Professional Documents
Culture Documents
Service Manual
MONITOR422 .
MONITOR 441
MONITOR 2 2 MONITOR 41
MONITOR 21, MONITOR 40
MONITOR HEATING SYSTEMS
Section 2: Installation
NOTE: Fuel tank musr be a minimum 3 feet away from flue pipe.
MONITOR HEATING SYSTEMS
Section 3: Operation
Figure 3-1,INDICATORS
11 12 13 14 15
OPERATION
21 22 23 10 17 18 19 20
- -~
Figure 3-2, ttemi4 3rd Indicator Light Programs 3rd automatic heater operation as
same as 1st Indicator Light.
Figure 32,ttem15 4th Indicator Light Programs 4th automatic heater operation as
same as 1st Indicator Light.
Figure 3-2,Item16 TIME push-button This switch is used to set time and change
switch display over.
Figure 3-2,Item17 TEMP push-button This switch is used set temperature and
switch change display over, in 2 degree increments.
figure 32,Item18 HOUR/UP, Programs time or temperature.
MINUTE/DOWN . NOTE: Each time push-button switch is
repetitiveaction pressed, the digit advances in incre-
push-button switch ments of one digit, If push-button is
pressed and held, the digits are
advanced repetitively.
Figure 3-2.Item19 SET push-button switch 'Sets' time and/or temperature.
If this control is not pressed after time and/or
temperature have been programmed, the time
and/or temperature programmed (as indicated
by display window) will not be accepted, and
will revert to previously programmedtime and/
w tempemre.
figure 32,Item20 CLEAR push-button switch Erases any programmed time and temperature.
When cleared, time and/or temperature previ-
ously pmgrammed and displayed disappear@)
frwn window.
IMPORTANT: Both current time and auto-
matically programmed
tims(s), tampamture(r) will
have to be reprogrammed tf
.kcblal operation is inter-
rupted by power failure or by
dbcocmecting heater plug
fmm wall outlst beyond 5
mkurbss nthh otarrs, the
h t o r will go brto MANUAL
mode of opemtion and main-
tahrr#wntwnpsmtureacwfd-
ing to ttm setting bmperature
you've #leded by using the
Jide sdector for the rseet
tempemmatthekwarrigtlt
hand Jde ot ths cabinet
ON/OFF push-button ON position (push-button is 'in')applies power
Figure 3-2,kern21
switch to the unit. When this occurs, the RUN indica-
tor lights to indicate that heater operation has
begun.
OFF position (push-button is 'our) remove
power fmm the heater. All circubexwpt for
Clock and Air Row -are shut down.
MONITOR HEATfNG SYSTEMS
Section 3: Operation
3-TI ,OUT OF N E L , Install the tank with the arrow pointing forward, and
During either manual or automatic operation of close the tank cover.
heater. fuel in the tank may be depleted.
The Monitor (in case of using external fuel tank) is STEPS: Turn.Heater ON
known to be out of fuel when all of the following Press ON O f f switch to ON. Proceed with normal
symptoms are present heater operation.
- Burner Status indicator lights blink. 342 RECOVERY FROM A POWER FAILURE
- Absence of flame (visually verified through view For the power intemption of up to 5 minutes, the
set memory is- kept and will resume operation
plate on wall of Combustion Chamber).
automatically with the set memory.
For power intemptions beyond 5 minutes, heater
m.Tum Heater OFF will resume operation (after a 3 minutes cool down
Press ON/OR switch to O R .
period) in the MANUAL mode and maintain room
temperature according to the setting temperature
STEP2: . Flll Fuel Tank
selected by ustng the SLIDE SELECTOR for the
A, Close shut-off valve at outlet of ~ u eTank.
l
reset temperature at the lower right hand side of
5. Drain Fuel Tank (from battom; if possible) to
the Cabinet
remove all condensation, debris, and old fuel.
When the TIME push-button switch is pressed or
C, Fill Fuel Tank with fresh, crystal clear kerosene.
. D. Upon completion of stepC. open shut-off valve the TIMER SElECTOR push-button switch is pressed
which was closed in stepA above. to illuminate the CLOCK SET indicator light, the
Display Wlndow will show 88:88 indicating the
STEP3: Turn Heater ON need to reset the clock and re-program the heater
Press ON!OFF switch to ON. Proceed with normal for automatic aperation.
heater operation. REMAM In wrkr to dispby mmt temperature,
It .hould be wt before tfie heater is
The Monitor 422 (in case of using capsule .fuel tank)
plugged h and energized.
is known to be out of fuel as follows:
New rewt tsmpemtaire selected after
When the E M P N indicator light illuminates plugged kn will take effect only after a
and flashes, a buaer will sound for twenty powsr-
seconds. The burner mode is changed to 'Low"
automatically, and Men, the heater will shut off
after 30 minutes. 3-13 RECOVERY FROM OVERHEAT
The Monitor is protected against damage resulting
The remaining burning time is indicated at the
from an ovetrtteat condition by two 110'C (Monitor
Display Window.
422).nsc (Monitor441) automatic reset tfmnostats.
Refueling: h the event of an overneat the thennostats are
triggered to cut off the flow of kerosene to. the
STEPk 1urn Heater OFF B u m Pat. the flame is extinguished automatically,
Press ONfOFF switch and wait 15 minutes for the
heater to tool.
a user is alerted to Fhe condition by
blinkin0 of the Bumer Status indicatws.
STEP2. Utt Out the Capsuk Fuel Tank To recover from an overheat condition. as
--
Open the tank carer and lift out the capsule fuel diin@d below:
tank
STEPI: Turn OFF Heater
Turn the tank upside down. and remove the fuel
. -2: Allow Monitor H d e r to cod
Fill the Capsule Fod Tank NOTE: Bewrettmtheaterbscodtotwch.
Fill the capsule fuel tank with fresh, c-1 clear
kerosene by using a siphon. A period of 30 to 6minutes should be sufficient to
permit heater to cool completely.
-4: M&I tht hpwk Fuel tank
Replace and tighten the fuel caD.To insure proper unplug mbr
fuel flaw, be sure the cap is secured Disconnect heater power cad from wall outlet
Section 3: Operation
-
from exterior of cabinet, including exterior of Com-
bustion Chamber and Heat Exchanger. m.Tum M m b r ON
M ReplacsLouver Aswmbiy STEPlO: Reprogram heater
OPERATION SW
SENSOR SW
I ( ROOM TEMP
SET TEMP .-
/
FLAME I
I
PHOTO TRIAC.
PHOTO COUPLER
L E D INDICATOR
I l l
i b ' I BUZZER -
MONITOR HEATING SYSTEM:S
Section 4: Maintenance
,....._
Check ail fuel pipes for leaks and 3/S" OD copper tubing Fuel piping must be secure and
loose connections tree of leaks; Replace tubing
when necessary.
lnspect exhaust piping tor leaks or Ali exhaust pipes must be covered
loose connections by a elath insulation caver.
If cloth cover shows signs of
discoloration at joints, check
o-rings.
Check fuel for water and/or ether Fuel color should be crystal clear.
contamination. if fuel is contaminated, see Cor-
If the capsule tank is used on the rective Maintenance procedure,
Monitor 422 the capsule tank filter paragraph 4-9,
should be checkecl, cleaned or
replaced, as weil as the constant
levet valve strainer.
lnspect Fuel Pipe for obstruction
lnspect electrical wiring for
cracks, signs of deterioration, bare
WA'RNING:
wires and;or loose connectors UNPLUG HEATER BEFORE PRO-
CEEOING. HEATER MUST ALSO
BE COOL BEFORE SiARTING.
Clean heater Clean, lint-free elath and a mild Wipe down exterior of heater cabi-
non-abrasive household cleaning net. Vacuum heater interior (if
agent. USE ONL Y NON- necessary).
PETROLEUM DISTILLAïE
CLEANERS.
Clean Air Circulation Fan (Monthly) Vacuum fan cage. Wipe tan
blades.
lnspect airpiping tor leaks or loose Look for cracks, wear, or signs of
connections. deterioration; replace if necessary.
lnspec:t rubber Air Hose at rear of
heater.
Clean fuel constant leve! Valve Clean Kerosene Reter to paragraph 4-5. Procedure
filter. lnspect fusible link Valve is described in paragraph 4-6.
input fltting. Check Leveling Guide.
_,
Clean only if necessary. Verity that
heater is leve!.
lnspect flue _pipe for obstruction tf blocked, clean and vacuum.
or corrosion. tf corroded badly, replace.
35
MONITOR HEATING SYSTEMS
Section 4: Maintenance
lnspect air holes in Sumer Pot Use a smal!, stitf brush or a short
length of soft copper wire to clean
any blocked heles.
The M422 may need air holes
reamed with a torchtip cleaner if
partially black on a 5 tc 7 year
basis.
Clean lgniter Scrape any carbon deposits from
igniter.·
Check air piping that interconnect Replace air piping that is wom.
Combustion Blower and Air Pres- broken or brittle.
sure Switch.
Check for cartlon build up in fuel Disconnect copper fuel piping from
inlet going into bum chamber (every bum chamber and clear fuel inlet
year) tine by reaming with a solid pieœ of
wire(such as copper,bailing wire,or
coat hanger) which should be able
to go in approximately 3" without
obstruction.
NOTE: Removing anti retightening
bumer fuel connection
must be done when the
burner cools down com-
pletely. If it is done when
the bumer is hot. the weld-
ing on the fuel joint may
break. Fixing targue for
nut;30-40kg • cm(26
-35lb•in)
4-3 INSPECT EXHAUST1AIR PIPING securely, especially at joints.
Verity that ali exhaust and air pipes are free of leaks C. Tum heater ON.
and loose connections, as specified below: O. Carefully apply a small amount of soapy water
(with a paint brush) to the surface areas of the
STEPl: Remove Protective Cloth air/exhaust piping.
Remove cloth insulation cover(s) from ali exhaust Any leaks that may exist will be readily
pipes. identified by the appearance. of bubbtes.
STEP2: Inspection of Exhaust/Air Piping STEP3: Retum to Operating Condition
A. Visually inspect beth air and exhaust piping tor A. Tum heater OFF.
obvious cracks, leaks, or .loose connections. B. Dry ali pipes with paper towels.
Black carbon deposits may be evidence of C. Repair any leaks that have been tound (if
these leaks, and' o-rings may need to be necessary, replace the tubing).
replaced. 0. Replace elath insulation covers.
8. Be sure that ali pipes are installed tightly and 36
MONITOR HEATING SYSTEMS
Section 4: Maintenance
s:
A Turn heater ON.
Look (downward) ttlrough window on the Corn~
bustionChamber. Verity that igniter is glowing.
caver plate at the bottom of the Fuel Constant
Levet Valve. Remove the cover plate.
NOTE: Position a six inch U shaped piece of metal
If igniter does not glow, something is wrong. or cardboard under strainer cover to drain
Refer to the Troubleshooting Chart in Section 6 fuel into a pan.
of this Service Manual tc diagnose the problem. B. Caretully remove the rubber gasket which is
C. An altemate inspection is to fee! the igniter located behind the covPr plate.
caver atter the unit has been in the ignition
STEP2: Inspection and Cleaning
stage tor about 5 minutes. lt should be warm.
A. Pull the filter straight out of the fuel reservoir.
8, If the filter is dirty (but undamaged), rinse the
CAlJTION: If igniter is broken,do not operate the filter in fresh, clean kerosene tc remove ali
·oN 10FF" switch button repeatedly. particles. Replace damaged filters.
C, To drain off upper portion of fuel constant leve!
STEP3: Reassembly of Heater valve, back out phillips head screw which is
Tum the heater OFF and replace the Louver Assem· located slightly above and tc the lett of filter
bly. cover plate. (See Fig4-1)
O. If upper portion drain is dirty or containing
4-5 CLEAN FUEL CONSTANT LEVEL VALVE FIL· water. then remove pump and inspect and
TER clean its screen.
Contaminants are trapped by the filter tc prevent
them from clogging the Fuel Constant Leve! Valve. STEP3: Reassembly
A. Push the (new or cleaned) filter back into the
The filter, itself has a great number of small pores. bottom of the fuel reservoir.
Whenever a filter is tom or disfigured ·(enlarged 8. Replace both the. rubber gasket and the cover
pores), it should immediately be replaced. plate. (Take . care to properly align the screw
lnspect and clean the filter as indicated by the heles in the gasket and cover plate).
procedure below: C. Wipe up any spilled fuel.
--:-?
==--d
StTainer ----.;~·d"• ....,
SIJainer
eo-r :___==~-~<· . Strainer
1
Stra•ner
Caver
~~~~J~
/ .. ._.
37
MONITOR HEATING SYSTEMS
Section 4: Maintenance
4-6 CLEANING NSIBLE UNK VALVE INTAKE FIS- STEPP: Installation of New Fuse
TING ON M422 A, Install a new fuse into the fuseholder. The fuse
At periodic intervals, the fitting on the Fusible Link must be a 2WV, 2 amp or a 250-V, 10 amp type
Valve should be cleaned to prevent any accumula- as marked on the printed circuit board.
tion of foreign materials from clogging the inlet. This Do not use oversized fuses.
is accomplished as follows: 8. Reptace the Front Cover and the Louver
Assembly and plug the heater into the wall
outlet.
UNPLUG THE HEATER. POWER TO THE HEATER IMPORTRNT: Whenever the heater is unplugged,
SHOULD BE OFF DURING THE PERFORMANCEOF the.Microprocessor must be repro.
THIS PROCEDURE. srammed when Dower is restored.
-
STEP(: Close off Fuel Supply
4-9 FUEL CONTAMINATION
A. Shut off fuel at the Storage Tank or remove fuel
Fuel, contamination is often difficult to diagnose,
from the fuel sump tank with siphon and syrlnge
even though it will adversely affect heater operation
if using the capsule fuel tank.
and performance. The best course of action to take
B. Manually turn handle to close Fusible Link
when fuel contamination is suspected is to examine
Valve.
all of the system's fuel filters, beginning with the fuel
NOTE: Place paper towels underneath the Fusible storage tank. If a Monitor Kerosene Lifter is part of
Link Valve to catch any spilled fuel. me fueling system, examine and clean that unit's
STEP2: Clean Valve filter, as well as the filter located in the Fuel Con-
A. Loosen hex nut on Fusible Link Valve inlet stant Level Valve. When it has been determined that
fittlng at rear of me heater. Disconnect the water or some other contaminants have infiltrated
copper tub~ngwhich delivers the fuel from the the fuel, the following action must be taken:
storage or the fuel sump tank.
B. Using a small, straight piece of wire carefully
and slowly ream-out the inlet fitting on the
Fusible Link Valve. BEFORE PROCEEDING FURTHER, UNPLUG THE
Avoid scratching the inside wall of the fitting. HEATER
STEPI: Remove Contarninetion
With a cotton swab, wipe the interior area of the
A, Shut O f f the fuel supply at the storage tank or
inlet fitting.
at the Fusible Link Valve.
STEP3: Reconnect Fuel Line B. Drain off the contaminants from the fuel storage
A. Reconnect the copper tub~ngto the intake tank or the fuel sump tank(M-422). Fill with
fitting and tlghten the hex nut. fresh, clean fuel.
B. Turn ON fuel at Fusible Link Valve and at SIEP2: Clsan the
storage tank or fuel sump tank. A. Clean fuel constant level valve filter and filter
C. Check for leaks. compartment.
4-7 CORRECTIVE MAINTENANCE B. Remove the Louver Assembly and Solenold
The two procedures below are remed~esfor very Bump on the constant level valve. Clean the
generalized types of operating difficult~es. Solenoid Pump filter.
4-8 REPLACEMEM OF N S E S
SIEP3: Reinstall Cleaned Components
A. Rep1ace the cmmnts coKect'y and lnstall
A short circuit or s~milarelectrical malfunction could
new gasket.
cause the fuse to blow. Troubleshoot the cause of
the blown fuse.
B. Turn on the fuel at the storage tank and at the
fusible llnk valve, and apply power to the heater.
Replace the fuse as follows: If problem still exists and contammated fuel IS
suspected it can be checked by
A. Shutting off the fuel supply at the storage tank
and at the fusible llnk valve.
DO NOT REPUCE N S E WHILE POWER 8 ON.
B. Drain off fuel at constant level valve.
STEP(: Removal of Fuse C. Dcconnect fuel ltne at back of heater and hook
A. Unplug heater. Remove LOWer Assembly and up a 5 gallon qu~cktank w ~ t hwoven good fuel.
Front Cover. D. Test run heater to see if problem clears up wrth
8. Remove the fuse from fuseholder on the Printed use of new fuel.
Circuit Board. -qQ+++
I 38
MONITOR HEATING SYSTEMS
Section Servicing
u
Figure 5-1
B. Put the burner cloth on the burner bottom,
afterwards press and straighten out the
burner cloth so that it is glued flat and even NOTE: The Burner Cloth is not symmetrical in
1 [jy-'m
on the burner bottom. shape, therefore make sure to place it in
8. On the Monitor 44l the correct position so that the wider side
A. Apply glue arround the burner cloth as of the cloth is at lett side of the lgniter
shown in Figure 5-2. Shield as shown in Figure 5 5 .
Oue
b
\
.--___..' tion ring is warped, has cracked or is detenorat-
ing excessively it should be replaced.
10. When reassembling the unit check that com-
*OePl 'Is- Ftgure 5-2 bustion ring is positioned with the correct side
B. As shown in Figure 5-3 and 5-4, insert the up and is sitting squarely on all three support
Burner Cloth narrow between the Nozzle s c r e w s ( ~ 2 2or
) pins(Ni-441) inside the bumer
Collar and the Igniter Shield, then push the Pot.
Bumer Cloth, using your fingers or a screw 11. Reassemble by reversing the procedure foll-
driver, so that it slips in under the Naule owed during disassembly.
Collar. Afrerwards press and straighten out
the Bumer cloth so that it is glued fiat and NOTE: Use of the economy plus feature can
even on the Burner battom. minimize service calls and extend corn-
ponent life.
NOTE: in some m e s , pulling out the Fuel Nozzle
and Collar may make this procedure easier.
An easy out can be inserted into nozzle to
hetp break loose and remove it.
40
MONITOR HEATlNG SYSTEMS
Section 5: Servicing
NOTE: Make sure the position of flame detector rod is centered between combustion ring and bumer pot
before reassernbiing.(See Figure 5-6)
Gap
M-441: 4mm (0.16) or more
M-422:3mm (0.12') or more
Burner II 11 '
Pot
5-5 CLEANING THE FUEL INLET 2, Push a piece of wire (about the same size as
When cleaning the combustion chamber and the the I.D. of fuel inlet pipe) into the fuel inlet
bumer pot, the fuel inlet nozzle should also be nozzle.
cleaned. This can be done as follows: 3, If obstruction is felt twist wire back and forth (to
brake up soot and carbon) so that wire ulti-
1, Disconnect copper fuel line at bum chamber. mately penetrates igniter shield.
On M422, also check air holes surrounding
fuel inlet for blockage and clear if necessary.
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
High Speed
Combust~onBlower F on PCB 921M-422)
Low Speed (Ql is Off) ~~(~-441)
Res~stor G on PCB 1WM-422)
22(M41)
*Pulse can only be measured with a hlgh impedance d~gltalvolt meter.
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
TP 3 12V If:30% 12V f 30% 12V f 30% 12V f 30% 12V f 30%
Waillng unlil
~igh Medium-High Medium-Low Low OFF Posl-purge pragrammed Lime
comes on'
TP 2 5V f 10% 5V k 10% 5 V f 10% 5V f 10% 5 V f 10% 5W f 10% 5V f 1 0 1
TP 3 12V f 30% 12V f 30% 12V f 30% 12V f 30% 12V f 30% 12Vf 30°/o 12V f 30%
TP 4 1.5 -3.2V 1.5-3.2V 1.5-3.2V 1.5 - 3.2V 1.5-3.2V 1.5-3.2V 1.5- 3.2V
TP 5 pulse pulse pulse pulse pulse pulse pulse
lnfinitly
TP 6 1.2V min. 1.2V min. 1.2V min. 1.2V min. OV variable OW
TP 7 5V 5V 5V 5V 5V 5V 5V
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
2
2
/
-0
0 -.
2 ,
-W +W +Q +Q +Q + Q + '
,
m - m m n o '
, Q
'
5n i5'i
/ (Pa
4
d
ul rd
U l c r . < <-
c
1 . g 2 a g .
? 5 --
d $
0 ; s n
L "b < ~
E , ._ < <
0 5
c I3 . I C q q f
5 -- ce,
J
d - 5
2 2 E
w d
c 93 . 1 c -a q- ,L
-
. 5P
MONITOR HEATING SYSTEMS
Section 6: Troubleshooting
After power on, power supply to the micro- Timer clock circuit bad or power
1 1 1
7 r/ processer timing circuit is incorrect. source to unlt above or below
L L/ - .
acceptable levels.
functioning.
: r
- I
1 When unit is shut off either manually or Driving circuit of RL6 or excess
:
I-
,'-
'- 1
' I-
I
'-
j automatically, flame rod does not detect fuel in burner pot.
I
' flame out within 300 seconds.
NOSW3t.i
cpalarrol pue passer 1aro1 l a s anten p r o 1 l u e l s u q l a n j c e ~
.uwo arler rue1 .yuet UI Ian1 s(
cPaddols ue j uotceInan9 sen
'ES BB srror(s moputr*
l e l d s # a ~(uolldnnalul
dallno llev ul pauasul
ramod a ~ getaql
e u Bnld o dsl
r a ~ re"
REASON
1 I CORRECTIVE MEASURE
able 10 change
mrpln(lC121.
Failw 01 TR anay
llcM
I
Failua 01 citmlalfim
Ian mla
W a c s cidahon
Isr mta.
I
Fail- PI biec
-
-
Failw ol mnbrnlim
blm:
- I
Max crrrhaum
blaa I
Fsilus d resirta la
9 -1irn~m-a.
- Failua 01 darpa
sdemid.
M a c a daroer
Jdemid I
Failua ol camcitr,
Icill. I
Failua ol mi-
REASON
I t mas nK.9
than t 3Vdc .I
rPs 7
R e ~ l a c nIranrlmma,
I
Failme ol diode
lDIW
1
M. caairtinp d 2 hwblsd 8lip.m clip¶. 2-0- ~ i n c 04 ~ sinaubled
S
- I-114- wm ua w t ~d i d . and 1-114- wan ~ m OHM k rssbla.
fhacrmp~mnbmm(ob.~dlopm~hreguenc*u.homh
-
d'wmb o k Iml* crmponM S U I ud ~ po)uWl.
(lum h a m ctcuil b mn& Ih. unit ij
bmsd 4 h m d i t d y nnm )Ir p.prg. p . h s a ~w l s ; *hen mod. liiht
q Ihd 0 D tl Hma dimowclod OH Ih. PCB and rspbced
with Um c b m Th mil lhould I h n cmlinw tunclkminp u
n- --
Failua ol * i t i t q l
a
d(pard.
Cored win-
I
Cored imQIbMn
1
I REASON
1 CORRECTIVE MEASURE
Is window
curlain loo
Curlain or other obslruclion
covers clrculalion air Inlel.
- Cleen guard.
close to Ihe
rear of unil?
I
I Keep curtain ltom unit.
C
Main Printed
Wiring Board
Pressure
Switch Semor (Thermistor)
Over lieat
Thermostat
Slide Switch
Solenoid Valve
+ Ground
Power
Blower for ma
Combustion
Blower for Fan
Resistor Clrculat~on Juncl~onBox
Thermostat
RUN A ECONOMY
D EMPTY BURNER STATUS TEMP SET
~ PLUS
m 0"
Main Printed
Wiring Board Empty ~ a G pSwttch
(Float Sw~tch)
Pressure
Swrtch Sensor (Thermistor)
Over Heat
Thennostat I
+
'
F J
Ground
Power
Blower for Cord
Combustlon
Blarver for F=,
Resistor ~ l ~ u l a t l ~ n Thermostat Junctton fiox
Note: These Readings a r e to be taken after the heater has fully warmed up.
(Approximately 5 xni-~~u&s orrHkfi~e.)The damper adjustment can only be
done on Low or Low-Med Ranges.
MONITOR 441
SERVICE PARTS LIST