ELECTRICAL LOAD ASHIRWAD CHS BUILDING AT VIRAR(W)

Fire Emergency
Load (KW) only
lighting

Sr.No Connected Demand QTY Total Connected Total Demand


. Area Description Load (KW) Load (KW) (NOS) Load (KW) Load (KW)
I GROUND FLOOR PLAN
SHOP-1 to SHOP-14 46.98KW 33.08KW 14 46.98KW 33.08KW

II FIRST FLOOR PLAN


SHOP-1 to SHOP-11 44.08KW 32.81KW 11 44.08KW 32.81KW

II FIRST FLOOR PLAN


OFFICE - 1 35.75KW 25.64KW 1 35.75KW 25.64KW
OFFICE - 2 8.50KW 6.10KW 1 8.50KW 6.10KW
OFFICE - 3 7.04KW 5.05KW 1 7.04KW 5.05KW
BANQUET HALL 13.66KW 9.65KW 1 13.66KW 9.65KW
TOTAL FOR COMMERCIAL PART 156.03KW 112.33KW

IV RESIDENTIAL TOWER
1RK (290sft) 6.97w/sqft 2.02KW 1.35KW 13 26.28KW 17.52KW
1BHK (441sft) 6.97w/sqft 3.07KW 2.05KW 2 6.15KW 4.10KW
1BHK (496sft) 6.97w/sqft 3.46KW 2.30KW 30 103.72KW 69.14KW
1BHK (510sft) 6.97w/sqft 3.55KW 1.42KW 43 152.86KW 61.14KW
2BHK (720sft) 6.97w/sqft 5.02KW 2.01KW 28 140.52KW 56.21KW
2BHK (785sft) 6.97w/sqft 5.47KW 2.19KW 15 82.07KW 32.83KW
3BHK (947sft) 6.97w/sqft 6.60KW 2.64KW 15 99.01KW 39.61KW
TOTAL FOR RESIDENTIAL PART 610.61KW 280.55KW

VI COMMON AREA
EXTERNAL LIGHTING LOAD 2.50KW 2.50KW
1 LIGHTING AND POWER LOAD 30.00KW 18.00KW 6.66
2 LIFT 12.00KW 9.60KW 2 24.00KW 19.20KW
3 PLUMBING:
3.1 DOMESTIC PUMP- 10HP 7.46KW 4.48KW 2 14.92KW 8.95KW
3.2 FLUSHING PUMP- 7.5HP 5.60KW 3.36KW 2 11.19KW 6.71KW
3.4 RAIN WATER COLLECT SUMP PUMP 2.24KW 1.34KW 1 2.24KW 1.34KW
3.5 STP ELECRICAL LOAD (120 KLD) 18.00KW 10.80KW 1 18.00KW 10.80KW
TOTAL COMMON AREA LOAD IN 84.85KW 56.71KW

VII FIRE EMERGENCY LOAD


1 HYDRANT PUMP- 75 HP 55.95KW 55.95KW
2 SPRINKLER PUMP- 75HP 55.95KW 55.95KW
3 JOCKEY PUMP- 7.5HP 5.60KW 2 11.19KW
4 BOOSTER PUMP- 12.5HP 9.33KW 2 18.65KW
5 LIFT-2NOS 12.00KW 9.60KW 2 24.00KW 24.00KW
TOTAL OF TOWER 166KW

TOTAL I,II,III,IV, V & VII


WITHOUT FIRE EMERGENCY LOAD 851.5KW 449.6KW
KVA @ 0.8PF 562.0KVA
RECOMMENDED KVA FROM
SUPPLY COMPANY 562.0KVA

D.G SET - 1 FOR RESIDENTIAL


BUILDINGH
FOR RESIDENTIAL &
COMMERCIAL, BUILDING
DG RATING:
TOTAL FIRE EMERGENCY LOAD 142.6KW
KVA @ 0.8PF 178.2KVA
80% LOADING OF DG SET 222.8KVA
RECOMMENDED DG RATING 250.0KVA

NOTE: IN CASE ON NORMAL POWER FAILURE THE DG WILL GIVE BACK UP TO COMMON AREA OF THE BUILDING (LIKE:
LIFTS, PUMPS AND COMMON AREA LIGHTING).
IN CASE OF FIRE EMERGENCY THE DG WILL GIVE BACK UP TO ONLY FIRE PUMPS AND FIRE LIFTS.