Professional Documents
Culture Documents
FEBRUARY 2023
TABLE OF CONTENTS
2
CHAPTER IV – CONCLUSION ............................................................................... 71
REFERENCES ........................................................................................................ 73
3
CHAPTER I – INTRODUCTION
Senior citizens are social demographic based on age, which usually refers to
elderly people, especially those who are retired and over sixty years of age. It is said
that elderly people living in urban cities are having a difficulty in experiencing a good
quality of air that they breathe. However, the main issue here is not bounded only to
those living in urban areas. It includes people living from far and different places who
are coming to the city for a certain transaction for instance. As we get older, regulating
our body’s core temperature is a challenge. This is also due to the increasing number
of population and rising of numerous infrastructures, in which good air quality is now a
dilemma.
Government office is one example of an establishment that should be designed
properly in order to meet the desired thermal comfort, especially when it is intended
for public utilization. Just like any other offices, this establishment that is to be designed
for a centralized air-conditioning possesses various thermal load variability because of
its purpose and overall capacity, which contains numerous spaces or rooms that varies
with its function. Moreover, in order for one to be effective and efficient, a designer
must also consider the size of the building to be air-conditioned, its geographical
location, the insulation and heat transmission from the roof down to the walls, the
building’s overall lighting to be utilized, the number of occupants, including the
appliances and electronic devices since the abovementioned contribute heat and may
distort the overall function and efficiency of the said air-conditioning systems. Since
again, such spaces have discrete number of lighting, occupancy, and electronic
devices or appliances used, including that of the activities done by the occupants of
the said building.
The number of lighting for a typical government office is somehow innumerable.
Considering its primary occupants, the need for a satisfactory amount of luminance is
quite necessary for some reasons. As the number of lightings increases, its heat loss
also increases. That is why in order to effectively minimize its effect, the utilization of
right lighting materials should be properly selected as to also balance both its efficiency
and cooling load factors.
Additionally, the number of appliances and other electronic devices as well as
various human activities contributes to the overall cooling load of the building. It is built
to accommodate numerous occupants all in certain periods, for instance. It contains
4
rooms and offices that vary in size, in which it is believed to utilize several electronic
components that directly affect both the sensible and latent heat load of the building.
The main purpose of an air-conditioner is to provide cold air in an enclosed
space by literally eliminating the heat and humidity of said space. Cooling loads
composed of the abovementioned factors should actually be removed in order to
maintain a desirable temperature. In order achieve the sole purpose of air-conditioning,
proper calculations of the cooling loads should be done. Aside from the building’s
cooling load, the ducting pipe and air handling unit, which are one of the vital
components, must also be specified for a centralized air-conditioning systems.
Providing air-conditioning to offices make it more comfortable to the occupants, at the
same time ensuring a good air quality. All of these considerations are essential to
effectively design a centralized air-conditioning system for a three-storey senior citizen
and OCMS (Ormoc City Medical Society) office.
Providing elderly people all the necessities that they need is being regulated
by the government. Constructing an office intended for them is included in the said
republic act. It is in line as we are living in a tropic country where temperature is
expectedly uncomfortable, especially during summer. Relative to that, adding an air-
conditioning system minimizes the discomfort that the occupants perceive, most
especially that they are sensitive with the air quality that they respire.
5
abovementioned contributing factors, and including heat transmission from
outside.
4. Design a ducting system in accordance to the calculated cooling load of the
building.
5. Design a cooling system that would adhere to the cooling requirement of the
condenser of the refrigeration system.
6. Design a piping system that carries both water and refrigerant fluids starting
from the AHU to the refrigeration system, then to the cooling system, which
includes the make-up water system.
7. Determine the appropriate machinery and equipment required for each system
such as the refrigeration, cooling, piping, and ducting, ensuring that it would
suffice to the prescribed air-conditioning design specifications.
The design study is governed by the following scope and limitations as declared
below:
6
9. The design study makes use of the standard vapor compression cycle for its
refrigeration system.
10. The design study does not anymore include insulation materials to be applied
to the building’s wall for simplicity.
11. The equipment and machine specifications to be utilized in the design such as
the AHU, cooling tower, evaporator, condenser, pump, diffuser, and etc.,
including that of the material specifications such as on the sheet metal, water
and refrigerant pipes, are all dependent upon its availability on the internet.
Moreover, all the materials and equipment are taken from online electronic
catalogues and brochures.
The steps and undertakings configured in this design study, in conjunction with
all the data and specifications intentionally created for a design of a centralized air-
conditioning system, are expected to benefit the following demographic;
Engineers – The outcome of this design study would also benefit engineers,
especially those who are in the field of air-conditioning, refrigeration, and the likes in
achieving and acquiring more knowledge particularly in the design and innovative
technologies relating to centralized air-conditioning system.
Consumers – The result of this design study would provide an idea to the
consumers with regards to the proper selection of air-conditioning systems appropriate
7
for their desired space or room to be air-conditioned in view of its economy, efficiency,
and durability.
Air-conditioning is a process such that it conditions the air in order to meet the
desired thermal comfort of the occupants in an indoor space. Its function is to maintain
a level of personal comfort by sustaining a certain temperature within that room for
instance. The process involves cooling and dehumidifying the re-circulated air entering
an enclosed space through the utilization of a cooling coil or an air washer. This
happens when the outside temperature and humidity increases especially during
summer time. The process observes the constant room sensible heat factor line
(RSHF), which represents the psychrometric process of the supply air within the
conditioned space and is the ratio of the room sensible heat (RSH) and room total heat
(RTL), which is also the sum of the RSH and the room latent heat (RLH) as represented
in the equation below.
𝑅𝑆𝐻 𝑅𝑆𝐻
𝑅𝑆𝐻𝐹 = =
𝑅𝑇𝐻 𝑅𝑆𝐻 + 𝑅𝐿𝐻
The RSHF line in the Psychrometric chart intersects with the saturation line
with the corresponding temperature as the air-conditioning system’s apparatus dew
point temperature 𝑡𝐴𝐷𝑃 as can be seen in Figure 1.
Figure 1. Locus of Supply Air States for Cooling and Apparatus Dew Point
8
The locus of all possible supply air condition is represented by line i-S. Note
that these possible states do not deviate, either be higher or lower from the 𝑡𝐴𝐷𝑃 that
would meet the given condition line.
Conduction is the transfer of heat through a solid, which means that it occurs
when two objects directly have a contact with each other. It is the most straightforward
amongst the three heat transfer methods. Additionally, conduction is one of the
reasons for constructing walls with insulation. Meanwhile, unlike in conduction,
convection does not require any direct contact between objects. It occurs when a fluid,
either a vapor or liquid, creates a motion in which the fluid’s heat energy moves with it
at the same time. Say the heat energy that comes from the outside air passes through
a leaky window into a building is an example of heat transfer via convection. Radiation,
on the other hand, utilizes neither of the two that were in the abovementioned modes
of heat transfer. Instead, radiant heat transfer is said to occur through electromagnetic
waves in the air. Accordingly, if all the three types of heat namely, conduction,
convection, and radiation occur at the same time, the heat transfer calculation can be
simplified into a single equation below. (Stoecker and Jones’ Refrigeration and Air-
conditioning 2nd ed.)
𝑞 = ℎ𝐴∆𝑡
Where,
9
given that the h for radiation is expressed as
Where:
Shown in Figure 1.2a is the linearized form of equations for the three modes of
heat transfer, which is utilized to calculate the thermal resistance. The thermal
resistance, on the other hand, is derived using the concept of Ohm’s Law taking into
consideration q as the current, ∆𝑡 as the potential difference, and 𝑅𝑇 as the resistance
as shown in Figure 2.
b
a
Figure 2. (a) Linearized Heat Transfer Rate Equation, (b) Thermal Resistance, and (c) Heat Transfer
from One Room to Another
10
1.6.3 Standard Vapor Compression Cycle
11
1.6.4 Bernoulli Principle
Bernoulli equation implies that when the velocity of a fluid increases, its
pressure decreases. Basically, it is estimation between pressure, velocity, and
elevation, which is valid only to stable and consistent regions having negligible
frictional effect as shown in Figure 4. By employing the concept of the conservation of
linear momentum, the resulting Bernoulli equation is expressed as
𝑃 𝑣2
+ + 𝑔𝑍 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝜌 2
where:
This equation considerably aids to the ducting design computation since the
ducts permit the air fluid to move within with considerable pressure, temperature,
elevation, viscosity and compressibility. It is also a method for figuring out how big the
ducts should be and how much air should flow through each room or space.
12
1.6.5 Pressure Drop in Rectangular Ducts
The most popular ducting style is rectangular since it requires less installation
area. Because none of the ducts were manufactured with an absolute surface polish,
they all had a significant amount of surface roughness, which increased frictional
resistance and head losses. It is said that a rectangular duct loses pressure at a rate
that is noticeably higher than a round one of the same volume. In rectangular systems,
the pressure loss increases with increasing aspect ratio. It is also challenging to
measure the turbulent friction factor accurately in such ducts. The pressure drop takes
into account the inverse relationship with conduit diameter as well as the proportional
relationships with frictional coefficient, fluid velocity, and fluid density for a particular
rectangular duct. It is expressed,
𝐿 𝑣2
∆𝑝 = 𝑓 ( ) (𝜌)
𝐷𝑒𝑞 2
where:
2𝑎𝑏
= 𝑎+𝑏 , where a and b are the width and length of the inside duct
The equal friction approach as shown in Figure 6, is one of the techniques used
to scale up ducts for multi-branch duct systems. By creating a constant pressure loss
13
per unit of duct length, this generates a preliminary estimate for duct sizing. Due to the
smaller duct and lower cost, this approach gives a better design than the others. The
steps in this design method are as follows:
14
CHAPTER II – REVIEW OF RELATED LITERATURE
2.1 Introduction
15
2.2 Air-conditioning system
The study of the thermodynamic properties of moist air is the subject of the
scientific discipline known as psychometrics. When designing air conditioning systems,
the first challenge is to understand the components that affect the building's heat gain
or heat loss; this process is called heating or cooling load estimation. Once this is
16
complete, the next challenge is to design air conditioning systems that meet the
requirements of the building. The reactive challenge consists of "designing" controlled
processes in order to keep the intended condition or state-point within the occupied
space. These controlled processes are typically referred to as the system processes
that use psychometrics.
A graphic representation of the status or condition of the air at any given time
is provided by the Psychrometric Chart. It illustrates the characteristics of air, including
dry bulb temperature (shown by vertical lines), wet bulb temperature (represented by
lines that slope gently downhill to the right), dew point temperature (represented by
horizontal lines), and relative humidity (represented by circles) (the curves on the
chart). Using the chart, you can discover the other two of these characteristics if you
have any two of them already. The usefulness of the chart extends beyond the simple
representation of these fundamental properties; it also describes the moisture content
(scale on the far right), energy content (scale on the outer diagonal on the upper left),
specific volume (lines sloping sharply downward to the right), and specific volume
(lines sloping sharply downward to the right), among other aspects of the air. A
psychrometric chart is helpful in calculating and analyzing the amount of effort and
energy that is transferred during the many processes that are involved in air
conditioning. When it comes to real-world applications, the psychrometric analysis
performed by HVAC contractors that is performed most frequently entails monitoring
the dry and wet bulb temperatures of air that is coming into and going out of a cooling
coil. If these temperatures as well as the volumetric air flow rate (CFM) through the coil
of an appliance are known, it is possible to verify the appliance's cooling capacity. It is
possible to locate two spots on a psych chart and read the corresponding enthalpy
17
values for them by making use of the dry bulb temperature and the wet bulb
temperature information.
Regarding the design of HVAC systems, there are many papers and
evaluations available. Chapter 4 of the 2016 ASHRAE Handbook on HVAC Systems
and Equipment contains some of the relevant material. This chapter is titled "Air
Handling and Distribution." According to ASHRAE, the fundamental concept of an all-
air system is to supply air to a room at conditions such that the sensible and latent heat
gains in the space, when absorbed by supply air flowing through the space, will bring
the air to the desired room conditions. This is accomplished by supplying air at
conditions such that the air flows through the space.
18
CHAPTER III – METHODOLOGY
3.1 Introduction
19
3.2 Building Design
As this paper is being made, the building is being constructed at Brgy. Cogon-
Combado, Ormoc City, Leyte. Specifically, it is located at these coordinates:
11.024014 N, 124.5998996 E. The area is generally urbanized as it lies within the city
capital. It is surrounded by several other commercial buildings such as the city DRRMO
and the city hall, but is still surrounded with considerable vegetation scattered over the
general area.
According to data from World Weather Online, the maximum temperatures at
each month of each year from 2009 to September 2022 vary drastically. Throughout
this time period, the location has a maximum registered temperature of around 35 °C,
which occurred on the month of May in 2019. Similar temperature conditions were
observed throughout several days of the same month, but a relative humidity of around
82% was observed during such days on the 15th. Particularly, such conditions were
registered at around 9:00 +GMT8 (World Weather Online, n.d.). Essentially, these are
taken as the external conditions that are considered in determining the overall cooling
load to be dealt with by the system.
20
with tabulated data, as well as being substantially accurate and sufficient for the
purposes of the design.
Here, the process essentially involves determining the external cooling loads,
such as the air infiltration and heat transmission from various sources, especially solar
radiation. Along with these are the internal cooling loads that prevail within the building.
These encompass the heat emitted from lighting, the occupants, and other sources
like electrical equipment. All these essentially comprise the overall cooling load that
the system shall deal with.
As the primary design requirement, the ambient conditions regulated within the
building is determined. According to a study from De La Salle University, the ASHRAE
55 general standard temperature for optimal thermal comfort is around 25 °C.
However, in the same study, it was observed that the preferred temperature in different
office buildings involved a range of values that were lower than the expected standard.
Such values could all be approximated to be more or less 24 °C, in general (Benjamin
A. et. al., 2017). This would be reasonable as the PSME Code also specifies that a
desirable indoor temperature for substantially high outdoor temperatures would be
around 23 to 28 °C. With such, the desired temperature to be maintained inside the
building is set as 24 °C. Moreover, still basing on ASHRAE 55, such temperature
condition is associated with 50% relative humidity (Canadian Centre for Occupational
Health & Safety, 2023).
On the other hand, as established, the outside conditions are based on the
extreme recorded ambient conditions of the location. The set values are essentially
assumed to occur at 9:00 AM, at the time when the peak load might happen.
Specifically, the temperature is 35 °C, with a relative humidity of 82%. All
aforementioned information is presented in Table 1.
21
counted as two light sources with such power rating in the calculation.
Meanwhile, 14-watt square recessed slim downlights are utilized in other,
generally smaller, rooms or spaces, while surface mounted pinlights are utilized
outside. However, as such have less wattage, they are deemed negligible for
the calculations. With that said, the design cooling load is given by,
𝑄 = 3.41(𝑁)(𝑊)(𝐹𝑢𝑙 )(𝐹𝑠𝑎 )(𝐶𝐿𝐹)
where
𝑁 − 𝑛𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑙𝑎𝑚𝑝𝑠 𝑜𝑟 𝑙𝑖𝑔ℎ𝑡 𝑏𝑢𝑙𝑏𝑠
𝑊 − 𝑝𝑜𝑤𝑒𝑟 𝑟𝑎𝑡𝑖𝑛𝑔 𝑖𝑛 𝑊𝑎𝑡𝑡𝑠
𝐹𝑢𝑙 − 𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔 𝑢𝑠𝑒 𝑓𝑎𝑐𝑡𝑜𝑟
𝐹𝑠𝑎 − 𝑠𝑝𝑒𝑐𝑖𝑎𝑙 𝑏𝑎𝑙𝑙𝑎𝑠𝑡 𝑎𝑙𝑙𝑜𝑤𝑎𝑛𝑐𝑒 𝑓𝑎𝑐𝑡𝑜𝑟
𝐶𝐿𝐹 − 𝑐𝑜𝑜𝑙𝑖𝑛𝑔 𝑙𝑜𝑎𝑑 𝑓𝑎𝑐𝑡𝑜𝑟, 𝑏𝑦 ℎ𝑜𝑢𝑟 𝑜𝑓 𝑢𝑠𝑒
Here, the special ballast factor would be 𝐹𝑠𝑎 = 1.18 for each of the 40-
watt lamp fixtures, while 𝐹𝑢𝑙 = 1, as prescribed in ASHRAE 1997 for
commercial applications.
The senior citizen center is set to generally operate at typical office
hours—from 8 AM to 5 PM. However, employees and clients may still occupy
the building beyond such schedules due to other reasons; thus, some
allowance of around 4 hours is considered to account for such circumstances.
With this, the building is assumed to be occupied for 12 hours throughout the
day. Considering the involvement of large windows in the building’s design, the
lights would normally be turned off throughout the morning. However, to
maximize the system’s capacity, as well as to account for other possible
circumstances, it is assumed that all lighting fixtures are turned on and used
throughout the 12 hours of occupancy. Based on Chapter 28 Table 38 of
ASHRAE 1997, the cooling load factor (CLF) of Zone Type C for a full 12 hours
of continuous operation is CLF = 0.95. This is employed together with the other
parameters to obtain the estimated design cooling load for each room. The
overall cooling loads of each floor corresponding to lighting usage are detailed
in Table 2.
22
Office 2 4 40 12 643.81 N/A 0.95 N/A 611.62 N/A
Social Pension Office 8 40 12 1287.62 N/A 0.95 N/A 1223.24 N/A
OSCA Office Lobby 8 40 12 1287.62 N/A 0.95 N/A 1223.24 N/A
OCMS Office Lobby 10 40 12 1609.52 N/A 0.95 N/A 1529.04 N/A
OCMS Office 4 40 12 643.81 N/A 0.95 N/A 611.62 N/A
TOTAL 9480 N/A
Second Floor
Conference Room 16 40 12 2575.23 N/A 0.95 N/A 2446.47 N/A
Function Room 1 24 40 12 3862.85 N/A 0.95 N/A 3669.71 N/A
Function Room 2 24 40 12 3862.85 N/A 0.95 N/A 3669.71 N/A
Clinic 12 40 12 1931.42 N/A 0.95 N/A 1834.85 N/A
Waiting Area and
14 40 12 2253.33 N/A 0.95 N/A 2140.66 N/A
Lobby
TOTAL 13761 N/A
23
The building is predominantly an office building, where clients can
transact with personnel and where its officials and other relevant groups can
congregate. It also includes lavatories, a clinic to provide healthcare services,
and function rooms where meetings and seminars can be held. The variation
is mainly observable at its different floors. The first floor primarily functions as
an office where services are rendered, while the second floor offers spaces that
accommodate other relevant activities.
24
With that, the first floor is essentially identified as an office space.
Moreover, each room is intended for different purposes; thus, further involves
a varying number of people. Based on the Table 3, it is advised to allocate at
least 10 m2 per person in single offices and 1.5 m2 in others, on average. With
this, the number of occupants can be determined simply by dividing the
corresponding values for the total area of every room and the minimum area
per person of such room.
𝑡𝑜𝑡𝑎𝑙 𝑎𝑟𝑒𝑎
𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 =
𝑚𝑖𝑛𝑖𝑚𝑢𝑚 𝑎𝑟𝑒𝑎 𝑝𝑒𝑟 𝑝𝑒𝑟𝑠𝑜𝑛
However, as a design decision, the actual capacity of the room
determined from this is not directly taken as the average number of occupants
at a time. Some allowances are applied to account for circumstances where
more people are operating in the building or in any room than usual. The default
capacity is taken as 60% of the assumed maximum number of occupants of
any room. Thus, the obtained values are still adjusted according to this
condition. With this, the system can still successfully handle a greater—but
rather unlikely—number of occupants in the building.
Then, approximating the number of occupants in the second floor
essentially follows a similar thought-process. It is constituted of meeting and
function rooms and a clinic. Based on the table, it is generally advised to allot
1.5 m2 per person in conference rooms, 0.6 m2 in congregation or assembly
rooms such as the function rooms, and 5 m2 in clinics.
However, some of the rooms already have a set capacity that still has a
tolerance to accommodate slightly more people. Based on such, some of the
values obtained from the calculations are somewhat inaccurate to the actual
conditions of the aforementioned rooms, especially the function rooms and
offices of the department heads. With this, the number of occupants of such
rooms are based on their actual exact capacity instead; nonetheless, the
aforementioned allowances are still applied for good measure.
Now, those occupants are essentially utilizing such rooms and doing
certain activities. In this building, they could simply be doing sedentary or
average activities. With such, heat is gained in the respective rooms according
to the type of activity and the number of hours such is done by the occupants
in the space. Determining the heat gained is based upon the ASHRAE 1997
Chapter 28 Table 3 and 37. With such data, the sensible and latent design
cooling loads can be determined, which is given by,
25
𝑄𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 = 𝑁(𝑄𝑆)(𝐶𝐿𝐹)
𝑄𝑙𝑎𝑡𝑒𝑛𝑡 = 𝑁(𝑄𝐿)(𝐶𝐿𝐹)
where
𝑁 − 𝑛𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑝𝑒𝑜𝑝𝑙𝑒 𝑖𝑛 𝑡ℎ𝑒 𝑠𝑝𝑎𝑐𝑒
𝑄𝑆 − 𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 ℎ𝑒𝑎𝑡 𝑔𝑎𝑖𝑛𝑒𝑑 𝑓𝑟𝑜𝑚 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑐𝑦
𝑄𝐿 − 𝑙𝑎𝑡𝑒𝑛𝑡 ℎ𝑒𝑎𝑡 𝑔𝑎𝑖𝑛𝑒𝑑 𝑓𝑟𝑜𝑚 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑐𝑦
𝐶𝐿𝐹 − 𝑐𝑜𝑜𝑙𝑖𝑛𝑔 𝑙𝑜𝑎𝑑 𝑓𝑎𝑐𝑡𝑜𝑟, 𝑏𝑦 ℎ𝑜𝑢𝑟 𝑜𝑓 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑐𝑦
As established earlier, the senior citizen center is assumed to be
occupied for 12 hours throughout the day. Based on Chapter 28 Table 37 of
ASHRAE 1997, the cooling load factor of Zone Type C for a full 12 hours of
continuous occupancy is CLF = 0.96. This is employed together with the other
parameters to obtain the estimated design cooling load for each room. The
overall cooling loads of each floor corresponding to each activity of the
occupants are detailed in Table 4.
First Floor
Seated,
Dept. Head 12.75
Single
10 2 4 very light 70 50 0.96 0.96 254.80 182.00
Office 1 Office
work
Seated,
Dept. Head 16.00
Single
10 2 4 very light 70 50 0.96 0.96 254.80 182.00
Office 2 Office
work
Office
Office 1 65.25 Office 10 7 8
work
70 60 0.96 0.96 548.10 469.80
Office Seated,
Office 2 12.00 Meeting 1.5 8 10 very light 70 50 0.96 0.96 672.00 480.00
Room work
Social
Office
Pension 21.00 Office 4.65 5 6
work
70 60 0.96 0.96 379.35 325.16
Office
OSCA Office 48.45 Office 4.65 10 13
Seated at
67 33 0.96 0.96 837.72 412.61
Lobby rest
OCMS 53.45 Office 4.65 11 14
Seated at
67 33 0.96 0.96 924.17 455.19
Office Lobby rest
OCMS 9.61
Single
10 1 2
Seated at
67 33 0.96 0.96 103.04 50.75
Office Office rest
Second Floor
Seated,
Conference 29.23
Meeting
1.5 19 24 very light 70 50 0.96 0.96 1636.88 1169.20
Room Room
work
Function —
Lecture
— 60 75
Seated at
67 33 0.96 0.96 4824.00 2376.00
Room 1 Room rest
Function —
Lecture
— 60 75
Seated at
67 33 0.96 0.96 4824.00 2376.00
Room 2 Room rest
Moderate
Clinic — Clinic — 5 6 80 80 0.96 0.96 480.00 480.00
work
Waiting Area 67.20 Office 4.65 14 18
Seated at
67 33 0.96 0.96 1161.91 572.28
and Lobby rest
26
3.4.3 Air Infiltration Cooling Load Calculation
The premise here essentially involves air infiltrating the building, which
basically introduces heat from the outside and into the volume of the rooms.
With this, the calculation deals with the rooms that bound and enclose the
inside environment. This basically only considers those rooms wherein one or
two of its walls, boundaries, or surfaces are in direct contact with the air from
the outside environment and can essentially serve as potential passages for its
infiltration.
With the inside conditions, as established, the temperature is set as
24°C with a relative humidity of 50%. With this, the humidity ratio is w = 0.0093.
On the other hand, while the outside conditions are 35°C with a relative
humidity of 82%, the humidity ratio is thus, w = 0.02968.
The sensible and latent design cooling loads are determined by,
𝑉
𝑄𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 = 𝑁 ( ) (𝑐𝑝𝑎𝑖𝑟 )(𝑡𝑜 − 𝑡𝑖 )(𝐶𝐿𝐹)
𝑣
𝑉
𝑄𝑙𝑎𝑡𝑒𝑛𝑡 = 𝑁 ( ) (ℎ𝑓𝑔𝑎𝑖𝑟 )(𝑤𝑜 − 𝑤𝑖 )(𝐶𝐿𝐹)
𝑣
where
𝑁 − 𝑛𝑢𝑚𝑏𝑒𝑟 𝑜𝑓 𝑎𝑖𝑟 𝑐ℎ𝑎𝑛𝑔𝑒 𝑝𝑒𝑟 ℎ𝑜𝑢𝑟
𝑉 − 𝑣𝑜𝑙𝑢𝑚𝑒 𝑜𝑓 𝑟𝑜𝑜𝑚
𝑣 − 𝑠𝑝𝑒𝑐𝑖𝑓𝑖𝑐 𝑣𝑜𝑙𝑢𝑚𝑒 𝑜𝑓 𝑜𝑢𝑡𝑠𝑖𝑑𝑒 𝑎𝑖𝑟
𝑡𝑜 − 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑜𝑓 𝑜𝑢𝑡𝑠𝑖𝑑𝑒 𝑎𝑖𝑟
𝑡𝑖 − 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑜𝑓 𝑖𝑛𝑠𝑖𝑑𝑒 𝑎𝑖𝑟
𝑤𝑜 − ℎ𝑢𝑚𝑖𝑑𝑖𝑡𝑦 𝑟𝑎𝑡𝑖𝑜 𝑜𝑓 𝑜𝑢𝑡𝑠𝑖𝑑𝑒 𝑎𝑖𝑟
𝑤𝑖 − ℎ𝑢𝑚𝑖𝑑𝑖𝑡𝑦 𝑟𝑎𝑡𝑖𝑜 𝑜𝑓 𝑖𝑛𝑠𝑖𝑑𝑒 𝑎𝑖𝑟
Here, 𝑐𝑝𝑎𝑖𝑟 = 1, ℎ𝑓𝑔𝑎𝑖𝑟 = 2444.7 𝑘𝐽/𝑘𝑔, and 𝑣 = 0.91 𝑚3 /𝑘𝑔 for the
outside conditions. Then, based on ASHRAE 1997, CLF = 1 in this case,
whether sensible or latent, for a commercial building. Meanwhile, the number
of air changes per hour is given by,
𝑁 = 𝑎 + 𝑏(𝑉𝑒𝑙) + 𝑐(𝑡𝑜 − 𝑡𝑖 )
where
𝑉𝑒𝑙 − 𝑤𝑖𝑛𝑑 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦
According to the PSME code, the wind velocity shall not exceed
0.254m/min. To maximize the conditions, Vel = 0.254 m/min or around
0.004233 m/s. Then, the coefficients a, b, and c are experimentally determined
constants. Exact values for such are based on the typical values presented in
27
Table 4-5 in Refrigeration and Air Conditioning by Stoecker and Jones. The
senior citizen center generally has a tight construction; thus, a = 0.15, b = 0.010,
and c = 0.007. The overall cooling loads are detailed in Table 5.
28
Figure 7. Sun Position
Realistically, given the organization of the city and the features of that
particular area, the orientation of the building itself deviates away from facing
north. Its supposed front side and essentially its main entrances face towards
the southwest direction. With that and with the sunlight coming from the
northeast, two un-sunlit areas can be observed—the front side and left side of
the building, wherein the left side faces NW and the front faces SW. On the
other hand, the sunlit areas include the rear side, right side, and the roof,
wherein the rear faces towards NE and the right faces SE.
29
Here, the cooling loads would vary with the extent of exposure to
sunlight and with the type of material of the walls or boundaries that are
involved. The building features various glass doors and windows at the front
and rear. These are simply regular single horizontal sheets of glass. The walls
are around 150-mm-thick concrete slabs.
Wall
Un-sunlit Heat Instantaneous Cooling Design Cooling
Material of Dimensions
Area Transfer Load Load Factor Load
Unexposed Area Wall (meters) ∆T
(sq. Coefficient
or Surface
L H meter) (W/m2-K) SH LH SH LH SH LH
First Floor
OSCA Office &
glass 7.00 2.40 16.80 7.9 11.00 1459.92 N/A 1 N/A 1459.92 N/A
Lobby
Front
OCMS Office glass 3.60 2.40 8.64 7.9 11.00 750.82 N/A 1 N/A 750.82 N/A
Side
OCMS Office
glass 4.40 2.40 10.56 7.9 11.00 917.66 N/A 1 N/A 917.66 N/A
Lobby
Dept. Head
concrete 4.25 3.60 15.30 3.9 11.00 656.37 N/A 1 N/A 656.37 N/A
Office 1
Office 1 concrete 1.75 3.60 6.30 3.9 11.00 270.27 N/A 1 N/A 270.27 N/A
Left
Side
OCMS Office concrete 2.64 3.60 9.50 3.9 11.00 407.72 N/A 2 N/A 815.44 N/A
OCMS Office
concrete 2.38 3.60 8.57 3.9 11.00 367.57 N/A 1 N/A 367.57 N/A
Lobby
TOTAL 3027 N/A
Second Floor
Conference
glass 7.45 2.40 17.88 7.9 11.00 1553.77 N/A 1 N/A 1553.77 N/A
Front Room
Side
Function Room 2 glass 5.00 2.50 12.50 7.9 11.00 1086.25 N/A 1 N/A 1086.25 N/A
30
Waiting Area and
glass 4.50 2.50 11.25 7.9 11.00 977.63 N/A 1 N/A 977.63 N/A
Lobby
Stairway concrete 4.00 9.00 36.00 3.9 11.00 1544.40 N/A 1 N/A 1544.40 N/A
Conference
concrete 3.95 3.60 14.22 3.9 11.00 610.04 N/A 1 N/A 610.04 N/A
Left Room
Side
Function Room 1 concrete 6.00 3.60 21.60 3.9 11.00 926.64 N/A 1 N/A 926.64 N/A
31
with summer conditions in the month of July, which is substantially unfit
for this design. An alternative is available—at 32° north latitude in May—
which evidently still has significant deviation; nonetheless, the data
based on this is the closest that is available. Essentially, the design
cooling load involving sunlit glass surfaces is assumed at 32° latitude.
From there, another issue arises. Values for SCL that are based
at 32° latitude are technically also not available. What are available are
other relevant values that are employed in a slightly different process,
which still yields the design cooling load at sunlit glass surfaces. The
alternative equation involves the use of the solar heat gain factor
(SHGF) and a different cooling load factor. This was previously the
default process to be employed in estimating the design cooling load at
sunlit areas, but due to some intricacy, the ASHRAE replaced it with the
SCL method to streamline the process. Overall, this alternative is given
by,
𝑄 = 𝐴(𝑆𝐶)(𝑆𝐻𝐺𝐹)(𝐶𝐿𝐹)
where
𝑆𝐻𝐺𝐹 − 𝑠𝑜𝑙𝑎𝑟 ℎ𝑒𝑎𝑡 𝑔𝑎𝑖𝑛 𝑓𝑎𝑐𝑡𝑜𝑟
From Table 4-10, in the month of May and at 32° north latitude,
SHGF = 530 W/m2 for glass facing NE/NW and SHGF = 480 W/m2 for
glass facing SE/SW. Then, from Table 4-12, for glass with interior
shading, at north latitudes, and at 0900 h solar time, CLF = 0.58 for
glass facing NE and CLF = 0.81 for glass facing SE. The overall cooling
loads of each floor corresponding to each sunlit surface are detailed in
Table 7.
First Floor
concrete 4.00 3.60 8.76 3.9 — — 22.00 751.61 N/A 1 N/A 751.61 N/A
Office 2
glass 2.35 2.40 5.64 7.9 480 0.25 22.00 1657.03 N/A 0.81 N/A 1342.20 N/A
Right
Side (SE) Social
concrete 4.20 3.60 15.12 3.9 — — 22.00 1297.30 N/A 1 N/A 1297.30 N/A
Pension
OSCA
Office & concrete 3.90 3.60 14.04 3.9 — — 22.00 1204.63 N/A 1 N/A 1204.63 N/A
Lobby
Dept. Head
concrete 3.00 3.60 10.80 3.9 — — 22.00 926.64 N/A 1 N/A 926.64 N/A
Office 1
Dept. Head
concrete 4.00 3.60 14.40 3.9 — — 22.00 1235.52 N/A 1 N/A 1235.52 N/A
Office 2
Back Side
concrete 7.50 3.60 20.25 3.9 — — 22.00 1737.45 N/A 1 N/A 1737.45 N/A
(NE)
Office 1
glass 4.50 1.50 6.75 7.9 530 0.25 22.00 2067.53 N/A 0.58 N/A 1199.16 N/A
Office 2 concrete 7.00 3.60 25.20 3.9 — — 22.00 2162.16 N/A 1 N/A 2162.16 N/A
32
TOTAL 11857 N/A
Second Floor
Function
concrete 11.20 3.60 40.32 3.9 — — 22.00 3459.46 N/A 1 N/A 3459.46 N/A
Right Room 2
Side (SE)
Clinic concrete 2.00 3.60 7.20 3.9 — — 22.00 617.76 N/A 1 N/A 617.76 N/A
concrete 12.00 3.60 31.95 3.9 — — 22.00 2741.31 N/A 1 N/A 2741.31 N/A
Function
Room 1
glass 7.50 1.50 11.25 7.9 530 0.25 22.00 3445.88 N/A 1 N/A 3445.88 N/A
Back Side
(NE)
concrete 7.00 3.60 19.20 3.9 — — 22.00 1647.36 N/A 1 N/A 1647.36 N/A
Clinic
glass 4.00 1.50 6.00 7.9 530 0.25 22.00 1837.80 N/A 1 N/A 1837.80 N/A
Roof concrete 21.50 13.00 291.75 3.9 — — 22.00 25032.15 N/A 1 N/A 25032.15 N/A
The heat gain rating is the energy emitted by the appliances (see
ASHRAE 1997 chapter 28 tables 5-9), and CLF is the cooling load factor by
hour of occupancy (see ASHRAE 1997 chapter 28 table 37 for unhooded and
39, for hooded equipment). For Zone Type C at 12 hours with unhooded
equipment, the CLF = 0.96, and at 8 hours, CLF = 0.91. For hooded equipment,
at 12 hours, CLF = 0.94, and at 8 hours, CLF = 0.87. The list of appliances and
equipment as well as their respective design cooling load are tabulated in Table
8 below.
Heat Gain
Instantaneous Cooling Load Design Cooling Load
No. Rating No. of
Appliance/ Load (Watts) Factor (Watts)
Room of (Watts) Hours in
Equipment
Items Operation
SH LH SH LH SH LH SH LH
First Floor
Personal
DEPT. Computer 1 133 0 133 0 12 0.96 0.96 127.68 0
HEAD brand 1
OFFICE 1
Laser Printer 1 248 0 248 0 8 0.91 0.91 225.68 0
33
Smart Phone* 3 200 0 600 0 12 0.96 0.96 576.00 0
paper
1 2420 0 2420 0 8 0.91 0.91 2202.20 0
shredder
Desktop
1 181 0 181 0 8 0.91 0.91 164.71 0
copier
Personal
Computer 6 133 0 798 0 12 0.96 0.96 766.08 0
Brand 1
Copier (Large)
30-60 2 6600 0 13200 0 8 0.91 0.91 12012.00 0
OFFICE 1 copies/min
paper
6 2420 0 14520 0 8 0.91 0.91 13213.20 0
shredder
Smart Phone 6 200 0 1200 0 12 0.96 0.96 1152.00 0
SECOND FLOOR
34
Speakers* 4 100 0 400 0 8 0.91 0.91 364.00 0
FUNCTION Smart Phone* 75 200 0 15000 0 12 0.96 0.96 14400.00 0
ROOM 2
Personal
Computer 2 133 0 266 0 12 0.96 0.96 255.36 0
brand 1
Projector* 1 120 0 120 0 8 0.91 0.91 109.20 0
CONFERE
NCE 45
Coffee Maker 1 1050 450 1050 8 0.91 0.91 955.50 409.50
ROOM 0
Water cooler
1 1750 0 1750 0 12 0.96 0.96 1680.00 0
30L/ hr
Blood
Pressure 2 33 0 66 0 8 0.91 0.91 60.06 0
Meter
Blanket
1 504 0 504 0 12 0.96 0.96 483.84 0
Warmer
CLINIC Pulse
2 21 0 42 0 8 0.91 0.91 38.22 0
Oximeter
Water cooler
1 1750 0 1750 0 12 0.96 0.96 1680.00 0
30L/ hr
Refrigerator
1 690 0 690 0 12 0.96 0.96 662.40 0
(Small)
TOTAL 36144.74 409.50
The overall cooling load the system is intended to address is simply the
sum of the individual design cooling loads from the various external and internal
sources in each floor. Now, considering the variable extent of usage on the
various equipment and lighting fixtures in the building, there could be
circumstances wherein the actual heat gains from these sources exceed the
initial estimation and assumptions. Some adjustments are made, wherein a 5%
allowance is applied on the initial design cooling load of the aforementioned
sources, to account for such possibility. Meanwhile, the rest are simply
retained. With that said, the results of the cooling load calculations are
tabulated in table. Figure 9 illustrates the proportions of the cooling loads
prevalent in the building.
35
1 44552.45 819.00 1.05 46780.07 859.95 47640.02
Miscellaneous
2 36144.74 409.50 1.05 37951.98 429.98 38381.95
Total 166033.78 33986.60 200020.38
14% 12%
Lighting
13%
Occupants
13%
Miscellaneous
Heat Transmission (Sunlit)
43% Heat Transmission (Un-sunlit)
Air Infiltration
36
Figure 10. The Air-conditioning Process
37
166.03
𝑚𝑠 =
1.006(24 − 18)
𝑚𝑠 = 27.51 𝑘𝑔/𝑠
b) specific enthalpy at point 1
@ 𝑝𝑜𝑖𝑛𝑡 2: 𝐷𝐵𝑇 = 24 ℃ ; 𝑅𝐻 = 50%
@ 𝑝𝑜𝑖𝑛𝑡 5: ℎ = 47.8 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑤 = 0.0093
𝑄𝑆 + 𝑄𝐿 = 𝑚𝑠 (ℎ2 − ℎ1 )
𝑄𝑆 + 𝑄𝐿
ℎ1 = ℎ2 −
𝑚𝑠
195.38 + 33.99
ℎ1 = 47.8 −
32.46
ℎ4 = 40.70 𝑘𝐽/𝑘𝑔
c) other properties of other points (via Psychrometric Chart)
@ 𝑝𝑜𝑖𝑛𝑡 1: 𝐷𝐵𝑇 = 18 ℃ ; 𝑤 = 0.0088
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑣 = 0.835 𝑚3 /𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 3: 𝐷𝐵𝑇 = 25 ℃ ; 𝑤 = 0.0093
@ 𝑝𝑜𝑖𝑛𝑡 5: ℎ = 49 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑣 = 0.858 𝑚3 /𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 4: 𝐷𝐵𝑇 = 35 ℃ ; 𝑅𝐻 = 82%
@ 𝑝𝑜𝑖𝑛𝑡 5: ℎ = 111.3 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑤 = 0.0297
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑣 = 0.914 𝑚3 /𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝐷𝐵𝑇 = 25.3 ℃ ; 𝑅𝐻 = 50%
@ 𝑝𝑜𝑖𝑛𝑡 5: ℎ = 51.7 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑤 = 0.0102
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑣 = 0.86 𝑚3 /𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 6: 𝐷𝐵𝑇 = 16 ℃ ; 𝑤 = 0.0088
@ 𝑝𝑜𝑖𝑛𝑡 5: ℎ = 38 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 5: 𝑣 = 0.83 𝑚3 /𝑘𝑔
d) mass flow rate of ventilating air 𝑚0 and recycled air 𝑚𝑅
𝑚0 ℎ4 + 𝑚𝑅 ℎ3 = 𝑚𝑠 ℎ5
𝑚0 ℎ4 + (𝑚𝑠 − 𝑚0 )ℎ3 = 𝑚𝑠 ℎ5
𝑚𝑠 (ℎ5 − ℎ3 ) 𝑚𝑅 = 𝑚𝑠 − 𝑚0
𝑚0 =
ℎ4 − ℎ3 𝑚𝑅 = 27.51 − 1.19
27.51(51.7 − 49) 𝑚𝑅 = 26.32 𝑘𝑔/𝑠
𝑚0 = = 1.19 𝑘𝑔/𝑠
111.3 − 49
38
e) refrigeration capacity
𝑄𝑟𝑒𝑓 = 𝑚𝑠 (ℎ5 − ℎ6 )
𝑄𝑟𝑒𝑓 = 27.51 (51.7 − 38)
𝑄𝑟𝑒𝑓 = 𝟑𝟕𝟔. 𝟖𝟖 𝒌𝑾 ≈ 𝟐𝟏, 𝟒𝟑𝟐. 𝟖 𝑩𝑻𝑼/𝒎𝒊𝒏 ≈ 𝟏𝟎𝟕. 𝟏𝟗 𝑻𝑹
Here, the equal friction method is employed. Such method is generally adopted
for the ducting design of commercial buildings, wherein it simply assumes uniform
friction losses throughout the system. The design friction loss factor for such is typically
0.1 to 0.2 inch of column of water (W.C.) per 100-foot length of the duct.
First, the total sensible heat load for every room is considered. This is employed
in determining the required mass flow rate of the air. This is given by,
𝑄𝑆
𝑚𝑆 =
𝐶𝑝 (𝑡𝑆 − 𝑡𝑅 )
where
𝑄𝑆 − 𝑡𝑜𝑡𝑎𝑙 𝑠𝑒𝑛𝑠𝑖𝑏𝑙𝑒 ℎ𝑒𝑎𝑡 𝑙𝑜𝑎𝑑
𝑡𝑆 − 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑜𝑓 𝑠𝑢𝑝𝑝𝑙𝑦 𝑎𝑖𝑟
𝑡𝑅 − 𝑡𝑒𝑚𝑝𝑒𝑟𝑎𝑡𝑢𝑟𝑒 𝑜𝑓 𝑡ℎ𝑒 𝑟𝑜𝑜𝑚
Both the sensible heat load and the mass flow rate of supply air are employed
in determining the required volume flow rate of the air that is supplied into the room,
which would realize the refrigerating effect. This is given by,
𝑚𝑆
𝑉=
𝜌𝑎𝑖𝑟
39
Applying such analyses on every room, the individual mass and volume flow
rate required for each room are detailed in Table 10.
With that, the specifications of the ducting system shall base on the established
required flow rate for each room. The lengths of the main and branching ducts simply
depend on the organization of the rooms and the structure of the interior of the building.
The ducting layouts are detailed in the following figures. The main line starts from the
AHU and leads towards the second floor then to the first floor. The various branching
ducts lead to the individual diffusers of each room.
40
Main Duct Return Duct
(a)
(b)
41
(a)
(b)
Regarding the various fittings involved, assumptions were employed for their
equivalent lengths in some index runs. The reducer at the main line was set as 8 feet
(2.44 meters), while that of the branch lines was set as 4 feet (1.22 meters). Meanwhile,
Figure 13 was referred to for the other duct fittings. From which, elbow No. 16 was
chosen for the main lines, which has an equivalent length 40 feet (12.19 m), elbow No.
42
14 for the branch lines with 10 feet (3.05m), and the elbow No. 23 for the duct entrance
with 10 feet (3.05 m).
The required air flow rate per duct section simply depends on the required air
flow rate to be supplied for each room, which is detailed in Table 10. With that, these
are employed in determining the velocity of the airflow at each duct section and the
required dimension of the duct through the use of the friction loss chart. As established,
the friction loss factor is typically 0.1 – 0.2. For the design, the value is simply set as
0.15 inch of water/100 ft. This essentially assumes that the all the materials and
equipment are considerably imperfect; thus, the system is set to overcome such
potential losses. When the actual installations turn out to actually be desirable and
impose minimal losses, the system then has the capacity to slightly overperform to
account for more extreme operating conditions.
The parameters are plotted in the chart, wherein the intersections indicate the
approximate airflow velocity at a certain duct section in feet per minute (fpm). In the
43
same plot, the required diameter of the duct section is also indicated. This was done
for each flow rate towards a distinct diffuser.
To achieve a more accurate diameter for the ducts, the following is employed
instead.
4(𝐶𝐹𝑀)
𝐷=√ × 12
𝜋(𝑓𝑝𝑚)
where
𝐷 − 𝑑𝑢𝑐𝑡 𝑑𝑖𝑎𝑚𝑒𝑡𝑒𝑟 𝑖𝑛 𝑖𝑛𝑐ℎ𝑒𝑠
𝐶𝐹𝑀 − 𝑎𝑖𝑟 𝑣𝑜𝑙𝑢𝑚𝑒 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒
𝑓𝑝𝑚 − 𝑎𝑖𝑟 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦
The obtained dimension specifies a diameter for a perfectly circular duct. To
optimize the figure in its consumption of space, this diameter is converted into
equivalent dimensions for a rectangular figure. The corresponding rectangular figure
assumes the same performance as with that of a circular figure, but may not consume
as much vertical space. This is achieved by employing the following relation.
1.3(𝑎𝑏)0.625
𝐷𝑒 =
(𝑎 + 𝑏)0.25
44
where
𝐷𝑒 − 𝑒𝑞𝑢𝑖𝑣𝑎𝑙𝑒𝑛𝑡 𝑑𝑢𝑐𝑡 𝑑𝑖𝑎𝑚𝑒𝑡𝑒𝑟
𝑎 − 𝑟𝑒𝑐𝑡𝑎𝑛𝑔𝑢𝑙𝑎𝑟 𝑙𝑒𝑛𝑔𝑡ℎ
𝑏 − 𝑟𝑒𝑐𝑡𝑎𝑛𝑔𝑢𝑙𝑎𝑟 ℎ𝑒𝑖𝑔ℎ𝑡
Alternatively, a table can also be referred to for quick selection of typical or
preferred dimensions (see Figure 15). The chart is taken from the ASHRAE Handbook,
Fundamentals 1989, which lists various diameters for ducts and their equivalent
45
C-D main duct 7.38 14035.45 0.15 0.0111 2150 34.60 50 x 21 34.6
main
D 8 13516.30 0.15 0.0120 2100 34.35 49 x 21 34.3
reducer
D-E main duct 4.10 13516.30 0.15 0.0062 2100 34.35 49 x 21 34.3
main
E 8 12997.15 0.15 0.0120 2080 33.85 48 x 21 34.0
reducer
E-F main duct 2.95 12997.15 0.15 0.0044 2080 33.85 48 x 21 34.0
main
F 8 12478.00 0.15 0.0120 2050 33.41 47 x 21 33.7
reducer
F-G main duct 10.25 12478.00 0.15 0.0154 2050 33.41 47 x 21 33.7
main
G 8 11904.28 0.15 0.0120 2000 33.03 46 x 21 33.3
reducer
G-H main duct 8.75 11904.28 0.15 0.0131 2000 33.03 46 x 21 33.3
main
H 8 9193.65 0.15 0.0120 1900 29.79 39 x 20 30.1
reducer
H-I main duct 5.94 9193.65 0.15 0.0089 1900 29.79 39 x 20 30.1
main
I 40 9193.65 0.15 0.0600 1900 29.79 39 x 20 30.1
elbow
I-J main duct 9.35 9193.65 0.15 0.0140 1900 29.79 39 x 20 30.1
branch
A-1 8.69 2099.85 0.15 0.0130 1350 16.89 19 x 13 17.1
duct
branch
A 10 2099.85 0.15 0.0150 1350 16.89 19 x 13 17.1
elbow
branch
M-2 4.10 2099.85 0.15 0.0062 1350 16.89 19 x 13 17.1
duct
branch
M 10 2099.85 0.15 0.0150 1350 16.89 19 x 13 17.1
elbow
branch
M-3 4.10 2099.85 0.15 0.0062 1350 16.89 19 x 13 17.1
duct
branch
M 10 2099.85 0.15 0.0150 1350 16.89 19 x 13 17.1
elbow
branch
C-4 8.69 2099.85 0.15 0.0130 1350 16.89 19 x 13 17.1
duct
branch
C 10 2099.85 0.15 0.0150 1350 16.89 19 x 13 17.1
elbow
branch
D-5 9.18 519.15 0.15 0.0138 950 10.01 15 x 6 10.1
duct
branch
D 10 519.15 0.15 0.0150 950 10.01 15 x 6 10.1
elbow
branch
E-6 11.48 519.15 0.15 0.0172 950 10.01 15 x 6 10.1
duct
branch
E 10 519.15 0.15 0.0150 950 10.01 15 x 6 10.1
elbow
branch
F-7 1.64 519.15 0.15 0.0025 950 10.01 15 x 6 10.1
duct
branch
F 10 519.15 0.15 0.0150 950 10.01 15 x 6 10.1
elbow
branch
G-8 2.46 573.72 0.15 0.0037 940 10.58 14 x 6 9.8
duct
branch
G 10 573.72 0.15 0.0150 940 10.58 14 x 6 9.8
elbow
branch
H-L 9.84 2710.63 0.15 0.0148 1450 18.51 28 x 11 18.7
duct
branch
H 10 2710.63 0.15 0.0150 1450 18.51 28 x 11 18.7
elbow
branch
L-9 11.00 2710.63 0.15 0.0165 1450 18.51 28 x 11 18.7
duct
branch
L 10 2710.63 0.15 0.0150 1450 18.51 28 x 11 18.7
elbow
branch
J-10 8.69 2298.41 0.15 0.0130 1350 17.67 28 x 10 17.7
duct
branch
J 10 2298.41 0.15 0.0150 1350 17.67 28 x 10 17.7
elbow
branch
J-11 8.69 2298.41 0.15 0.0130 1350 17.67 28 x 10 17.7
duct
branch
J 10 2298.41 0.15 0.0150 1350 17.67 28 x 10 17.7
elbow
branch
J-K 8.20 4596.83 0.15 0.0123 1650 22.60 32 x 14 22.7
duct
branch
J 8 4596.83 0.15 0.0120 1650 22.60 32 x 14 22.7
reducer
branch
K-12 8.69 2298.41 0.15 0.0130 1350 17.67 28 x 10 17.7
duct
branch
K 10 2298.41 0.15 0.0150 1350 17.67 28 x 10 17.7
elbow
branch
K-13 8.69 2298.41 0.15 0.0130 1350 17.67 28 x 10 17.7
duct
46
branch
K 10 2298.41 0.15 0.0150 1350 17.67 28 x 10 17.7
elbow
branch
M-N 15.58 2802.36 0.15 0.0234 1450 18.82 26 x 12 19.0
duct
branch
M 8 2802.36 0.15 0.0120 1450 18.82 26 x 12 19.0
reducer
branch
N-14 2.46 2802.36 0.15 0.0037 1450 18.82 26 x 12 19.0
duct
branch
N 10 2802.36 0.15 0.0150 1450 18.82 26 x 12 19.0
elbow
First Floor
duct
Fan 10 22635.07 0.15 0.0150 2380 41.76 61 x 25 41.7
entrance
Fan - O main duct 7.71 22635.07 0.15 0.0116 2380 41.76 61 x 25 41.7
main
O 8 21630.71 0.15 0.0120 2350 41.08 59 x 25 41.1
reducer
O-P main duct 2.46 21630.71 0.15 0.0037 2350 41.08 59 x 25 41.1
main
P 8 13028.37 0.15 0.0120 2080 33.89 50 x 20 33.7
reducer
P-Q main duct 9.02 13028.37 0.15 0.0135 2080 33.89 50 x 20 33.7
main
P 40 8602.35 0.15 0.0600 1880 28.96 38 x 19 29.0
elbow
P-X main duct 10.50 8602.35 0.15 0.0157 1880 28.96 38 x 19 29.0
main
Q 8 12024.01 0.15 0.0120 2030 32.95 47 x 20 32.8
reducer
Q-R main duct 7.05 12024.01 0.15 0.0106 2030 32.95 47 x 20 32.8
main
R 8 11019.66 0.15 0.0120 2000 31.78 46 x 19 31.6
reducer
R-S main duct 19.35 11019.66 0.15 0.0290 2000 31.78 46 x 19 31.6
main
S 8 9545.50 0.15 0.0120 1950 29.96 41 x 19 30.0
reducer
S-T main duct 2.30 9545.50 0.15 0.0034 1950 29.96 41 x 19 30.0
main
T 40 6754.48 0.15 0.0600 1780 26.38 38 x 16 26.4
elbow
T-U main duct 13.12 6754.48 0.15 0.0197 1780 26.38 38 x 16 26.4
branch
O-1 2.13 1004.35 0.15 0.0032 1130 12.77 18 x 8 12.9
duct
branch
O 10 1004.35 0.15 0.0150 1130 12.77 18 x 8 12.9
elbow
branch
Q-2 9.18 1004.35 0.15 0.0138 1130 12.77 18 x 8 12.9
duct
branch
Q 10 1004.35 0.15 0.0150 1130 12.77 18 x 8 12.9
elbow
branch
R-3 1.64 1004.35 0.15 0.0025 1130 12.77 18 x 8 12.9
duct
branch
R 10 1004.35 0.15 0.0150 1130 12.77 18 x 8 12.9
elbow
branch
S-W 12.30 1474.17 0.15 0.0185 1230 14.82 25 x 8 14.9
duct
branch
S 10 1474.17 0.15 0.0150 1230 14.82 25 x 8 14.9
elbow
branch
W-4 3.28 1474.17 0.15 0.0049 1230 14.82 25 x 8 14.9
duct
branch
W 10 1474.17 0.15 0.0150 1230 14.82 25 x 8 14.9
elbow
branch
T-5 5.74 2791.02 0.15 0.0086 1450 18.79 32 x 10 18.8
duct
branch
T 10 2791.02 0.15 0.0150 1450 18.79 32 x 10 18.8
elbow
branch
U-6 5.41 2510.09 0.15 0.0081 1400 18.13 34 x 9 18.2
duct
branch
U 10 2510.09 0.15 0.0150 1400 18.13 34 x 9 18.2
elbow
branch
U-7 5.41 2510.09 0.15 0.0081 1400 18.13 34 x 9 18.2
duct
branch
U 10 2510.09 0.15 0.0150 1400 18.13 34 x 9 18.2
elbow
branch
U-V 6.40 1734.30 0.15 0.0096 1280 15.76 25 x 9 15.9
duct
branch
U 8 1734.30 0.15 0.0120 1280 15.76 25 x 9 15.9
reducer
branch
V-8 16.40 1734.30 0.15 0.0246 1280 15.76 25 x 9 15.9
duct
branch
V 10 1734.30 0.15 0.0150 1280 15.76 25 x 9 15.9
elbow
branch
X-9 3.28 3876.63 0.15 0.0049 1550 21.41 31 x 13 21.5
duct
47
branch
X 10 3876.63 0.15 0.0150 1550 21.41 31 x 13 21.5
elbow
branch
X-Y 13.45 4725.72 0.15 0.0202 1630 23.06 37 x 13 23.2
duct
branch
X 8 4725.72 0.15 0.0120 1630 23.06 37 x 13 23.2
reducer
branch
Y-10 4.92 2933.67 0.15 0.0074 1450 19.26 34 x 10 19.3
duct
branch
Y 10 2933.67 0.15 0.0150 1450 19.26 34 x 10 19.3
elbow
branch
Y-11 4.92 1792.05 0.15 0.0074 1300 15.90 29 x 8 15.9
duct
branch
Y 10 1792.05 0.15 0.0150 1300 15.90 29 x 8 15.9
elbow
At each room, the cooling air is supplied via diffusers. To account for the
variability of the cooling load, different round ceiling diffusers are employed based on
the estimated required volume flow rate in the branch ducts that lead to the rooms. Full
information on the models is detailed in APPENDIX H, which outlines the full
specifications for a quick selection of the various diffusers manufactured by the
company SAFID.
The number of diffusers of each type was set to meet the required volume flow
rate for each room, while still providing considerable allowance for extreme
circumstances. This simply entails that the design flow rate is adequately greater than
with what was computed. With that, the number of diffusers employed and the effective
design flow rate are detailed in Table 12.
48
Finally, the material of the ducts themselves was opted to be made from gauge
9 galvanized steel. Such would sufficiently be thick, while not being too costly.
Moreover, the sheet metal would also ensure that the ducts would be rigid and strong,
while being resistant to rust and corrosion. Further specifications of the chosen
material are detailed in APPENDIX I.
Looking back to Table 10, all spaces or rooms in both floors of the whole
building would necessitate a total airflow rate of around 47,872.28 cfm or 22,593.20L/s,
The opted Carrier 39G2230 AHU has a rated airflow capacity that ranges from around
8,000 L/s – 25,000 L/s or 16,900 cfm – 52,900 cfm, as indicated on the quick selection
chart in APPENDIX G. Moreover, as established, the estimations thus far have also
been adjusted to be higher than the theoretical conditions to accommodate more
extreme conditions. Therefore, given the capacities of the chosen equipment, the
AHU’s singular fan would indeed suffice in realizing the required airflow for the air-
conditioning system. With this, only one AHU remains necessary for this design, since
its default operating range adequately fits the needs of the design.
From which, return duct lines are also necessitated to optimize the performance
of the overall system. These are just as crucial as the main supply vents. Here, the
majority of the air in the spaces are returned to the AHU to be recirculated and to
maintain or equalize the pressure of the building. As a general rule, the return ducts
should at least have the same size or be larger than the supply ducts (Summers &
Zim's, Inc., n.d.). Moreover, they shall not be as intricate as the supply ducting.
Generally, at least one return vent is necessary per room, wherein it could be extended
to two or more for substantially larger rooms (UpgradeHome, n.d.). The grilles—where
the air exits the room and flows back to the AHU—shall be established as not to
interfere with the effective delivery of conditioned air of the diffusers. Moreover, they
shall also not be positioned in areas where they are obstructed by furniture or other
elements. With such, the layouts for the return ducts are detailed in the following
figures.
49
Figure 16. First Floor Plan with Return Ducting
Figure 16 depicts the layout in the first floor, while Figure 17 is that of the
second floor.
50
3.5.3 Exhaust
51
With such, the over ducting system in the main building is illustrated as follows.
(a)
(b)
Figure 19. Overall Ducting Layout; (a) First Floor; (b) Second Floor
52
Figure 20. Parking Building Roof Exhaust
53
are designed and decided upon base on the opted heat exchangers and the other
requirements of fulfilling the refrigeration cycle.
3.6.1 Evaporator
3.6.2 Pump
̇
𝑉𝑝𝑢𝑚𝑝 = 𝜈𝑚𝑝𝑢𝑚𝑝
̇
𝑉𝑝𝑢𝑚𝑝 = (1.0057 × 10−3 )(16.22)
̇
𝑉𝑝𝑢𝑚𝑝 = 𝟎. 𝟎𝟏𝟔𝟑𝟏 𝒎𝟑 /𝒔 or 𝟐𝟓𝟖. 𝟓𝟐 𝒈𝒑𝒎
Therefore, the evaporator line of the AHU requires a pump with a
capacity of around 258.52 gpm to realize the refrigeration cycle. With this, the
54
Barmesa 911S-2x3-6 centrifugal pump was opted. This can operate near its
best efficiency point at around 270 gpm, as illustrated in APPENDIX M.
Essentially, only one unit of which is necessary to be utilized. Such operating
conditions are desirable as it is near its best efficiency point. Moreover, it is
adequately well over the required capacity of the system, which allows for
operating in more extreme conditions.
3.6.3 Condenser
This component also allows to interface the whole system with a cooling
tower system. The refrigerant is essentially cooled by rejecting the heat into the
cooling tower circuit. This is discussed on a later section. Here, one brand and
type were simply assumed and selected to base the rest of the design upon.
With this, an ACME AHX condenser was opted. It operates with Refrigerant 22
on Tcond = 105 °F or 40.56 °C, and with the refrigerant entering at T = 160 °F or
71.11 °C. The specific AHX model is established on the next section.
3.6.4 Compressor
55
employing the varying energy states throughout each unit in the refrigeration
system. Plotting the properties of R-22 on the P-h diagram proceeds as follows.
@ 𝑝𝑜𝑖𝑛𝑡 1:
𝑇𝑒𝑣𝑎𝑝 = 1.67 ℃
ℎ = 405.7 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 2:
𝑇 = 71.11 ℃
ℎ ≈ 443 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 3:
𝑇𝑐𝑜𝑛𝑑 = 40.56 ℃
ℎ = 250.3 𝑘𝐽/𝑘𝑔
@ 𝑝𝑜𝑖𝑛𝑡 4:
ℎ = ℎ3
ℎ = 250.3 𝑘𝐽/𝑘𝑔
a) mass flow rate of R-22
𝑄𝑒𝑣𝑎𝑝 = 𝑚𝑟𝑒𝑓 (ℎ1 − ℎ4 )
𝑄𝑒𝑣𝑎𝑝 376.88
𝑚𝑟𝑒𝑓 = =
(ℎ1 − ℎ4 ) (405.7 − 250.3)
𝑚𝑟𝑒𝑓 = 𝟐. 𝟒𝟑 𝒌𝒈/𝒔
b) compressor power
𝑊 = 𝑚𝑟𝑒𝑓 (ℎ2 − ℎ1 ) = 2.43(443 − 405.7)
𝑊 = 𝟗𝟎. 𝟔𝟒 𝒌𝑾
With this, the ZR380K – TW7 Copeland Scroll compressor was opted.
It runs at 380V, 60 Hz, 3 Phase. It operates with refrigerant 22 and has a rated
maximum power input of 32.7 kW. Further information is detailed in APPENDIX
L.
The number of compressors is determined by,
𝑊
𝑛=
𝑊𝑐𝑜𝑚𝑝
90.64
𝑛=
32.7
𝑛 = 2.77 ⟹ 𝟑 𝒖𝒏𝒊𝒕𝒔
Therefore, the system essentially necessitates utilizing three (3) units
of such compressor.
56
Going back to the condenser specifications, the mass flow rate of the
refrigerant is around 2.43 kg/s. With this, the actual condenser heat can be
determined. This proceeds as follows.
𝑄𝑐𝑜𝑛𝑑 = 𝑚𝑟𝑒𝑓 (ℎ2 − ℎ3 )
𝑄𝑐𝑜𝑛𝑑 = 2.43(443 − 250.3)
𝑄𝑐𝑜𝑛𝑑 = 𝟒𝟔𝟖. 𝟐𝟔 𝒌𝑾 𝑜𝑟 𝟏𝟑𝟑. 𝟏𝟖 𝒕𝒐𝒏𝒔
Therefore, the system actually requires a condenser heat of around
133.18 tons to realize the refrigeration cycle. With this, the particular condenser
model was opted to be the ACME AHX-1208B-1 condenser, which has a
nominal capacity of 150 tons. Essentially, only one unit of which is necessary
to be utilized. Its specified capacity is desirable as it is adequately well over the
required capacity of the system, which allows for operating in more extreme
conditions. Further information is detailed in APPENDIX K.
After the heat from the various spaces/rooms of the building is extracted
by the cooling air, transferred to the refrigerant, and transferred to the cooling
water, it is finally rejected into the atmosphere. It is interfaced with the
condenser of the refrigerating system to cool the refrigerant down and to further
remove heat. This component ultimately extracts all that energy and directs it
away from the location via flowing water and atmospheric air.
Here, one brand and type were simply assumed and selected to base
the rest of the design upon. With this, a Cooling Tower Systems (CTS) tower
from its T-2 model line was opted. It operates by means of counter flow and
induced draft. Water is set to enter at Ti = 95 °F or 35 °C, leave at To = 85 °F or
29.44 °C, and with a wet bulb temperature of Twb = 75 °F or 23.89 °C. It also
specifies an evaporation loss of water flow of 0.93%. The specific T-2 model is
determined based on the necessary volume flow rate of water to extract the
heat from the condenser effectively. This proceeds as follows.
a) mass flow rate of water
𝑄𝑐𝑜𝑛𝑑 = 𝑚𝑤 𝐶(𝑇𝑖 − 𝑇𝑜 )
𝑄𝑐𝑜𝑛𝑑
𝑚𝑤 =
𝐶(𝑇𝑖 − 𝑇𝑜 )
468.26
𝑚𝑤 =
4.187(35 − 29.44)
𝑚𝑤 = 𝟐𝟎. 𝟏𝟏 𝒌𝒈/𝒔
57
b) volume flow rate of water
@ 𝑇𝑜 = 29.44℃
𝑣 = 1.004 × 10−3 𝑚3 /𝑘𝑔
𝑉𝑤̇ = 𝜈𝑚𝑤
𝑉𝑤̇ = (1.004 × 10−3 )(20.11)
𝑉𝑤̇ = 𝟎. 𝟎𝟐𝟎𝟏𝟗 𝒎𝟑 /𝒔 or 𝟑𝟐𝟎. 𝟎𝟐 𝒈𝒑𝒎
Therefore, the system actually requires a flow rate of around 320.02gpm
to realize the refrigeration cycle. With this, the particular model was opted to
be the CTS Model T-2125 cooling tower. It has a rated water flow rate of
369gpm. Essentially, only one unit of which is necessary to be utilized. Its
specified capacity is desirable as it is adequately well over the requirements of
the system, which allows for operating in more extreme conditions. Further
information is detailed in APPENDIX N. Accordingly,
c) pump capacity for cooling tower
̇
𝑉𝑝𝑢𝑚𝑝 = 𝑉𝑤̇
̇
𝑉𝑝𝑢𝑚𝑝 = 𝟑𝟐𝟎. 𝟎𝟐 𝒈𝒑𝒎
Therefore, the cooling tower circuit requires a pump with a capacity of
around 320.02 gpm. With this, the Barmesa 911M-3x4-10H A40 centrifugal
pump was opted. This can operate near its best efficiency point at around 340
gpm near a head of 10 m, as illustrated in APPENDIX M. Essentially, only one
unit of which is necessary to be utilized. Such operating conditions are
desirable as it is near its best efficiency point. Moreover, it is adequately well
over the required capacity of the system, which allows for operating in more
extreme conditions.
58
As established, the Model T-2125 cooling tower specifies losses of
water flow due to evaporation of around lossevap = 0.93%. Thus, the make-up
water for the cooling tower is simply determined by,
a) mass flow rate of make-up water
𝑚𝑚𝑢 = 𝑚𝑤 𝑙𝑜𝑠𝑠𝑒𝑣𝑎𝑝
𝑚𝑚𝑢 = (20.11)(0.0093)
𝑚𝑚𝑢 = 𝟎. 𝟏𝟖𝟕𝟎 𝒌𝒈/𝒔
Accordingly,
b) pump capacity for make-up water
𝑚𝑚𝑢
̇
𝑉𝑝𝑢𝑚𝑝 =
𝜌
0.1870
̇
𝑉𝑒𝑣𝑎𝑝 =
1000
̇
𝑉𝑒𝑣𝑎𝑝 = 𝟎. 𝟎𝟎𝟎𝟏𝟖𝟕 𝒎𝟑 /𝒔 or 𝟐. 𝟗𝟔 𝒈𝒑𝒎
With this, one water pump with a capacity of 2.96 gpm shall be
employed for circulating the make-up water. This is elaborated further later on.
From which, the other required design specifications for the circuit are
determined to meet the needed flow rate. This primarily involves the piping
system that this circuit shall operate in. Particularly, this only involves the piping
which connects the pump to the cooling tower.
c) losses
Throughout this pipe line, several fittings or devices are involved which
impose minor losses. The specific articles are simply assumed. These are
detailed as follows. Their corresponding friction factors k are indicated, which
are all based on Table 13 (Neutrium, 2012).
1 – globe valve (½ open): k = 8.5
2 – elbow (90° curved; long radius): k = 0.45
4 – unions/fittings: k = 0.04
6 – coupling: k = 0.04
59
Table 13. Loss Coefficients for Pipe Fittings
Then, the pipes are to be made from galvanized iron. Based on Table
14 (Cengel & Boles, 2011), the absolute roughness values for galvanized iron
pipes is ε = 0.15 mm.
60
d) Reynold’s number
𝜌𝐷𝑉
𝑅𝑒 =
𝜇
𝑚𝑚𝑢
𝜌𝐷 𝜌𝐴
𝑅𝑒 =
𝜇
𝐷𝑚𝑚𝑢
𝑅𝑒 =
𝜇𝐴
where,
𝑅𝑒 − 𝑅𝑒𝑦𝑛𝑜𝑙𝑑′ 𝑠 𝑛𝑢𝑚𝑏𝑒𝑟
𝐴 − 𝑐𝑟𝑜𝑠𝑠 𝑠𝑒𝑐𝑡𝑖𝑜𝑛𝑎𝑙 𝑎𝑟𝑒𝑎 𝑜𝑓 𝑝𝑖𝑝𝑒
𝑚𝑚𝑢 − 𝑚𝑎𝑠𝑠 𝑓𝑙𝑜𝑤 𝑟𝑎𝑡𝑒 𝑜𝑓 𝑚𝑎𝑘𝑒𝑢𝑝 𝑤𝑎𝑡𝑒𝑟
𝜇 − 𝑑𝑦𝑛𝑎𝑚𝑖𝑐 𝑣𝑖𝑠𝑐𝑜𝑠𝑖𝑡𝑦 @ 𝑇 = 29.44°𝐶
𝜇 = 0.0008068 𝑃𝑎 − 𝑠
𝐷𝑚𝑚𝑢
𝑅𝑒 =
𝜇𝐴
(0.1524)(0.1963)
𝑅𝑒 =
𝜋(0.1524)2
(8.068 × 10−4 ) ( )
4
(0.1524)(0.1963)
𝑅𝑒 =
𝜋(0.1524)2
(8.068 × 10−4 ) ( )
4
𝑅𝑒 = 𝟐𝟎𝟑𝟐. 𝟕𝟑 ⟹ 𝑙𝑎𝑚𝑖𝑛𝑎𝑟
e) friction factor
Since the Reynold’s number falls within the range of laminar flow, the
friction factor is simply determined by,
64
𝑓=
𝑅𝑒
64
𝑓=
2040
𝑓 = 0.03148
f) pump head
This pertains to the total head and height required by the pump to
account for all the major and minor losses imposed by the pipe lines and to
successfully supply the makeup water to the cooling tower. This is determined
by employing the Darcy-Weisbach equation and incorporating the minor losses.
61
0.1963
𝑉=
𝜋(0.1524)2
1000 ( 4 )
𝑉 = 0.01078 𝑚/𝑠
Three (3) piping systems were calculated and sized for the design's piping
system: the refrigeration system (1), the cooling tower (2), and the make-up water
system (3).
62
All of the pipes that will be used in the design and through which water will flow
are Schedule 80 galvanized iron pipes. Table 15 shows the pipe schedules and sizes
that were chosen.
Copper tubing will be applied when using the R22 refrigerant. According to the
ACME DXT-1410-S-2P-2C evaporator's specifications and schematic diagram, the
liquid line has a diameter of 3 1/8 inches (79.375 mm), so a copper tube with an inside
diameter of 2.907 inches (73.838 mm) is chosen. The evaporator's specifications were
chosen rather than the condenser's because the evaporator requires a larger tubing
diameter. Schedule 0.109 applies to the copper tubing; see Table 16 below.
63
Table 16. Copper Tubing Schedules and Sizes
By dividing the computed mass flowrate of the refrigerant, which is 2.55 kg/s,
by the density of the R22 refrigerant at 40.67°C, which is 1128.4 kg/m3, one can
calculate the volume flowrate of the refrigerant. Thus, the refrigerant's volume flowrate
is 0.00226 m3/s, the cooling tower's volume flowrate is 0.02119 m3/s, and the volume
flowrate to and from the evaporator and AHU is 0.01706 m3/s.
The k-values for the pipe fittings are taken from Table 13, and the pipe friction
factor f as calculated above, is 0.03148.
The piping system arrangement in Figure 22 is used to help calculate the
lengths of the pipes. The equivalent lengths of various pipe fittings are shown in Table
17 (Neutrium, 2012), which may be found by multiplying the pipe diameter by the (L/D)
eq values, which will yield a length in meters.
64
Table 17. Equivalent Lengths for Pipe Fittings
Again, the head losses are determined by the Darcy-Weisbach Equation. With
that,
Table 18 presents the calculated values for the piping system, such as the
volume flowrate, the liquid velocity, the pipe diameters, equivalent lengths, and the
head losses.
65
Table 18. Piping System Sizing
Figure 22 illustrates the Piping system layout of the whole centralized air-
conditioning system. While Figure 23, Figure 24, Figure 26 shows the individual piping
system layout for the, AHU-Evaporator line, the Refrigerant lines, and the Condenser-
Cooling Tower lines, respectively.
66
Figure 24. Piping System Layout (AHU – Evaporator)
67
Figure 26. Piping System Layout (Condenser – Cooling tower)
A proposed configuration for the location of the finished AHU, cooling tower,
and remainder of the refrigeration system on the building's roof deck is shown in the
following figures. They depict a 3D perspective of the structure with some of the
equipment installed and established on the rooftop. The component sizes are not
necessarily to scale and are only generally proportional to the building floor plan or
building model.
68
Figure 27. Building Perspective View
69
Figure 29. System on Building; Rear View
70
CHAPTER IV – CONCLUSION
71
The centralized air-conditioning system will be the most efficient and practical
solution to cooling multiple rooms in a building at once. This will make the living space
more comfortable, healthier, and extremely desirable to individuals who plan to stay in
it, especially during the hot summer months in the city.
72
REFERENCES
Benjamin A. et. al. (2017). A Study on Thermal Comfort of Office Employees in the
Philippines.
Bhatia A. (2007). Air Conditioning Psychrometrics.
Canadian Centre for Occupational Health & Safety. (2023). Retrieved from Thermal
Comfort for Office Work.
Cengel, Y. A., & Boles, M. A. (2011). Thermodynamics: An Engineering Approach (7th
ed.). New York, NY: McGraw-Hill.
Chow et al., A. C. (2001). Building-mix optimization in district-cooling system
implementation. 1-3.
Chua. et al. (2013). Achieving better energy-efficient air conditioning - A review of
technologies and strategies. Applied Energy, 87-104.
Environmental Protection Agency. (1991, December). Retrieved from Building Air
Quality: A Guide for Building Owners and Facility Managers EPA document #
402-F-91-102.
Fong K.F. et. al. (2010). Comparative study of different solar cooling systems for
buildings in subtropical city. Solar Energy, 227-244.
Gwerder, M. (2013). Final report: Use of weather and occupancy forecasts for optimal
building climate control – Part II: controller design (OptiControl-II).
Halawa E. et. al. (2012). The adaptive approach to thermal comfort: A critical overview.
Energy and Buildings, 101-110.
Holopainen R. et. al. (2014). Comfort assessment in the context of sustainable
buildings: Comparison of simplified and detailed human thermal sensation
methods. Building and Environment, 60-70.
Jordi et. al. (2013). Operational optimisation of a complex trigeneration system
connected to a district heating and cooling network. 1536-1542.
Li, Z., & Y., J. (2009). Analysis on cooling energy consumption of residential buildings
in China׳s urban areas. 82-88.
Neutrium. (2012, October 12). Retrieved from PRESSURE LOSS FROM FITTINGS -
EXCESS HEAD (K) METHOD.
Niccolò A., R. A. (2013). Cost optimal analysis of heat pump technology adoption in
residential reference buildings. Renewable Energy, 615-624.
Perez. et al. (2011). The map of energy flow in HVAC systems. Applied Energy, 5020-
5031.
SCHRECENGOST R. (2019, January 21). AHU types, components, and
configurations.
Shimoda et al., T. N. (2008). Verification of energy efficiency of district heating and
cooling system by simulation considering design and operation parameters.
Building and Environment, 569-577.
73
Soederman, J. (2007). Optimisation of structure and operation of district cooling
networks in urban regions. 2665-2676.
Summers & Zim's, Inc. (n.d.). Supply Vs. Return Air Vents. Retrieved from
https://sumzim.com/supply-vs-return-
vents/#:~:text=The%20earliest%20HVAC%20systems%20featured,two%20or
%20three%20being%20ideal
Suncalc. (2015). Retrieved from
https://www.suncalc.org/#/11.0233,124.6043,9/2019.05.15/09:00/1/3
The Engineering Toolbox. (n.d.). Retrieved from
https://www.engineeringtoolbox.com/number-persons-buildings-d_118.html
The Engineering Toolbox. (n.d.). Retrieved from Transmission Heat Loss through
building elements: https://www.engineeringtoolbox.com/heat-loss-
transmission-d_748.html
UpgradeHome. (n.d.). How Many Return Air Vents do I Need. Retrieved from
https://upgradedhome.com/how-many-return-air-vents-do-i-need/
World Weather Online. (n.d.). Retrieved from
https://www.worldweatheronline.com/cogon-cumbado-weather-
averages/ormoc/ph.aspx
Zhang, W. H. (2017). Comparison analysis of energy consumption characteristics
between decentralized and centralized AC systems in residential buildings by
commissioning. . Frontiers of Architectural Research, 42-52.
74
APPENDICES
75
APPENDIX A
76
APPENDIX B
SECOND FLOOR PLAN
77
APPENDIX C
ASHRAE PSYCHROMETRIC CHART NO. 1
78
APPENDIX D
FRICTION LOSS CHART
79
APPENDIX E
80
APPENDIX F
R-22 P-H DIAGRAM
81
APPENDIX G
82
APPENDIX H
ROUND CEILING DIFFUSER SPECIFICATIONS
83
84
APPENDIX I
SHEET METAL GAUGES AND SPECIFICATIONS
85
APPENDIX J
EVAPORATOR SPECIFICATION
86
87
APPENDIX K
CONDENSER SPECIFICATIONS
88
89
APPENDIX L
COMPRESSOR SPECIFICATIONS
90
91
APPENDIX M
PUMP SPECIFICATIONS
92
APPENDIX N
COOLING TOWER SPECIFICATIONS
93
94
95