Fire Emergency
Load (KW) only
lighting
IV RESIDENTIAL TOWER
1RK (290sft) 6.97w/sqft 2.02KW 1.35KW 13 26.28KW 17.52KW
1BHK (441sft) 6.97w/sqft 3.07KW 2.05KW 2 6.15KW 4.10KW
1BHK (496sft) 6.97w/sqft 3.46KW 2.30KW 30 103.72KW 69.14KW
1BHK (510sft) 6.97w/sqft 3.55KW 1.42KW 43 152.86KW 61.14KW
2BHK (720sft) 6.97w/sqft 5.02KW 2.01KW 28 140.52KW 56.21KW
2BHK (785sft) 6.97w/sqft 5.47KW 2.19KW 15 82.07KW 32.83KW
3BHK (947sft) 6.97w/sqft 6.60KW 2.64KW 15 99.01KW 39.61KW
TOTAL FOR RESIDENTIAL PART 610.61KW 280.55KW
VI COMMON AREA
EXTERNAL LIGHTING LOAD 2.50KW 2.50KW
1 LIGHTING AND POWER LOAD 30.00KW 18.00KW 6.66
2 LIFT 12.00KW 9.60KW 2 24.00KW 19.20KW
3 PLUMBING:
3.1 DOMESTIC PUMP- 10HP 7.46KW 4.48KW 2 14.92KW 8.95KW
3.2 FLUSHING PUMP- 7.5HP 5.60KW 3.36KW 2 11.19KW 6.71KW
3.4 RAIN WATER COLLECT SUMP PUMP 2.24KW 1.34KW 1 2.24KW 1.34KW
3.5 STP ELECRICAL LOAD (120 KLD) 18.00KW 10.80KW 1 18.00KW 10.80KW
TOTAL COMMON AREA LOAD IN 84.85KW 56.71KW
NOTE: IN CASE ON NORMAL POWER FAILURE THE DG WILL GIVE BACK UP TO COMMON AREA OF THE BUILDING (LIKE:
LIFTS, PUMPS AND COMMON AREA LIGHTING).
IN CASE OF FIRE EMERGENCY THE DG WILL GIVE BACK UP TO ONLY FIRE PUMPS AND FIRE LIFTS.