POWER TRANSFORMER DETAILS

MAKE : VENKATESWARA
SL NO : 197
TYPE : Copper wound Transformer
STANDARD : IS: 2026
RATED POWER : 10 MVA/16 MVA
RATED VOLTAGE HV : 110 KV
LV : 22/11 KV
RATED CURRENT HV : 84 A
LV : 420/840 A

IMPEDANCE VOLTAGE %:
MAX TAP : 11.79
NOR TAP : 10.16
MIN TAP : 10.03
MAX TEMP RISE IN OIL : 50 C
MAX WDG TEMP : 55 C
MAX AMBIENT TEMP : 50 C
PO.NO:
CE/TR/SE/TRII/ET/A1/T-1855/PO.TR.2602/D.232/14.Dt:20.09.2014
ON LOAD TAP CHANGER
MAKE : CTR
TYPE :RMV 111 200 D 110/66 12 21 26
SERIAL NO :33678
YEAR OF MANUFACTURE :2014
CONTROL CIRCUIT VOLTAGE :110V
DRIVE MOTOR SUPPLY : 415V
TAPPING POSITION :1 to 21
DIRECTION OF POWER FLOW :Forward

BUSHING CT DETAILS

CT DETAILS CURRENT RATIO


HV BUSHING CT 90/1A
LV BUSHING CT 450/0.577A
HV WTI CT 90/1.75A
LV WTI CT 450-900/1.75A

LV LINK CONNECTIONS

KV PHASE 2U PHASE 2V PHASE 2W


11KV 1-4 1-4 1-4
2-3 2-3 2-3

22KV 4-3 4-3 4-3