Quick Reference Guide: Greenheck Method
Quick Reference Guide: Greenheck Method
GREENHECK METHOD
Steps 1 through 4 are the steps required to obtain the total exhaust rate using the Greenheck Method.
QE
See page 14 for an example calculation.
QF
QC
49
App_Des Guide v6 Nov 04.qxp 8/17/05 8:14 AM Page 50
HOOD FACTORS
50
App_Des Guide v6 Nov 04.qxp 8/19/05 7:31 AM Page 51
The table to the right ranks various ways of introducing Tempered MUA GOOD No Air Conditioning
make-up air into a kitchen, both tempered and
untempered. To use the chart follow these steps: Perforated Ceiling Back Supply Plenum
1. Decide whether the goal is comfort or low cost. Perforated Face Air Supply Plenum
2. Choose how to introduce make-up air into the kitchen
per the column reflecting either comfort or cost. Back Supply
Perforated Face
Plenum
Notice supply options that have superior performance Air Supply Plenum Perforated Ceiling
are listed first and decrease in performance near the Variable Supply Variable Supply
bottom of the list. Plenum Plenum
Register Face Air Curtain
Recommended Supply
Supply Type Dimensions
Rate
inches cfm/linear ft. fpm
The table to the right lists the various methods Back Supply 6 wide 145 290
of supplying air to the space. The
Air Supply Plenum 12 wide 110 150
recommended supply rate columns list the
External
recommended airflow for each supply option in Air Supply Plenum 24 wide 180 150
two ways. Variable Supply 11 high
160 150
Plenum 9 wide
Choose the appropriate supply option and use
Face Supply
either the corresponding cfm/lineal ft or the 18 wide 150 150
Plenum
velocity in feet per minute when designing or
Perforated 16 high
adjusting the system for maximum 150 150
Combination 8 wide
performance.
Register 12 high
130
Combination 8 wide
Perforated Face 16 high 150 150
Internal
13
51
App_Des Guide v6 Nov 04.qxp 8/17/05 8:14 AM Page 52
52
App_Des Guide v6 Nov 04.qxp 8/17/05 8:14 AM Page 53
13
53