OPERATING MANUAL

UNIVERSAL TEMPERATURE CONTROLLER


UTC-121,221 & 421
UTC 121

 UTC 221

UTC 421


 °C

 PV

 R
 SV

SET ENT

UTC 121 UTC 221 UTC 421

Technical Specification
Model UTC 121 UTC 221 UTC 421
UPPER:- 4 Digit 7 seg 0.56”,red LED Display UPPER:- 4 Digit 7 seg 0.39”,red LED Display
Display
LOWER:- 4 Digit 7 seg 0.4”,green LED Display LOWER:- 4 Digit 7 seg 0.28”,green LED Display
Size 96 X 96 X 50 72 X 72 X 85 48 X 48 X 95
Panel Cutout 92 X 92 68 X 68 44 X 44
Input J, K, PT-100 (selectable)
Temperature J: 0 to 600°C / K: 0 to 1200°C /
Range PT-100: -99 to 400ºC /PT.1: -99.0 to 400.0°C
Control Action TP / ON-OFF (selectable)
Output 1 relay, 1 C/O contact, 230V AC, 5A ,1 SSR, 12V DC, 30 mA
Power Supply 100 to 250V AC, 50 / 60 Hz smps

Note :
1) Press + key for 3 sec to go to Factory Setting mode.
2) Press SET key to go to next parameter.
3) Press or to enter value or to select option.
4) Every time the instrument is turned ON, following pattern will be
displayed
POWER ON POWER ON

... .   
All digit segment will be turned ON for 3 sec
... .


Previous or default sensor input will be display for 2 sec


 Process Value 


 Set Value 
[
[ UTC 121
UTC 221 [ UTC 421 [
Page - 4 www.multispanindia.com
SET POINT SETTING  PROCESS VALUE
 SET VALUE

 SET POINT



Press SET key for 6 sec to enter Password
parmeter
BASIC CONFIGURATION  Password Message


TO ENTER BASIC
CONFIGURATION
SETTING, ENTER “73”

 Password Message



SET

 Input ( J / K / Pt.1 / Pt100 )


 K .  

 OFF-SET


 Set Point Low Limit




 Set Point High Limit




 Control Action

TP   ON-OFF

Press SET key  Relay Mode

 

Press ENT key to Save & Exit


Press SET key

Page - 2 www.multispanindia.com
Note :
1) Press SET key to enter into an Internal setting.
2) Press SET key to go to next parameter.
3) Press or key to enter value or to select option.

CONTROL PARAMETER
TO ENTER CONTROL
PARAMETER
SETTING, ENTER “37”
 Password Message

SET
IF TP SELECTED IF ON-OFF SELECTED

Time Proportional   ON-OFF


Parameters   Parameters

Proportional   Hysteresis


Band  
If Heat is selected
then press ENT key
If Cool is to Save & Exit.
Cycle Time  Selected

 Delay time

Manual Reset 

Press ENT key
to Save & Exit
Press ENT key
to Save & Exit
Sr. Parameter Range for J, K, PT100 Range for PT.1 sensor
1 PB 1 to 15 1.0 to 15.0
2 CT 4 sec to 30 sec 4 sec to 30 sec
3 MR -10 to +10°C -10.0 to +10.0°C
4 Delay time 1 sec to 999 sec 1 sec to 999 sec
5 Hysteresis 1°C to 50°C 0.1°C to 50.0°C
6 Off-set correction -20°C to +20°C -20.0°C to +20.0°C

Page - 3 www.multispanindia.com
Note :
1) Press SET key to go to next parameter.
2) Press or key to enter value or to
select option.

FACTORY SETTING
Process Value FACTORY SETTING
Set Value  Press + key for 3 sec
SR. PARAMETER VALUES
1 PB 5
Factory Setting 
 2 CT 8 sec
3 MR 0°C
 : press key to apply factory set values as shown in table. 4 OFFSET 0°C
 : press key to escape from factory setting. 5 HYSTERESIS 3°C
6 DELAY TIME 6 sec

1) Connection Diagram with Relay Output.:


8 L 1
SUPPLY
T/C 100-250V AC
(SMPS)
9 N 2
20 19 18 17 16 15 14 13 12 11
10 3 10 L
SUPPLY
1
T/C NO T/C 100 To 250V AC
- - 9 N 2
11 C 4
SUPPLY
NC
8 NC
3
100-250V AC 12 5
RELAY
(SMPS) NC C NO 7 RELAY C 4
L N 13 6
1 2 3 4 5 6 7 8 9 10 14 7
6 NO
5

UTC 121 UTC 221 UTC 421

2) Connection Diagram with SSR Output.:

8 L 1
SUPPLY
T/C 100-250V AC
(SMPS)
9 N 2

20 19 18 17 16 15 14 13 12 11 10 3 10 L 1
- SUPPLY
O/P - T/C 100 To 250V AC
S.S.R
-
T/C
- 11
9 N 2
4
SUPPLY
12 5
8 3
100-250V AC
(SMPS) 7 4
L N 13
O/P
6 S.S.R
1 2 3 4 5 6 7 8 9 10
S.S.R 6 5
14 7

UTC 121 UTC 221 UTC 421

Product improvement and upgrade is a constant procedure. So for more updated operating information and support, please
contact our Helpline : +91-9978991474/75 or Email at marketing@multispanindia.com
Page - 4 www.multispanindia.com