You are on page 1of 5

Block No. 89, Survey No.

113/2, Opposite Navapura Patiya,


Village: Motaborasara, At: Kim, Taluka: Mangrol,Dist : Surat, Gujarat, INDIA
Email ID: nikhil@kaypee.co.in ; info@kaypee.co.in
Cell No. +91 92277 66696 / 93289 08676 / 88668 34177
LEADING MANUFACTURERS OF POWER & DISTRIBUTION TRANSFORMERS
AWARDED BIS CERTIFICATION UPTO 2500 KVA & ISO 9001:2015 UNIT
Ref : OFFER/KPC/APL/22-23/301 DATE : 17.02.2023
M/s. Acutesun Private Limited [GSTIN: 24AAXCA9449F1Z4]
rd
“Victoria Palae” B-301, 3 Floor,
VIP Circle, Near White House,
Utran, Mota Varachha,
Surat – 394 105 [Gujarat]
Kind Attn : Mr. Jay Kumar
Email : purchase@acutesun.com : admin@acutesun.com
Sub : Offer for 800 KVA / 11 KV /0.433 KV Transformer with OLTC as per IS :
1180 (Level-I)
Ref : Telephonic discussions
[As per New Guidelines from BIS for Old Level-2 is now known New Level-1
applicable from 01.04.2022]
Dear Sir,

We are thankful to you for your interest in our product and welcome your inquiry.

With reference to your requirement of Transformer, we are pleased to quote


Energy Efficient & Cost effective lowest price for design, manufacturing, testing &
supply of 800 KVA, 11/ 0.433KV “Energy Efficient Transformer with On Load Tap
Changer as per IS : 1180 (Level-I) as per following Annexure:

1. Technical Particulars : ANNEXURE – A


2. Specification and Fittings : ANNEXURE – B
3. Price, Commercial Terms & Condition : ANNEXURE – C

It is our sincere effort to provide you with a product of Top most quality at very
affordable price. We ensure that, product is tasted as per INDIAN STANDARD
norms.

Thanking you in anticipation.

Yours truly,
For Kay Pee Corporation

Yogendra (Nikhil) Satbhaya Hiren Patel


Vice President (Sales & Sales Promotion) Partner
Mob : +91 93289 08676 / +91 92277 66696 Mob : +91 88668 34177
Email: nikhil@kaypee.co.in Email: info@kaypee.co.in
Contd to Page….2/-
LEADING MANUFACTURERS OF POWER & DISTRIBUTION TRANSFORMERS

AWARDED BIS CERTIFICATION UPTO 2500 KVA & ISO 9001:2015 UNIT

TECHNICAL PARTICULARS - ANNEXURE “A”

No. ITEM Unit PARTICULARS


1.01 GENERAL SPECIFICATIONS:
1 Make “KAY PEE”
2 Rated KVA KVA 800 KVA
Energy Efficiency Transformer
3 Service & Duty Continuous, Step down
Distribution Transformer
4 Type Oil Cooled
5 Location Outdoor
6 Type of Cooling ONAN
7 Wound Copper Double Wound
1.02 SYSTEM PARTICULARS:
1 Nominal Voltage (V) V 11000
2 Highest System Voltage (V) V 12000
3 No. of Phases 3
4 Frequency (Hz) Hz 50
5 Voltage Variation ± 10 %
6 Frequency Variation ±3%
7 Combined Voltage and Frequency variation ± 10 %
1.03 TERMINAL ARRANGEMENT:
1 HV 11KV/250 A Cable Box
2 LV 1.1KV/1250 A Cable Box
3 Orientation of HV & LV 180 Degree
1.04 RATING:
1 Rated Voltage of H.V. (Volts) V 11000
2 Rated Voltage of L.V. (Volts) V 433
3 Rated current of HV (Amps) A 41.99 @ U P F
4 Rated current of LV (Amps) A 1066.73 @ U P F
5 Temperature Rise (in Oil) 40 ºC
6 Temperature Rise (in Winding) 45 ºC
1.05 WINDING CONNECTION DETAILS:
1 Connections:
a. H.V. Winding Delta
b. L.V. Winding Star
c. Neutral brought out for Earthling Yes, Solidly Earthed
2 Tapings on HV Winding For HV Variation
a. No. of Positions 17 Positions
b. Range ± 10% in steps of 1.25% by OLTC
3 Tap Switch Make MacPower
4 Vector Symbol Dyn 11

Contd to Page….3/-
LEADING MANUFACTURERS OF POWER & DISTRIBUTION TRANSFORMERS

AWARDED BIS CERTIFICATION UPTO 2500 KVA & ISO 9001:2015 UNIT

TECHNICAL PARTICULARS - ANNEXURE “A”

No. ITEM Unit PARTICULARS


1.06 LOSSES AND OTHERS:
1 Total Losses @ 50% Load Watts 2287 (Maximum)
2 Total Losses @ 100 % Load Watts 6402 (Maximum)
3 % Impedance at 75 ºCat normal Tap % 5%
4 No Load Current Approx. Less than 3% of full load current
1.07 EFFICIENCY:
1 Efficiency at 75 Degree C @UPF @ 0.8 P F
a. 100% Full Load % 99.222 99.029
b. 75% Full Load % 99.348 99.187
c. 50% Full Load % 99.436 99.295
d. 25% Full Load % 99.417 99.273
2 Maximum efficiency (Percentage) % 99.417 %
3 Load at which Max. efficiency occurs kVA % At 42 % Load
1.08 REGULATION @UPF @ 0.8 P F
1 @100% Load 0.792 3.572
2 @75% Load 0.571 2.667
3 @50% Load 0.365 1.770
1.09 % RESISTANCE 0.6688
1.10 % REACTANCE 4.955
1.11 Power Frequency Apply
1 HV 28 kV
2 LV 3 kV
1.12 Impulse Voltage withstand HV/LV 75 Kv / Nil
1.13 OVERALL DIMENSIONS (Approximate):
Length x Width x Height Mm 3500 x 2100 x 2200
1.14 OVERALL WEIGHT (Approximate):
1 Core & Winding Kgs 1830
2 Tank & Fitting Kgs 1600
3 Oil ( 1070 Kgs) Ltrs 1185
4 Total Kgs 4600
1.15 I.S. REFERENCE As per IS : 1180 (Leval-I)
1.16 I.S. TOLERANCE % ± 10 %
1.17 MATERIALS
1 CONDUCTOR E.C. Grade D.P.C. Copper Wire & Strips
2 LAMINATION CRGO., HP - 80/90 Grade
3 INSULATION “A” Class
4 PAINT Epoxy Quoted Paint
5 OIL POWER OIL (IS-335/1993)

Contd to Page….4/-
KAY PEE CORPORATION
SPECIFICATION AND FITTINGS - ANNEXURE “B”
No Description Qty

1 Oil conservator complete with plain oil level gauge, filling hole with 1 No
cap and drain Plug.
2 Silica gel dehydrating breather – (for main transformer tank) 1 No
3 Explosion Vent 1 No
4 Thermometer Pocket 2 Nos
5 Lifting Lugs for Tap cover 2 Nos
6 Air release plug for main tank 1 No
7 Top Oil Filter Valve 1 No
8 Bottom Filter cum Drain Valve 1 No
9 Manual Operated Off Circuit Tap Changer 1 No
10 Pressed Steel Cooling Radiators 4 Nos
11 HV Cable Box (11KV/250A) 1 No
12 LV Cable Box (1.1KV, 1250A) 1 No
13 Additional natural bushing for solid/ NGR Earthing (1.1KV, 250A) 1 No
14 Rating Diagram Plate 1 No
15 Bi-Directional Flat Roller – Optional 4 Nos
16 Lifting Lugs for complete Transformer 4 Nos
17 Plain Oil Level Gauge 1 No
18 Inspection Cover 1 No
19 Jacking Pad 4 Nos
(Applicable for 1600 KVA Rating and above Ratings) – {Optional}
20 OPTIONAL PROTECTION applicable for 1000 KVA Rating & above
I Marshalling Box with O.T.I & W.T.I. with Alarm and Trip contact 1 No
II Buchholz Relay 1 No
III Magnetic Oil Level Gauge (M.O.G.) {Optional @ Extra Cost} 1 No

List of Routine Tests

Name of Routine Test Unit Ex-Works (Kim) Price

Measurement of Load Losses & Current FREE


Measurement of No Load Losses & Current FREE
Measurement of Winding Resistance FREE
Measurement of voltage ratio & checking of vector FREE
relationship
Measurement of Insulation Resistance FREE
Measurement of Impedance Voltage FREE
Induced Over Voltage Withstand Test FREE
Separate Source Voltage Withstand Test FREE
BDV Test of Oil FREE

Note: All above Routine Tests as described in IS 2026 / IS 1180 (Part-I), shall be
Carried out at our works Free of cost. Any Type / Special Tests, if required,
shall be carried out at our works on chargeable basis ONLY.
Contd to Page….5/-
LEADING MANUFACTURERS OF POWER & DISTRIBUTION TRANSFORMERS

PRICE, COMMERCIAL TERMS & CONDITIONS - ANNEXURE “C”

RATING 800KVA / 11 / 0.433KV with OLTC as per Level - I


18,81,000=00
UNIT PRICE-INR
[INR: Eighteen Lacs Eighty One Thousand Only]
Extra as applicable. Present rate of GST is @18%. However,
GST Taxes & Duties prevailing at the time of dispatch will be
levied.
PRICE VARIATION FIRM, Till Order execution.
F.O.R. Freight/Transit Insurance to be arranged & paid by Purchaser
PACKING INCLUSIVE (For Domestic Supply only)
Octroi / Entry Tax Extra, if applicable to your Account
a) 40% Advance with Purchase Order
PAYMENT b) Balance with 100% Taxes & Duties against Performa
Invoice prior to Dispatch.
Minimum 1-2 months after receipt of Purchase Order along
DELIVERY with approved drawings and Advance. However, delivery
shall be agreed upon during finalization of order.
VALIDITY Offer is valid for 7 days from the date of Offer
THIRD PARTY We welcome Third party Inspection and Testing. Expenses for
INSPECTION the same will be borne by you
We also welcome your Testing Engineer for final Inspection &
TESTING
Testing at our works
18 months from the date of dispatch against manufacturing
WARRANTY
defect and poor workmanship only
We are able to provide you additional support in terms of
Standby
Arrangement
Stand by Transformer, which is available with us within short
period.
ACCESSORIES Additional Accessories, require will be charged EXTRA
INTEREST & We will issue Inspection call before 7 days of readiness of
STORAGE COST transformer for Routine Tests Inspection at our works. In case,
TOWARDS NON
If you will not organize inspection as per scheduled date &
LIFTING OF
TRANSFORMER time, you will have to make payment immediately failing
IN STIPULATED which, we will charge Interest @24% p.a. plus 1% storage
TIME charges per week from the date of readiness of Transformer.
If the delay cause due to event of Natural Calamities like Earth
quake, cyclone, tsunami, riot, war or any other unforeseen
FORCE
circumstances that may result from an Act of GOD, we are not
MAJEURE
liable for any penalty.
Jurisdiction Subject to S U R AT Jurisdiction