Professional Documents
Culture Documents
RATIO : 400-800-1200/1-1-1-1-1
QTY. : 18 Nos.
ISO : 110005261/40
DIRECTION OF ARROW-"X"
1. NOMINAL CREEPAGE DISTANCE: 3813 mm.
2. TOTAL WEIGHT OF C.T : 480 Kgs (APPROX.)
10
9
11
7
12
8
CT RATIO: 400-800-1200/1-1-1-1-1
NAME DATE
TYPE OSKF-145
SL.No./YR. -
FREQ.50 Hz REF.STD. IEC:61869-1&2
kA
HSV/NSV 123/110 kV BIL 230/550 kV(r.m.s)/kVp Ith 31.5/1 Sec.
OIL Wt. 105 kg. TOTAL Wt. 480 kg. Idyn 80 kAp
FOR 400/1 RATIO TAKE OUTPUT FROM 3S1-3S2 WITH 3S2-S' SHORTED.
RATED SEC.CURRENT (A) 1 1 1 1 1 FOR 800/1 RATIO TAKE OUTPUT FROM 3S1-3S3 WITH 3S3-S' SHORTED.
Tender No.-------
FOR 1200/1 RATIO TAKE OUTPUT FROM 3S1-3S4 WITH 3S4-S' SHORTED.
OUTPUT (VA) 30 30 10 10 30
ACCURACY CLASS 5P 5P 0.5 0.5 5P FOR 400/1 RATIO TAKE OUTPUT FROM 4S1-4S2 WITH 4S2-S' SHORTED.
FOR 800/1 RATIO TAKE OUTPUT FROM 4S1-4S3 WITH 4S3-S' SHORTED.
I.S.F/A.L.F 20 20 20 FOR 1200/1 RATIO TAKE OUTPUT FROM 4S1-4S4 WITH 4S4-S' SHORTED.
- - - - - NOTE:-
GROUNDING - EFFECTIVELY GROUNDED
KPV (V) - - - - - RATED EXTENDED PRIMARY CURRENT = 120% CONTINUOUS
P1 P2
"A" "A"
1S1 1S2 1S3 1S4 2S1 2S2 2S3 2S4 3S1 3S2 3S3 S' 3S4 4S1 4S2 4S3 S' 4S4 5S1 5S2 5S3 5S4
PRIMARY CONNECTION P1 - P2 P1 - P2 P1 - P2
& DISCONNECTED ONLY FOR TAN DELTA
Connection with our enquiry/
MEASUREMENT SECONDARY CONNECTION CORE-1 1S1 - 1S2 1S1 - 1S3 1S1 - 1S4
02. EARTHING LINK TO BE RECONNECTED FIRMLY CORE-2 2S1 - 2S2 2S1 - 2S3 2S1 - 2S4
GE T&D India Limited,
BEFORE C.T'S ENERGISED CORE-3 3S1 - 3S2 S' 3S1 - 3S3 S' 3S1 - 3S4 S'
CORE-4 4S1 - 4S2 S' 4S1 - 4S3 S' 4S1 - 4S4 S'
CORE-5 5S1 - 5S2 5S1 - 5S3 5S1 - 5S4
431-B-6125 Rev:00
NOTES:-
01. OUTDOOR PROOF (MATERIAL : STAINLESS STEEL 0.5 mm THICK )
It is not to be used for any other purpose nor
on request. It is submitted as confidential in
CT RATIO: 400-800-1200/1-1-1-1-1
This drawing is the property of
DRG.No.
5 SECONDARY WINDING
3
6 HEAD INSULATION
4 7 PRIMARY PAD
8 SECONDARY CORES
5
9 TANK
6
10 INSULATOR
7
11 ACTIVE PART
8 12 BASE
13 TERMINAL BOX
9
14 L.V. BUSHING FOR TAN DELTA
& CAPACITANCE MEASUREMENT
10
14
11
15
16
CT RATIO: 400-800-1200/1-1-1-1-1
NAME DATE
01
3S1
3S2
3S3
3S4
4S1
4S2
4S3
4S4
S'
S'
VIEW-X X
GASKET
LEGEND
CABLE ENTRY PLATE
1. SECONDARY TERMINAL BLOCKS WITH NECESSARY SHORTING LINKS
2. GASKET. (TYPE : NBR/EPDM)
3. CABLE ENTRY ALUMINIUM PLATE (278 x 122 x 4)
NOTES:
a) TERMINAL BOX CONFORMS TO IP:55 DEGREE PROTECTION AS PER IS/IEC60947-1:2004 CT RATIO: 400-800-1200/1-1-1-1-1
NAME DATE
DRN. Nitin 12.06.2019 TYPICAL VIEW OF SECONDARY TERMINAL 110005261/40
CHD. Mayank 12.06.2019 BOX FOR 123 kV C.T (TYPE OSKF-145)
APPD. S Mohan 12.06.2019 (120% EXTENDED PRIMARY CURRENT)