METAL-ENCLOSED BUS Std C37.23-2003

Table 10—Segregated and nonsegregated-phase bus—


preferred rated withstand current

Rated
Rated Rated momentary
maximum short-time withstand currenta
voltage withstand current
(kV ac) (kA rms symmetrical) (kA rms asymmetrical) (kA peak)

0.635 22.0 29 51
42.0 56 97
65.0 86 150
85.0 113 196
4.760 31.5 49 82
40.0 62 104
50.0 78 130
63.0 98 164
8.250 40.0 62 104
15.000 20.0 31 52
25.0 39 65
31.5 49 82
40.0 62 104
50.0 78 130
63.0 98 164
15.500 20.l 31 52
31.5 49 82
40.0 62 104
27.000 16.0 25 42
25.0 39 65
38.000 16.0 25 42
25.0 39 65 --````,,-`-`,,`,,`,`,,`---

31.5 49 82
40.0 62 104
aTo obtain the momentary withstand current value in rms asymmetrical amperes, multiply the short-time
withstand current rating by 1.33 for bus rated up to 0.635 kV ac and by 1.55 for bus rated above 0.635 kV
ac. To obtain the peak momentary withstand current value, multiply the short-time withstand current rating
by 2.3 for bus rated up to 0.635 kV ac and by 2.6 for bus rated higher than 0.635 kV ac. To obtain the peak
momentary withstand current value for dc bus, multiply the short-time withstand current by 1.65. The mul-
tiplying factors (2.6 and 1.55) for bus duct rated higher than 0.635 kV ac are in accordance with the intro-
duction of ANSI C37.06-2000 [B3].9 The multiplying factors (2.3 and 1.33) for bus rated up to 0.635 kV
ac are in accordance with Note 5 of 5.4.4 of IEEE Std C37.20.1-2002 [B14]. The multiplying factor (1.65)
for dc bus is in accordance with 5.5 of IEEE Std C37.14 -2002 [B13], and 6.2.4.1.1 of IEEE Std C37.20.1-
2002 [B14].

9The numbers in brackets correspond to those in the bibliography in Annex B.