You are on page 1of 4

OPERATING MANUAL

UNIVERSAL TEMPERATURE CONTROLLER


UTC-1202, 2202 & 4202
UTC 1202

 UTC 2202

UTC 4202

 

 

UTC-1202 UTC-2202 UTC-4202

Technical Specification
Model UTC-1202 UTC-2202 UTC-4202
UPPER:- 4 Digit 7 seg 0.56”,red LED Display UPPER:- 4 Digit 7 seg 0.39”,red LED Display
Display
LOWER:- 4 Digit 7 seg 0.4”,green LED Display LOWER:- 4 Digit 7 seg 0.28”,green LED Display
Size 96 X 96 X 50 72 X 72 X 85 48 X 48 X 95
Panel Cutout 92 X 92 68 X 68 44 X 44
Input J, K, PT-100 (selectable)
Temperature J: 0 to 600°C / K: 0 to 1200°C /
Range PT-100: -99 to 400ºC /PT.1: -99.0 to 400.0°C
Control Action TP/PID / ON-OFF (selectable)
Output 2 relay, 1 C/O contact, 230V AC, 5A ,1 SSR, 12V DC, 30 mA
Power Supply 110 to 250V AC, 50 / 60 Hz smps

Note :
1) Press + key for 3 sec to go to Factory Setting mode.
2) Press SET key to go to next parameter.
3) Press or to enter value or to select option.
4) Press key for 6 sec to start/stop PID auto-tunning.
5) Every time the instrument is turned ON, following pattern will be
displayed

POWER ON POWER ON

... .
... .
All digit segment will be turned ON for 3 sec   

 
Previous or default sensor input will be display for 2 sec
 

 Process Value 


 Set Value 
[
[ UTC-1202
UTC-2202 [ UTC-4202 [

Page - 1 www.multispanindia.com
 PROCESS VALUE
SET POINT SETTING  SET VALUE

 SET POINT 1




 SET POINT 2


BASIC CONFIGURATION  Press SET key for 5 sec to enter
Password parmeter
 Password Message
TO ENTER BASIC 
CONFIGURATION
SETTING, ENTER “73”

 Password Message



SET

 Input ( J / K / Pt.1 / Pt100 )


K .  

 OFF-SET


 Set Point Low Limit




 Set Point High Limit




 Control Action


   PID/ON-OFF/TP

 HEAT, COOL, H-AL, L-AL, I-AL, O-AL,OFF



IF R1MD=OFF
 SOKT,SKRG,SKPS,ALMT,ONDL,OFF

IF T1MD=OFF
 SEC/MIN/HOUR


 HEAT, COOL, H-AL, L-AL, I-AL, O-AL, E-AL, OFF



IF R2MD=OFF
 SOKT,SKRG,SKPS,ALMT,ONDL,OFF

IF T2MD=OFF
 SEC/MIN/HOUR


 INDIVIDUAL/RELATIVE

Press ENT key to Save & Exit
Page - 2 www.multispanindia.com
Note :
1) Press SET key to enter into an internal setting
2) Press SET key to go to next parameter.
3) Press or key to enter value or to
select option.

CONTROL PARAMETER

TO ENTER CONTROL
PARAMETER  Password Message
SETTING, ENTER “37” 
IF PID SELECTED IF ON-OFF SELECTED IF TP SELECTED

PID   ON-OFF  TP


Parameters   Parameters  Parameters
IF R1MD = OFF
Proportional   Hysteresis 
Constant   
IF T1MD = OFF
Integral   
Constant   
IF R1MD = OFF
or E-AL
Derivative   
Constant
  
IF T2MD = OFF IF T1MD = SOAK
or SKPS or SKRG
Cycle Time   
  
IF R2MD = OFF
or E-AL
Manual Reset  Press ENT key 
 to Save & Exit 
IF T1MD = SOAK
or SKPS or SKRG IF T2MD = OFF
 
 
IF R2MD = OFF
or E-AL Press ENT key
 to Save & Exit

Sr. Parameter Range for J, K, PT100 Range for PT.1 sensor
IF T2MD = OFF 1 PC 00.00 to 99.99 00.00 to 99.99
2 IC 0.000 to 9.999 0.000 to 9.999
 3 DC 0 to 9999 0 to 9999
4 CT 4 sec to 99 sec 4 sec to 99 sec
 5 MR -9 to +9 -9.0 to +9.0
6 PB 2 to 20 2.0 to 20.0
7 Delay time 1 sec to 999 sec 1 sec to 999 sec
Press ENT key 8 Hysteresis 1°C to 50°C 0.1°C to 50.0°C
to Save & Exit 9 Off-set correction -20°C to +20°C -20.0°C to +20.0°C

Page - 3 www.multispanindia.com
Note :
1) Press SET key to go to next parameter.
2) Press or key to enter value or to
select option.

FACTORY SETTING
FACTORY SETTING
SR. PARAMETER VALUES
Process Value 1 PC 5.00
Set Value  Press + key for 3 sec 2 IC 0.225
3 DC 25
Factory Setting  4 CT ( For PID) 10 SEC.
  5 PB 4°C
6 CT ( For TP) 12
7 MR 0°C
 : press ENT key to apply factory set values as shown in table. 8 OFFSET 0°C
 : press ENT key to escape from factory setting. 9 HYSTERESIS-1 3°C
10 HYSTERESIS-2 3°C
11 TIME-1 6 SEC
12 TIME-2 6 SEC

Connection Diagram
8 L 1
SUPPLY
T/C 100-250V AC
(SMPS)
9 N 2
20 19 18 17 16 15 14 13 12 11 10 L 1
SUPPLY
10 3 T/C 100-250V AC
O/P NO 9 N 2
S.S.R T/C

11 RELAY-1 C
+
4
8 S.S.R 3
SUPPLY
NC
NC
100-250V AC 12 NC 5 NO
(SMPS)
RELAY-1 RELAY-2 7 R2 R1 4
NC C NO NC C NO C
N 13 C RELAY-2 C
L O/P 6
S.S.R 6 5
1 2 3 4 5 6 7 8 9 10 14 7
NO
NO

UTC-1202
UTC-2202 UTC-4202

Product improvement and upgrade is a constant procedure. So for more updated operating information and support, please
contact our Helpline : +91-9978991474/75 or Email at marketing@multispanindia.com