CATALOGUE FOR

SAFE VISIBLE FLAME


SCANNER (Rev Apr 2019)

(Corner, Tilting, Tangential Firing Boiler)

BOILER CONTROLS PRIVATE LIMITED


No.1/5, ALEXANDRIA ROAD, CANTONMENT,
TIRUCHIRAPPALLI–620001. TAMIL NADU.
Phone: +91-431-2412419
E-mail: bcplsv30@gmail.com , sales@bcplsv.com
Website: www.bcplsv.com
CATALOG FOR SAFE VISIBLE FLAME SCANNER

SS–II is designed to detect the flame in the


INTRODUCTION: furnace from two different sources using single Flame
Scanner Head.
The SAFE VISIBLE FLAME SCANNER is
designed for monitoring the flame from individual The SS–I & SS–II Safe Scan systems consist of
Oil/Coal Burner and sending the signal to the control four Flame Scanner assemblies located in Guide pipes
room through Scanner Amplifier circuits. Design at each corner of the furnace and an electronic
objectives of the Scanner are to: Chassis mounted remotely in a Flame Scanner Panel.
a) Detect the presence of FLAME/NO FLAME in the
individual Burners. The Scanner electronics circuitry will
b) Monitor and Control the individual Oil/Coal discriminate between an individual oil gun flame and
Burner flame. a background fireball flame by sensing the different
c) Indicate whether the Oil/Coal Burner flame is characteristics [Frequency and Intensity levels] of the
adequate & if the respective burner needs to be Rays/Light they emit.
retained or removed from service.

PRINCIPLE OF OPERATION:

Flame Detection works on the dynamic &


static properties of primary combustion zone and
visible flicker frequency of Flame for each type of
Fuel [Coal/Oil]. Based on the principle of detection,
the Flame Scanner is classified into SAFE SCAN–I &
SAFE SCAN–II.

SS–I is designed for use on Coal fireball. It The Rays/Light is transmitted from the burner
recognizes the characteristics of ray/light radiated back to the boiler side electronics via a fiber optic
from the fuel nozzle flames. light guide. The head electronics convert the rays/
light to a current signal which is transmitted to a
remote amplifier chassis for flame recognition by
additional electronics circuits.

In addition to analyzing the current signal for


a Flame/No Flame condition, an Advanced
programmed monitoring system continuously
evaluates the boiler side electronics and the
associated faults.

Ray/light is directly related to the burning The Flame Scanner system has an in-built
process & is given off in substantial quantities so that Self-checking feature which actuates a ‘Fault’ alarm
a stable flame cannot be masked by unburnt coal. SS– (contact closure) and a light emitting diode (LED) in
I senses the rays/light given off by the flame and the control panel when the Intensity/Frequency of
recognize a coal flame by its characteristics. the Scanner falls out of the preset limits.

Boiler Controls (P) Ltd., www.bcplsv.com


CATALOG FOR SAFE VISIBLE FLAME SCANNER

MECHANICAL COMPONENTS: DETECTOR HEAD ASSEMBLY

The Mechanical assembly comprises of a The Detector Head assembly comprises of a


Stationary part called the Flame Scanner Guide pipe Scanner Head containing Lens for observing the
assembly and a Removable part called the Flame Flame and one end of a Fiber Optic cable. The FOC is
contained within a flexible Hose.
Scanner Head assembly.

FLAME SCANNER GUIDE PIPE

The Scanner
Head should not be exposed to a continuous
temperature above 300°F without cooling air.

Flame Scanner Guide pipe assembly consists COOLING AIR REQUIREMENTS:


of a Rigid Guide pipe section, Flexible section, Cooling
Air manifold & Cover plate. The external cooling air passes through the
Guide, the flexible Hose and the Annulus between
the Scanner Head and Housing. The air is discharged
in to the furnace at the top of the scanner head,
FLAME SCANNER HEAD ASSEMBLY thereby removing any heat picked up by the scanner
from the hot combustion air. Cooling airflow
The Flame Scanner assembly has sections
requirements per scanner is 50NM3/Hour
namely Detector Head assembly, Flexible Metal Hose,
@150mmwcl (above max furnace pressure).
Rigid Pipe and the Scanner Housing assembly(IP
65/67) is available .
FIBER-OPTIC CABLE
A weatherproof quick disconnect coupling is
The Fiber Optic Cable housed inside the
provided to conveniently connect the external wiring.
Flame Scanner Assembly transfers the light as
The scanner housing couples the Flame seen by the Scanner Lens to the Scanner Head
Scanner assembly to the Guide pipe and contains the electronics present in the Scanner Housing. The
electronics for conditioning the fiber-optic- Collimator shield and the Lens on the end of the
transmitted signal. FOC should also be inspected periodically for
cleanliness. The degree of fouling will depend on
Further Dimensions are customized as per the type of fuel used, the plant operating
furnace depth and site requirement. characteristics and the cleanliness of the cooling
air. FOC will withstand a temperature of 600°C
and has transmission band of 300 to 2600 NM.

FLAME SCANNER HEAD ASSEMBLY

DT: 13.07.10

Boiler Controls (P) Ltd., www.bcplsv.com


CATALOG FOR SAFE VISIBLE FLAME SCANNER

SCANNER HOUSING ELECTRONICS L & M CARD

The light energy passing via FOC strikes the The L & M card performs the following functions:
Photo-diode and gets converted to a small electrical 1. Generation of Flame/No Flame logic signal
current. The electrical current coming from the from Oil/Coal & visual intensity FAULT
Photo-diode is converted to Voltage signal by the warnings.
integrated circuits. As the flame brightness reduces, 2. Indication of Flame intensity on the display
Current reduces and the output Voltage increases. If bar graph from 0 to 100%.
the boiler was not in operation the current would 3. Distribution of Power to the associated
be zero. Scanner Head.

LAMP DRIVE CARD

The function of this module is to generate the


fireball “Flame/No flame” logic signal.

POWER SUPPLY CARD

Power for the Electronic Chassis and its


associated Scanner Head Assemblies originate from
the Power Supply card. Three power distribution rails
INTENSITY & FAULT DETECTION CARD transmit +15V, -15V DC and a common return.
General specifications are as follows:
The Current signal from the Scanner Housing Input Voltage: 110V/230V AC
Electronics module enters the Intensity and Fault Output Voltage: ±15 VDC
Detection [IFD] card & gets transformed into a milli- Output Current: ±0.50A
Volt signal.

At this point, a high voltage represents low 2/4 FLAME INDICATION AND FAULT
ALARM CARD
intensity and a low voltage represents high intensity.
Thus based on the value of Intensity the The 2/4 card performs the following functions:
healthiness/Quality of the Flame can be found. 1. Provides a contact closure when at least 2 out
of the 4 Flame Scanner Heads are detecting
FREQUENCY DETECTION CARD the fireball flame.
2. It provides a contact closure when a Fault is
Active flame signal consisting of Frequency
detected on any Scanner Cable or Scanner
and Intensity information enters the Frequency
Head Electronics.
Detection [FD] card from the IFD card.
The 2/4 card has two Relays with Mercury-
The FD card is used to determine if the Oil
gun flame frequency and the Fireball flame frequency
exists within the frequency spectrum of the active
flame signal. It helps to actuate a ‘Fault’ alarm
(contact closure) if the Intensity/Frequency of the
incoming Flame falls out of the preset limits.

Boiler Controls (P) Ltd., www.bcplsv.com


CATALOG FOR SAFE VISIBLE FLAME SCANNER

Wetted contacts hence position sensitive. Display Real Data – Tricolor Bar Graph display is
RETROFIT: provided.
Retrofitting existing Flame scanners with
Processor based Flame Scanner is relatively easy and
Scanner Cooling air requirements are also the same.
If a new cooling air system is required it shall also be
supplied by BCPL.
With our vide experience, UV/Other Flame
Scanners are upgraded with the NEW Processor
based Safe Flame Scanner gaining substantial savings
in high speed diesel oil consumption. This has further
enhanced two mill operations, without oil support
and safe scanner are working satisfactorily.
BCPL is capable of implementing the R&M
scheme with short shutdown period without
affecting power generation. BCPL has completed Applicable with all regulations & as per
numerous jobs in retrofitting Flame scanner in the standards of NFPA 8502.
DCS based FSSS systems and Relay panels. Touchscreen facility [Latest] with less UCB space.
Application: Corner, Tilting, Tangential Fired
Boilers
Features:
Reliable Oil/Coal burner Flame monitoring.
Flame Trend Analysis available.

PERSONAL COMPUTER (OPTIONAL)


We shall supply PC/Laptop with or without
printer optional, Data Logging, Anti-virus Software
etc.

In-built 4–20mA Output which is fully configurable


and Compatible with DCS.
Improved Safety, Operational Flexibility & Better
Maintainability. Avoid spurious trips.
As a regular feature a HMI colored touch
screen/Remote Flame Output Meter is available to
indicate flame intensity in the control desk.
Failure of this PC/Laptop will not generate
any trip it is just for indication.

ISO 9001:2015

Boiler Controls (P) Ltd., www.bcplsv.com


CATALOG FOR SAFE VISIBLE FLAME SCANNER

TECHNICAL SPECIFICATION

Burn-in test, Elevated Temperature test, Dry Heat


Type Tests
test, Humidity test, Vibration test, Bump test
Type of Flame Scanner Make: BCPL, Model–SVFS
Type of Sensor Visible Range, Photo-Diode
Type of Guide pipe Rigid/Flexible / Length As Required
Type of Electronics card Micro Processor /microcontroller /Solid State Design
Spectral transmission band for FOC 300–2600nm, 600°C
Operating Voltage of Electronics card ±15 V DC /24 VDC
Type of Self check mechanism Available. In-built
View of Angle 30° / 45°/60°
Max. Withstand temp. of Scanner Head 120 C ( with Cooling Air )
Type of Flame Scanner Cable assembly Special shielded, 2 pair Scanner cable
Type of Amplifier Logarithmic/Microcontroller model
Electrical scanner Output Intensity ,Frequency ,Relay contact ,Fault contact
No. of Output contacts As per number of Oil/Coal Burner at site.
Cooling Air at 50 NM 3 per hour per Scanner @
Type of protection for focusing lens
100mmwcl (above furnace pressure) – Optional
Rated Power consumption (4 scanners) 110/230 VA
No. of analog outputs provided in 4–20mA One from Amplifier
for intensity meter Another one to Remote indication/Computer.
Available Complete – Optional as per Customer
Computer with Flame Scanner Software
requirement

Flame scanner Head assembly IP65/IP67 Certified

Calibration & Test Kit – Head Assembly


Test Kit for scanner
Test Kit for all cards

Boiler Controls (P) Ltd., www.bcplsv.com


CATALOG FOR SAFE VISIBLE FLAME SCANNER

FLAME SCANNER CERTIFICATION

Flame scanner tested in ETDC- Electronics Test & Development Centre, Govt. of India
Flame scanner tested in CIMFR -Central Institute of Mining & Fuel Research, Govt. of India.
SH3 Certified
CANADIAN STANDARDS ASSOCIATION Certified
NFPA85 Certified
Certified for CE MARKING

BCPL IN-HOUSE FACILIY

BCPL is having full equipped division for manufacturing of Flame Scanners as per varied
customer requirements. BCPL also possess additional strength on keeping various spares readily
stocked for immediate customer usage.
BCPL has completed numerous jobs in retrofitting Safe Visible Flame scanner in the DCS
based FSSS systems and Relay based logic panels.
Flame Scanner software with computer.
Panel REAR Portion

Flame Scanner Testing & Calibration.

Boiler Controls (P) Ltd., www.bcplsv.com


CATALOG FOR SAFE VISIBLE FLAME SCANNER

OUR SELECTED USERS LIST FOR FLAME SCANNER SYSTEM

CUSTOMER PROJECT
Madhya Pradesh Power Gen Corpn Ltd., Sanjay Gandhi TPS (Unit#3)
Madhya Pradesh Power Gen Corpn Ltd., Satpura TPS (Unit#1&2)
Andhra Pradesh Power Gen. Corpn. Ltd., (Through ABB,
Ramagundam TPS
Bangalore)
Gujarat State Electricity Corporation Ltd., Sikka TPS (Unit#1)
Uttarpradesh Rajya Vidyut Utpadan Nigam Ltd., Obra TPS (Unit#8)
Chhattisgarh State Power Gen. Co. Ltd., Hasdeo TPS–Korba(W) (Unit#1&2)
Andhra Pradesh Power Gen. Corpn. Ltd., Vijayawada TPS, Unit#1
Gujarat State Electricity Corporation Ltd., Wanakbori TPS (Unit#1-3)
Gujarat State Electricity Corporation Ltd., Wanakbori TPS (Unit#4-6)
National Thermal Power Corporation Unchahar TPS (Unit#1)
Gujarat State Electricity Corporation Ltd., Ukai TPS (Unit#1&2)
Gujarat State Electricity Corporation Ltd., GandhinagarTPS (Unit#1&2)
Jindal Steel Ltd., Jindal
National Thermal Power Corporation Tanda TPS (Unit #1-4)
Torrent Power Ltd., [Aeco] D, E, F Stations
Tenughat Vidyut Nigam Ltd., Tenughat TPS
Alstom Power India Ltd., Durgapur TPS
Tamilnadu Generation & Development Co., Ennore TPS (Unit #1&2)
Torrent Power Ltd., [Aeco] “C” Station
Alstom Power India Ltd., Bokaro TPS
Alstom Power India Ltd., Bhatinda (Unit #1&2)

REGISTERED OFFICE : FACTORY ADDRESS:


No.1/5, Alexandria Road, Cantonment, No.1/4, Kumaramangalam Industrial Estate,
Tiruchirappalli–620001. Tamil Nadu, India. Mathur, Pudukkottai District. Pin–622515.
Ph: 0431-2412419 ; Fax: 0431-2414401 Tamil Nadu, India.
E-mail: bcplsv30@gmail.com E-mail:sales@bcplsv.com
www.bcplsv.com