Flame Scanner Catalogue 2019
Flame Scanner Catalogue 2019
PRINCIPLE OF OPERATION:
SS–I is designed for use on Coal fireball. It The Rays/Light is transmitted from the burner
recognizes the characteristics of ray/light radiated back to the boiler side electronics via a fiber optic
from the fuel nozzle flames. light guide. The head electronics convert the rays/
light to a current signal which is transmitted to a
remote amplifier chassis for flame recognition by
additional electronics circuits.
Ray/light is directly related to the burning The Flame Scanner system has an in-built
process & is given off in substantial quantities so that Self-checking feature which actuates a ‘Fault’ alarm
a stable flame cannot be masked by unburnt coal. SS– (contact closure) and a light emitting diode (LED) in
I senses the rays/light given off by the flame and the control panel when the Intensity/Frequency of
recognize a coal flame by its characteristics. the Scanner falls out of the preset limits.
The Scanner
Head should not be exposed to a continuous
temperature above 300°F without cooling air.
DT: 13.07.10
The light energy passing via FOC strikes the The L & M card performs the following functions:
Photo-diode and gets converted to a small electrical 1. Generation of Flame/No Flame logic signal
current. The electrical current coming from the from Oil/Coal & visual intensity FAULT
Photo-diode is converted to Voltage signal by the warnings.
integrated circuits. As the flame brightness reduces, 2. Indication of Flame intensity on the display
Current reduces and the output Voltage increases. If bar graph from 0 to 100%.
the boiler was not in operation the current would 3. Distribution of Power to the associated
be zero. Scanner Head.
At this point, a high voltage represents low 2/4 FLAME INDICATION AND FAULT
ALARM CARD
intensity and a low voltage represents high intensity.
Thus based on the value of Intensity the The 2/4 card performs the following functions:
healthiness/Quality of the Flame can be found. 1. Provides a contact closure when at least 2 out
of the 4 Flame Scanner Heads are detecting
FREQUENCY DETECTION CARD the fireball flame.
2. It provides a contact closure when a Fault is
Active flame signal consisting of Frequency
detected on any Scanner Cable or Scanner
and Intensity information enters the Frequency
Head Electronics.
Detection [FD] card from the IFD card.
The 2/4 card has two Relays with Mercury-
The FD card is used to determine if the Oil
gun flame frequency and the Fireball flame frequency
exists within the frequency spectrum of the active
flame signal. It helps to actuate a ‘Fault’ alarm
(contact closure) if the Intensity/Frequency of the
incoming Flame falls out of the preset limits.
Wetted contacts hence position sensitive. Display Real Data – Tricolor Bar Graph display is
RETROFIT: provided.
Retrofitting existing Flame scanners with
Processor based Flame Scanner is relatively easy and
Scanner Cooling air requirements are also the same.
If a new cooling air system is required it shall also be
supplied by BCPL.
With our vide experience, UV/Other Flame
Scanners are upgraded with the NEW Processor
based Safe Flame Scanner gaining substantial savings
in high speed diesel oil consumption. This has further
enhanced two mill operations, without oil support
and safe scanner are working satisfactorily.
BCPL is capable of implementing the R&M
scheme with short shutdown period without
affecting power generation. BCPL has completed Applicable with all regulations & as per
numerous jobs in retrofitting Flame scanner in the standards of NFPA 8502.
DCS based FSSS systems and Relay panels. Touchscreen facility [Latest] with less UCB space.
Application: Corner, Tilting, Tangential Fired
Boilers
Features:
Reliable Oil/Coal burner Flame monitoring.
Flame Trend Analysis available.
ISO 9001:2015
TECHNICAL SPECIFICATION
Flame scanner tested in ETDC- Electronics Test & Development Centre, Govt. of India
Flame scanner tested in CIMFR -Central Institute of Mining & Fuel Research, Govt. of India.
SH3 Certified
CANADIAN STANDARDS ASSOCIATION Certified
NFPA85 Certified
Certified for CE MARKING
BCPL is having full equipped division for manufacturing of Flame Scanners as per varied
customer requirements. BCPL also possess additional strength on keeping various spares readily
stocked for immediate customer usage.
BCPL has completed numerous jobs in retrofitting Safe Visible Flame scanner in the DCS
based FSSS systems and Relay based logic panels.
Flame Scanner software with computer.
Panel REAR Portion
CUSTOMER PROJECT
Madhya Pradesh Power Gen Corpn Ltd., Sanjay Gandhi TPS (Unit#3)
Madhya Pradesh Power Gen Corpn Ltd., Satpura TPS (Unit#1&2)
Andhra Pradesh Power Gen. Corpn. Ltd., (Through ABB,
Ramagundam TPS
Bangalore)
Gujarat State Electricity Corporation Ltd., Sikka TPS (Unit#1)
Uttarpradesh Rajya Vidyut Utpadan Nigam Ltd., Obra TPS (Unit#8)
Chhattisgarh State Power Gen. Co. Ltd., Hasdeo TPS–Korba(W) (Unit#1&2)
Andhra Pradesh Power Gen. Corpn. Ltd., Vijayawada TPS, Unit#1
Gujarat State Electricity Corporation Ltd., Wanakbori TPS (Unit#1-3)
Gujarat State Electricity Corporation Ltd., Wanakbori TPS (Unit#4-6)
National Thermal Power Corporation Unchahar TPS (Unit#1)
Gujarat State Electricity Corporation Ltd., Ukai TPS (Unit#1&2)
Gujarat State Electricity Corporation Ltd., GandhinagarTPS (Unit#1&2)
Jindal Steel Ltd., Jindal
National Thermal Power Corporation Tanda TPS (Unit #1-4)
Torrent Power Ltd., [Aeco] D, E, F Stations
Tenughat Vidyut Nigam Ltd., Tenughat TPS
Alstom Power India Ltd., Durgapur TPS
Tamilnadu Generation & Development Co., Ennore TPS (Unit #1&2)
Torrent Power Ltd., [Aeco] “C” Station
Alstom Power India Ltd., Bokaro TPS
Alstom Power India Ltd., Bhatinda (Unit #1&2)