Innovators in Protection Technology Technical reference

General motor circuit application table


for reduced voltage starting

Breaker type and current rating, star-delta, auto-transformer resistor or


reactance starting

ZS125
E125
S125
Motor rating Approx. FLC Din-T H125
(kW) (Amps) C & D curve Safe-T L125
0.37 1.1 4 6
0.55 1.5 4 6 20
0.75 1.8 4 6 20
1.1 2.6 6 6 20
1.5 3.4 10 6 20
2.2 4.8 10 10 20
3.0 6.5 16 16 20
4 8.2 20 16 20
4.5 9 20 16 20
5.5 11 25 20 20
7.5 14 32 25 20
10 19 40 40 32
11 21 50 40 32
15 28 50 50 50
18.5 34 63 63 50
22 40 80 1) 63 63
25 46 100 1) 80 100
30 55 125 1) 100 100
37 66 125 1) 100
45 80 125
55 100
75 135
90 160
110 200
132 230
160 270
185 320
200 361
220 380
250 430
280 480
300 510
375 650
450 750

Notes: 1) 80, 100 and 125 amp refers to Din-T10H type.


2
) Electronic TemBreak MCCB only.

9
If co-ordination to IEC 60947-4-1 is required refer to co-ordination tables.
Reduced voltage table is based on holding 120 % FLC continuously and 350 %
FLC for 20 seconds.
Din-T MCBs are calibrated to IEC 898 Curve ‘C’ & ‘D’. Selected sizes of ‘D’
Curve are available from stock refer NHP.

9 - 40 NHP Sales 1300 NHP NHP GST not included