You are on page 1of 1

TRANSFORMER SIZING

Topse Process Solutions Pvt. Ltd.


Client Name: Krishna Anti oxidents Prepared By: AV
Project No: P-2324-29 Checked By: AP
Document No: P-2324-29-ELE-DOC-03 Approved By: SS
Date: 45281 Rev: R0

Sr. No. Description Total Connected Diversity Loading Total Running


Load(KW) Factor Factor Load(KW)
1Ø/3Ø 1Ø/3Ø
A Process Equipments
A.1 Process equipments 1803.00 0.96 0.80 1384.00

B Utility MCC panel


B.1 Utility MCC panel 785.00 0.72 0.80 454.00

C Lighting
C.1 All rooms 87.00 0.96 0.96 76.00

D ETP & MEE


D.1 ETP & MEE 40.00 1.00 0.80 32.00

SUBTOTAL 2715.00 1946.00


5 % Contigency 136.00 97.00
TOTAL (KW) 2851.00 2043.00
POWER FACTOR 0.95 0.80
TOTAL (KVA) 3002.00 2554.00
Running Load 2554.00
Maximum Demand (KVA) 2554.00
Suggested Transformer 3000.00
% loading on transformer 0.85