9-26 Transformers

Electrostatically Shielded Transformers


January 2003
Single- and Three-Phase Types EP, DS-3, EPT, DT-3, 60 Hz Vol. 1, Ref. No. [0326]

Single- and Three-Phase, Application Description Options and Accessories


Types EP, DS-3, EPT, DT-3, 60 Hz Electrostatically shielded transformers Please refer to Page 9-113.
are used to protect sensitive electrical
equipment from undesirable high fre-
quency signals commonly generated Product Specifications
by lighting, switching surges, motors, Frequency
and SCRs feeding noise back into the
line. An electrostatic shield, consisting Eaton’s Cutler-Hammer standard dry
of a single turn of aluminum foil placed type distribution transformers are
between the primary and secondary designed for 60 Hertz operation. Trans-
winding, is used to provide from formers required for other frequencies
30 to 70 dB attenuation of wide band are available and must be specifically
line-to-ground (common mode) noise. designed.

Typical uses of shielded isolation Overload Capability


transformers include: Short-term overload is designed into
Type DT-3 ■ Suppression of transients and noise transformers as required by ANSI.
which travels from its source to the Dry type distribution transformers
9 Product Description sensitive load equipment. will deliver 200% nameplate load for
one-half hour; 150% load for one hour;
■ Suppression of noise and transients and 125% load for four hours without
Types EP, EPT at the point where the noise or being damaged provided that a con-
transients are originating, thus stant 50% load precedes and follows
■ Sand and Resin Encapsulated design. preventing them from backfeeding the overload. See ANSI C57.96-01.250
■ Suitable for indoor or outdoor from the source to the feeders. for additional limitations.
applications. ■ Transform one voltage level to
■ Totally enclosed, non-ventilated another. Continuous overload capacity is not
enclosures. ■ Isolate one circuit from another.
deliberately designed into a trans-
■ Enclosures are NEMA 3R rated. former because the design objective is
to be within the allowed winding tem-
■ Mountable in any position indoors
and upright only outdoors.
Features, Benefits perature rise with nameplate loading.
■ 185ºC Insulation System, 115ºC and Functions Insulation System and Temperature Rise
rise standard. Industry standards classify insulation
■ UL listed.
■ Available in single-phase ratings systems and rise as shown below:
■ 60 Hz operation standard,
through 37.5 kVA and 4160 volts
50/60 Hz operation available. Table 9-25. Insulation System Classification
primary (EP).
■ Short-term overload capability Ambient + + =
■ Available in three-phase ratings
as required by ANSI. Winding Hot Temp.
through 75 kVA and 4160 volts Rise Spot Class
primary (EPT). ■ Meet NEMA ST-20 sound levels.
40°C 55°C 10°C 105°C
Types DS-3, DT-3 Standards and Certifications 40°C
40°C
80°C
115°C
30°C
30°C
150°C
185°C
■ Ventilated, NEMA 2 enclosure 40°C 150°C 30°C 220°C
standard. Industry Standards
■ Suitable for indoor applications, All Cutler-Hammer dry type distribution The design life of transformers having
outdoors when weathershields are and control transformers by Eaton different insulation systems is the
also installed. Corporation are built and tested in same — the lower temperature systems
accordance with applicable NEMA, are designed for the same life as the
■ Upright mounting only.
ANSI and IEEE Standards. All 600 volt higher temperature systems.
■ 220ºC Insulation System, 150ºC class transformers are UL listed unless
rise standard. otherwise noted. Enclosures
■ Available in single-phase ratings Eaton’s Cutler-Hammer ventilated
15 – 167 kVA and up to 4160 volts Seismically Qualified transformers, Types DS-3 and DT-3
primary (DS-3). Eaton’s Cutler-Hammer manufactured utilize a NEMA 2 rated (drip-proof)
■ Available in three-phase ratings dry type distribution transformers are enclosure as standard, and are rated
15 – 1500 kVA and up to 4160 volts seismically qualified, and exceed NEMA 3R with the addition of
primary (DT-3). requirements of the Uniform Building weathershields. Eaton’s Cutler-
Code (UBC) and California Code Title 24. Hammer encapsulated transformers,
Types EP and EPT, utilize a NEMA 3R
rated enclosure as standard.

For more information visit: www.cutler-hammer.eaton.com CA08101001E


Transformers 9-27
Electrostatically Shielded Transformers
January 2003
Vol. 1, Ref. No. [0327] Single- and Three-Phase, Types EP, 60 Hz

Sound Levels Table 9-26. Average Sound Levels Series-Multiple Windings


All Eaton’s Cutler-Hammer 600 volt kVA NEMA Average 1 Series-multiple windings consist of
class general purpose dry type distri- Sound Level in dB 2 similar coils in each winding which
bution transformers are designed to 0–9 40
can be connected in series or parallel
meet NEMA ST-20 sound levels listed 10 – 50 45 (multiple). Transformers with series-
here. These are the sound levels mea- 51 – 150 50 multiple windings are designated with
sured in a soundproof environment. 151 – 300 55 an “X” or “/” between the voltage
Actual sound levels measured at an 301 – 500 60 ratings, such as voltages of “120/240”
installation will likely be higher due to 501 – 700 62 or “240 X 480.” If the series-multiple
701 – 1000 64
electrical connections and environ- 1001 – 1500 65 winding is designated by an “X,” the
mental conditions. Lower sound levels 1
winding can be connected only for a
Applies to general purpose ventilated
are available and should be specified transformers only.
series or parallel. With the “/” designa-
when the transformer is going to tion, a mid-point also becomes avail-
be installed in an area where sound Winding Terminations able in addition to the series or parallel
may be a concern. Primary and secondary windings are connection. As an example, a 120 X 240
terminated in the wiring compartment. winding can be connected for either
Encapsulated units have copper leads 120 (parallel) or 240 (series), but a
or stabs brought out for connections. 120/240 winding can be connected
Ventilated transformers have leads for 120 (parallel), or 240 (series), or
brought out to aluminum pads that are 240 with a 120 mid-point. 9
pre-drilled to accept Cu/Al lugs. Lugs are
not supplied with these transformers. Technical Data
Eaton’s Cutler-Hammer recommends
external cables be rated 90°C (sized at and Specifications
75°C ampacity) for encapsulated
designs and 75°C for ventilated designs. Please refer to Page 9-115.

Product Selection
Additional Product Selection information begins on Page 9-129.
Table 9-27. Single-Phase Selection Information — Types EP, 60 Hz
kVA Full Cap. Taps Type °C Dimensions (Inches) Wt. Dimensions (mm) Wt. Frame Wiring Weathershield Catalog Price
FCAN FCBN Temp. H W D Lbs. H W D kg Diagram Catalog Price Number U.S. $
Rise Number Number U.S. $

120 x 240 Volts to 120/240 Volts


3 — — EP 115 14-1/8 7-3/4 8 65 359 197 203 29 FR176 90B Indoor- — S10N11E03N 1,155.
5 — — EP 115 16 10-3/8 9-7/8 113 406 263 251 51 FR177 90B Outdoor — S10N11E05N 1,560.
7.5 — — EP 115 16 10-3/8 9-7/8 123 406 263 251 55 FR178 90B — S10N11E07N 2,010.
10 — — EP 115 19 13-3/8 10-1/2 193 482 339 266 87 FR179 90B Indoor- — S10N11E10N 2,450.
15 — — EP 115 19 13-3/8 10-1/2 216 482 339 266 98 FR180 90B Outdoor — S10N11E15N 3,060.
25 — — EP 115 22-3/8 16-3/8 14-1/8 375 568 416 359 170 FR182 90B — S10N11E25N 4,800.
120 Volts to 120 Volts
3 — — EP 115 14-1/8 7-3/4 8 65 359 197 203 29 FR176 77A Indoor- — S12N12E03N 1,155.
5 — — EP 115 16 10-3/8 9-7/8 113 406 263 251 51 FR177 77A Outdoor — S12N12E05N 1,560.
7.5 — — EP 115 16 10-3/8 9-7/8 123 406 263 251 55 FR178 77A — S12N12E07N 2,010.
10 — — EP 115 19 13-3/8 10-1/2 193 482 339 266 87 FR179 77A Indoor- — S12N12E10N 2,450.
15 — — EP 115 19 13-3/8 10-1/2 216 482 339 266 98 FR180 77A Outdoor — S12N12E15N 3,060.
25 — — EP 115 22-3/8 16-3/8 14-1/8 375 568 416 359 170 FR182 77A — S12N12E25N 4,800.
208 Volts to 120/240 Volts
3 — — EP 115 14-1/8 7-3/4 8 65 359 197 203 29 FR176 578A Indoor- — S29N11E03N 1,320.
5 — — EP 115 16 10-3/8 9-7/8 113 406 263 251 51 FR177 578A Outdoor — S29N11E05N 1,950.
7.5 — — EP 115 16 10-3/8 9-7/8 123 406 263 251 55 FR178 578A — S29N11E07N 2,585.
10 — — EP 115 19 13-3/8 10-1/2 193 482 339 266 87 FR179 578A Indoor- — S29N11E10N 3,100.
15 — — EP 115 19 13-3/8 10-1/2 216 482 339 266 98 FR180 578A Outdoor — S29N11E15N 3,300.
25 — — EP 115 22-3/8 16-3/8 14-1/8 375 568 416 359 170 FR182 578A — S29N11E25N 5,200.
208 Volts to 208 Volts
3 — — EP 115 14-1/8 7-3/4 8 65 359 197 203 29 FR176 77B Indoor- — S29N29E03N 1,320.
5 — — EP 115 16 10-3/8 9-7/8 113 406 263 251 51 FR177 77B Outdoor — S29N29E05N 1,950.
7.5 — — EP 115 16 10-3/8 9-7/8 123 406 263 251 55 FR178 77B — S29N29E07N 2,585.
10 — — EP 115 19 13-3/8 10-1/2 193 482 339 266 87 FR179 77B Indoor- — S29N29E10N 3,100.
15 — — EP 115 19 13-3/8 10-1/2 216 482 339 266 98 FR180 77B Outdoor — S29N29E15N 3,300.
25 — — EP 115 22-3/8 16-3/8 14-1/8 375 568 416 359 170 FR182 77B — S29N29E25N 5,200.
Note: Contact your local Cutler-Hammer sales office for CE Mark transformer requirements.

For other ratings or styles not shown, or for


special enclosure types (including stainless
steel) refer to Eaton’s Cutler-Hammer. Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . DT-1

CA08101001E For more information visit: www.cutler-hammer.eaton.com