Professional Documents
Culture Documents
Abstract—Most meter specifications presently do not define laboratory tests [1-5], and a few examples in the field [6-8]
accuracy requirements in the presence of harmonics. Meter indicated that the errors introduced by severe distortion could
designs could therefore use different definitions or algorithms result in differences up to 3% for active energy (kWh).
that produce different measurements in the presence of Modern digital ‘Smart’ meters could eliminate these errors by
harmonics. Smart Grid environments with Distributed digitally filtering the harmonic energy from the total energy
Generation could have significant levels of distortion, and
(P), and therefore registering only the 60Hz energy supplied or
revenue meters must be able to distinguish between the energy
traded at 60 Hz (50Hz) and harmonics. The IEEE-1459 Standard purchased (P1).
provides a power definition model that is ideal for revenue
metering. Efforts to revise Canadian meter specifications to cater Most varh meters in the field today apply algorithms to
for harmonic-rich environments have been hampered by several approximate either the Budeanu definition (Q B), that sums the
factors, including a lack of empirical data on the magnitude of reactive components at different frequencies [9], or the Fryze
the problem and concerns that present meter technology could definition (QF) that derives reactive power as the orthogonal
not address the problem cost-effectively. BC Hydro initiated the difference between apparent power S and active power P [10].
Harmonic Impact Project (HIP) to show that off-the-shelf smart Where harmonics are present, the difference between QB and
meters could implement the proposed definitions, and to obtain
QF can be large, often over 50% and sometimes several
and evaluate empirical field data based on several power
definitions. The HIP project confirms that these metering hundred percent.
inequities exist and that their magnitude can be significant. The
project also confirms that the IEEE-1459 fundamental-only As with watts and vars, VA can be defined as inclusive of
power definitions are suitable for revenue metering and can be harmonic content (S) or excluding harmonics (S1). Most
implemented by present meter technology. meters today implement S, which can be significantly higher
(over 15%) than S1 where severe distortion exists. Meters
Index Terms— Revenue Metering, Power Definitions, Harmonics, should measure S for equipment capacity requirements and S 1
IEEE 1459-2010 for revenue metering purposes.
I. INTRODUCTION II. BACKGROUND
III. THE HARMONIC IMPACT PROJECT IV. THE HIP METER DESIGN
The Harmonic Impact Project (HIP) was initiated by BC Most modern Smart Meters, essentially digital meters with
communications capability, contain a Digital Signal Processor
Hydro to provide answers to some of the above problems; in
(DSP) for metrology and one or more additional processors for
particular to prove that present metering technology can
handling the metering, communications, and security
implement fundamental-only power definitions and to obtain
functions.
empirical data to compare traditional P, Q, and S meter
readings to IEEE-1459 P1, Q1, and S1 readings, from 30
diverse consumers. The goals of the HIP project included
answering the following questions:
Authorized licensed use limited to: Universidad Industrial de Santander. Downloaded on December 04,2020 at 01:34:58 UTC from IEEE Xplore. Restrictions apply.
Sometimes this functionality is incorporated into a single ii) The third site (H-005) had low voltage and current
chip. The 71M65xx family of chips by Maxim is used by distortion levels as at the previous two sites, however the
several meter manufacturers. The DSP in these metering chips customer was absorbing harmonic energy from the
can be reprogrammed to provide measurements based on distribution system, with a difference between P and P1
different definitions. Fig. 1 shows the basic architecture of the usually between 0.1% and 0.2%.
Vision FM2S meter.
iii) The fourth site (H-003) was a ‘modern’ home, with a
The author has described the modifications to the Vision lot of electronics, very efficient loads, and natural gas
meter firmware, as well as the testing of the revised program heated, usually generating harmonic energy into the
in a previous paper [17]. The modifications were applied to distribution system. This home had voltage THD
single phase meters suitable for residential customers, as well consistently under 3% and significant current distortion
as three phase meters for industrial loads. HIP meters were with THD often in the 40% to 60% range. The difference
installed at four residential sites to evaluate the billing impacts between P and P1 at this site varied between 0.1% and
of using fundamental power components, and nine industrial 0.2%, with the customer usually generating harmonic
sites likely to have nonlinear loads. energy.
Authorized licensed use limited to: Universidad Industrial de Santander. Downloaded on December 04,2020 at 01:34:58 UTC from IEEE Xplore. Restrictions apply.
2) A comparison was made between the total energy P and A comparison was made between the P and P1 register
the fundamental energy P1 recorded by the HIP meters at readings from the KV meters. Several of these meters
each site for each calendar month. registered low consumption (under 500kWh) and were
excluded. Of the remaining 42 meters:
i) At seven of the nine sites the difference between P
and P1 was under 0.1%, with some generating and others 1) One had a P register reading 2.6% lower than the P 1
absorbing harmonic energy. reading.
ii) At the remaining two sites, P1 was lower than P by 2) Eight (~20%) had differences between P and P 1 greater
4.4% (H-204) and 9.9% (H-209). Note that both of these than 0.5%. Five were generating harmonic power and three
sites had very little consumption (average loads of less were absorbing it.
than 10kW), and that these differences may be due to
metering errors under low-load conditions.
The ratios of P to P1, QF to Q1, and S to S1 are shown in VIII. SUMMARY OF HIP PROJECT RESULTS
Figure 3 for the nine C&I HIP sites.
The project has shown that:
Authorized licensed use limited to: Universidad Industrial de Santander. Downloaded on December 04,2020 at 01:34:58 UTC from IEEE Xplore. Restrictions apply.
for the 9 C&I HIP meters and 50 KV2c meters. However,
they can exceed the Canadian statutory limit of 3% for
reactive and apparent energy for customers with nonlinear X. REFERENCES
loads.
[1] L. S. Czarnecki, “Considerations on the Reactive Power in
5) The fundamental-only power definitions eliminate the Nonsinusoidal Situations”, IEEE Trans. on Instrumentation and
Measurement, 1984.
inequities as expected. [2] L.S. Czarnecki, “What is wrong with the Budeanu concept of Reactive
Power and Distortion Power and why it should be abandoned”, IEEE
6) The billing impact of moving to the fundamental-only Trans. On Instrumentation and Measurement, Sept 1987, pp 834-837.
power definitions will be negligible (<0.1%) for BC Hydro [3] R. Arseneau, P. Filipski, “Application of a Three-Phase Non-Sinusoidal
Calibration System for Testing Energy and Demand meters under
customers with low distortion levels. The active energy Simulated Field Conditions”, IEEE Transactions on Power Apparatus
(kWh) impact for customers with high levels of distortion, and Systems, 1988.
ranged from about -3% to +3%, with about 20% of the [4] P.S. Filipski, "Polyphase Apparent Power and Power Factor under
KV2c sites registering differences of over 0.5%. As some Distorted Waveform Conditions", IEEE Trans. on Power Delivery,
vo1.6, 1991.
customers generate harmonic energy while others absorb it, [5] P. S. Filipski, P. W. Labaj, “Evaluation of Reactive Power Meters in the
the net effect was a bill increase of about 0.1% for the 42 Presence of High Harmonic Distortion”, IEEE PES Winter Meeting
KV2c meters. If BC Hydro was to experience an average 1992.
kWh revenue increase of 0.1% from fundamental-only [6] A. J. Berrisford, “Should a Utility Meter Harmonics?”, IEE MATES
Conference, Glasgow, UK, 1992.
metering, this would amount to less than C$3 million [7] M. B. Hughes, “Electric Power Measurements – A Utility’s
annually. Perspective”, IEEE, 2002
[8] R. Arseneau and M. B. Hughes, “Selecting Revenue Meters for
7) Of the nine Polyphase HIP sites, six would face PF Harmonic Producing Loads”, IEEE 11th International Conference on
Harmonics and Quality of Power, Lake Placid, NY, USA, 2004.
penalties between 2% and 20% lower with fundamental [9] C. I. Budeanu, “Puissances reactives at fictives”, 1927, Institut Romain
reactive and apparent power definitions, than they would if de l’Energie.
their meters applied RMS Apparent Power or Fryze [10] S. Fryze, “Wirk- Blind- und Scheinleistung in Electrischen Stromkreisen
Reactive Power definitions. If BC Hydro were to lose 10% mit nich-sinusoidalen Verlauf von Strom und Spannung, 1932, ETZ.
[11] “Recommendations of the VA Joint Working Group”, 2008,
of their present PF penalty revenue, the company would https://www.ic.gc.ca/eic/site/mc-mc.nsf/eng/lm04350.html
suffer an annual loss of approximately C$1 million, from a [12] IEEE Standard Definitions for the Measurement of Electric Power
revenue base of over C$4 billion. This is less than 0.025%. Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced
Conditions, IEEE Std. 1459, 2010.
[13] T. Zhang, J. Orr, A. Emanuel, “The Need for a New Generation of var
8) It was not possible to install HIP meters at transmission Meters”, IEEE, 2015.
customers. Nevertheless, if BC Hydro lost 10% of the kVA [14] R. Quijano Cetina, A. J. Roscoe, P. S. Wright, “Challenges for Smart
demand revenue from 10% of their transmission customers Electricity Meters due to Dynamic Power Quality Conditions of the
due to S1 metered rather than S, this would amount to a loss Grid: a Review”, IEEE AMPS 2017.
[15] “Electricity metering equipment (a.c.) - Particular requirements - Part
of under C$3 million. 24: Static meters for reactive energy at fundamental frequency (classes
0,5 S, 1S and 1)”, IEC, 2014.
8) The all-electric home (H-003) could be subject to [16] “R46-1/2: Active electrical energy meters” , OIML, 2012.
metering inequities of 300% for kVArh and 15% for kVAh [17] A. J. Berrisford, “A Smarter Meter: IEEE-1459 Power Definitions in an
Off-the-Shelf Smart Meter”, IEEE I2MTC Conference, Pisa, Italy, 2015.
with existing MC and ANSI compliant meters, if these
quantities were required by the residential tariff.
Andrew J. Berrisford (M’97) was born in Cape
Town, South Africa. He started work at Eskom (the
national electric utility) in 1974, and after
IX. CONCLUSIONS completing his National Diploma in Electrical
Engineering (Light Current) he joined the Electrical
Measurements Section of Eskom’s R&D
The HIP project, with a limited number of sites, has Department, where he developed an interest in
nevertheless achieved its goals. Clearly it is no longer power definitions. Mr. Berrisford started Eskom’s
technically impossible, too expensive, or impractical to Load Research team in 1989 and spent several
meter only the 60Hz energy we produce and trade. The years developing load research applications for the
Forecasting, Rates, IEP and DSM Departments.
billing impact for the majority of BC Hydro customers, and He has presented papers at local and international conferences on electrical
for the company as a whole, would be negligible. For metering, load research, and related topics. He completed his M Sc in
customers with high levels of distortion, however, the HIP Electrical Engineering at the University of the Witwatersrand in 1997, left
meter field trials and KV2c meters indicate that bills could Eskom to start a consultancy, and then immigrated to Canada in 2000. He has
provided technical direction for the Customer and Energy Analytics team at
increase by up to 3% for harmonic generators, or decrease BC Hydro in Burnaby, BC, Canada, for the past thirteen years.
by up to 3% for harmonic absorbers.
Authorized licensed use limited to: Universidad Industrial de Santander. Downloaded on December 04,2020 at 01:34:58 UTC from IEEE Xplore. Restrictions apply.