Split Air Conditioners

ACUM-L + CADX-L Series


Range 4 TR to 21 TR
( 15 kW to 74 kW )
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22

Contents

Introduction................................02 Fan Performance............................... 10


Legend........................................02 Electrical Data .....................................11
Nomenclature.............................02 Typical Wiring Diagram .....................12
Component Features.......................03 Dimensional Data ...............................13
Optional Features............................04 Recommended Line Sizes ..................16
Specifications..................................06 Recommended Clearances ................17
Capacity Ratings..............................08 Installation and commissioning .........18
Guide Specifications..........................20

Introduction
Legend
The new series of SKM air cooled split
The following legends are used throughout this manual: system air conditioner has been developed to
satisfy the needs in air conditioning practices,
cfm ........ Cubic feet per minute Ph ......... Phase meet high quality of job requirements every
Hz ......... Hertz PI .......... Power Input of Compressor time and to deliver the best in split system
kW ........ Kilowatts TR ......... Tons of Refrigeration performance.
kg .......... Kilogram V ........... Volts SKM air cooled split air conditioners consist
lbs ......... Pounds kPa ....... Kilopascal of ceiling suspended indoor air handler
l/s ......... Liters per second (CADX-L) matched with floor mounted
EWB...... Evaporator Wet Bulb air
outdoor air cooled condensing unit (ACUM-L)
MBh ...... BTUH x 1000 entering temperature.
series.
BPF....... By Pass Factor
SKM air cooled split air conditioners available
Nomenclature in 14 variations to cover the range from 4 to
21 TR (15 to 74 kW) in 50Hz at nominal AHRI
conditions. It is suitable to operate in a wide
range of ambient temperatures from 50 °F
ACU M - 060 L Y (10°C) to 125°F (52°C).

SKM split units are internally wired and


all that is required to be done on site is
Air Cooled Condensing Units Power Suppy Code
ducting, refrigerant piping, power wiring for
Y: 380-415V/3Ph/50Hz CADX-L motor from ACUM-L, thermostat
P: 440V/3Ph/50Hz wiring and power supply connection which
reduces installation work and consequently
M-series Model Designation keeps costs to a minimum. Two independent
Nominal Capacity (MBh)
refrigeration circuits are provided when two
compressors are used.

SKM split air conditioner are simply,


CA DX - 060 L Y

Comfort Air Conditioner Power Suppy


Y: 380-415V/3Ph/50Hz
P: 440V/3Ph/50Hz

Model Designation

Nominal Capacity (MBh)


You name it.....We cool it
Direct Expansion Cooling Coil

2 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
GENERAL FEATURES Condenser Coils
SKM split system air conditioners incorporate many features Condenser coils are manufactured from cross fin Waffle Louvre
and benefits in both the air handler and condensing units, which and Hi-X seamless copper tubes mechanically bonded to
together provides a heavy duty, robust and long lasting commercial aluminium fins to ensure optimum heat transfer. All coils are
unit’s application. tested against leakage by air pressure 450psig (3100 kPa)
SKM split air conditioners combined high efficiency components under water. An integral subcooling circuit is incorporated in the
to provide an extremely rugged and energy efficient split system lower section of the condenser to increase system capacity. The
that will provide cooling with higher efficiency for a long and additional condenser surface provides more cooling using less
extended period of time. energy at no additional cost.

SKM split system is ACUM-L+ CADX-L is yet another model in


the top class range of SKM products which uses the following
basic components: Condenser Fans

• High efficiency totally sealed hermetic scroll compressors Condenser fans are propeller type with aluminium alloy blades
utilizing the most current state of the art technology and provides and are directly driven by electric motors. Motors are internally
smooth, efficient and quiet operation. protected for overloads and Totally Enclosed Air Over (TEAO),
six pole with Class F insulation and minimum IP55 protection.
• Totally enclosed, class F insulated, IP55 protected condenser The TEAO and Class F insulation features ensure long life and
and evaporator fan motors. are unique to SKM. The condenser fans are individually, statically
and dynamically balanced at the factory. Complete fan assembly
• Heavy duty condenser and evaporator coils optimized and is mounted downward on the strong and acrylic coated fan guard
designed for a long life maintenance free operation. for the smaller units. For larger units fan, assembly is separate
and provided with suitable acrylic
• Cabinet construction specifically for gulf climate condition. coated fan guard.

• Electrical panel with many features as standard. Motors are wired to the control panel
to control the operation of these
• Factory matched performance and reliable output to minimize motors along with the compressors.
field decisions.

• Many standard features which are not included in residential


Figure 1: Condenser fan motor arrangement
domestic type split systems. for models ACUM-050L, 110L, 120L,
130L, 145L
•Typically, much heavier gauge tubing and thicker fins for
ruggedness and long life.

COMPONENT FEATURES

ACUM-L CONDENSING UNIT

Compressor Figure 2 : Condenser fan motor arrangement


for models ACUM-060L,070L,085L,
Compressors used in the ACUM-L series condensing units are 100L,160L,180L,205L,240L,260L
hermetically sealed, hi-efficiency, low noise, and compact scroll
with the following features:
Control Panel
• High efficiency. Outdoor condensing units are provided with IP-54 control panel
• Quiet operation, low sound levels. enclosure comprising all starting, operating and safety controls.
• Better debris handling. Following are the standard components used in the ACUM-L
• Self compensating of wear (“wear-in vs. wear-out”). control panel:
• 70% fewer moving parts than comparably sized reciprocating
compressors.
• All compressors are with DOL starting.
• Internal motor protection / Advanced scroll temperature
protection.
• Individual compressor and condenser fan motor contactors.
• Suction gas motor cooling.
• Suction screen. • Overload relays for condenser fan motors.
• Disc type check valve.
• Centrifugal force for oil lubrication.
• Control Relays and control circuit fuses.
• Brazed fittings as standard, rotalock as an option.
• Control disconnect for each refrigerant circuit.

You name it.....We cool it 3


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
• Anti-short cycle timer for compressors.
OPTIONAL FEATURES
• 24V Control Transformer.
As with all SKM air conditioning units, a wide range of options
• Starter (contactor & overload relay) for CADX-L evaporator are available with SKM Split Units on request.
fan motor. (Power wiring from ACUM-L control panel to CADX-L
motor to be done at site by others) Copper Fins (FC)

• Power and control terminal blocks. Pre Coated Aluminum Fins (FAP)

Unit Casing Aeris Coating for Aluminium Fins (FAA)/(FCA)


The unit casing used in the ACUM-L condensing unit is made /Copper Fins.
of zinc coated galvanised steel sheets conforming to JIS-G
3302 and ASTM A525 which is phosphatized and baked after 2” (50mm) Flat Filter Section (FFS)
an electrostatic powder coating in RAL7032 color scheme of For heavy filtration need a section can be provided without or
approximately 60 microns. This finish and coating can pass with aluminium cleanable filter (2AF).
a 1000 hour in 5% salt spray testing at 95°F (35°C) and 95%
relative humidity as per ASTM B117.
Voltage Monitoring Module (VMM)
To prevent ACUM-L unit operation in the event of Phase loss
CADX AIR HANDLING UNIT Phase reversal, and Under / Over voltage on the incoming line
voltage.
Evaporator Coils
All evaporator coils are made of inner grooved copper tubes
Voltage Monitoring Module as per DEWA (DVM)
mechanically bonded into cross wave aluminum fins to ensure Under voltage relay as per DEWA regulations. This option is
optimum heat transfer. Coils conform to AHRI-410. All evaporator available for Dubai, UAE only.
coils are tested against leakage by air pressure of 300 psig
(2068 kPa) under water. Each evaporator coil is supplied with a
factory sized and matched thermostatic expansion valves and External Overload Protection (EOP)
4 mounting holes for ceiling suspension. For those electrical specification requires additional overload
protection for the compressors.
Evaporator Fan & Drive
Evaporator fans are forward curved centrifugal double inlet, double High & Low Pressure Gauges (SDG)
width, statically and dynamically balanced. Bearings used in the Factory installed for each compressor to monitor the high side
fans are self aligning and lubricated for life. Evaporator fans are and low side operating pressure.
belt driven and use “V” belts with an adjustable variable pitch
motor pulley resulting in an accurate fan air flow adjustment.
Liquid Line Controls (CRSP)
Fans are driven by Totally Enclosed, IP55 Protected, 4 Pole Refrigeration specialties comprising solenoid valve, filter drier,
Class F insulated electric motors which conform to relevant sight glass and shut-off valve. Factory sizing and selection
IEC standards. ensures correctly sized and selected components to complete
the field installation.

Filter Low voltage thermostats (CHTS)


All CADX-L units are supplied as standard with 1” (25mm) thick Wall mounted 24 volts cooling/heating thermostats, supplied
permanent washable expanded aluminum flat filter having loose for field installation. (Not required with MCP option)
average dust arrestance 54% according to ASHRAE standard
52-76.
Rotalock Valves on compressors (RVC)
Casing \ Structure (CADX-L):
The unit casing for CADX-L is made of zinc coated galvanized
steel sheets conforming to JIS-G3302 and ASTM A525 which
is phosphatized and baked after an electrostatic powder
coating in RAL7032 color scheme of approximately 60 microns.
This finish and coating can pass a 1000 hour in 5% salt spray
testing at 95°F (35°C) and 95% relative humidity as per ASTM
B117. Panels and casing are insulated with 1” (25mm) thick
fiberglass (with BGT coating) thermal and acoustic insulation
having density of 2 lb/ft³. (32 kg/m³) and thermal conductivity
of 0.23 BTU.in/ft²°Fh (0.033 W/m°K). Insulation meets the
requirements of NFPA 90A and 90B for fire resistance.

4 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
Electric Heating (HC@)
Factory Installed Option
Electric heating batteries are made up of finned heating
elements, constructed from high quality 80/20 nickel chrome
resistance wire centred in metal tube by compressed Microprocessor Based Control (MCP)
magnesium oxide. Helical fins are tightly wound around the A compact and user friendly electronic controller is available as an
tubular heating element. option for the control of the split units. The controller comes with
a built in display, loose supplied room terminal and duct sensor.
Heater batteries when ordered comes with CADX-L mounted
control panel consisting of stage contactors, primary auto reset The main features of the controller are as follows:
thermal safety cut-out, secondary manual reset thermal safety
• Built-in display with keypad.
cut-out and air flow switch. Control of the heater stages will be
from ACUM-L control panel through heating/cooling thermostat • Room terminal for mounting in the conditioned space.
(either supplied by SKM or by customer). • Control of the indoor Fan & compressors.
• Control of the compressors is based on return duct temperature.
Following are the optional kW ratings for electric heater. • Alarm management.
• Built-in anti recycle time for the compressors.
• Automatic lead-lag for the compressors based on run time (for
ACUM CADX Heater (kW) Stages units with two compressors)
• Volt free contact for common fault.
050L 050L
6 • Remote start/stop provision.
060L 060L
070L 070L 7.5
085L 085L
9
100L 100L
1
110L 120L
12
120L 120L
130L 150L
145L 150L 15
160L 150L
180L 180L
18
205L 180L
2
240L 240L Figure 3
24
260L 240L
Table 1 The controller displays status of the indoor fan, compressors,
duct temperature and active alarms. Alarms can be automatic
Pump Down Facility (PD) or manual reset (factory default is auto reset). Set points are
The compressor will switch off each time with a Pump Down Cycle configurable from the controller display as well. The loose
in order to prevent Liquid refrigerant migration to the compressor supplied room terminal also shows the same information as
during off Cycle periods. the built-in display.
With this option, each circuit will be provided with an additional
discharge check valve to prevent Refrigerant Migration from High
side to Low side when the compressor is off.

Condenser Coil Guard (CGP)


Wire mesh guard, in painted finish, for condenser coils.
Recommended on ground level installation where coil needs to
be protected against vandalism.

You name it.....We cool it 5


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
CONDENSING UNIT SPECIFICATIONS
Condensing Unit ACUM 050L 060L 070L 085L 100L 110L 120L
Matched Air Handling Unit CADX 050L 060L 070L 085L 100L 120L 120L
MBh 50.7 63.8 72.1 84.8 96.5 116.0 125.8
Cooling Capacity (1)
kW 14.9 18.7 21.1 24.9 28.3 34.0 36.9
MBh 47.0 58.8 66.5 78.4 89.6 107.6 116.2
Cooling Capacity (2)
kW 13.8 17.2 19.5 23.0 26.3 31.5 34.1
Capacity Steps % 100-0 100-0 100-0 100-0 100-0 100-50-0 100-50-0
Type Hermetic - Scroll
Compressor
Qty. 1 1 1 1 1 2 2
Type Waffle louver fins and Hi-X tubes 3/8'' OD
Qty. 1 1 1 1 1 2 2
Outdoor Coil
ft² 20.0 26.7 26.7 26.7 26.7 40.0 40.0
Face Area
m² 1.86 2.48 2.48 2.48 2.48 3.72 3.72
No. Refrigerant Circuits 1 1 1 1 1 2 2
Liquid in 1/2 1/2 1/2 1/2 1/2 1/2 (x2) 1/2 (x2)
Connections (3)
Suction in 7/8 7/8 7/8 1 1/8 1 1/8 7/8 (x2) 7/8 (x2)
Type Propeller Direct Drive
Code/Qty 560 / 1 723 / 1 723 / 1 723 / 1 723 / 1 560 / 2 628 / 2
Outdoor Fan
cfm 4430 7090 7090 7030 7030 8760 9560
Air Flow
l/s 2091 3346 3346 3318 3318 4134 4512
Type Totally enclosed, Class-F insulation, 6-pole, IP55 Protected
Motor
Size / Qty. kW / # 0.25 / 1 0.75 / 1 0.75 / 1 0.75 / 1 0.75 / 1 0.25 / 2 0.37 / 2
Refrigerant Operating Charge lbs 6.9 8.6 8.6 13.9 14.3 22.1 22.1
R-22 (4) kg 3.1 3.9 3.9 6.3 6.5 10.0 10.0
lbs 321 354 363 446 453 688 697
Operating Weight Approximate
kg 146 161 165 202 206 312 316

Condensing Unit ACUM 130L 145L 160L 180L 205L 240L 260L
Matched Air Handling Unit CADX 150L 150L 150L 180L 180L 240L 240L
MBh 133.1 145.5 157.1 173.4 189.8 234.0 252.4
Cooling Capacity (1)
kW 39.0 42.7 46 50.8 55.6 68.6 74.0
MBh 123.2 134.5 145.3 160.0 176.4 216.5 232.2
Cooling Capacity (2)
kW 36.1 39.4 42.6 46.9 51.7 63.5 68.0
Capacity Steps % 100-50-0 100-50-0 100-50-0 100-50-0 100-50-0 100-50-0 100-50-0
Type Hermetic - Scroll
Compressor
Qty. 2 2 2 2 2 2 2
Type Waffle louver fins and Hi-X tubes 3/8'' OD
Qty. 2 2 2 2 2 2 2
Outdoor Coil
ft² 40.0 40.0 40.0 40.0 48.0 54.7 54.7
Face Area
m² 3.72 3.72 3.72 3.72 4.46 5.08 5.08
No. Refrigerant Circuits 2 2 2 2 2 2 2
Liquid in 1/2 (x2) 1/2 (x2) 1/2 (x2) 1/2 (x2) 1/2 (x2) 5/8 (x2) 5/8 (x2)
Connections (3)
Suction in 7/8 (x2) 7/8 (x2) 7/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2)
Type Propeller Direct Drive
Code/Qty 628 / 2 628 / 2 723 / 2 723 / 2 729 / 2 823 / 2 823 / 2
Outdoor Fan
cfm 9560 9560 13900 13900 15540 19640 19640
Air Flow
l/s 4512 4512 6560 6560 7334 9269 9269
Type Totally enclosed, Class-F insulation, 6-pole, IP55 Protected
Motor
Size / Qty. kW / # 0.37 / 2 0.37 / 2 0.75 / 2 0.75 / 2 1.1 / 2 1.1 / 2 1.1 / 2
Refrigerant Operating Charge lbs 22.1 22.3 22.9 23.1 25.5 31.7 31.7
R-22 (4) kg 10.0 10.1 10.4 10.5 11.5 14.4 14.4
lbs 707 713 780 860 946 909 913
Operating Weight Approximate
kg 321 324 354 390 429 413 414
Table 2
Notes:
(1) The capacity ratings are based on AHRI standard 210/240 & 340/360. Evaporator entering air conditions of 80°F/67°F
(26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of 95°F (35°C) dry bulb.

(2) Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of
115°F(46°C) dry bulb.

(3) Connections are based on 25 ft maximum linear distance between the outdoor & indoor unit and 66 ft maximum lift.

(4) Refrigerant operating charge is for combined condensing uint with the matching air handling unit and 25 ft (7.6m) of interconnecting
refrigerant lines.

Capacity for condition (1) & (2) are gross which doesn’t include the effect of evaporator fan motor heat.

6 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
AIR HANDLING UNIT SPECIFICATIONS
Air Handling Unit CADX 050L 060L 070L 085L 100L 120L 120L
Matched Condensing Unit ACUM 050L 060L 070L 085L 100L 110L 120L
MBh 50.7 63.8 72.1 84.8 96.5 116.0 125.8
Cooling Capacity (1)
kW 14.9 18.7 21.1 24.9 28.3 34.0 36.9
MBh 47.0 58.8 66.5 78.4 89.6 107.6 116.2
Cooling Capacity (2)
kW 13.8 17.2 19.5 23.0 26.3 31.5 34.1
Type Hi-X tubes 3/8'' OD
Indoor Coil ft² 4.17 5.81 5.81 6.25 7.99 7.99 7.99
Face Area
m² 0.39 0.54 0.54 0.58 0.74 0.74 0.74
Refrigerant Control Expansion Valve(s)

Liquid in 1/2 1/2 1/2 1/2 1/2 1/2 (x2) 1/2 (x2)
Connections (3)
Suction in 7/8 7/8 7/8 1 1/8 1 1/8 7/8 (x2) 7/8 (x2)
Type Centrifugal DIDW Belt Drive
Code AT-10/10 AT-10/10 AT-10/10 AT-12/12 AT-12/12 AT-12/12 AT-12/12
Indoor Fan
cfm 1700 2000 2400 2800 3000 3600 3600
Air Flow
l/s 802 944 1133 1321 1416 1699 1699
Type Totally Enclosed, Class F insulated, IP55 Protected
Motor
Size / Qty. kW / # 0.55 / 1 0.55 / 1 0.75 / 1 1.1 / 1 1.1 / 1 1.5 / 1 1.5 / 1
lbs 204 225 225 265 310 334 334
Operating Weight Approximate
kg 93 102 102 120 141 151 151

Matched Air Handling Unit CADX 150L 150L 150L 180L 180L 240L 240L
Matched Condensing Unit ACUM 130L 145L 160L 180L 205L 240L 260L
MBh 133.1 145.5 157.1 173.4 189.8 234.0 252.4
Cooling Capacity (1)
kW 39.0 42.7 46 50.8 55.6 68.6 74.0
MBh 123.2 134.5 145.3 160.0 176.4 216.5 232.2
Cooling Capacity (2)
kW 36.1 39.4 42.6 46.9 51.7 63.5 68.0
Type Hi-X tubes 3/8'' OD
Indoor Coil ft² 11.67 11.67 11.67 14.17 14.17 19.36 19.36
Face Area
m² 1.08 1.08 1.08 1.32 1.32 1.80 1.80
Refrigerant Control Expansion Valve(s)
Liquid in 1/2 (x2) 1/2 (x2) 1/2 (x2) 1/2 (x2) 1/2 (x2) 5/8 (x2) 5/8 (x2)
Connections (3)
Suction in 7/8 (x2) 7/8 (x2) 7/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2) 1 1/8 (x2)
Type Centrifugal DIDW Belt Drive
Code AT-15/15 AT-15/15 AT-15/15 AT-12/12 SC2 AT-12/12 SC2 AT-15/15 SC2 AT-15/15 SC2
Indoor Fan
cfm 4200 4800 4800 5800 6200 8000 8000
Air Flow
l/s 1982 2265 2265 2737 2926 3775 3775
Type Totally Enclosed, Class F insulated, IP55 Protected
Motor
Size / Qty. kW / # 1.5 / 1 1.5 / 1 1.5 / 1 2.2 / 1 2.2 / 1 2.2 / 1 2.2 / 1
lbs 442 442 459 469 469 678 678
Operating Weight Approximate
kg 200 200 208 213 213 308 308
Table 3
Notes:
(1) The capacity ratings are based on AHRI standard 210/240 & 340/360. Evaporator entering air conditions of 80°F/67°F
(26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of 95°F (35°C) dry bulb.

(2) Evaporator entering air conditions of 80°F/67°F (26.7°C/19.5°C) dry bulb / wet bulb and condenser entering air temperature of
115°F(46°C) dry bulb.

(3) Connections are based on 25 ft maximum linear distance between the outdoor & indoor unit and 66 ft maximum lift.

Capacity for condition (1) & (2) are gross which doesn’t include the effect of evaporator fan motor heat.

You name it.....We cool it 7


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
CAPACITY RATINGS
AFR Condenser Entering Air Temperature
Model
ACUM cfm EWB 95°F (35°C) 105°F (41°C) 115°F (46°C) 118.4°F (48°C) 125°F (52°C)
+ l/s Total Capacity Sensible Capacity PI* PI* Sensible Capacity PI* Total Capacity Sensible Capacity PI* Total Capacity Sensible Capacity PI*
CADX (BPF) °F °C MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
1146 62 16.7 43.4 12.7 36.1 10.6 3.6 41.8 12.2 35.4 10.4 4 40.2 11.8 34.7 10.2 4.5 39.6 11.6 34.4 10.1 4.7 38.5 11.3 34 10 5
541 67 19.4 47.2 13.8 30.3 8.9 3.6 45.5 13.3 29.7 8.7 4.1 43.9 12.9 29 8.5 4.6 43.3 12.7 28.8 8.4 4.8 42.2 12.4 28.3 8.3 5
0.17 72 22.2 50.8 14.9 24.3 7.1 3.7 49.1 14.4 23.7 7 4.2 47.3 13.9 23.1 6.8 4.7 46.7 13.7 22.9 6.7 4.8 46.4 13.6 22.8 6.7 4.9
1700 62 16.7 46.5 13.6 44.1 12.9 3.6 44.8 13.1 43.4 12.7 4.1 43 12.6 42.7 12.5 4.6 42.4 12.4 42.4 12.4 4.7 41.2 12.1 41.2 12.1 5
050L
802 67 19.4 50.7 14.9 36.3 10.6 3.7 48.9 14.3 35.6 10.4 4.2 47 13.8 34.9 10.2 4.7 46.3 13.6 34.7 10.2 4.8 46 13.5 34.6 10.1 4.9
+
050L 0.22 72 22.2 54.7 16 28.2 8.3 3.8 52.7 15.4 27.6 8.1 4.3 50.6 14.8 26.9 7.9 4.8 50 14.6 26.7 7.8 4.9 49.6 14.5 26.6 7.8 5
2292 62 16.7 48.5 14.2 48.5 14.2 3.7 46.7 13.7 46.7 13.7 4.1 44.8 13.1 44.8 13.1 4.6 44.1 12.9 44.1 12.9 4.8 42.9 12.6 42.9 12.6 5.1
1082 67 19.4 53 15.5 41.9 12.3 3.8 51 14.9 41.2 12.1 4.3 48.9 14.3 40.5 11.9 4.7 48.2 14.1 40.2 11.8 4.9 47.9 14 40.1 11.8 5
0.26 72 22.2 57.1 16.8 31.8 9.3 3.9 55 16.1 31.1 9.1 4.4 52.7 15.5 30.4 8.9 4.9 - - - - - - - - - -
1597 62 16.7 56 16.4 48.3 14.2 4.1 53.9 15.8 47.4 13.9 4.7 51.5 15.1 46.4 13.6 5.3 50.7 14.9 46 13.5 5.5 49.2 14.4 45.4 13.3 5.8
754 67 19.4 61.2 17.9 40.5 11.9 4.2 59 17.3 39.6 11.6 4.7 56.5 16.6 38.6 11.3 5.3 55.7 16.3 38.3 11.2 5.5 54.2 15.9 37.7 11.1 5.9
0.17 72 22.2 66 19.3 32.2 9.4 4.3 63.6 18.6 31.4 9.2 4.8 61.1 17.9 30.5 8.9 5.4 60.3 17.7 30.2 8.9 5.6 58.7 17.2 29.7 8.7 6
060L 2000 62 16.7 58.4 17.1 54.4 15.9 4.1 56.1 16.4 53.4 15.7 4.7 53.6 15.7 52.4 15.3 5.3 52.8 15.5 52 15.2 5.5 51.2 15 51.2 15 5.9
+ 944 67 19.4 63.8 18.7 44.9 13.2 4.2 61.4 18 44 12.9 4.8 58.8 17.2 43 12.6 5.4 58 17 42.7 12.5 5.6 56.4 16.5 42.1 12.3 5.9
060L 0.19 72 22.2 68.7 20.1 35 10.3 4.3 66.1 19.4 34.2 10 4.9 63.6 18.6 33.4 9.8 5.5 62.8 18.4 33.1 9.7 5.7 61.1 17.9 32.5 9.5 6.1
3193 62 16.7 62.5 18.3 62.5 18.3 4.2 59.9 17.6 59.9 17.6 4.8 57.2 16.8 57.2 16.8 5.4 56.3 16.5 56.3 16.5 5.5 54.6 16 54.6 16 5.9
1507 67 19.4 68.2 20 56.4 16.5 4.3 65.5 19.2 55.5 16.3 4.9 62.8 18.4 54.5 16 5.5 61.9 18.1 54.2 15.9 5.7 60.1 17.6 53.6 15.7 6.1
0.26 72 22.2 73.2 21.5 42.3 12.4 4.4 - - - - - - - - - - - - - - - - - - - -
1597 62 16.7 61.5 18 50.8 14.9 4.9 59.1 17.3 49.7 14.6 5.6 56.6 16.6 48.6 14.2 6.3 55.8 16.3 48.2 14.1 6.5 54.2 15.9 47.5 13.9 6.9
754 67 19.4 66.9 19.6 42.7 12.5 5.1 64.4 18.9 41.7 12.2 5.7 61.8 18.1 40.7 11.9 6.4 61 17.9 40.4 11.8 6.6 59.4 17.4 39.8 11.7 7
0.17 72 22.2 71.9 21.1 34.3 10.1 5.2 69.3 20.3 33.4 9.8 5.9 66.7 19.6 32.5 9.5 6.5 65.8 19.3 32.2 9.4 6.8 65.4 19.2 32 9.4 6.9
070L 2400 62 16.7 66.2 19.4 62.4 18.3 5.1 63.5 18.6 61.3 18 5.7 60.8 17.8 60.2 17.6 6.4 59.9 17.6 59.8 17.5 6.6 58.2 17.1 58.2 17.1 7
+ 1133 67 19.4 72.1 21.1 51.3 15 5.2 69.3 20.3 50.3 14.7 5.9 66.5 19.5 49.3 14.4 6.5 65.6 19.2 48.9 14.3 6.8 65.1 19.1 48.8 14.3 6.9
070L 0.22 72 22.2 77.5 22.7 39.9 11.7 5.3 74.7 21.9 38.9 11.4 6 71.7 21 38 11.1 6.8 70.8 20.7 37.7 11 7 70.3 20.6 37.5 11 7.1
3193 62 16.7 68.9 20.2 68.9 20.2 5.1 66.1 19.4 66.1 19.4 5.8 63.2 18.5 63.2 18.5 6.4 62.3 18.2 62.3 18.2 6.7 60.5 17.7 60.5 17.7 7
1507 67 19.4 75.1 22 58.8 17.2 5.3 72.1 21.1 57.8 16.9 5.9 69.2 20.3 56.8 16.6 6.6 68.2 20 56.4 16.5 6.9 67.7 19.9 56.3 16.5 7
0.26 72 22.2 80.8 23.7 44.7 13.1 5.3 77.7 22.8 43.7 12.8 6.1 74.6 21.9 42.7 12.5 6.9 73.6 21.6 42.4 12.4 7.2 73.1 21.4 42.3 12.4 7.2
1719 62 16.7 70.9 20.8 56.8 16.6 5.3 68.3 20 55.6 16.3 6 65.3 19.1 54.2 15.9 6.9 64.3 18.8 53.8 15.8 7.2 62.3 18.3 52.9 15.5 7.7
811 67 19.4 77.1 22.6 48.1 14.1 5.4 74.4 21.8 47 13.8 6.1 71.4 20.9 45.8 13.4 7 70.4 20.6 45.3 13.3 7.3 68.4 20.1 44.6 13.1 7.8
0.17 72 22.2 83 24.3 39 11.4 5.5 80.2 23.5 37.9 11.1 6.2 77.2 22.6 36.9 10.8 7.1 76.2 22.3 36.5 10.7 7.3 74.2 21.7 35.8 10.5 7.9
085L 2800 62 16.7 77.8 22.8 72.4 21.2 5.4 74.8 21.9 71.2 20.9 6.1 71.5 21 69.8 20.5 7 70.4 20.6 69.4 20.3 7.3 68.2 20 68.2 20 7.8
+ 1321 67 19.4 84.8 24.9 59.7 17.5 5.5 81.7 23.9 58.5 17.2 6.3 78.4 23 57.3 16.8 7.1 77.3 22.7 56.9 16.7 7.4 75.1 22 56.1 16.5 7.9
085L 0.23 72 22.2 91.5 26.8 46.6 13.7 5.6 88.3 25.9 45.5 13.3 6.4 84.9 24.9 44.4 13 7.2 83.8 24.6 44.1 12.9 7.5 81.5 23.9 43.3 12.7 8
3438 62 16.7 80.2 23.5 80.2 23.5 5.4 77.1 22.6 77.1 22.6 6.2 73.7 21.6 73.7 21.6 7 72.5 21.3 72.5 21.3 7.3 70.3 20.6 70.3 20.6 7.8
1622 67 19.4 87.5 25.6 65.7 19.3 5.6 84.3 24.7 64.6 18.9 6.3 80.9 23.7 63.4 18.6 7.1 79.7 23.4 62.9 18.4 7.4 77.5 22.7 62.2 18.2 7.9
0.26 72 22.2 94.5 27.7 50.5 14.8 5.7 91.2 26.7 49.4 14.5 6.5 87.6 25.7 48.3 14.2 7.3 86.4 25.3 47.9 14 7.6 84 24.6 47.2 13.8 8.1
2196 62 16.7 83.7 24.5 69.4 20.3 6.1 80.8 23.7 68.1 20 7 77.6 22.7 66.7 19.6 7.9 76.5 22.4 66.2 19.4 8.2 74.5 21.8 65.3 19.2 8.8
1036 67 19.4 91 26.7 58.4 17.1 6.3 87.9 25.8 57.1 16.7 7.1 84.7 24.8 55.9 16.4 8 83.6 24.5 55.4 16.2 8.3 81.5 23.9 54.6 16 8.9
0.17 72 22.2 97.9 28.7 46.8 13.7 6.4 94.7 27.8 45.7 13.4 7.3 91.3 26.7 44.5 13 8.2 90.1 26.4 44.1 12.9 8.5 87.8 25.7 43.3 12.7 9
100L 3000 62 16.7 88.6 26 81.3 23.8 6.2 85.4 25 79.9 23.4 7.1 82 24 78.5 23 8 80.9 23.7 78.1 22.9 8.3 78.7 23.1 77.1 22.6 8.8
+ 1416 67 19.4 96.5 28.3 67.2 19.7 6.4 93.1 27.3 65.9 19.3 7.2 89.6 26.3 64.5 18.9 8.1 88.4 25.9 64.1 18.8 8.4 86 25.2 63.2 18.5 9
100L 0.21 72 22.2 103.9 30.5 52.5 15.4 6.5 100.3 29.4 51.3 15 7.4 96.4 28.2 50 14.7 8.3 95 27.8 49.6 14.5 8.7 92.4 27.1 48.7 14.3 9.2
4392 62 16.7 93.7 27.5 93.7 27.5 6.3 90.2 26.4 90.2 26.4 7.2 86.5 25.4 86.5 25.4 8.1 85.3 25 85.3 25 8.4 82.9 24.3 82.9 24.3 8.9
2073 67 19.4 102.2 29.9 80.5 23.6 6.5 98.4 28.8 79.2 23.2 7.4 94.4 27.7 77.8 22.8 8.3 93 27.3 77.3 22.7 8.6 90.4 26.5 76.4 22.4 9.1
0.26 72 22.2 110 32.3 61.1 17.9 6.7 105.9 31 59.8 17.5 7.6 101.3 29.7 58.4 17.1 8.6 - - - - - - - - - -
2196 62 16.7 95.6 28 77.8 22.8 6.8 92.3 27.1 76.3 22.4 7.8 89 26.1 74.7 21.9 8.9 87.8 25.7 74.2 21.7 9.3 85.5 25.1 73.1 21.4 10
1036 67 19.4 104 30.5 65.9 19.3 7 100.6 29.5 64.4 18.9 7.9 97 28.4 62.9 18.4 9.1 95.7 28.1 62.4 18.3 9.5 93.3 27.3 61.4 18 10.2
0.09 72 22.2 111.9 32.8 53.3 15.6 7.2 108.2 31.7 51.9 15.2 8.2 104.4 30.6 50.5 14.8 9.3 103.1 30.2 50 14.7 9.7 100.6 29.5 49.1 14.4 10.4
110L 3600 62 16.7 106.5 31.2 101.8 29.8 7 102.6 30.1 100.1 29.4 8 98.6 28.9 98.5 28.9 9.1 97.2 28.5 97.2 28.5 9.5 94.4 27.7 94.4 27.7 10.2
+ 1699 67 19.4 116 34 83.7 24.5 7.3 111.8 32.8 82.1 24.1 8.3 107.6 31.5 80.5 23.6 9.4 106.1 31.1 80 23.4 9.8 103.3 30.3 78.9 23.1 10.5
120L
0.13 72 22.2 124.4 36.5 64.8 19 7.7 120.1 35.2 63.4 18.6 8.8 115.8 34 62 18.2 9.9 114.4 33.5 61.5 18 10.2 111.6 32.7 60.6 17.8 10.9
4392 62 16.7 110 32.2 110 32.2 7.1 105.9 31 105.9 31 8.1 101.6 29.8 101.6 29.8 9.2 100.1 29.3 100.1 29.3 9.6 97.3 28.5 97.3 28.5 10.3
2073 67 19.4 119.7 35.1 92.4 27.1 7.5 115.3 33.8 90.8 26.6 8.5 110.9 32.5 89.3 26.2 9.6 109.4 32.1 88.7 26 10 106.4 31.2 87.7 25.7 10.6
0.14 72 22.2 128.2 37.6 70.4 20.6 8 123.7 36.2 68.9 20.2 9.1 - - - - - - - - - - - - - - -
2196 62 16.7 102 29.9 80.8 23.7 7.8 98.5 28.9 79.2 23.2 8.9 94.5 27.7 77.3 22.6 10.2 93 27.3 76.6 22.4 10.6 90.3 26.5 75.3 22.1 11.4
1036 67 19.4 111.3 32.6 69 20.2 7.9 107.6 31.5 67.4 19.8 9.1 103.4 30.3 65.6 19.2 10.3 101.9 29.9 65 19 10.7 99.1 29 63.8 18.7 11.5
0.09 72 22.2 120.1 35.2 56.4 16.5 8.1 116.2 34 54.9 16.1 9.2 111.8 32.8 53.2 15.6 10.4 110.3 32.3 52.7 15.4 10.8 107.4 31.5 51.6 15.1 11.5
120L 3600 62 16.7 115.1 33.7 105.4 30.9 8 110.8 32.5 103.6 30.4 9.1 106 31.1 101.5 29.8 10.3 104.3 30.6 100.8 29.6 10.7 101.2 29.6 99.5 29.2 11.5
+ 1699 67 19.4 125.8 36.9 87.4 25.6 8.2 121.2 35.5 85.6 25.1 9.3 116.2 34.1 83.8 24.6 10.5 114.5 33.6 83.1 24.4 10.9 111.4 32.6 81.9 24 11.6
120L 0.13 72 22.2 135.5 39.7 68.6 20.1 8.3 130.7 38.3 66.9 19.6 9.5 125.7 36.8 65.2 19.1 10.7 124 36.3 64.7 19 11.1 120.8 35.4 63.6 18.6 11.9
4392 62 16.7 119.3 35 117.6 34.5 8.1 114.7 33.6 114.7 33.6 9.2 109.7 32.1 109.7 32.1 10.4 107.9 31.6 107.9 31.6 10.8 104.7 30.7 104.7 30.7 11.5
2073 67 19.4 130.4 38.2 96.4 28.2 8.2 125.5 36.8 94.6 27.7 9.4 120.3 35.3 92.7 27.2 10.6 118.6 34.8 92 27 11 115.3 33.8 90.8 26.6 11.7
0.14 72 22.2 140.4 41.1 74.3 21.8 8.4 135.2 39.6 72.7 21.3 9.6 130.1 38.1 71 20.8 10.8 128.4 37.6 70.4 20.6 11.3 125 36.6 69.3 20.3 12.1
Table 4

8 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
CAPACITY RATINGS
AFR Condenser Entering Air Temperature
cfm EWB 95°F (35°C) 105°F (41°C) 115°F (46°C) 118.4°F (48°C) 125°F (52°C)
Model
l/s Total Capacity Sensible Capacity PI* Total Capacity Sensible Capacity PI* Total Capacity Sensible Capacity PI* Total Capacity Sensible Capacity PI* Total Capacity Sensible Capacity PI*
(BPF) °F °C MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW MBh kW MBh kW kW
3208 62 16.7 116 34 98.6 28.9 8.3 111.7 32.7 96.7 28.4 9.5 107.1 31.4 94.7 27.8 10.9 105.6 30.9 94.1 27.6 11.4 102.6 30.1 92.8 27.2 12.2
1514 67 19.4 126.5 37.1 82.7 24.2 8.5 122.1 35.8 80.9 23.7 9.7 117.4 34.4 79.1 23.2 11.1 115.8 33.9 78.5 23 11.5 112.7 33 77.3 22.6 12.3
0.17 72 22.2 136.5 40 66.1 19.4 8.7 131.8 38.6 64.5 18.9 9.9 126.9 37.2 62.7 18.4 11.3 125.2 36.7 62.2 18.2 11.7 122 35.7 61 17.9 12.5
130L 4200 62 16.7 121.8 35.7 113.3 33.2 8.4 117.2 34.4 111.4 32.7 9.7 112.4 32.9 109.4 32.1 11 110.7 32.5 108.7 31.9 11.4 107.5 31.5 107.4 31.5 12.2
+ 1982 67 19.4 133.1 39 93.6 27.4 8.7 128.3 37.6 91.8 26.9 9.9 123.2 36.1 89.9 26.3 11.2 121.5 35.6 89.3 26.2 11.6 118.2 34.6 88 25.8 12.4
150L 0.2 72 22.2 143.7 42.1 73.2 21.5 8.9 138.7 40.6 71.5 21 10.1 133.2 39.1 69.7 20.4 11.4 131.4 38.5 69.1 20.3 11.9 127.8 37.4 67.9 19.9 12.7
6417 62 16.7 129.6 38 129.6 38 8.6 124.6 36.5 124.6 36.5 9.8 119.3 35 119.3 35 11.1 117.5 34.4 117.5 34.4 11.5 114.1 33.4 114.1 33.4 12.3
3028 67 19.4 141.9 41.6 115.1 33.7 8.8 136.6 40 113.2 33.2 10.1 130.9 38.4 111.2 32.6 11.4 128.9 37.8 110.5 32.4 11.8 125.2 36.7 109.3 32 12.6
0.26 72 22.2 153.6 45 87 25.5 9.1 147.8 43.3 85.2 25 10.3 - - - - - - - - - - - - - - -
3208 62 16.7 124.2 36.4 102.3 30 9.6 119.5 35 100.2 29.4 10.9 114.5 33.6 97.9 28.7 12.3 112.8 33.1 97.2 28.5 12.7 109.5 32.1 95.8 28.1 13.6
1514 67 19.4 135.1 39.6 86.1 25.2 9.9 130.2 38.2 84.2 24.7 11.2 125.1 36.7 82.1 24.1 12.5 123.3 36.1 81.4 23.9 13 120.1 35.2 80.1 23.5 13.8
0.17 72 22.2 145.3 42.6 69.2 20.3 10.1 140.2 41.1 67.4 19.8 11.4 134.9 39.5 65.5 19.2 12.8 133.2 39 64.9 19 13.2 129.9 38.1 63.8 18.7 14
145L 4800 62 16.7 133.6 39.2 125.4 36.8 9.8 128.4 37.6 123.3 36.1 11.1 122.9 36 121 35.5 12.5 121.1 35.5 120.3 35.3 12.9 117.6 34.5 117.6 34.5 13.7
+ 2265 67 19.4 145.5 42.7 103.2 30.3 10.1 140.1 41.1 101.2 29.7 11.4 134.5 39.4 99.1 29.1 12.8 132.6 38.9 98.4 28.9 13.2 129 37.8 97.2 28.5 14
150L 0.22 72 22.2 156.6 45.9 80.3 23.5 10.3 151 44.2 78.5 23 11.6 145.1 42.5 76.5 22.4 13.1 143.1 41.9 75.9 22.2 13.6 139.5 40.9 74.7 21.9 14.4
6417 62 16.7 139.3 40.8 139.3 40.8 10 133.7 39.2 133.7 39.2 11.3 127.9 37.5 127.9 37.5 12.6 126 36.9 126 36.9 13 122.4 35.9 122.4 35.9 13.8
3028 67 19.4 151.8 44.5 118.6 34.7 10.2 146 42.8 116.5 34.2 11.5 140 41 114.4 33.5 12.9 138 40.5 113.7 33.3 13.4 134.3 39.4 112.4 33 14.2
0.26 72 22.2 163.4 47.9 90.1 26.4 10.3 157.3 46.1 88.2 25.8 11.8 151 44.3 86.2 25.3 13.4 148.9 43.6 85.6 25.1 14 148 43.4 85.3 25 14.2
3208 62 16.7 132.1 38.7 110.1 32.3 9.3 127.3 37.3 107.9 31.6 10.5 122.0 35.8 105.6 30.9 11.8 120.2 35.2 104.7 30.7 12.3 116.7 34.2 103.2 30.2 13.2
1514 67 19.4 143.8 42.1 92.8 27.2 9.5 138.8 40.7 90.7 26.6 10.7 133.4 39.1 88.5 25.9 12.1 131.5 38.5 87.8 25.7 12.5 128.0 37.5 86.4 25.3 13.4
0.17 72 22.2 154.8 45.4 74.6 21.9 9.7 149.6 43.8 72.7 21.3 10.9 144.0 42.2 70.7 20.7 12.3 142.1 41.6 70.0 20.5 12.8 138.4 40.6 68.7 20.1 13.7
160L 4800 62 16.7 144 42.2 137.5 40.3 9.5 138.6 40.6 135.2 39.6 10.7 132.7 38.9 132.7 38.9 12.0 130.7 38.3 130.7 38.3 12.5 126.8 37.2 126.8 37.2 13.4
+ 2265 67 19.4 157.1 46.0 113.2 33.2 9.7 151.5 44.4 111.1 32.6 10.9 145.3 42.6 108.7 31.9 12.3 143.2 42.0 107.9 31.6 12.8 139.2 40.8 106.4 31.2 13.7
150L 0.22 72 22.2 169.3 49.6 88.0 25.8 9.7 163.4 47.9 86.0 25.2 11.0 156.8 46.0 83.8 24.6 12.7 - - - - - - - - - -
6417 62 16.7 150.9 44.2 150.9 44.2 9.6 145.1 42.5 145.1 42.5 10.8 138.8 40.7 138.8 40.7 12.2 136.7 40.1 136.7 40.1 12.6 132.6 38.9 132.6 38.9 13.5
3028 67 19.4 164.8 48.3 131.4 38.5 9.7 158.6 46.5 129.2 37.9 11.0 151.9 44.5 126.8 37.2 12.5 149.7 43.9 126.0 36.9 13.1 145.4 42.6 124.5 36.5 14.0
0.26 72 22.2 - - - - - - - - - - - - - - - - - - - - - - - - -
4604 62 16.7 152.8 44.8 133.6 39.2 11.1 146.7 43 131 38.4 12.6 140.1 41.1 128.2 37.6 14.3 137.9 40.4 127.3 37.3 14.9 133.8 39.2 125.5 36.8 15.9
2173 67 19.4 166.4 48.8 111.3 32.6 11.3 160.2 47 108.9 31.9 12.9 153.7 45 106.4 31.2 14.5 151.5 44.4 105.6 31 15.1 147.3 43.2 104 30.5 16.1
0.19 72 22.2 179.4 52.6 88.2 25.9 11.6 173 50.7 86 25.2 13.2 166.4 48.8 83.7 24.5 14.8 164.1 48.1 83 24.3 15.3 159.7 46.8 81.5 23.9 16.3
180L 5800 62 16.7 159 46.6 150.6 44.1 11.2 152.6 44.7 148 43.4 12.7 145.8 42.7 145.2 42.6 14.4 143.5 42.1 143.5 42.1 14.9 139.1 40.8 139.1 40.8 15.9
+ 2737 67 19.4 173.4 50.8 123.9 36.3 11.5 166.9 48.9 121.5 35.6 13 160 46.9 119 34.9 14.7 157.7 46.2 118.1 34.6 15.2 153.3 44.9 116.5 34.1 16.2
180L 0.22 72 22.2 187.3 54.9 96.4 28.3 11.8 180.5 52.9 94.2 27.6 13.4 173.4 50.8 91.9 26.9 15 170.9 50.1 91.1 26.7 15.5 166.2 48.7 89.6 26.3 16.5
7792 62 16.7 165.8 48.6 165.8 48.6 11.3 159 46.6 159 46.6 12.9 151.9 44.5 151.9 44.5 14.5 149.6 43.8 149.6 43.8 15 145 42.5 145 42.5 16
3677 67 19.4 181.2 53.1 142.9 41.9 11.7 174.2 51.1 140.4 41.2 13.2 167 49 137.9 40.4 14.8 164.5 48.2 137 40.2 15.3 159.8 46.8 135.4 39.7 16.3
0.26 72 22.2 196 57.4 108.6 31.8 12 188.7 55.3 106.3 31.2 13.6 181 53 103.9 30.5 15.2 178.3 52.3 103.1 30.2 15.8 - - - - -
4604 62 16.7 165.4 48.5 139.1 40.8 12.1 159.6 46.8 136.6 40 13.9 153.4 45 133.9 39.2 15.8 151.3 44.3 133 39 16.4 147.3 43.2 131.2 38.5 17.6
2173 67 19.4 179.8 52.7 116.6 34.2 12.4 173.8 50.9 114.2 33.5 14.1 167.4 49.1 111.7 32.7 16 165.3 48.4 110.9 32.5 16.6 161 47.2 109.2 32 17.7
0.19 72 22.2 193.4 56.7 93.1 27.3 12.7 187.1 54.8 90.9 26.6 14.4 180.4 52.9 88.6 26 16.2 178.1 52.2 87.8 25.7 16.8 173.6 50.9 86.2 25.3 17.9
205L 6200 62 16.7 174.4 51.1 161.7 47.4 12.3 168.2 49.3 159.1 46.6 14 161.6 47.4 156.4 45.8 15.9 159.3 46.7 155.5 45.6 16.5 155 45.4 153.7 45 17.6
+ 2926 67 19.4 189.8 55.6 133.3 39.1 12.6 183.3 53.7 130.8 38.3 14.3 176.4 51.7 128.3 37.6 16.1 174 51 127.4 37.3 16.7 169.4 49.7 125.7 36.9 17.8
180L 0.22 72 22.2 204.4 59.9 103.9 30.5 12.9 197.4 57.9 101.6 29.8 14.7 189.9 55.7 99.2 29.1 16.5 187.3 54.9 98.4 28.8 17.1 182.3 53.4 96.7 28.4 18.2
7792 62 16.7 180.3 52.8 180.3 52.8 12.4 173.8 50.9 173.8 50.9 14.1 166.9 48.9 166.9 48.9 16 164.5 48.2 164.5 48.2 16.6 159.9 46.9 159.9 46.9 17.7
3677 67 19.4 196.4 57.6 148.3 43.5 12.8 189.5 55.5 145.8 42.7 14.5 182.2 53.4 143.2 42 16.3 179.7 52.7 142.3 41.7 16.9 174.8 51.2 140.6 41.2 17.9
0.26 72 22.2 211.5 62 113.6 33.3 13.1 204 59.8 111.2 32.6 14.8 195.9 57.4 108.6 31.8 16.7 193.1 56.6 107.7 31.6 17.4 187.6 55 106 31.1 18.5
6292 62 16.7 206.5 60.5 181.6 53.2 14.4 198.9 58.3 178.3 52.3 16.5 190.6 55.9 174.8 51.2 18.9 187.7 55 173.6 50.9 19.7 182.3 53.4 171.4 50.2 21.1
2969 67 19.4 224.6 65.8 151 44.3 14.8 216.6 63.5 148 43.4 16.9 208.1 61 144.7 42.4 19.3 205.1 60.1 143.6 42.1 20.1 199.7 58.5 141.6 41.5 21.5
0.19 72 22.2 241.5 70.8 119.3 35 15.1 233.2 68.4 116.5 34.1 17.3 224.5 65.8 113.5 33.3 19.7 221.5 64.9 112.5 33 20.5 216 63.3 110.6 32.4 21.9
240L 8000 62 16.7 214.9 63 205.7 60.3 14.6 206.8 60.6 202.4 59.3 16.7 198.1 58.1 198.1 58.1 19 195.1 57.2 195.1 57.2 19.9 189.5 55.5 189.5 55.5 21.3
+ 3775 67 19.4 234 68.6 168.8 49.5 15 225.5 66.1 165.7 48.6 17.1 216.5 63.5 162.4 47.6 19.5 213.4 62.6 161.3 47.3 20.3 207.7 60.9 159.2 46.7 21.7
240L 0.22 72 22.2 251.8 73.8 130.8 38.3 15.4 243 71.2 127.9 37.5 17.6 233.7 68.5 124.9 36.6 19.9 230.6 67.6 123.9 36.3 20.7 224.8 65.9 122 35.8 22
10649 62 16.7 223.5 65.5 223.5 65.5 14.7 214.9 63 214.9 63 16.9 205.7 60.3 205.7 60.3 19.2 202.6 59.4 202.6 59.4 20 196.7 57.6 196.7 57.6 21.5
5025 67 19.4 243.5 71.4 193.8 56.8 15.2 234.5 68.7 190.6 55.9 17.4 225 66 187.3 54.9 19.7 221.8 65 186.2 54.6 20.5 215.8 63.3 184.1 54 21.9
0.26 72 22.2 262.2 76.9 146.7 43 15.6 252.9 74.1 143.8 42.1 17.8 - - - - - - - - - - - - - - -
6292 62 16.7 222.4 65.2 188.5 55.2 16.7 213.6 62.6 184.7 54.1 19 204.2 59.8 180.6 52.9 21.6 201 58.9 179.2 52.5 22.4 194.9 57.1 176.7 51.8 23.9
2969 67 19.4 241.7 70.8 157.7 46.2 17.1 232.5 68.1 154.1 45.2 19.5 222.7 65.3 150.3 44 22 219.4 64.3 149 43.7 22.8 213.3 62.5 146.7 43 24.2
0.19 72 22.2 259.5 76.1 125.6 36.8 17.5 249.9 73.2 122.2 35.8 19.9 239.8 70.3 118.7 34.8 22.3 236.5 69.3 117.6 34.5 23.1 230.2 67.5 115.4 33.8 24.4
260L 8000 62 16.7 232.1 68 212.8 62.4 16.9 222.8 65.3 209 61.2 19.3 212.7 62.4 204.8 60 21.8 209.4 61.4 203.4 59.6 22.6 203.1 59.5 200.9 58.9 24
+ 3775 67 19.4 252.4 74 175.7 51.5 17.4 242.5 71.1 172 50.4 19.7 232.2 68 168.1 49.3 22.1 228.7 67 166.8 48.9 22.9 222.3 65.2 164.5 48.2 24.3
240L 0.22 72 22.2 270.7 79.3 137 40.2 17.8 260.4 76.3 133.6 39.2 20.2 249.9 73.2 130.2 38.2 22.5 246.4 72.2 129 37.8 23.2 239.7 70.3 126.9 37.2 24.5
10649 62 16.7 242 70.9 242 70.9 17.1 232 68 232 68 19.5 221.4 64.9 221.4 64.9 21.9 217.9 63.9 217.9 63.9 22.7 211.3 61.9 211.3 61.9 24.2
5025 67 19.4 263 77.1 200.7 58.8 17.6 252.5 74 197 57.7 20 241.7 70.8 193.1 56.6 22.3 238 69.8 191.9 56.2 23.1 231.3 67.8 189.5 55.5 24.4
0.26 72 22.2 281.8 82.6 152.9 44.8 18.1 270.8 79.4 149.4 43.8 20.4 259.8 76.2 146 42.8 22.7 256.2 75.1 144.8 42.4 23.4 249.1 73 142.6 41.8 24.7
Table 5
Notes:
1. See Page 2 for legend
2. Ratings are based on 80°F (26.7°C) return air dry bulb temperature.
3. Direct interpolation is permissible. Do not extrapolate.
4. SKM Computer Selection Software are available for quick and accurate selections..
5. Shaded area in gray are at 120°F condenser entering air temperature.

* Power input mentioned in this page should not be used for cable or fuse selection. MCA and MFA values given in the electrical
data page 11 should be referred for the same.

You name it.....We cool it 9


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22

Fan Performance
Internal Static External Static Pressure in.wg (Pa)
Air Flow Rate
ACUM-L + CADX-L Pressure 0.2 (50) 0.4 (100) 0.5 (125) 0.6 (150) 0.8 (200) 1.0 (250) 1.25 (312) RPM RANGE
cfm l/s in.wg Pa RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
1146 541 0.24 59.7 615 0.11 747 0.15 808 0.17 865 0.19 972 0.24 1069 0.29 1181 0.36
050L + 050L 1700 802 0.51 127.8 787 0.27 886 0.33 933 0.35 979 0.38 1068 0.44 1152 0.51 1251 0.59
778
2292 1082 0.96 239.3 1010 0.61 1085 0.68 1122 0.72 1158 0.76 1230 0.83 1299 0.91 1383 1.01
to
1597 754 0.24 59.8 635 0.18 745 0.23 798 0.25 849 0.28 948 0.34 1040 0.39 1148 0.47
1004
060L + 060L 2000 944 0.36 90.2 737 0.32 827 0.37 871 0.40 915 0.43 1000 0.50 1082 0.56 1180 0.65
3193 1507 0.96 239.2 1098 1.17 1156 1.25 1184 1.29 1213 1.33 1270 1.42 1326 1.51 1395 1.63
1597 754 0.24 59.8 635 0.18 745 0.23 798 0.25 849 0.28 948 0.34 1040 0.39 1148 0.47 812
070L + 070L 2400 1133 0.53 131.4 853 0.52 929 0.58 967 0.62 1004 0.65 1077 0.72 1149 0.80 1236 0.89 to
3193 1507 0.96 239.2 1098 1.17 1156 1.25 1184 1.29 1213 1.33 1270 1.42 1326 1.51 1395 1.63 1047
1719 811 0.24 59.7 524 0.17 639 0.23 692 0.26 743 0.30 836 0.37 921 0.45 1017 0.55 747
085L + 085L 2800 1321 0.62 155.7 724 0.55 801 0.63 838 0.68 875 0.72 947 0.82 1017 0.92 1100 1.06 to
3438 1622 0.96 239.3 863 0.96 926 1.06 957 1.12 988 1.17 1049 1.29 1108 1.40 1181 1.55 931
2196 1036 0.24 59.7 535 0.24 632 0.31 680 0.35 726 0.39 815 0.47 898 0.55 994 0.66 702
100L + 100L 3000 1416 0.43 107.5 661 0.53 734 0.62 770 0.66 806 0.71 877 0.80 946 0.90 1030 1.03 to
4392 2073 0.96 239.2 920 1.55 970 1.67 995 1.73 1020 1.79 1069 1.91 1119 2.04 1180 2.20 875
2196 1036 0.28 69.7 554 0.26 652 0.33 699 0.36 744 0.40 832 0.48 913 0.57 1008 0.68
110L + 120L 3600 1699 0.74 185.5 804 0.94 865 1.04 895 1.09 925 1.14 985 1.25 1044 1.36 1117 1.51
798
4392 2073 1.13 282.7 963 1.65 1013 1.77 1038 1.83 1063 1.90 1113 2.02 1162 2.15 1223 2.32
to
2196 1036 0.28 69.7 554 0.26 652 0.33 699 0.36 744 0.40 832 0.48 913 0.57 1008 0.68
995
120L + 120L 3600 1699 0.74 185.5 804 0.94 865 1.04 895 1.09 925 1.14 985 1.25 1044 1.36 1117 1.51
4392 2073 1.13 282.7 963 1.65 1013 1.77 1038 1.83 1063 1.90 1113 2.02 1162 2.15 1223 2.32
3208 1514 0.24 59.7 458 0.35 534 0.44 571 0.49 608 0.54 678 0.65 745 0.77 823 0.93 564
130L + 150L 4200 1982 0.40 98.6 552 0.70 612 0.81 641 0.87 670 0.93 728 1.05 784 1.19 852 1.36 to
6417 3028 0.96 239.2 797 2.31 837 2.47 857 2.55 877 2.63 916 2.80 954 2.97 1002 3.19 704
3208 1514 0.24 59.7 458 0.35 534 0.44 571 0.49 608 0.54 678 0.65 745 0.77 823 0.93
145L + 150L 4800 2265 0.52 130.0 616 1.01 669 1.13 695 1.20 720 1.26 771 1.40 822 1.54 883 1.73
625
6417 3028 0.96 239.2 797 2.31 837 2.47 857 2.55 877 2.63 916 2.80 954 2.97 1002 3.19
to
3208 1514 0.28 69.7 471 0.37 546 0.47 583 0.52 619 0.57 688 0.68 753 0.80 830 0.95
780
160L + 150L 4800 2265 0.61 152.7 639 1.07 691 1.19 717 1.26 743 1.32 793 1.46 843 1.61 904 1.80
6417 3028 1.14 282.8 834 2.45 874 2.61 894 2.69 913 2.77 952 2.95 991 3.12 1038 3.35
4604 2173 0.29 71.1 - - 688 0.75 735 0.83 782 0.92 872 1.09 957 1.28 1056 1.53
180L + 180L 5800 2737 0.46 114.7 699 1.09 778 1.27 817 1.37 856 1.46 932 1.67 1006 1.88 1094 2.16
705
7792 3677 0.87 215.7 902 2.50 961 2.73 990 2.84 1020 2.96 1078 3.21 1136 3.47 1207 3.81
to
4604 2173 0.29 71.1 - - 688 0.75 735 0.83 782 0.92 872 1.09 957 1.28 1056 1.53
879
205L + 180L 6200 2926 0.53 132.4 739 1.31 813 1.50 849 1.60 886 1.70 958 1.91 1028 2.14 1113 2.43
7792 3677 0.87 215.7 902 2.50 961 2.73 990 2.84 1020 2.96 1078 3.21 1136 3.47 1207 3.81
6292 2969 0.29 71.1 - - 578 0.97 617 1.08 655 1.19 729 1.43 799 1.68 880 2.01
240L + 240L 8000 3775 0.47 117.0 595 1.45 660 1.68 691 1.80 723 1.93 785 2.20 845 2.49 917 2.87
629
10649 5025 0.87 215.7 762 3.22 811 3.52 835 3.67 860 3.83 908 4.15 955 4.49 1014 4.94
to
6292 2969 0.29 71.1 - - 578 0.97 617 1.08 655 1.19 729 1.43 799 1.68 880 2.01
784
260L + 240L 8000 3775 0.47 117.0 595 1.45 660 1.68 691 1.80 723 1.93 785 2.20 845 2.49 917 2.87
10649 5025 0.87 215.7 762 3.22 811 3.52 835 3.67 860 3.83 908 4.15 955 4.49 1014 4.94
Table 6

Notes:
Areas shaded in blue indicate factory setting of rpm.
Areas shaded in gray indicate operating range outside the standard motor. Shift one step larger motor size in this area.
Internal static pressure is based on pressure drops through evaporator coil, fan casing & 1” washable flate filter.
The shown rpm range is with standard pulleys combination.

10 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
ELECTRICAL DATA
POWER SUPPLY 380-415V/3Ph/50Hz
Model Unit Characteristic Compressor Condenser Fan motor Model Evaporator Fan Motor
ACUM MFA MCA ICF QTY RLA LRA QTY FLA LRA CADX FLA LRA
050L 25 15 66 1 8 62 1 0.7 2.5 050L 1.5 5.8
060L 32 18 81 1 10 74 1 1.7 5.8 060L 1.5 5.8
070L 32 21 109 1 12 101 1 1.7 5.8 070L 2.0 8.3
085L 50 27 104 1 16 95 1 1.7 5.8 085L 2.7 12.6
100L 50 28 120 1 17 111 1 1.7 5.8 100L 2.7 12.6
110L 40 30 83 2 10 66 2 0.7 2.5 120L 3.6 19.2
120L 40 30 93 2 10 74 2 0.9 4.0 120L 3.6 19.2
130L 40 30 93 2 10 74 2 0.9 4.0 150L 3.6 19.2
145L 50 34 122 2 12 101 2 0.9 4.0 150L 3.6 19.2
160L 63 36 125 2 12 101 2 1.7 5.8 150L 3.6 19.2
180L 63 48 124 2 16 95 2 1.7 5.8 180L 5.2 26.3
205L 80 51 147 2 17 111 2 2.8 11.0 180L 5.2 26.3
240L 80 56 156 2 19 118 2 2.8 11.0 240L 5.2 26.3
260L 100 62 159 2 22 118 2 2.8 11.0 240L 5.2 26.3
Table 7

POWER SUPPLY 440V/3Ph/50Hz

Model Unit Characteristic Compressor Condenser Fan motor Model Evaporator Fan Motor
ACUM MFA MCA ICF QTY RLA LRA QTY FLA LRA CADX FLA LRA
050L 25 15 66 1 9 62 1 0.7 2.5 050L 1.3 5.0
060L 32 19 81 1 11 74 1 1.7 5.8 060L 1.3 5
070L 40 22 109 1 13 101 1 1.7 5.8 070L 1.7 7.2
085L 50 29 103 1 18 95 1 1.7 5.8 085L 2.4 11
100L 50 29 119 1 19 111 1 1.7 5.8 100L 2.4 11
110L 40 31 83 2 11 66 2 0.7 2.5 120L 3.1 16.6
120L 50 32 93 2 11 74 2 0.9 4.0 120L 3.1 16.6
130L 50 32 93 2 11 74 2 0.9 4.0 150L 3.1 16.6
145L 50 37 122 2 13 101 2 0.9 4.0 150L 3.1 16.6
160L 63 36 126 2 13 101 2 1.7 5.8 150L 3.1 16.6
180L 80 50 125 2 18 95 2 1.7 5.8 180L 4.5 22.7
205L 80 54 148 2 19 111 2 2.8 11.0 180L 4.5 22.7
240L 80 59 157 2 21 118 2 2.8 11.0 240L 4.5 22.7
260L 100 67 161 2 24 118 2 2.8 11.0 240L 4.5 22.7
Table 8

Legend
MFA Maximum Fuse Amps (for fuse sizing), complies with RLA Rated Load Amps. (at worst operating condition)
NEC Article 440-22 & 430-52. LRA Locked Rotor Amps
FLA Full Load Amps
MCA Minimum Circuit Amps.(for wire sizing), complies with
NEC article 440-33.
ICF Maximum Instantaneous Current Flow

Note :
Voltage imbalance not to exceed ± 2 % of the rated voltage

You name it.....We cool it 11


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
Typical Wiring Diagram
ACUM- Models: 050L - 100L
PTB
** L1
L2
L3
N
C1 C2 C3 **SHORT
PROVIDE OVERCURRENT, EARTH FAULT PROTECTION,
CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY
LOCAL & NATIONAL ELECTRIC CODE.

T1 T3
OL2 O L3 FIELD WIRING
T2 LEGEND
R Y B BY OTHERS
C CONTACTOR
CM CFM CCH CRANK CASEHEATER
CF CONTROL FUSE
CFM CONDENSER FAN MOTOR
CF1 CF2
CM COMPRESSOR MOTOR
2A 4A CS CONTROL SWITCH
EFM EVAPORATOR FAN MOTOR
HPS HIGH PRESSURE SWITCH
C1 TH (BY O THERS) EFM
CS C1 LPS LOW PRESSURE SWITCH
C R G Y CADX-L OL OVERLOAD RELAY
PTB POWER TERMINAL BLOCK
TFR TRANSFORMER
C3
TH THERMOSTAT
TDR TIME DELAY RELAY
------ FIELD WIRING AND
TFR
CR1 CR2 FIELD SUPPLIED DEVICES
220V-240V

MODEL: ACUL-51050,51060,51070,
24V
CCH

HPS OL2
M 51085 & 51095

OL3 LPS *TYPICAL WIRING DIAGRAM SHOWN IN


SUITABLE FOR 380~415V/3Ph/50Hz ONLY.
TDR FOR 440V/3Ph/50Hz PLEASE CONSULT SKM.

CR1 CR2 C3 TDR C1 C2

N
E CONTROL CIRCUIT

ACUM- Models: 110L - 260L

PTB POWER SUPPLY (V/Ph/Hz)


**L1
L2
L3
** SHORT
PROVIDE OVERCURRENT, EARTH FAULT PROTECTION,
CIRCUIT AND DISCONNECT MEANS AS REQUIRED BY
N LOCAL & NATIONAL ELECTRIC CODE.
C1 C2 C3 C4 C5

L EGE ND
C CONTACTOR
T1 T3 T1 T3
T2 T2 OL3 OL4 OL5 FIELD WIRING CCH CRANK CASE HEATER
R Y B BY OTHERS CF CONTROL FUSE
CFM CONDENSER FAN MOTOR
CM1 CM2 CFM1 CFM2
CM COMPRESSOR MOTOR
CS CONTROL SWITCH
CF1 CF2
EFM EVAPORATOR FAN MOTOR
2A 10A FCS FAN CYCLING SWITCH
HPS HIGH PRESSURE SWITCH
C1 C2 LPS LOW PRESSURE SWITCH
TH (BY OTHERS) CS1 CS2 C1 C2
EFM OL OVERLOAD RELAY
C R G Y1 Y2 PTB POWER TERMINAL BLOCK
CADX-L TFR TRANSFORMER
C5 C5
TH THERMOSTAT
TDR TIME DELAY RELAY
------ FIELD WIRING AND
TFR FIELD SUPPLIED DEVICES
CR1 CR2 CR3
220V-240V

24V

FCS1 FCS2
CCH1

CCH2

HPS1 HPS2
*TYPICAL WIRING DIAGRAM SHOWN IN
SUITABLE FOR 380~415V/3Ph/50Hz ONLY.
M M
FOR 440V/3Ph/50Hz PLEASE CONSULT SKM.

OL5 LPS1 LPS2


OL3 OL4
TDR1 TDR2 MODELS: ACUL- 52110, 52120,
52145, 52160,
52180, 52205,
CR1 CR2 CR3 C5 TDR1 C1 TDR2 C2 C3 C4

N
52225, 52240, 52260
E CONTROL CIRCUIT

12 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
Condensing Unit Dimensional Data
Models: ACUM- 050L

[152]
6 1 4-Ø0.79[20]HOLES
2 FOR ANCHOR BOLTS

A1 L E GE ND
A3
1- CONDENSER COIL
2- CONDENSER FAN
3- CONTROL PANEL
A2 A4 4- COMPRESSOR

ALL DIMENSIONS ARE IN INCHES [mm]


[152]
6

A1-A4 ARE LOADING POINTS


28 30
[711] [762]

3
ACCESS FOR
[1024]
40.31

COMPRESSOR
[1074]
42.28

SUC.Ø POWER SOURCE


HOLE Ø1 [25]
CONTROL CIRCUIT
LIQ.Ø HOLE Ø0.75 [19]

4 1.6 8 2
1.97
[50]

28 [40] [203] [50]


[711]

Models: ACUM- 060L, 070L, 085L & 100L


[152]

2
6

[51]

A1 A3 LEGEND
1- CONDENSER COIL
2- CONDENSER FAN
1 3- CONTROL PANEL
4- COMPRESSOR

ALL DIMENSIONS ARE IN INCHES [mm]


A2 A4 A1-A4 ARE LOADING POINTS
[152]
6

38 38
2 [965] [965]

3
[1219]
47.99

[1024]

POWER SOURCE
40.31

SUC.Ø HOLE Ø1 [25]


LIQ.Ø CONTROL CIRCUIT
HOLE Ø0.75 [19]

4 ACCESS FOR
1.97

1.6 1.6
[50]

11 2 COMPRESSOR
[40] 38 [40] [279] [50]
[965]

You name it.....We cool it 13


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
Condensing Unit Dimensional Data
Models: ACUM- 110L, 120L, 130L, 145L, 160 & 180L
MODEL: ACUM- 110L, 120L, 130L, 145L, 160 & 180L
LEGEN D
[254]

A1 A3
10

1- CONDENSER COIL
2- CONDENSER FAN
4-Ø0.79[20] HOLES
2 FOR ANCHOR BOLTS 3- CONTROL PANEL
4- COMPRESSOR

ALL DIMENSIONS ARE IN INCHES [mm]


A1-A4 ARE LOADING POINTS
ACCESS
*ADD 145mm FOR MODELS 160L & 180L
FOR UPWARD CONDENSER FAN

1 M O DE LS A CUM L
DIMENSION
A2 A4 110L 120L 130L 145L 160L 180L
[254]

16.4 16.4 16.4 16.4 8.4 8.4


10

A [416] [416] [416] [416] [213] [213]

43 74
[1092] [1880]
AIR OUT
[1024]

* AIR IN
40.31
[1124]
44.25

4 SUC. Ø#1 ACCESS SUC. Ø#2


[100]

[152]
3.94

RIGGING HOLES
6

Ø0.79 [20] x 4Nos. LIQ. Ø#1 POWER SOURCE LIQ. Ø#2


HOLE Ø1 [25] CONTROL CIRCUIT
HOLE Ø0.75[19]

Models: ACUM- 205L, 240L & 260L


4-Ø0.79[20] HOLES
FOR ANCHOR BOLTS
[254]
10

A1
A2

ACCESS

1
[254]

A3 A4
10

43 80
[1092] [2032] 2
3
[1472]
57.96

[1227]
48.31

AIR IN
[247]
9.72

4
[100]

[152]
3.94

CONTROL CIRCUIT
6

RIGGING HOLES SUC.Ø #1 HOLES Ø1 [25] SUC.Ø #2


Ø0.79[20] x 4Nos. LIQ.Ø #2
LIQ.Ø #1 POWER SOURCE
HOLES Ø 1 1/2 [38]

14 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22

Air Handling Unit Dimensional Data


Models: CADX-050L to 150L

1.5 0.75
MODEL DIMEN SION S [38] [19]

1.97
[50]

[89]
3.5
CADX L W H A B C D E F J G
A CCESS
050L 45 48 21.2 20 37.5 16 17.48 17.48 1.61 11.38 13.03
[1143] [1219] [538] [508] [952] [406] [444] [444] [41] [289] [331]
060L 45 48 25.2 24 38 20 17.48 17.48 1.69 11.38 13.03 A1 A3
[1143] [1219] [640] [610] [965] [508] [444] [444] [43] [289] [331]
070L 45 48 25.2 24 38 20 17.48 17.48 1.69 11.38 13.03
[1143] [1219] [640] [610] [965] [508] [444] [444] [43] [289] [331]
45 55 25.2 24 45 16 19.72 19.72 2.24 13.43 15.55
085L [1143] [1397] [640] [610] [1143] [406] [501] [501] [57] [341] [395]

B
50 56 27.2 26 46 20 20.2 20.2 3.50 13.43 15.55
100L [1270] [1422] [690] [660] [1168] [508] [514] [514] [89] [341] [395]
50 56 27.2 26 46 20 20.2 20.2 3.50 13.43 15.55
*120L [1270] [1422] [690] [660] [1168] [508] [514] [514] [89] [341] [395]
FILTER
58 70 30.2 29 60 25 25.73 25.73 2.48 15.91 18.54
*150L [1474] [1778] [767] [737] [1524] [635] [653] [653] [63] [404] [653]
REMOVAL

LEGEND *MODELS WITH DOUBLE CIRCUITS A2 A4


1- EVAPORATOR FAN USE DRAIN SIZE 1[25] FOR MODELS 150L&180L 4-Ø0.5 [13]

[165]
2- EVAPORATOR FAN MOTOR

6.5
MOUN TIN G HOLES
ALL DIMESIONS A RE IN INCHES [mm]
3- EVAPORATOR COIL A1-A4 ARE LOADING POINTS
4- 1"THK. FLAT FILTER

W L
USE DRAIN SIZE Ø1[25] FOR MODELS 150 to 240
D G E
F

1 2 3 4

LIQ.Ø
J

SUC.Ø
S/A
A
H

C
R/A

CABLE
EN TRY Ø
[30]

[83]
1.2

3.3

DRAIN Ø3/4 [19]


2.5 ACCESS
[63]

Models: CADX-180L & 240L


MODEL: CADX-180L & 240L
1.5 4-Ø0.5 [13] .7
[102]

MOUNTING HOLES
[50]

4
2

[38] ACCESS [19]


MODEL DIMENSIONS
CADX L W H A H1 B D E F J G

180L 60 70 33.2 32 1.2 60 13.2 13.2 8.98 13.43 43.7


[1524] [1778] [843] [813] [30] [1524]
[334] [334] [228] [341] [1109]
61.4 MODEL
92 35.2 33.5 1.8 82DIMENSIONS
19.86 19.86 6 15.91 52.28
240L C DX [895]
CA
CADX
[1560] [2337] L [850]
W H[45] A [2083]
H1 [504]
B [504]
D [152]
E F[404] J [1328]
G

180L 60 70 33.2 32 1.2 60 13.2 13.2 8.98 13.43 43.7


[1524] [1778] [843] [813] [30] [1524] [334] [334] [228] [341] [1109]
LEGE ND 61.4 92 35.2 33.5 1.8 82 19.86 19.86 6 15.91 52.28
240L [1560] [2337] [895] [850] [45] [2083] [504] [504] [152] [404] [1328]
1- EVAPORATOR FAN
2- EVAPORATOR FAN MOTOR
B

3- EVAPORATOR COIL
4- 1"THK. FLAT FILTER
LEGE ND
1- EVAPORATOR FAN
ALL DIMENSIONS ARE IN INCHES [mm]
A1-A4 ARE LOADING POINTS 2- EVAPORATOR FAN MOTOR
3- EVAPORATOR COIL FILTER
4- 1"THK. FLAT FILTER REMOVAL

ALL DIMENSIONS ARE IN INCHES [mm]


A1-A4 ARE LOADING POINTS A CCESS
[152]
6

W 1 L
[25]
D G E
1 2 4

SUC.Ø#1 5
F

LIQ.Ø#1
SUC.Ø#2
J

LIQ.Ø#2 S/A
A
H

[635]
25
[83]

CABLE ENTRY
3.3
H1

2.5 Ø 1 [25] DRAIN Ø1 [25]


[63]

You name it.....We cool it 15


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
WEIGHTS & LOADING POINTS
Weights:
LOADING POINTS LOADING POINTS
TOTAL TOTAL
CONDENSING A1 A2 A3 A4 WEIGHT AIR HANDLING A1 A2 A3 A4 WEIGHT
UNIT ACUM UNIT CADX
lbs lbs lbs lbs lbs lbs lbs lbs lbs lbs
kg kg kg kg kg kg kg kg kg kg
79 82 79 81 321 59 55 48 43 204
050L 050L
36 37 36 37 146 27 25 22 19 93
87 91 87 89 354 65 61 53 47 225
060L 060L
39 41 39 40 161 29 28 24 21 102
89 93 89 91 363 65 61 53 47 225
070L 070L
40 42 40 41 165 29 28 24 21 102
110 114 110 112 446 76 71 62 55 265
085L 085L
50 52 50 51 202 34 32 28 25 120
112 116 112 114 453 81 84 73 72 310
100L 100L
51 53 51 52 206 37 38 33 33 141
171 171 173 173 688 87 90 78 78 334
110L 120L
78 78 78 78 312 39 41 36 35 151
173 173 175 175 697 87 90 78 78 334
120L 120L
79 79 80 80 316 39 41 36 35 151
176 176 178 178 707 115 120 104 103 442
130L 150L
80 80 81 81 321 52 54 47 47 200
177 177 179 179 713 115 120 104 103 442
145L 150L
80 80 81 81 324 52 54 47 47 200
194 194 196 196 780 119 124 108 107 459
160L 150L
88 88 89 89 354 54 56 49 49 208
214 214 216 216 860 119 133 105 113 469
180L 180L
97 97 98 98 390 54 60 48 51 213
235 235 238 238 946 119 133 105 113 469
205L 180L
107 107 108 108 429 54 60 48 51 213
226 226 229 229 909 171 192 152 162 678
240L 240L
103 103 104 104 413 78 87 69 74 308
227 227 230 230 913 171 192 152 162 678
260L 240L
103 103 104 104 414 78 87 69 74 308
Table 9

Recommended Suction and Liquid Line Sizes:


PIPE LENGTH - FEET (m)
Models
25 (7.6) 50 (15.2) 75 (22.9) 100 (30.5)

Circuit A Circuit B Circuit A Circuit B Circuit A Circuit B Circuit A Circuit B

Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction Liquid Suction
050L 050L 1/2 7/8 - - 1/2 7/8 - - 1/2 7/8 - - 1/2 1 1/8 - -
060L 060L 1/2 7/8 - - 1/2 1 1/8 - - 1/2 1 1/8 - - 1/2 1 1/8 - -
070L 070L 1/2 7/8 - - 1/2 1 1/8 - - 1/2 1 1/8 - - 5/8 1 1/8 - -
085L 085L 1/2 1 1/8 - - 1/2 1 1/8 - - 5/8 1 1/8 - - 5/8 1 3/8 - -
100L 100L 1/2 1 1/8 - - 5/8 1 1/8 - - 5/8 1 1/8 - - 5/8 1 3/8 - -
110L 120L 1/2 7/8 1/2 7/8 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
120L 120L 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8
130L 150L 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8
145L 150L 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8
160L 150L 1/2 7/8 1/2 7/8 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8
180L 180L 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8
205L 180L 1/2 1 1/8 1/2 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8
240L 240L 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8 5/8 1 3/8
260L 240L 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 1/8 5/8 1 3/8 5/8 1 3/8 3/4 1 3/8 3/4 1 3/8
Table 10
Notes :

1. Pipe diameters are based on equivalent length of copper tubing sizes.


2. Pipe sizes are based on 2ºF (1.1ºC) or less temperature losses for liquid and suction line in equivalent pipe length.
3. If the condensing unit is below the evaporating unit, the maximum lift should not exceed to 66 feet.
4. Do not exceed 100 feet piping length without checking with SKM.
5. These sizes are for guidance only. For detailed proper piping, refer to recognized piping references like ASHRAE
Guide and Data Book.

The recommended or required suction and liquid line sizes do not necessarily correspond with the refrigerant
connections available on the outdoor or indoor unit. Necessary transformation may be required and it’s field performed.

16 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22

Recommended Clearances
UNIT CLEARENCE

SPACING FOR AIR FLOW SPACING FOR SERVICE

ALL DIMENSIONS ARE IN INCHES[mm] 30 30


[762] [762]

[762]
30
[762]
30

[1143]
45
[762]
30

30 30
[762]

[762] [762]
30

ACUM- 050L to 100L


30 30
SINGLE UNIT [762] [762]
ACUM- 050L to 100L

MULTIPLE UNIT

UNIT CLEARENCE

SPACING FOR SERVICE SPACING FOR AIR FLOW

ACUM- 110L to 260L

52 52
[1321] [1321]
[1322]

[1322]
52

52
[762]
30
[762]
30
[1322]

[1322]
52

52

SINGLE UNIT

52 88 52
[1321] [2235] [1321]
[1322]

[1322]
52

52
[762]

[762]
30

30
[762]

[762]
30

30
[1322]

[1322]
52

52

MULTIPLE UNIT

You name it.....We cool it 17


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22

Installation and Commissioning

• Install the unit in such a location which is flat and strong enough to support its weight.

• All field wiring must comply with applicable local and national codes.

• Service spacing should be provided as shown in the figure. If any obstacles are around the unit, distributed air is short-circuited
so that the unit stops frequently and access to the unit is difficult for inspection and aftersales services.

INSTALLATION & COMMISSIONING

SPACING FOR SERVICE SPACING FOR AIRFLOW

No obstacle

3000mm
AIR OUT
No obstacle
3000mm

AIR OUT
AIR OUT

L
RO
NT E L
L CO PAN IN
RO
NT EL
A IR
AI
CO PAN R IN

R IN
AI

A IR
IN
ION
CT
UI D SU LI NE
LI QLI NE UI D N
LIQLINE UCTINOE
S LI AIR
IN
IN
A IR
L
RO
NT UIT OL
COCIRC IT TR IT
CU R ON CU
CIROWE C CIR
R P IN
WE IT
POIRCU
A IR AIR
C
UID
IN
LIQLINE
ACUM- 050L
ION
CT
SU LINE
ACUM- 110L to 145L

No obstacle
3000mm

No obstacle
3000mm

AIR OUT

L
RO
NT EL A IR
CO PAN IN
AIR OUT
I N
A IR

ION
CT
UID SU LINE
LI QLINE RO
L
NT E L
CO PAN IN
R IN A IR
AI
L
RO
NT IT
C OCIRCU
A IR
R
WE IT
IN
POI RCU
C
UI D I ON
ACUM- 060L to 100L LIQLINE CT E
SU LIN AIR
IN

OL
IT TR IT
CU R ON CU
CIROWE C CIR
P IN
AIR AIR
UID
IN
LIQLINE

ION
CT
SU LINE
ACUM- 160L to 260L

18 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22

Typical Refrigeration Piping


LEGEND
1 SIGHT GLASS 4 SHUT OFF VALVE
2 SOLENOID VALVE 5 LIQUID LINE
3 FILTER DRIER 6 SUCTION LINE

NOTE:- EXPANSION VALVE


INSIDE CADX L

ACUM L CADX L

1 R /A
6 2
5 3
4

CADX L
LEGEND
1 SIGHT GLASS 4 SHUT OFF VALVE
2 SOLENOID VALVE 5 LIQUID LINE
R/
A 3 FILTER DRIER 6 SUCTION LINE

1
2 NOTE:- EXPANSION VALVE
INSIDE CADX L
3
4

6 ACUM L
5

* INVERTED TRAP WITHOUT PUMP DOWN CONTROL.


DOTTED WITH PUMP DOWN CONTROL.

Refrigerant Piping:
Correct design and size of refrigerant piping is necessary to proper operation. The refrigerant piping generally should be
designed to accomplish the following:

a) To ensure proper refrigerant feed to the evaporator.

b) To provide practical refrigerant line sizes without excessive pressure drop.

c) To maintain uniform return of lubricating oil to the compressor.

d) To prevent refrigerant from entering the compressor and causing compressor damage due to “slugging”.

You name it.....We cool it 19


SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
GUIDE SPECIFICATIONS
GENERAL CONDENSING UNIT CASING
Split air conditioner shall be composed of a ceiling suspended air Units casing shall be made of hot dip galvanized steel sheets
handling unit & floor mounted air cooled condensing unit, rated (zinc coated) conforming to JIS-G3302 and ASTMA525 that
in accordance with AHRI standards 210 / 240 and 340 / 360. shall be phosphatized and then electrostatically dry powder
Unit should be capable to operate in a wide range of ambient coated of approx 60 microns to provide an extremely tough,
temperatures from 50°F (10°C) to 125°F (52°C) and shall be scratch resistance, excellent anti corrosive protection that
selected in accordance with project requirements and installed can pass 1000 hours in 5% salt spray testing at 95°F relative
as per Instruction, Operation & Maintenance Manual. humidity as per ASTM B117.

CONDENSING UNIT AIR HANDLING UNIT CASING


The unit casing for CADX-L is made of zinc coated galvanized
The condensing unit shall be composed of compressor(s), coil(s)
steel sheets conforming to JIS-G3302 and ASTM A525 which
and condenser fan(s) and motor(s).
is phosphatized and baked after an electrostatic powder coat
of approximately 60 microns. This finish and coating can pass
a 1000 hour in 5% salt spray testing at 95°F (35°C) and 95%
COMPRESSOR relative humidity as per ASTM B117. Panels and casing are
Compressor shall be hermetically sealed, compact high efficiency insulated with 1” (25mm) thick fiberglass (with BGT coating)
and low noise scroll type. These compressors are refrigerant gas thermal and acoustic insulation having density of 2 lb/ft³. (32
cooled, furnished with advanced scroll temperature protection kg/m³) and thermal conductivity of 0.23 BTU.in/ft²°Fh (0.033
or internal motor protection. W/m°K). Insulation meets the requirements of NFPA 90A and
90B for fire resistance.

CONDENSER COIL(S) EVAPORATOR COIL


Condenser coils shall be air cooled with integral sub cooler, Evaporator coil shall be constructed of inner grooved copper
constructed of special inner grooved seamless copper tubes tubes 3/8” OD mechanically bonded to aluminum cross wave fins.
3/8” OD mechanically expanded into waffle louver aluminum Coil consists of headers of seamless copper tubing, thermostatic
fins. These coils shall be tested against leakage by air pressure expansion valve(s) & multi-circuited distributor(s). These coils
of 450 psig (3100 kPa) under water, cleaned & dehydrated at shall be tested against leakage by air pressure of 300 psig (2068
the factory. Kpa) under water, cleaned & dehydrated at the factory. Coil shall
conform to AHRI-410.

CONDENSER FAN(S) & MOTOR(S) EVAPORATOR FAN AND MOTOR


Condenser Fans shall be direct driven propeller type discharging Fans of evaporators shall be forward curved, double inlet
air vertically upward, equipped with statically & dynamically double width (DIDW), centrifugal type, Statically & dynamically
balanced aluminum alloy blades, inherent corrosion resistant balanced, mounted on a single heavy duty statically & shaft
shaft & PVC coated steel wire fan guard. Condenser fan with permanently lubricated bearings & driven by V belt with
motor(s) shall be Totally Enclosed Air Over (TEAO), 6 poles an adjustable variable pitch motor pulley. Motor shall be Totally
with class-F insulation, minimum IP55 protection & wired to Enclosed Fan Cooled (TEFC), 4 poles, class-F insulated,
unit control panel. minimum IP55 protection & wired to unit control panel.

CONTROL PANEL FILTERS


Outdoor condensing units shall be provided with IP-54 control Air handling units shall be provided with air filter. Filter should
panel enclosure comprising all starting, operating and safety be 1” (25mm) standard or 2” (50mm) thick optional washable
controls. Following shall be the standard components used in aluminum media with average dust arrestance 54% based on
the condensing unit control panel: ASHRAE standards 52.1.

• All compressors shall be with DOL starting.


• Individual compressor and condenser fan motor contactors.
• Overload relays for condenser fan motors.
• Control Relays and control circuit fuses.
• Control disconnect for each refrigerant circuit.
• Anti-short cycle timer for compressors.
• 24V Control Transformer.
• Starter (contactor & overload relay) for indoor unit evaporator
fan motor.
• Power and control terminal blocks.

20 YYou
You
Yo nname
ou name
na
ame iit.....We
me it.....We
t......
..W ccool
We cool
We oo iit
ol it
t
SKM Split Air Conditioners
ACUM-L + CADX-L Series - R22
Spare Parts Division
Sharjah, United Arab Emirates
Tel: +971 6 5347347
Fax: +971 6 5349292
Email: spareparts@skm.ae
HEAD OFFICE
P.O Box: 6004 Service Centre
Sharjah, United Arab Emirates Sharjah, United Arab Emirates
Tel: +971 6 5347347 Tel: +971 6 5347347
Fax: +971 6 5349292 Fax: +971 6 5349292
Email: sales@skm.ae Email: aftersales@skm.ae

REGIONAL OFFICES
UAE Saudi Arabia
Abu Dhabi P.O Box: 27788 AL Messila HVAC Equipment Factory
Abu Dhabi, United Arab Emirates (Part of SKM A/C factory in
Saudi Arabia)
Tel: +971 2 6445223 Saudi Arabia, Eastern provenance
Fax: +971 2 6445145 AD Dammam
Email: abudhabisales@skm.ae 2nd industrial city
Al Ain Al Ain, United Arab Emirates Abqiq main road Hail Street
Tel: +966 3 8123332 / 4 / 5
Tel: +971 3 7619921 Fax: +966 3 8123337 / +966 3 8123092
Fax: +971 3 7619941
Email: alainsales@skm.ae Egypt
Dubai P.O Box: 98822 9 Mosadak Street,
3rd floor, Dokki, Giza, Egypt
Dubai, United Arab Emirates Tel: +20 2 37619617 / +20 2 37621974
Tel: +971 4 2940900 Fax: +20 2 37621973
Fax: +971 4 2940029 Email: egyptsales@skm.ae
Email: dubaisales@skm.ae
Algeria
Kuwait Aissat Idir ( EX-ENMA) City
P.O Box: 1215-PC 15463 Bldg1, Flat 2, Dar El Beida Algiers,
Dasman, Kuwait Algeria
Tel: +965 2 2492200 Tel: +213 21 508197
Fax: +965 2 2494400 Fax: +213 21 508197
Email: kuwaitsales@skm.ae Email: algeriasales@skm.ae

DISTRIBUTORS
Saudi Arabia Qatar
info@fawazgroup.com Mannai Trading Co. WLL
P.O Box: 76
Al Khobar Doha, Qatar
Fawaz Ref. & Air Conditioning Co.
P.O Box: 1189 Tel: +974 4 4558787 / +974 4 4558788
Al Khobar, Saudi Arabia Fax: +974 4 4558781
Tel: +966 3 8598666 Email: dohasales@skm.ae
Fax: +966 3 8598520 HVAC@mannai.com.qa
Email: abarbarawi@fawazgroup.com
Jeddah Iraq
Fawaz Ref. & Air Conditioning Co. Al Rawbitt Al Iraqia Co.
P.O Box: 13218 Erbil – Bagdad – Basra
Jeddah, Saudi Arabia Tel: +964 7507441111
Tel: +966 2 6691848 +964 7711117776
Fax: +966 2 6608316 +965 99608916
Email: jamal@fawazgroup.com
Email: info@alrawabitt.com
Riyadh
Fawaz Ref. & Air Conditioning Co. Iran
P.O Box: 85123 Hivasanat 4th Floor, Building. No. 74,
Riyadh, Saudi Arabia 5th Golestan Ave.
Tel: +966 1 4794499 Abazar Blvd Ayatollah Kashani Exp.,
Fax: +966 1 4785354 Tehran
Email: saleem@fawazgroup.com Tel: +98 21 44951422 / 23
Fax: +98 21 44952135
Jordan Email: info@hivasanat.com
Ideal A/C Systems Co. L.L.C
Al Gardenz Street, Building 111, Kuwait (for Unitary Products Only)
Al Bakri Complex British Link Kuwait (BLK)
P.O Box 5502 Amman, Jordan 11953 P.O Box: 53054 Al Nuzha
Tel: +962 6 5538640 Tel: +965 1820099
Fax: +962 6 5538641 Fax: +965 22465005
Email: tariq@idealac.com Email: rawad@blk.com.kw

You name it.....We cool it 077/2013 A 21