ESTIMASI 

KEBUTUHAN LISTRIK PADA BANGUNAN
Nama Bangunan  RUMAH SAKIT UMUM DAERAH
Lokasi KABUPATEN CIANJUR
Jumlah Lantai       5
Luas Tanah
Luas Bangunan 3,283 m2

RINCIAN LUAS BANGUNAN
LANTAI LUASAN (m²) TOTAL (m²)
GEDUNG DIAGNOSTIC CENTER
Lantai 1 1,262 m2
Lantai 2 1,010 m2
3,283 m2
Lantai 3 680 m2
Roof Top 331 m2
GEDUNG IBS
Ground Floor 394 m2
Lantai 1 1,270 m2 2,879 m2
Lantai 2 1,215 m2
TOTAL 6,162 m2
PARAMETER STANDAR
Jenis / Fungsi  Misc Power  Air Conditioner  Demand 
Standar Lighting VA/m2
Bangunan VA/m2 VA/m2 Factor 
Rumah Sakit ME for BUILDING 33 11 60 0.8
Halls /  corridors ME for BUILDING 5 0 0

ESTIMASI KEBUTUHAN LISTRIK TIAP LANTAI

LANTAI LUAS  LIGTHING AIR CONDITIONER MISC. POWER TOTAL DAYA


m² kVA kVA kVA kVA
GEDUNG DIAGNOSTIC CENTER
Lantai 1 1,262 m2 42 76 14 132
Lantai 2 1,010 m2 34 61 12 107
Lantai 3 680 m2 23 41 8 72
Roof Top 331 m2 11 20 4 35
GEDUNG DIAGNOSTIC IBS
Ground Floor 394 m2 14 24 5 43
Lantai 1 1,270 m2 42 77 42 161
Lantai 2 1,215 m2 41 73 41 155
TOTAL (KVA) 705

ESTIMASI KEBUTUHAN LISTRIK PERALATAN
PERALATAN KAPASITAS
UNIT kVA
LIFT 20
MOBILE XRAY 5
MAMOGRAPHI 5
MRI 50
CT‐SCAN 80
ROTGEN 5
POMPA 15
HYDRANT 150
TOTAL (KVA) 330
     TOTAL

Lighting 207 kVA


Air Conditioner 372 kVA
Misc. Power 126 kVA
T. Connected Load 1035 kVA
Demand Factor 0.8
Diversity Factor 1.2
Peak Load 690 kVA

KEBUTUHAN PLN
865 kVA

KEBUTUHAN PERALATAN
System Voltage ( P-P ) 400 Volt Linear Load: General Equipments, Heater
System Voltage ( P-N ) 230 Volt Non-Linear Load: UPS,Invertor,Ballast,VFD
Future Load Expansion 0% % 1
Average Intermittent Use of
0.8 (0.7 To 1.0) 0.8
Equipment
Total Connected Load on Diesel Generator Set Starting Condition Running Condition
Load Full Full Full
Sr.N Starting Running Diversity Motor Starting Starting Starting
Equipment Load Type Supply Qty Load Load Load
o Load Kw/Hp P.F P.F Factor Starter Amp Kva Kw
Kva Kw Amp RESULTS
1 Total Load RSUD CIANJUR Non-Linear 3Ph 1 692 Kw 0.8 0.8 0.8 Y-D 1598 1107 886 1107 886 999 Starting Kva 1107
0 0 0 0 0 0 Starting Kw 886
0 0 0 0 0 0 Starting Amp 1598
0 0 0 0 0 0 Running Kva 1107
0 0 0 0 0 0 Running Kw 886
0 0 0 0 0 0 Running Amp 999
0 0 0 0 0 0 Alternator Details
0 0 0 0 0 0 Voltage (P-N) 230
0 0 0 0 0 0 Efficiency 80%
0 0 0 0 0 0 Engine Overload Capacity 130% (Appro 130% To 150%)
0 0 0 0 0 0
0 0 0 0 0 0 Required Generator Rating
0 0 0 0 0 0 Generator KVA 886 (Select D.G near This Value)
0 0 0 0 0 0 Engine KW 921
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0 Calculate D.G Set Efficiency & Unit Calculate Approximate
0 0 0 0 0 0 Rate of Power Fuel Consumption
0 0 0 0 0 0 D.G Size ( Kva ) 1000
0 0 0 0 0 0 D.G P.F 1 D.G Size (Kva) 115
0 0 0 0 0 0 D.G Running Hours 20 D.G P.F 0.8
0 0 0 0 0 0 Diesel Consumption (Liter) 1000 D.G Operation Full Load
0 0 0 0 0 0 KWH Reading of Meter 10000
0 0 0 0 0 0 M.F of KWH Meter 1 Required Diesel
0 0 0 0 0 0 Diesel Rate /Liter (Rs) 40 Liter/Hour 23.11
0 0 0 0 0 0 Efficiency of D.G 50%
0 0 0 0 0 0 KWH/Liter (Unit Per Liter) 10
0 0 0 0 0 0 Unit Rate of Power (Rs) 4.0
0 0 0 0 0 0
PERHITUNGAN KEBUTUHAN TRAFO
01- (MV/LV)
Primary Rated Voltage (kV.) = 20.0
Secondary Rated Voltage (kV.) = 0.400
Max. Demand Load (kW) = 828
PF. After Correction = 0.8
Max. Apparent Power (KVA) = 1035
Trans. Type = oil
Permissible loading percentage (%) = 80
Calculated Trans. Rating (KVA) = 1293.75
The Nearest standard Trans. Rating (KVA) = 1500
Transformer Loading percentage (%) = 69
SUCCEED RATING