You are on page 1of 1

KANOHAR|

KANOHAR ELECTRICALS LIMITED


MEERUT (INDIA)
TRANSFORMER TO is: 20265
KVA 2000 coOLING ONAN
vOLTS AT NO LOAD
HV11000 FREQUENCY Hz
LV 433 IMPEDANCE VOLTAGE 10

AMPERES
HV 104.97
LV 2666.74
VECTOR GROUP
CORE & WNDING KG
Dyn-1
2575 EE
HV WEIGHT OF OL KG 1235
PHASES
LV3 VOLUME OF OIL LTR 1488
MAX TEMP RISE OIL/WOG. C 50 55 TOTAL WEIGHT
KG5935
WINDING MATERIAL COPPER YEAR OF MANUFACTURE 2008

CUSTOMER'S REF.
DIAGRAM DRG. NO.
MAKER'S SERIAL NO.|

OFF CIRCUIT TAP CHANGER NO LOAD VOLTAGE


CONNECTIONS H.V. L.V.
SWITCH POSITION
6 11550 433
11275 433
4-7 11000 4 33
7-3 10725 433
3-8 10450 433

NCT S /2w i2u


2N 2U 2V 2W 1W
2N2V 1V

10 1W
VECTOR GROUP-Dyn1
BIL(kV)
WTI CT HV LI75AC28
105/1.5A
7.5VA
CLASS-5
NCT
3000/1A, CLASS PS,

[ 4 0 RCT + 20ov],
30mA AT Vk/2

09