This document provides a technical specification for a 1000 KVA, 3 phase, 60 Hz power transformer. Key details include copper windings, a Dyn11 vector group, delta-star winding configuration, 13800V rated high voltage and 400-231V rated low voltage. The transformer has an efficiency of 98.39% at 100% load and 99.03% at 50% load, with regulations of 1.45% at unity power factor and 4.5% at 0.8 power factor. It is an ONAN cooled, ground mounted unit meeting IEC-60076 standards, using mineral oil as insulation.
This document provides a technical specification for a 1000 KVA, 3 phase, 60 Hz power transformer. Key details include copper windings, a Dyn11 vector group, delta-star winding configuration, 13800V rated high voltage and 400-231V rated low voltage. The transformer has an efficiency of 98.39% at 100% load and 99.03% at 50% load, with regulations of 1.45% at unity power factor and 4.5% at 0.8 power factor. It is an ONAN cooled, ground mounted unit meeting IEC-60076 standards, using mineral oil as insulation.
This document provides a technical specification for a 1000 KVA, 3 phase, 60 Hz power transformer. Key details include copper windings, a Dyn11 vector group, delta-star winding configuration, 13800V rated high voltage and 400-231V rated low voltage. The transformer has an efficiency of 98.39% at 100% load and 99.03% at 50% load, with regulations of 1.45% at unity power factor and 4.5% at 0.8 power factor. It is an ONAN cooled, ground mounted unit meeting IEC-60076 standards, using mineral oil as insulation.
Number of Phases 3 Rated Frequecncy Hz 60 Rated High Voltage V 13800 Rated Low Voltage V 400-231 Winding Material [HV/LV] Copper No.of HV Taps +/- 2 X 2.5 % Vector Group Dyn11 Connection [LV/HV] Delta - Star Insulation class A Impedance[%] WILL FURNISH LATER Max.Ambient Temp 50ºC Temp.Rise [Oil/Winding] 50/55ºC Type of Cooling ONAN No.of Terminals[HV/LV] HV - 3 , LV - 4 No.Load Loss[W] WILL FURNISH LATER Load Loss at Principal Tap[W] WILL FURNISH LATER Power Frequency Test Voltage HV 38KV Power Frequency Test Voltage LV 3KV Primary Rated Current A 41.89 Secondary Rated Current A 1443.38 HV Bushing Position Tank Longer Wall LV Bushing Position Tank Longer Wall ɳ @ 100% @ UPF 98.39 ɳ @ 50% @ UPF 99.03 % Regulation @UPF 1.45 % % Regulation @ 0.8PF 4.5 % Transformer type Hermitically Sealed type Mounting type Ground Mounted Paint RAL-7033 Standard / Specs. IEC-60076 Oil Type Mineral Oil
Transformer Accessories : 36KV-630A-C-TYPE Porcelain Bushing-1KV-1800A 5-Position Tap changer DGPT Pressure relief valve Drain Valve Rating and Diagram Plate