773)3
TO
Maximum KW at a given RPM 10 4
EF
2 13
00
EL
11⁄2
Maximum RPM 2004
TH
105
O
1 0
T
5 2
CT
RPM x 7.07 ft/min.
LE
850
Tip Speed
SE
T
RPM x 0.036 m/s DO
NO 600
0 0
0 5 10 15 20 25
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
34
®
30 USF-400 - AF
12
15 20 25 30
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
10
30 in.
Wheel Diameter
17
762 mm
32
20 8
VE
CUR
5.17 ft2 15
Outlet Area 50
TEM
0.48 m2 15 6 5
SYS
(RPM/571)3
HIS
13
Maximum BHP at a given RPM 29
FT
Maximum KW at a given RPM (RPM/630)3 4 3
TO
10 11
50
EF
2
EL
Maximum RPM 1732
TH
11⁄2 950
TO
5 2 1
CT
RPM x 7.85 ft/min.
LE
750
Tip Speed
SE
T
RPM x 0.040 m/s DO
NO 550
0 0
0 5 10 15 20 25 30
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40 50
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
35
®
33 USF-400 - AF
12
20 25 30 40
RPM
15 HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
33 in.
Wheel Diameter 10
838 mm 20 8
15
Static Pressure (in. wg)
75
URV
6.26 ft2 71⁄2
C
Outlet Area
EM
14
0.58 m2 15 6 00
YST
S
5
HIS
Maximum BHP at a given RPM (RPM/487)3 12
08
FT
(RPM/537)3
TO
Maximum KW at a given RPM 10 4
3
EF
10
50
EL
Maximum RPM 1575
TH
2
85
TO
11⁄2 0
5 2
CT
RPM x 8.64 ft/min. 700
LE
Tip Speed
SE
T
RPM x 0.044 m/s NO 500
DO
0 0
0 5 10 15 20 25 30 35
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40 50
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
36
®
36 USF-400 - AF
12
25 30 40 50
20 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
15
36.5 in.
Wheel Diameter
927 mm 20 8
VE
14
CUR
10
7.66 ft2
24
Outlet Area
TEM
0.71 m2 15 6 71⁄2 12
SYS
50
HIS
Maximum BHP at a given RPM (RPM/412)3 10
FT
5 92
(RPM/454)3
TO
Maximum KW at a given RPM 10 4
EF
EL
3 90
0
Maximum RPM 1424
TH
2
TO
75
5 2 11⁄2 0
CT
RPM x 9.56 ft/min.
LE
600
Tip Speed
SE
T
RPM x 0.049 m/s DO
NO 450
0 0
0 5 10 15 20 25 30 35 40 45
Imperial data - Metric data
Volume (cfm x 1000)
0 20 40 60
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
37
®
40 USF-400 - AF
12
25 30 40 50
20 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
12
83
9.31 ft2 10
E
RV
Outlet Area
CU
0.86 m2
11
15 6 71⁄2
50
EM
ST
Maximum BHP at a given RPM (RPM/351)3
SY
98
4
IS
5
(RPM/387)3
TH
Maximum KW at a given RPM 10 4
OF
85
0
FT
3
LE
Maximum RPM 1283
E
70
TH
0
5 2 2
TO
RPM x 10.54 ft/min.
T
C 550
LE
Tip Speed SE
RPM x 0.054 m/s DO
NO
T 400
0 0
0 1 2 3 4 5
Imperial data - Metric data
Volume (cfm x 10000)
0 2 4 6 8
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
38
®
44 USF-400 - AF
12
30 40 50 60
25 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10 20
44.5 in.
Wheel Diameter
1130 mm 20 8
15
11.39 ft2
E
Outlet Area
RV
10
1.06 m2
50
CU
10
15 6
EM
ST
Maximum BHP at a given RPM (RPM/297)3 71⁄2
SY
89
1
IS
(RPM/327)3
TH
Maximum KW at a given RPM 10 4 5
OF
75
FT
0
Maximum RPM 1161
LE
3
65
E
TH
0
5 2
TO
55
RPM x 11.65 ft/min. CT 0
Tip Speed SE
LE
400
RPM x 0.059 m/s DO NOT
0 0
0 1 2 3 4 5 6
Imperial data - Metric data
Volume (cfm x 10000)
0 2 4 6 8 10
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
39
®
49 USF-400 - AF
12
40 50 60 75
30 RPM
HP
Density 0.075 lb/ft3
25 Density 1.2 kg/m3
25 10
49 in.
Wheel Diameter 20
1245 mm 20 8
10
RVE
54
13.8 ft2 15
Outlet Area
CU
95
1.28 m2 0
EM
15 6
ST
10
SY
Maximum BHP at a given RPM (RPM/253)3
IS
80
TH
71⁄2 9
Maximum KW at a given RPM (RPM/279)3 10 4
OF
70
T
5
EF
0
EL
Maximum RPM 1054 60
TH
0
TO
5 2 50
T
RPM x 12.83 ft/min. 0
EC
L
Tip Speed T
SE
350
RPM x 0.065 m/s DO
NO
0 0
0 1 2 3 4 5 6 7 8
Imperial data - Metric data
Volume (cfm x 10000)
0 2 4 6 8 10 12
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
40
®
07 USF-400 - BI
8
2
RPM
11⁄2 HP
18 Density 0.075 lb/ft3
7 Density 1.2 kg/m3
16
URVE
10.5 in. 6
Wheel Diameter 14 1 45
267 mm
YSTEM C
00
S
Outlet Area
OF THIS
0.06 m2 10 4
12
⁄ 35
00
(RPM/3659)3
T
Maximum BHP at a given RPM
HE LEF
8
3
Maximum KW at a given RPM (RPM/4034)3 30
00
T
6
CT TO
1
⁄4
2
Maximum RPM 4500 4
250
0
SELE
200
RPM x 2.75 ft/min. 1 0
NOT
Tip Speed 2
150
RPM x 0.014 m/s
DO
0
0 0
0 2 4 6 8 10 12
Imperial data - Metric data
Volume (cfm x 100)
0 2 4 6 8 10 12 14 16 18 20
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
41
®
08 USF-400 - BI
9
22 2 3
RPM
HP
20 8 11⁄2 Density 0.075 lb/ft3
Density 1.2 kg/m3
18
7
10.5 in.
CURVE
Wheel Diameter 16
267 mm 6 1
45
M
Static Pressure (in. wg)
14
SYSTE
0.645 ft2 40
Outlet Area 12
5 3
⁄4 50
0.06 m2
THIS
F
10 4
FT O
35
Maximum BHP at a given RPM (RPM/3471)3 12 ⁄ 00
E LE
8
Maximum KW at a given RPM (RPM/3827)3 3 1⁄3
O TH
30
00
6 14
⁄
CT T
Maximum RPM 4500 2 25
00
ELE
4
TS
RPM x 2.75 ft/min. 1
200
0
Tip Speed
NO
2 1500
RPM x 0.014 m/s
DO
0 0
0 2 4 6 8 10 12 14 16 18
Imperial data - Metric data
Volume (cfm x 100)
0 5 10 15 20 25 30
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
42
®
09 USF-400 - BI
9
22 2 3
RPM
HP
20 8 11⁄2 Density 0.075 lb/ft3
Density 1.2 kg/m3
18
7
10.5 in.
URVE
Wheel Diameter 16
267 mm
TEM C
6 1
45
Static Pressure (in. wg)
14
00
0.645 ft2
S SY S
Outlet Area 12
5 3⁄4 40
0.06 m2 50
F THI
10 4 1⁄2
EFT O
Maximum BHP at a given RPM (RPM/3304)3 35
00
8
(RPM/3643)3
HE L
Maximum KW at a given RPM 3 1⁄3
30
00
TO T
6 1
⁄4
Maximum RPM 4500 2
CT
25
00
ELE
4
200
RPM x 2.75 ft/min.
TS
1 0
Tip Speed
NO
2 150
RPM x 0.014 m/s 0
DO
0 0
0 5 10 15 20 25
Imperial data - Metric data
Volume (cfm x 100)
0 5 10 15 20 25 30 35 40
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
43
®
10 USF-400 - BI
9
22 2 3
RPM
HP
20 8 Density 0.075 lb/ft3
11⁄2 Density 1.2 kg/m3
18
7
10.5 in. 45
Wheel Diameter 16
00
E
267 mm
CURV
6 1
STEM
0.645 ft2 50
Outlet Area 12
5 3⁄4
SY
0.06 m2
HIS
35
10 4
OF T
00
Maximum BHP at a given RPM (RPM/3127)3 12
⁄
T
8
LEF
Maximum KW at a given RPM (RPM/3448)3 3 1⁄3 30
00
THE
6 14
⁄
Maximum RPM 4500
TO
2 25
00
CT
4
LE
200
RPM x 2.75 ft/min.
SE
1 0
Tip Speed
T
2
NO
150
RPM x 0.014 m/s DO
0
0 0
0 5 10 15 20 25 30
Imperial data - Metric data
Volume (cfm x 100)
0 5 10 15 20 25 30 35 40 45 50
Volume (m3/hr x 100)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
44
®
12 USF-400 - BI
12
5 71⁄2
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10 3
12.25 in.
Wheel Diameter
311 mm 20 8
VE
Static Pressure (in. wg)
42
2
CUR
70
0.86 ft2
TEM
Outlet Area
0.08 m2 1
6 1 ⁄2
38
00
SYS
15
HIS
Maximum BHP at a given RPM (RPM/2347)3 32
T
1
74
OF
Maximum KW at a given RPM (RPM/2588)3 10 4 3⁄4
EFT
28
EL
00
TH
1
⁄2
Maximum RPM 4270
TO
1
⁄3 23
00
5 2 1⁄4
CT
RPM x 3.21 ft/min.
LE
180
SE
Tip Speed 0
T
RPM x 0.016 m/s NO 130
0
DO
0 0
0 1 2 3 4 5
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
45
®
13 USF-400 - BI
12
5 71⁄2
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
13.5 in.
Wheel Diameter 3 38
75
343 mm
E V
20 8
CUR
Static Pressure (in. wg)
1.05 ft2
TEM
Outlet Area 2 34
00
SYS
0.10 m2 15 6
HIS
11⁄2
29
T
Maximum BHP at a given RPM (RPM/3242)3 71
OF
EFT
Maximum KW at a given RPM (RPM/3574)3 10 4
1
EL
25
34
⁄ 00
TH
Maximum RPM 3875
TO
1
⁄2 210
0
CT
5 2 1⁄3
LE
RPM x 3.53 ft/min. 170
SE
0
Tip Speed
T
O
N 1200
RPM x 0.018 m/s DO
0 0
0 1 2 3 4 5 6
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
46
®
15 USF-400 - BI
12
71⁄2 10
RPM
HP
5
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
15 in.
Wheel Diameter
381 mm 20
e
Static Pressure (Pa x 100)
8 34
cur v
Static Pressure (in. wg)
3 88
1.29 ft2
m
Outlet Area
yste
0.12 m2
31
15 6 2 00
is s
(RPM/1675)3
f th
Maximum BHP at a given RPM 11⁄2 26
74
ft o
Maximum KW at a given RPM (RPM/1847)3 10 4
le
1 23
the
00
3
⁄4
Maximum RPM 3488
to
19
00
ct
12
⁄
5 2
e le
RPM x 3.93 ft/min.
13
⁄ 150
ts
0
Tip Speed
no
1100
RPM x 0.020 m/s Do
0 0
0 1 2 3 4 5 6 7
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
47
®
16 USF-400 - BI
12
71⁄2 10 15
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
5
16.5 in.
Wheel Diameter
VE
419 mm 20 8
CUR
Static Pressure (in. wg)
31
1.57 ft2
EM
71
3
Outlet Area
YST
0.15 m2
SS
15 6 28
00
THI
Maximum BHP at a given RPM (RPM/1426)3 2
OF
24
EFT
31
(RPM/1576)3
1
Maximum KW at a given RPM 10 4 1 ⁄2
EL
21
TH
1 00
Maximum RPM 3171
TO
3
⁄4
CT
17
5 2 00
LE
1
⁄2
RPM x 4.32 ft/min.
SE
14
00
Tip Speed
T
NO
RPM x 0.022 m/s DO
100
0
0 0
0 1 2 3 4 5 6 7 8 9
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10 12 14
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
48
®
18 USF-400 - BI
12
71⁄2 10 15
5 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
18.25 in.
Wheel Diameter
464 mm 20 8 3
27
RVE
1.92 ft2
CU
Outlet Area 24
TEM
0.18 m2 15 6 2
00
S
SY
(RPM/1206)3
HIS
Maximum BHP at a given RPM 12
1⁄ 20
99
FT
Maximum KW at a given RPM (RPM/1330)3
TO
10 4
1 18
EF
00
EL
Maximum RPM 2738
TH
150
TO
0
5 2
T
EC
RPM x 4.78 ft/min. 120
EL
0
Tip Speed NO
T
S
900
RPM x 0.024 m/s DO
0 0
0 2 4 6 8 10
Imperial data - Metric data
Volume (cfm x 1000)
0 2 4 6 8 10 12 14 16
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
49
®
20 USF-400 - BI
12
71⁄2 10 15
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10 5
20 in.
Wheel Diameter 24
508 mm 20 8 98
RVE
2.3 ft2 3
CU
Outlet Area 22
00
0.21 m2
M
15 6
STE
2
SY
Maximum BHP at a given RPM (RPM/1035)3 19
15
IS
TH
11⁄2
Maximum KW at a given RPM (RPM/1141)3 10 4
OF
17
00
FT
1
LE
Maximum RPM 2498
E
34
⁄ 140
TH
0
TO
5 2
110
RPM x 5.24 ft/min.
CT
0
LE
Tip Speed T
SE
800
RPM x 0.027 m/s DO
NO
0 0
0 2 4 6 8 10 12
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
50
®
22 USF-400 - BI
12
10 15 20
71⁄2 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
22.25 in.
Wheel Diameter 5
22
565 mm 20 8 46
VE
Static Pressure (in. wg)
CUR
2.85 ft2 20
Outlet Area
EM
00
0.26 m2
T
15 6 3
SYS
HIS
Maximum BHP at a given RPM (RPM/867)3 17
22
FT
2
(RPM/956)3
TO
Maximum KW at a given RPM 10 4
11⁄2 15
EF
00
EL
Maximum RPM 2246
TH
1 130
0
TO
5 2
CT
110
0
RPM x 5.83 ft/min.
LE
SE
900
Tip Speed NO
T
RPM x 0.030 m/s DO
0 0
0 2 4 6 8 10 12 14 16
Imperial data - Metric data
Volume (cfm x 1000)
0 5 10 15 20 25
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
51
®
24 USF-400 - BI
12
10 15 20 25
RPM
HP
71⁄2 Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
24.5 in.
Wheel Diameter
622 mm
VE
20 8 5
C UR
Static Pressure (in. wg)
20
3.45 ft2
48
TEM
Outlet Area
0.32 m2
SYS
15 6
18
3
HIS
00
(RPM/750)3
T
Maximum BHP at a given RPM
OF
15
2 70
(RPM/827)3
EFT
Maximum KW at a given RPM 10 4
EL
11⁄2
13
TH
00
Maximum RPM 2048
TO
11
CT
5 2 00
LE
RPM x 6.41 ft/min. 90
SE
0
Tip Speed
T
O
N 70
RPM x 0.033 m/s DO
0
0 0
0 5 10 15 20 25
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
52
®
27 USF-400 - BI
12
15 20 25
10 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
71⁄2
27 in.
Wheel Diameter
686 mm 20 8
18
RVE
59
4.19 ft2 5
CU
Outlet Area
m2
M
0.39 15 6
STE
16
00
SY
Maximum BHP at a given RPM (RPM/638)3 3
HIS
14
25
FT
Maximum KW at a given RPM (RPM/703)3 10 4
TO
2
EF
12
00
EL
11⁄2
Maximum RPM 1859
TH
10
TO
00
5 2
CT
RPM x 5.83 ft/min. 800
LE
Tip Speed OT
SE
600
RPM x 0.030 m/s DO
N
0 0
0 5 10 15 20 25
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
53
®
30 USF-400 - BI
12
20 40
25 30
15 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
10
30 in.
Wheel Diameter 16
762 mm 20 8 71⁄2
88
VE
Static Pressure (in. wg)
CUR
5.17 ft2
TEM
Outlet Area
0.48 m2 14
SYS
15 6 5 50
HIS
Maximum BHP at a given RPM (RPM/528)3 12
FT
79
TO
(RPM/582)3
3
Maximum KW at a given RPM 10 4
EF
110
EL
2 0
TH
Maximum RPM 1688
TO
900
5
CT
2
LE
RPM x 7.85 ft/min. 700
SE
Tip Speed
T
NO
RPM x 0.040 m/s DO
500
0 0
0 5 10 15 20 25 30
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40 50
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
54
®
33 USF-400 - BI
12
20 25 30 40
RPM
15
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10
33 in.
Wheel Diameter 10
838 mm 20
15
E
8
URV
Static Pressure (in. wg)
6.26 ft2
C
12
7⁄
EM
Outlet Area 13
0.58 m2
YST
50
15 6
S
HIS
5
Maximum BHP at a given RPM (RPM/451)3
T
11
OF
63
(RPM/497)3
T
Maximum KW at a given RPM 10 4
EF
3 10
EL
00
TH
Maximum RPM 1517 2
TO
850
CT
5 2
LE
700
RPM x 8.64 ft/min.
SE
Tip Speed
T
550
NO
RPM x 0.044 m/s DO
0 0
0 5 10 15 20 25 30 35
Imperial data - Metric data
Volume (cfm x 1000)
0 10 20 30 40 50
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
55
®
36 USF-400 - BI
12
20 25 30 40 50
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
25 10 15
36.5 in.
Wheel Diameter
927 mm 20 8 13
VE
71
CUR
10
7.66 ft2
TEM
Outlet Area
0.71 m2 1 12
SYS
15 6 7 ⁄2 00
HIS
Maximum BHP at a given RPM (RPM/381)3
FT
10
5 51
TO
Maximum KW at a given RPM (RPM/420)3 10 4
EF
90
EL
3 0
TH
Maximum RPM 1371
TO
750
CT
5 2
LE
RPM x 9.56 ft/min. 600
SE
Tip Speed
T
NO 450
RPM x 0.049 m/s DO
0 0
0 5 10 15 20 25 30 35 40 45
Imperial data - Metric data
Volume (cfm x 1000)
0 20 40 60
Volume (m3/hr x 1000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
56
®
40 USF-400 - BI
10
20 25 30 40 50 60
RPM
HP
15 12 Density 0.075 lb/ft3
21 Density 1.2 kg/m3
20 8
40.25 in.
Wheel Diameter 11
00
1022 mm 10
RVE
15 6
9.31 ft2
CU
Outlet Area 71⁄2
M
0.86 m2 93
STE
6
SY
(RPM/326)3
HIS
Maximum BHP at a given RPM 10 4 5
FT
80
0
Maximum KW at a given RPM (RPM/359)3
TO
EF
3
EL
Maximum RPM 1221 65
TH
0
5 2
TO
T
EC
RPM x 10.54 ft/min. 500
EL
Tip Speed NO
T
S
40
RPM x 0.054 m/s DO
0
0 0
0 1 2 3 4 5
Imperial data - Metric data
Volume (cfm x 10000)
0 2 4 6 8
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
57
®
44 USF-400 - BI
10
25 30 40 50 60 75
20 RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
20 8 15
44.5 in.
11
05
Wheel Diameter
1130 mm
RVE
Static Pressure (Pa x 100)
10
CU
15 6 10
11.39 ft2
M
Outlet Area
STE
1.06 m2
SY
71⁄2 84
HIS
7
(RPM/276)3
FT
Maximum BHP at a given RPM 10 4
TO
5
Maximum KW at a given RPM (RPM/304)3
EF
70
EL
0
TH
Maximum RPM 1105 60
TO
0
5 2
CT
LE
50
0
RPM x 11.65 ft/min.
SE
T
Tip Speed DO
NO 40
0
RPM x 0.059 m/s
0 0
0 1 2 3 4 5 6
Imperial data - Metric data
Volume (cfm x 10000)
0 2 4 6 8 10
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
58
®
49 USF-400 - BI
10
25 30 40 50 60 75 100
RPM
HP
Density 0.075 lb/ft3
Density 1.2 kg/m3
8 20
10
20
03
49 in.
Wheel Diameter
1245 mm 15
RVE
87
5
15 6
13.8 ft2
CU
Outlet Area
EM
1.28 m2 10
ST
76
9
SY
HIS
Maximum BHP at a given RPM (RPM/235)3 10 4
71⁄2
T
OF
(RPM/259)3
65
Maximum KW at a given RPM 0
T
5
EF
EL
55
Maximum RPM 1003
TH
0
TO
5 2
T
450
EC
RPM x 12.83 ft/min.
EL
S
Tip Speed NO
T 35
0
RPM x 0.065 m/s DO
0 0
0 1 2 3 4 5 6 7
Imperial data - Metric data
Volume (cfm x 10000)
0 2 4 6 8 10
Volume (m3/hr x 10000)
The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not
include the effects of appurtenances (accessories). Power ratings (BHP/kW) do not include transmission losses. The sound power level ratings shown are
in decibels, referred to 10-12 watts calculated per AMCA Standard 301. The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301. Values shown are for inlet, LwiA, and outlet, LwoA sound power levels for installation type B: Free inlet, Ducted outlet. Outlet ratings include the
effects of duct end correction.
59
®
The following example explains the model number code for
both series of centrifugal fans.
USF - 2 06 - 10 - BI - I - A 30 - X
USF Certification
200, 300, 400 None
Fan Size X - UL/cUL 705 Listed (Electrical)
06 through 49 G - UL/cUL 762 Listed (Grease Exhaust)
10 Motor HP
Blade 4 = 1/4 15 = 11⁄2 100 = 10
BI-Backward Inclined 3 = 1/3 20 = 2 150 = 15
5 = 1/2 30 = 3 200 = 20
AF-Airfoil 7 = 3/4 50 = 5 300 = 30
10 = 1 75 = 71⁄2 400 = 40
Fan Class
Motor RPM
0, I, II, USF-400 only
M = 3500 B = 1170
A = 1770 J = 1425
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.
Prepared to Support
Green Building Efforts
Greenheck P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com