You are on page 1of 6

Technical Specification of Distribution Transformers (11/0.

416 kV) Ministry of Electricity (MoE)/IRAQ

Schedule "A"

Schedule of the Guaranteed Performance and Other Technical


Particulars (To be filled by the Tenderer for each rated capacity of
100, 250, 400, 630, and 1000 kVA).

No. Description Unit Specifications


Required Proposed
1 General
1.1 Manufacturer Name To be filled in ATC
1.2 Country of Manufacturing To be filled in KSA
1.3 Type
1.4 Model To be filled in 1000KVA
1.5 Applicable Standards IEC 60076 IEC60076
1.6 Location of service Outdoor Outdoor
1.7 Short circuit Test Report
1.8 Date of carried out To be filled in
1.9 Testing laboratory name and To be filled in
country
1.10 Certificate Provided Yes
2 Ratings
2.1 Continuous maximum rating KVA To be filled in 1000KVA
2.2 Rated voltage ratio
 Primary kV 11(+2 x 2.5%/- 11(+2 x 2.5%/-
2 x 2.5%) 2 x 2.5%)
 Secondary kV 0.416Y/0.24 0.416Y/0.24
2.3 Number of phase 3 3
2.4 Frequency Hz 50 50
2.5 Vector group symbol Dyn11 Dyn11
2.6 Cooling method ONAN ONAN
2.7 Maximum temperature rise at
rated power
 Top oil by thermometer K 45 45
 Winding by resistance K 50 50
 Hot spot of winding max K To be filled in 115
ambient temperature (550 C)
2.8 Impedance voltage at continuous % To be filled in
5
rated power
2.9 Winding connection:
 Primary Delta Detla
 Secondary Star (Neutral Star
brought out)

Page 15 of 19
Tolerance:+/-5%
Technical Specification of Distribution Transformers (11/0.416 kV) Ministry of Electricity (MoE)/IRAQ

3 Rated insulation level for Primary


 Impulse withstand voltage kV peak 75
75
(1.2/50μs)
 One minute 50Hz withstand kV rms 28 28
voltage
4 Design Details
4.1 Off-load tap changer
 manufacturer To be filled in CAPT/equivalent
 Tapping range +5%/-5% +5%/-5%
 Tapping step 2.5% 2.5%
4.2 Exciting current referred to HV
side and 50 Hz
 At 90% rated voltage. A To be filled in -
 At 100% rated voltage. A To be filled in -
 At 110% rated voltage. A To be filled in -
4.3 Power factor of exciting current % To be filled in -
at 100% rated voltage and 50 Hz
4.4 Iron losses at 50 HZ
 At 90% rated voltage. kW To be filled in 1.15
 At 100% rated voltage. kW To be filled in 1.6
 At 110% rated voltage. kW To be filled in 1.77
4.5 Copper losses at full load (on kW To be filled in
9.7
rating) and at 750 C
4.6 Total losses. (kW) To be filled in 11.3
4.7 Resistance voltage at full load (%) To be filled in 1.1
and at 750.
4.8 Reactance voltage at full load (%) To be filled in
4.88
and at 750
4.9 Impedance voltage at full load
750:
 At normal tap. (%) To be filled in 5
 At highest tap. (%) To be filled in 5.25
 At lowest tap. (%) To be filled in 4.75
4.10 Resistance of HV winding per Ω To be filled in
1.194
phase at 200 C
4.11 Resistance of LV winding per Ω To be filled in 0.00063
phase at 200 C
4.12 Regulation at full load at 750 C
 At 1.0 power factor. To be filled in 1.13%
 At 0.8 p.f lagging. To be filled in 4.15%
4.13 Efficiency at 750 C:
 At 100% load (%) To be filled in 98.9
 At 75% load (%) To be filled in 99.06 98.95

Page 16 of 19
Tolerance:+/-5%
Technical Specification of Distribution Transformers (11/0.416 kV) Ministry of Electricity (MoE)/IRAQ

 At 50% load (%) To be filled in 99.20


 At 25% load (%) To be filled in 99.12
4.14 Calculated thermal time constant Hrs. To be filled in 6
4.15 Maximum flux density at normal
voltage and frequency and at
normal ratio for:
 Core. (KI/sq.cm) To be filled in 1.7
 Yoke. (KI/sq.cm) To be filled in 1.7
4.16 Maximum flux density at 110%
voltage and frequency and at
normal voltage and frequency
and at normal ratio for:
 Core (KI/sq.cm) To be filled in 1.87
1.87
 Yoke (KI/sq.cm) To be filled in
4.17 Insulation level of:
 Core bolts. kV To be filled in 3

 Core bolts washer. kV To be filled in 3

 Side plates. kV To be filled in 3

 Core laminations. kV To be filled in


4.18 Current destiny in windings for:
 H.V. winding (Amps/sq.c To be filled in
0.0305
m)
 L.V. winding (Amps/sq.c To be filled in
0.0305
m)
4.19 Insulation on copper. To be filled in Enamel/paper
4.20 Insulation strength of winding.
a) Impulse full wave for:
(I) H.V. (kV) To be filled in 75
(II) L.V. (kV) To be filled in -
b) Impulse chopped wave
for:
(I) H.V. (kV) To be filled in 95
(II) L.V. (kV) To be filled in -
c) Applied voltage test (kV) To be filled in HV 28/LV 3
d) Induced voltage test (kV) To be filled in 22/0.832
4.21 Insulation strength of terminals.
 Over voltage test (kV) To be filled in 28
 Minimum wet withstand (kV) To be filled in 28
voltage
 Minimum impulse withstand (kV) To be filled in 75

 Minimum puncture or oil- (kV) To be filled in 28


immersed withstand voltage

Page 17 of 19
Tolerance:+/-5%
Technical Specification of Distribution Transformers (11/0.416 kV) Ministry of Electricity (MoE)/IRAQ

4.22 Type of core To be filled in CRGO


4.23 Max. noise level at 0.3 meter (dB) 55 55
4.3 Type of oil (As per IEC Yes YES
requirement )
4.4 Standards IEC 60296 IEC600296
4.5 Type of corrosion protection
• Inside tank To be filled in Shot blast
• Outside tank To be filled in Powder Coating with shot blast

4.6 Type of valves Clobe or gate Gate valve


valve
5 Dimension And Weight
5.1 Dimension of Transformer
 Under base to top most point. mm To be filled in 1800
 Under base to bushing mm To be filled in 1300
mounting flanges.
 Overall breadth. mm To be filled in 1400

 Overall length. mm To be filled in 1700


 Crane lift for untanking mm To be filled in 1970
core and coils
 Crane lift for removal of mm To be filled in
2100
bushings
5.2 Overall shipping dimensions of mm To be filled in 1700 1400 1800
the largest package
5.3 Thickness of transformer tank
 Sides. (mm) To be filled in 4

 Bottom. (mm) To be filled in 4

 Corrugated radiators. (mm) To be filled in 1.5


5.4 Volume of insulating oil (liter) To be filled in 650
5.5 Net weight of insulating oil (Kg) To be filled in 560
5.6 Total weight of transformer less (tons) To be filled in
2.44
oil
5.7 Weight of the largest shipping (tons) To be filled in 3.0
package
5.8 Net weight of core (Kg) To be filled in 1048
5.9 Net weight of copper
 H.V. (Kg) To be filled in 223

 L.V. (Kg) To be filled in 163


5.10 Net untanking weight of:
 Core (Kg) To be filled in 1048

 Frame (Kg) To be filled in 30


386
 Coil (Kg) To be filled in

Page 18 of 19
Tolerance:+/-5%
Technical Specification of Distribution Transformers (11/0.416 kV) Ministry of Electricity (MoE)/IRAQ

Schedule "B"
Oil Characteristics Table (To be filled by the Tenderer).

No. Description Unit Specifications


Required Proposed
1 Name of manufacturer To be filled in CHEMAOIL
Country of manufacturing To be filled in KSA

Type To be filled in Mineral oil


Standards IEC 60296 IEC60296

2 Reference Name of Oil To be filled in Uninhibited


3 Sludge Value % 0 0.8%

4 Flash Point (Closed) 


C To be filled in 135
5 Pour Point 
C To be filled in -40
6 Viscosity at 210 C CST To be filled in 8
7 Breakdown voltage (after kV >60 ex works
>60
treatment) ( >70 upon
treatment)
8 Acidity(Neutralization
Value): 0.03
 Total mgKOH/g To be filled in
 Inorganic
9 Saponification Value mgKOH/g To be filled in 157
10 Copper Diceleration To be filled in -
11 Crackle To be filled in -

12 Specific Gravity To be filled in 0.875


13 Sulfur Content To be filled in Not General req

14 Dielectric Dissipation Factor ≤ 0.001 ≤0.001


at 90 °C (after treatment)

Page 19 of 19

You might also like