You are on page 1of 3

Technical data of the fan: RZR 13-1250 fulfills the ErP requirements 2015

Description Value Dimension


Installation acc. DIN 24163 Part 1 B
Reference density (Rho1) 1.20 kg/m³
Medium temperature (t) 20 C
Air flow rate (V) 45000 ft³/min
Total pressure rise (dpt) 1.47 in wg
Dynamic pressure at discharge (pd2) 0.27 in wg
Static pressure rise (dpfa) 1.20 in wg
Fan speed (nv) 1) 461 min-1
Power on fan shaft (Pw) 10.5 kW
Absorbed power of the system (P1) with V-belt / flat belt drive 11.8 / 11.6 kW
Total efficiency (ETAt) 74 %
Static efficiency (ETAfa) 60 %
System efficiency (ETA faS ) (over all efficiency of fan (static), motor, and V-belt / flat belt drive) 54 / 55 %
Specific Fan Power (SFP-factor) with V-belt / flat belt drive 557 / 547 W/(m3/s)
Nozzle calibration factor (K10) 3000 m2s/h
Differential pressure on nozzle (dpD) 1.57 in wg
Velocity at discharge area (c) 10.6 m/s
Fan weight 1100 kg
1)
Speed deviations within ±4% may be possible with the final selection of the belt drive which may slightly modify technical

data

A-weighted sound power level discharge/intake LwA4/7 85/85 dB


2)
Unweighted octave sound power level Octave mid frequencies
63/125/250/500/1k/2k/4k/8k Hz
92/87/88/82/79/72/65/57 dB discharge LwOkt4
83/86/86/82/80/77/70/64 dB intake LwOkt7
2)
The octave sound power levels can be higher at octave bands at or close to blade passing frequency.

To motor: Siemens-IE3 1LE1003-1DB43-4AB4/IE3


Phases-Voltage-Frequency 3~400/690-50 V-Hz
Frame size-poles: 160-4
Rated power (PN) 15.00 kW
Rated speed (nN) 1475 min-1
Rated current (IN) 28,5/16,5 A
Speed up time at direct start (tA) 7 s
operational limits
Max. fan speed (nvmax) 1100 min-1
Max. power on shaft (Pwmax) 146 kW
Temperature range for conveying medium (tmin ...tmax) -20...80 C
ErP-Data at best efficiency and density 1.20 kg/m^3
measurement- / efficiency category B / total
design status of VSD without VSD
overall efficiency with V-belt / flat belt drive (ETAopt) 73.9 / 75.3 %
achieved efficiency grade with V-belt / flat belt drive (Nist) 73.6 / 74.9
required efficiency grade in 2013 / 2015 (N) 61 / 64
Air flow rate (Vopt) 36930 ft³/min
pressure rise (dpopt) 2.55 in wg
Fan speed (nvopt) 509 min-1
motor power input with V-belt / flat belt drive (P1opt) 14.94 / 14.68 kW
specific ratio (ddpopt) 1.006

Fan curve to RZR 13-1250

30.07.2021 1/3 proSELECTA II Version 2.02.07.29 / 131106 - June 2021


30.07.2021 2/3 proSELECTA II Version 2.02.07.29 / 131106 - June 2021
Dimensions to RZR 13-1250

Motor fitted to: without


Rotation: RD
Handing: 90

30.07.2021 3/3 proSELECTA II Version 2.02.07.29 / 131106 - June 2021