Professional Documents
Culture Documents
Design of Low and Medium Voltage Networks (1) - 1
Design of Low and Medium Voltage Networks (1) - 1
1
"تنويو"
اْ اٌغشض ِٓ ٘زا اٌىحاب ٘ ٛجّىيٓ ِٕٙذط جصّيُ األػّاي اٌىٙشتيٗ ِٓ أْ يى ْٛػٍي دسايٗ ٚٚػي جاَ
تىً خطٛات اٌحصّيُِٚ ،حطٍثات وً خطٚ ،ٖٛاألوٛاد اٌخاصٗ تاألػّاي اٌىٙشتيٗ.
ٚلذ زشصث في ٘زا اٌؼًّ -تمذس اعحطاػحي -أْ يعُ إٌظشيات ٚاٌمٛأيٓ ٚاألوٛاد اٌخاصٗ تىً ِشزٍٗ
ِٓ ِشازً اٌحصّيُ ،تدأة اٌخثشٖ ٚإٌظشٖ اٌؼٍّيٗ اٌحي جحطٍثٙا وً ِشزٍٗ ،زحي يى ْٛاٌّحذسب ػٍي دسايٗ
ٚٚػي واًِ تطشيمٗ اٌحصّيُ اٌغٍيّٗ.
ٚلذ زشصث -أيعا -ػٍي أْ يى ْٛأعٍٛب اٌىحاب ع ًٙفي اٌؼشض ،زحي يف ّٗٙاٌّحذسب تغٚ ٌٗٛٙيغش،
ٚزحي يغحفيذ ِٕٗ أوثش ػذد ِّىٓ ِٓ ِٕٙذعي جصّيُ األػّاي اٌىٙشتيٗ في وً ِىاْ ،زحي أٔٗ يّىٓ
ٌٍطالب أْ يمشأِ ٚسحٛيات اٌىحاب ٚيفّٙٔٛٙا تغٚ ،ٌٗٛٙوزٌه يغحفيذ ِٕٗ اٌخشيديٓٚ ،وثيش ِّٓ ٌٗ ازحىان
تاٌسياٖ اٌؼٍّيٗ ،فاٌىحاب يعُ اٌىثيش ِٓ ِحطٍثات اٌحصّيُ اٌحي عحفيذ اٌماسئ أيا وأث ِؼشفحٗ ٚخثشجٗ.
ٚيدة اٌحٕٛيٗ -أيعا -أْ ٘زا اٌىحاب ٌيظ اخحشاػا خذيذا ٚأّا ٘ ٛاخحٙاد ِٓ اٌىاجة ،اٌىحاب في اٌسميمٗ
ٌيظ اال ٔمً تحصشفٚ ،جٕظيُ ألػّاي وثيشٖ ِٛخٛدٖ ػٍي شثىة االٔحشٔثِ ،غ تؼط اٌضيادات أ ٚاٌسزف أٚ
إٌمً ،عٛاء واْ ٔمال واِال أ ٚخضئيا أ ٚتحصشفٚ ،وزٌه اظافٗ تؼط اٌفصٛي ٚاٌّؼٍِٛات اٌٙاِٗ اٌحي جُٙ
ِٕٙذعي اٌحصّيُ.
اْ ٘زٖ اٌطثؼٗ ٘ي اٌطثؼٗ األٌٚي ِٓ اٌىحابٚ ،عيىٕ٘ ْٛان غثؼات أخشي لادِٗ في اٌشٛٙس أ ٚاٌغٕٛات
اٌمٍيٍٗ اٌمادِٗ تارْ هللا ،جسحٛي ػٍي تؼط اٌحؼذيالت زحي ٔصً ألفعً ٔحيدٗ ِّىٕٗ ٚزحي ٔٛاوة
اٌّحغيشات في عٛق اٌؼًّ.
ِٓٚواْ ٌذيٗ أي أفىاسأ ٚجؼذيالت ٌحطٛيش ٘زا اٌؼًّ فيّىٕٕا اٌحٛاصً ػثش اٌفيغثٛن:
https://www.facebook.com/alaa.hmam.9
Alaa.hmam36@gmail.com
Eng_3laa36@yahoo.com
ٚفي إٌٙايٗ أعاي هللا اٌؼظيُ أْ يدؼً ٘زا اٌىحاب ِفيذا ٌىً ِٓ يمشأٖٚ ،أْ يدؼٍٗ في ِيضاْ زغٕاجٕا.
Eng/Alaa Hmam
2
INDEX
CHAPTER 1:
Basic AutoCAD Commands …………….…………………………………. 7
CHAPTER 2:
Load Estimation …………….……………………………………………… 23
CHAPTER 3:
Basic Definitions of Lighting …….………………………………………… 25
CHAPTER 4:
Parameters of Indoor Lighting Design …………………………………… 31
CHAPTER 5:
Lighting Design Using Manual Calculation ……………………………… 55
CHAPTER 6:
Lighting Design Using DIALux …………………………………………… 59
CHAPTER 7:
Sockets ……………………………………………………………………… 105
CHAPTER 8:
Indoor Wiring ………………………………………….…………………… 111
CHAPTER 9:
Lifts and Elevators ………….……………………………………………… 116
CHAPTER 10:
Heating Ventilation Air Condition (HVAC) ……………………………… 122
Eng/Alaa Hmam
3
CHAPTER 11:
Load Study ………………………….………………….…………………144
CHAPTER 12:
Panel Boards ……………………………...………………………….……149
CHAPTER 13:
Circuit Breaker ……………………………………………………………159
CHAPTER 14:
Cables ………………………………………………………………………167
CHAPTER 15:
Cable Routing ………………………………………………………………187
CHAPTER 16:
Bus Duct …………………….………………………………………………208
CHAPTER 17:
Phase Balance ……………………………………………………………… 219
CHAPTER 18:
Distribution Transformers …………………………………………………225
CHAPTER 19:
Diesel Generator ……………………….……………………………………235
CHAPTER 20:
Uninterruptible Power Supply (UPS) ………………………………………238
CHAPTER 21:
Automatic Transfer Switch (ATS) ………………………….………………241
Eng/Alaa Hmam
4
CHAPTER 22:
Ring Main Unit (RMU) …………………………………………………… 244
CHAPTER 23:
Distributors ………………………………………………………………… 251
CHAPTER 24:
Feeding System ………………..…………………………………………… 266
CHAPTER 25:
………………………… قولعد توصيل لحتغريو لحكهسبيو حلونشمت لحسكنيو بمحقس يلحودى.. 289
CHAPTER 26:
Power Factor Correction …………………………………………………… 298
CHAPTER 27:
Power System Representation Using ETAP ……………………….………. 314
CHAPTER 28:
Voltage Drop Calculation …………………………………………………… 322
CHAPTER 29:
Short Circuit Calculation …………………………………………………… 325
CHAPTER 30:
Street Lighting ……………………………………………………………….. 328
CHAPTER 31:
Coordination Study ………………………………………………………….. 347
CHAPTER 32:
Light Current …………………………...……………………………………. 366
Eng/Alaa Hmam
5
CHAPTER 33:
…………………………………………………… 399لحمصس يلحوقميسو يلحوستخلصمت
CHAPTER 34:
……………………………………….. 408نووذج تصوين كهسبي كمهل حوبني في هدينو بدز
Eng/Alaa Hmam
6
Chapter 1
Eng/Alaa Hmam
7
Eng/Alaa Hmam
8
Eng/Alaa Hmam
9
Eng/Alaa Hmam
10
Eng/Alaa Hmam
11
Eng/Alaa Hmam
12
Eng/Alaa Hmam
13
Eng/Alaa Hmam
14
Eng/Alaa Hmam
15
Eng/Alaa Hmam
16
Eng/Alaa Hmam
17
Eng/Alaa Hmam
18
Eng/Alaa Hmam
19
Eng/Alaa Hmam
20
Eng/Alaa Hmam
21
Eng/Alaa Hmam
22
Chapter 2
Load estimation
To calculate the total load of any project before starting the design.
1. Lighting Power
2. Power (Sockets)
3. HVAC
4. Others (Lifts, Fire pump, Laundry, Medical equipment, Water pump, and so on).
Small
Lighting power(sockets) A/C
place 2 2 Notes
VA/m 2 VA/m
VA/m
Banks 20 ; 40 30 50 : 70
Cafeteria 25 : 45 5 60 : 100
Basement Stores 30 : 50 15 -
Mid Floor 25 : 45 10 50 : 70
Upper Floor 20 : 40 5 -
Eng/Alaa Hmam
23
Garages 5 1.5 -
Hospital 20 : 30 10 50 - 70
Hotels 10 : 30 5 50 - 80
40 – 70 ()ػادي
Office 15 – 35 15 110 – 120
()ِشوضي
40 – 70 ()ػادي
Library 15 – 35 5 100 – 120
()ِشوضي
Schools 15 : 35 15 35 : 50
ػاٌي خذا
Theaters 20 : 30 10 700 : 1000 ْالْ اٌّىا
ِغٍك
Shops 30 : 50 10 50 – 90
اٌحىييف في
ٓاالِاو
ٗاٌصٕاػي
Industrial building 10 : 20 10 - ْٛيى
زغة
اٌطٍة
Eng/Alaa Hmam
24
Chapter 3
Basic Definitions of Lighting
Eng/Alaa Hmam
25
3.1.4 Illuminance:
E = Phi/A (lx)
The illuminance refers to the incidence of the light flux on a surface, per unit of surface
The illuminance is expressed in lux (lx).
Full moon 0.1 lx Emergency
lighting 1 lx Street lighting
10 lx winter day 10 000 lx
summer day 100 000 lx
Illuminance is measured with a lux meter.
3.1.5 Luminance:
L = E/A (cd/m2)
Luminance indicates the degree of brightness with which the human eye perceives a light
source or an illuminated surface.
The luminance is expressed in candela per square meter (cd/m2).
Luminance is measured with a luminance meter.
Eng/Alaa Hmam
26
3.1.7 Color rendering index Ra (%):
The color rendering index indicates to what degree the color rendering of a light source
deviates from that of an incandescent lamp.
With Ra (8), the color shift of eight reference colors is measured as a percentage.
The Ra is the average of these eight values.
A color rendering index of 100 to 90 is good, 90 to 80 are less good and lamps with a Ra
below 80 are unsuited for applications where color rendering is important.
Eng/Alaa Hmam
27
3.1.12 Specific luminous flux:
The specific luminous flux indicates how efficiently a lamp converts electrical energy to light
that is visible for human beings.
This is indicated in lumens per Watt (lm/W).
Eng/Alaa Hmam
28
3.2.1 Illuminance level:
To determine how much light is required, account must be taken of the type of visual task:
I. To be able to safely find the emergency exit in a building, 1 lx is sufficient.
II. To be able to distinguish facial expressions, approx. 20 lx is required.
III. For accent lighting in shop windows, 1500 – 2000 lx is usual.
IV. Operation tables must be illuminated with a minimum of 5000 lx.
V. In rooms where people work, legal minima apply for the illuminance, depending on
the room and on the visual task.
VI. These minima relate to the average illuminance in the working area.
VII. The uniformity in the working area may not be less than 0.7, and not less than 0.5 In
the immediate surroundings.
VIII. The initial illuminance values must be higher than the legal minima, because
account must be taken of light degradation caused by contamination and ageing of
lamps and fixtures.
3.3 Glare prevention:
Glare occurs when one part of the visual field is much brighter than the average brightness
to which the visual system is adapted.
Glare is divided into discomfort glare and disability glare.
Measures have to be taken to limit discomfort glare in lighting installations.
3.3.1 Shielding:
A shielding angle can be stated for open fixtures and for fixtures that are supplied with a
clear, non-structured covering.
The shielding angle is the angle from which the lamp or its reflection in the reflector is
no longer visible.
The following minima apply according to the European standard EN 12461, Lighting of
Indoor Work Places.
Eng/Alaa Hmam
29
Luminance (kcd/m2) Example Minimum shielding angle
1 to 20 fluorescent tube (º) 10
20 to 50 compact fluorescent lamp 15
50 to 500 discharge lamp (mat) 20
more than 500 discharge lamp (clear) 30
Eng/Alaa Hmam
30
Chapter 4
Eng/Alaa Hmam
31
Eng/Alaa Hmam
32
Eng/Alaa Hmam
33
4.2 Room Dimension:
To know number of luminaires which achieve the suitable LUX.?
N α area
Eng/Alaa Hmam
34
4.3 Ceiling Type:
4.3.1 Surface mounted ceiling:
Eng/Alaa Hmam
35
4.3.3 Suspended mounted ceiling:
Eng/Alaa Hmam
36
4.3.4 Gipson board mounted ceiling:
يفضل في حاله سقف الجبس استخدام اسبوتات
4.4 Work plane height:
Depends on furniture such as:
Take ―zero‖ if corridor or shops.
Take ―80cm‖ if office.
4.5 Environment:
To specify the index protection
Dust Moisture
[0 - 6] [0 – 8]
Eng/Alaa Hmam
37
4.6 Indoor or Outdoor Lighting:
To specify:-
4.6.1 Type of luminaire.
4.6.2 Maintenance factor [Indoor take 0.8 & outdoor take (0.6-0.4)].
Filament Lamps:
I. Incandescent Lamp:
Eng/Alaa Hmam
38
Power
(Watt) 60 W 75 W 100 W 150 W 200 W 300 W 500 W 1000 W
Eng/Alaa Hmam
39
II. Halogen or tungsten lamps:
Eng/Alaa Hmam
40
III. Reflected Lamps:
Eng/Alaa Hmam
41
Gas Discharge Lamps:
I. Fluorescent Lamps
Tube Compact
TL-D (T8) Lamps Integrated
TL-5 Lamps Non Integrated
Fluorescent tubes are a low-pressure mercury discharge lamp in which light is produced
predominantly through fluorescent powder activated by the discharge ultraviolet energy.
Eng/Alaa Hmam
42
For Surface mounted ceiling:
Eng/Alaa Hmam
43
58 watt lamps used in open area such as: Supermarket and Hyper malls.
Because it gives 5400lumen
Eng/Alaa Hmam
44
Compact Fluorescent Lamps: - (Saving Lamp)
Integrated type
Low lumen/watt
Used in spots:
Eng/Alaa Hmam
45
II. High Pressure Sodium [SON]:
Color: yellow
Eng/Alaa Hmam
46
III. Low Pressure Sodium [SOX]:
Life
type power lumen Lumen/watt C.R time
Eng/Alaa Hmam
47
IV. High Pressure Mercury [HPM]:
Color Rendering 4 5 %
Color: white
type power lumen Lumen/watt C.R Life time
V. Metal Halide:
Eng/Alaa Hmam
48
type lumen power Life time application
spots
3100 35W 10,000H
factories
MH 19000 250 W 10,000H
Sports area
100000 1000 W 10,000H
Eng/Alaa Hmam
49
LED Lighting:
LED stands for Light Emitting Diode.
Led is semiconductor device that allow current to pass through one direction. Once current
passes through, the diode emits light.
Advantages o f LED’S:
1. High efficiency (lumen/watt) about 100 lumen /watt.
2. High life time up to 50,000hr.
3. Dimmable.
4. Low temperature.
5. Different colors (RGB).
6. No maintenance.
Eng/Alaa Hmam
50
LED System:
Eng/Alaa Hmam
51
Efficiency
Color
Lamp type Power(watt) lumen Length Life time (lumen
rendering
/watt)
18W 1350 85% 60Cm 10,000 hr. 75 Lm/W
TL-D fluorescent 36W 3350 85% 120Cm 10,000 hr. 93 Lm/W
58W 5400 85% 150Cm 10,000 hr. 93 Lm/W
14W 1200 85% 60Cm 20,000 hr. 86 Lm/W
TL-5 fluorescent 28W 2900 85% 120Cm 20,000 hr. 103 Lm/W
35W 4000 85% 150Cm 20,000 hr. 114 Lm/W
18W 1300 82% ---------- 10,000 hr. 72 Lm/W
compact
fluorescent 26W 1800 82% ---------- 10,000 hr. 70Lm/W
(nonintegrated)
36W 2800 82% ---------- 10,000 hr. 78 Lm/W
20 W 300 100% ---------- 4000 hr. 15 Lm/W
35 W 600 100% ---------- 4000 hr. 18 Lm/W
Halogen
70 W 1 400 100% ---------- 4000 hr. 20 Lm/W
100 W 2 550 100% ---------- 4000 hr. 15 Lm/W
150 W 17500 25% ---------- 38,000 hr. 110 Lm/W
High pressure
250 W 33200 25% ---------- 38,000 hr. 128 Lm/W
sodium
400 W 56500 25% ---------- 38,000 hr. 138 Lm/W
Eng/Alaa Hmam
52
3.7.2 Ballast:
Types of Ballast:-
1. Magnetic Ballast
PF [0.4- 0.6]
Used in cold room
2. Electronic Ballast
PF (0.9-0.97)
Eng/Alaa Hmam
53
3.7.3 Housing:
Eng/Alaa Hmam
54
Chapter 5
Where
N: Number of Luminaires
n: number of lamps per luminaire
Lux: Lighting level, get from standard table (IEC, EC and NEC)
a: Room width
b: Room length
U.F: Utilization factor
M.F: Maintenance factor
Then by knowing the color of walls, celling and ground we can get the U.F from the table.
Eng/Alaa Hmam
55
2. Maintenance Factor (M.F):
Indoor lighting [M.F = 0.8]
Outdoor lighting [M.F = 0.4 - 0.6]
Eng/Alaa Hmam
56
3. Lux [ Lighting Level ]:
Take the value from standard tables codes (EC or IEC)
4. Lumen:
Get from specification of lamp in catalogues.
From calculation if the total number of luminaire in the room = [N], then to get the number of
luminaire in length and width calculate the following:
Example:
If we have office room with the following dimensions:
a= 8.5 m b= 8.5 m h= 4m
Lux= 500 Lux use (4X14 Watt) ----->lumen= 1200
Distance between two luminaire must be equal double distance between wall and
luminaire.
Eng/Alaa Hmam
57
Eng/Alaa Hmam
58
Chapter 6
Eng/Alaa Hmam
59
Eng/Alaa Hmam
60
Eng/Alaa Hmam
61
Eng/Alaa Hmam
62
Eng/Alaa Hmam
63
Eng/Alaa Hmam
64
Eng/Alaa Hmam
65
Eng/Alaa Hmam
66
Eng/Alaa Hmam
67
Eng/Alaa Hmam
68
Eng/Alaa Hmam
69
Eng/Alaa Hmam
70
Eng/Alaa Hmam
71
Eng/Alaa Hmam
72
Eng/Alaa Hmam
73
Eng/Alaa Hmam
74
Eng/Alaa Hmam
75
Eng/Alaa Hmam
76
Eng/Alaa Hmam
77
Eng/Alaa Hmam
78
Eng/Alaa Hmam
79
Eng/Alaa Hmam
80
Eng/Alaa Hmam
81
Eng/Alaa Hmam
82
Eng/Alaa Hmam
83
Eng/Alaa Hmam
84
Eng/Alaa Hmam
85
Eng/Alaa Hmam
86
Eng/Alaa Hmam
87
Eng/Alaa Hmam
88
Eng/Alaa Hmam
89
Eng/Alaa Hmam
90
Eng/Alaa Hmam
91
Eng/Alaa Hmam
92
Eng/Alaa Hmam
93
Eng/Alaa Hmam
94
Eng/Alaa Hmam
95
Eng/Alaa Hmam
96
Eng/Alaa Hmam
97
Eng/Alaa Hmam
98
Eng/Alaa Hmam
99
Eng/Alaa Hmam
100
Eng/Alaa Hmam
101
Eng/Alaa Hmam
102
Eng/Alaa Hmam
103
Eng/Alaa Hmam
104
Chapter 7
Sockets
7.1 Types of sockets:
7.1.1 Normal Sockets:
It is used for light load only. Its ratings are
2A, 3A, 5A and 10A. Rating (3A) and
(5A) can be used for bedrooms, entrance
and balcony which needs low electrical
power appliances such as T.V, Radio and
small electrical fans.
Eng/Alaa Hmam
105
7.1.4 Weather proof socket:
Eng/Alaa Hmam
106
7.1.7 Floor boxes:
A wide range of accessory
plates is available for power
data and telecommunication
services.
We use floor box for any
equipment with many plugs
like computers and it’s
attached.
Eng/Alaa Hmam
107
7.2 Sockets Design:
In Egyptian code which indicates that the distance between each socket is 3.65m but we put
in our consideration the place of furniture in the place which we insert socket in.
In corridors the distance between each socket is (6-8) m. We put three types of
sockets:
1. Normal sockets
2. Power sockets
3. Emergency sockets
In each normal circuit the designed current of normal or emergency is 5A so we
distribute the 8-12 outlets of sockets in each circuit where the rate of each
normal socket is 180 VA.
The circuit breaker of normal socket is 16A.
Its CSA of the cable is 3mm^2(from Egyptian code).
Power socket outlet is inserted in a separate circuit it is inserted for high power load like
bath heater.
We deign some of the outlets of socket in the emergency system (20%_30%) from normal
sockets.
The CSA of the cable of power socket is not less than 4mm^2.
When the utility of service is cut off this emergency socket is in service they are loaded
on the generator of the system in these abnormal conditions and in normal case they are
loaded on the transformer.
Eng/Alaa Hmam
108
Eng/Alaa Hmam
109
Eng/Alaa Hmam
110
Chapter 8
Indoor Wiring
Eng/Alaa Hmam
111
Eng/Alaa Hmam
112
Eng/Alaa Hmam
113
Eng/Alaa Hmam
114
Eng/Alaa Hmam
115
Chapter 9
Lifts and Elevators
Eng/Alaa Hmam
116
Eng/Alaa Hmam
117
Eng/Alaa Hmam
118
Eng/Alaa Hmam
119
Eng/Alaa Hmam
120
Eng/Alaa Hmam
121
Chapter 10
Heating Ventilation Air Condition (HVAC)
Eng/Alaa Hmam
122
Eng/Alaa Hmam
123
Eng/Alaa Hmam
124
Eng/Alaa Hmam
125
Eng/Alaa Hmam
126
Eng/Alaa Hmam
127
Eng/Alaa Hmam
128
Eng/Alaa Hmam
129
Eng/Alaa Hmam
130
Eng/Alaa Hmam
131
Eng/Alaa Hmam
132
Eng/Alaa Hmam
133
Eng/Alaa Hmam
134
Eng/Alaa Hmam
135
Eng/Alaa Hmam
136
Eng/Alaa Hmam
137
Eng/Alaa Hmam
138
Eng/Alaa Hmam
139
Eng/Alaa Hmam
140
Eng/Alaa Hmam
141
Eng/Alaa Hmam
142
Eng/Alaa Hmam
143
Chapter 11
Load Study
11.1 Introduction:
The main objective of distribution system is to supply customers with their power needs with
adequate level of quality.
In the low voltage distribution part some components are used of certain ratings to meet the
need of rated voltage and rated current.
Low voltage design for the residential complex involves load estimation starting from the
smallest dwelling unit till reaching the distribution transformer.
Load may be broadly classified into three categories:
1. Industrial loads.
2. Residential loads.
3. Commercial loads.
The term residential building encompasses buildings for private dwelling. Apartment buildings
may be considered as residential or commercial according to activity and type of loads.
Most of residential loads are single phase; hence special design is necessary in order to
avoid some undesired characteristics such as phase unbalance. Typical residential loads include
all appliance found in a house. For example:
1. Heaters.
2. Lighting.
3. Air conditioner.
4. Washing machines and dishwater machines.
5. Besides that, the typical lighting and sockets circuits
11.2 Important terms and factors:
11.2.1 Connected load:
It is the sum of continuous ratings of all the equipment connected loads to the supply system
but not necessary operating.
11.2.2 Demand Factor:
Each device has a maximum capacity for absorption of power. For the usual case device of a
group operated by an individual consumer can function independently. If all the devices run to
their fullest extent simultaneously, the maximum demand of the consumer on the energy
system would equal his connected load. However, experience demonstrates that the actual
maximum demand of a consumer will be less than his connected load since all the devices
never run at full load at the same time.
The relationship of maximum demand and connected load measured by:
Eng/Alaa Hmam
144
Maximum Demand
Demand Factor =ـــــــــــــــــــــــــــــــــــــــــــ
Connected Load
The demand factor depends upon the nature and activities of the consumer and to some
extent upon the location of the power system. Various studies indicate that demand factor
may vary from about 25% for hotels to 90 % for refrigeration plants. Each device will
reach its own maximum demand at some time during its operation, but the demand
factor measures the extent of a group of devices of which it is a part.
11.2.3 Diversity Factor:
Experience shows that the maximum demands of individual consumers do not occur
simultaneously but are spread out over a period of time this holds for consumers whose
activities and energy requirements are very similar. The time distribution of maximum
demands for similar types of consumers is measured by the diversity factor, where:
The group diversity factor is always greater than unity. Diversity factors for residential
consumers are usually highest at about 5.0, whereas large industrial consumers may have
values as low as 1.3. Since diversity exists between individual maximum demands; the
proportion contributed to the system maximum demand by each consumer is less than his
maximum demand.
The peak demand of a system is made up of the individual demands of the devices that
happen to be functioning at the time of the peak. At the time of the system peak demand the
demand of a particular group of similar consumers is seldom at the maximum value that it
may reach at some other time of the year. This diversity is measured by:
Eng/Alaa Hmam
145
Eng/Alaa Hmam
146
11.2.4 Load Factor:
Is the degree of variation of the load over a period of time is measured by the load factor,
which may be defined as:
The curve for the electrical load (Fig. 1) typifies a factory operation on a one-shift basis. In
early morning hours the demand is generally for lightning and auxiliary drive for the heating
boiler plant as well as some processes that require continuous energy supply such as
refrigeration and electric furnaces. About 5 a.m. some of the factory machinery starts running,
perhaps for warming prior to operation, or it may be that one department starts earlier in the
day than the reminder of the organization to synchronize the properly.
By 8 a.m. in this particular case the entire plant is running, and energy demand remains
substantially constant until shortly before noon. Load falls off as some of the machines shut
down during the lunch period the extent of the noon-hour dip depends upon the individual
factory. By 2 p.m. the load attains about the same level as during the morning. Shortly before
4 p.m. the load starts to drop as the day’s work ends in the various departments. At 6 p.m.
most of the machines are shut down, and the load gradually tapers off until about 9 or 10 p.m.
when the minimum demand is reached and continuous until the start of the next working day.
Industrial loads are affected by the seasons in need of heating and lighting.
Load Curves for Dwellings (Fig. 2) are typical of a residential community rather than just one
residence. During the early morning hour’s energy runs night lights, refrigerators, water
heaters, oil burners, and the like, in the winter the early risers require lights and, to prepare
breakfast, toasters, etc. after the rising and breakfast hour the demand decreases somewhat, and
equipment such as vacuum cleaners, radios, television sets water heaters, and occasional
lights makes a fairly constant demand for energy until about 4 p.m. cooking appliances then
cause a slight rise in demand.
Eng/Alaa Hmam
147
After 4 p.m. the early sunset of winter brings the lights into action, and the total rapidly
approaches its peak about 5 p.m. during the month of December. The high level of demand
persists until about 7 or 8 p.m. when the load drops fairly rapidly as the families retire or
leave home to seek entertainment elsewhere, minimum loads being again reached at about 1 a
.m. loads of this class are generally less during the summertime principally because many
families are away on vacation and cooking activity is at a minimum, the later sunsets cause a
late hour for the peak demand, which is much reduced in comparison with the winter demand.
Street light (Fig. 2.3) is about the only form of load that does not exhibit peak demands in the
ordinary sense. Normally all lights come on and are turned off almost simultaneously, the total
load remaining constant during the hours of darkness. The turning on of light and their turning
off are usually synchronized respectively, with the time of sunset and sunrise. Hence, in the
summertime the lights will be functioning for a much shorter time than during the winter.
Eng/Alaa Hmam
148
Chapter 12
Panel Boards
Eng/Alaa Hmam
149
12.1.3 Outgoing circuit breakers or fuses.
It used to protect cables connected to loads and loads.
May be three phase or single phase.
Eng/Alaa Hmam
150
12.1.4 Indicted lamps.
Eng/Alaa Hmam
151
12.1.7 Insulations.
All parts should be insulated to protect all components.
Eng/Alaa Hmam
152
Eng/Alaa Hmam
153
Eng/Alaa Hmam
154
12.3 Types of panel board.
NORMAL transformer N
transformer
EMERGENCY E
generator
transformer
generator
Eng/Alaa Hmam
155
Eng/Alaa Hmam
156
Eng/Alaa Hmam
157
12.4 Panel board location.
Eng/Alaa Hmam
158
Chapter 13
Circuit Breakers
13.1 Introduction:
The circuit breaker is an absolutely essential device in the modern world, and one of the most
important safety mechanisms in electrical design.
A circuit breaker is an automatically operated electrical switch designed to protect an electrical
circuit from damage caused by overload or short circuit. Its basic function is to detect a fault
condition and, by interrupting continuity, to immediately discontinue electrical flow. Unlike a
fuse, which operates once and then has to be replaced, a circuit breaker can be reset (either
manually or automatically) to resume normal operation Circuit breakers are made in
varying sizes, from small devices that protect an individual household appliance up to
large switchgear designed to protect high voltage circuits feeding an entire city.
Eng/Alaa Hmam
159
13.4 Classification of Circuit Breakers:
13.4.1 According to the Arc Extinguishing Medium:
13.4.1.1 Air circuit breakers.
13.4.1.2 Mineral oil circuit breakers.
13.4.1.3 Vacuum circuit breakers.
13.4.1.4 Sculpture hexafluoride (SF6) C.B.
13.4.1.5 Air-blast circuit breakers.
13.4.2 According to the Operating Voltage:
13.4.2.1 Low Voltage C.B. (up to 600-1000volt)
13.4.2.2 Medium voltage C.B. (1 : 33 kilovolt)
13.4.2.3 High voltage C.B. (33 : 240 kilovolt)
13.4.2.4 Extra High Voltage C.B. (more than 240 kilovolt)
Eng/Alaa Hmam
160
All low voltage circuit breakers are air circuit breakers, where the arc is extinguished in
the air under the atmospheric pressure, low voltage circuit breakers are manufactured as a
complete device that consists on all basic components inside its enclosure, called direct
tripping circuit breakers.
Low voltage circuit breakers models:
1. Miniature C.B.
Eng/Alaa Hmam
161
3. Low Voltage Power C.B.
Molded case C.B. Is an integrated unit, tightly closed and enclosed by molded case
made from insulating material, in case of a failure in any part the hole breaker should be
replaced
Low voltage power C.B. consists of a group of modular units that can be replaced, adding
parts to it or applying maintenance on it, also trip unit can be replaced according to design;
Low voltage power C.B. has a larger size than molded case C.B.
Comparison between molded case and power circuit breakers:
Where continuity of service is mandatory, the short-time capability of the power
circuit breaker is required.
If circuit breakers are operated relatively infrequently where selection is not important, the
molded case breaker provides the most economical solution.
If the interrupting capability of the power circuit breaker is not high enough, this can be
achieved by means of an integral fuse.
Power C.B.s can in generally withstand short time delay for a period of one second while
molded case C.B.s don’t necessary have this advantage and if present it is only for a period
of half second.
Eng/Alaa Hmam
162
Circuit Breaker Ratings
CB
10 16 20 25 32 40 50 63 80 100 125 160 200 250 400 630 800 1000 1250 1600 2000 2500 3200 4000 5000 6300
(A)
MCB ACB
MCCB
Eng/Alaa Hmam
163
Rated Making Current: The maximum value of current that can pass in the C.B. at
closing.
Rated Short-time Current: The maximum r.m.s symmetrical current that can pass in the
C.B. for one second.
13.7 FUSES:
13.7.1 Types of fuses:
13.7.1.1 Semi-enclosed Fuse:
Eng/Alaa Hmam
164
13.7.1.3 High Rupture Capacity Fuse (HRCF):
Eng/Alaa Hmam
165
Where:
Semi enclosed and cartridge used in low voltage.
High Rupture Capacity used in medium voltage.
H.R.C.F used to protect transformer from short circuit.
aM fuse used to protect short circuit protection in motors, transformer and other load with high
2
inrush currents due to the good current limiting capability and low I t values.
Rating of fuses start from 10A, 16A, 20A, 25, 32, 40, 50, 63, 80, 100, 125, 160, 200, 250, 320,
400, 630, 800, 1000, and 1250A.
EX:
Eng/Alaa Hmam
166
Chapter 14
Cables
Eng/Alaa Hmam
167
Eng/Alaa Hmam
168
Eng/Alaa Hmam
169
Eng/Alaa Hmam
170
Eng/Alaa Hmam
171
Eng/Alaa Hmam
172
Eng/Alaa Hmam
173
Eng/Alaa Hmam
174
Eng/Alaa Hmam
175
Eng/Alaa Hmam
176
Eng/Alaa Hmam
177
Eng/Alaa Hmam
178
Eng/Alaa Hmam
179
Eng/Alaa Hmam
180
Eng/Alaa Hmam
181
Eng/Alaa Hmam
182
Eng/Alaa Hmam
183
Eng/Alaa Hmam
184
Eng/Alaa Hmam
185
Eng/Alaa Hmam
186
Chapter 15
Cable Routing
Eng/Alaa Hmam
187
Eng/Alaa Hmam
188
Eng/Alaa Hmam
189
Eng/Alaa Hmam
190
Eng/Alaa Hmam
191
Eng/Alaa Hmam
192
Eng/Alaa Hmam
193
Eng/Alaa Hmam
194
Eng/Alaa Hmam
195
Eng/Alaa Hmam
196
Eng/Alaa Hmam
197
Eng/Alaa Hmam
198
Eng/Alaa Hmam
199
Eng/Alaa Hmam
200
Eng/Alaa Hmam
201
Eng/Alaa Hmam
202
Eng/Alaa Hmam
203
Eng/Alaa Hmam
204
Eng/Alaa Hmam
205
Eng/Alaa Hmam
206
Eng/Alaa Hmam
207
Chapter 16
Bus Duct
Eng/Alaa Hmam
208
Eng/Alaa Hmam
209
Eng/Alaa Hmam
210
Eng/Alaa Hmam
211
Eng/Alaa Hmam
212
Eng/Alaa Hmam
213
Eng/Alaa Hmam
214
Eng/Alaa Hmam
215
Eng/Alaa Hmam
216
Eng/Alaa Hmam
217
Eng/Alaa Hmam
218
Chapter 17
Phase Balance
Eng/Alaa Hmam
219
Eng/Alaa Hmam
220
Eng/Alaa Hmam
221
Eng/Alaa Hmam
222
Eng/Alaa Hmam
223
Eng/Alaa Hmam
224
Chapter 18
Distribution Transformers
18.1 Transformer Construction:
Eng/Alaa Hmam
225
Eng/Alaa Hmam
226
1 Oil filter valve 11 Grounding terminal
Eng/Alaa Hmam
227
Eng/Alaa Hmam
228
18.2.2 According to turns ratio:
3. Measuring transformers.
Voltage transformers and current transformers
4. Autotransformer- Tapped autotransformer.
229
5. Oil immersed, water –cooled.
6. Oil–immersed, forced oil –cooled.
7. Oil–immersed, combination self –cooled and water cooled.
18.3 Types of distribution transformers:
1. Oil type transformer:
Main components of oil type transformer
1- Low voltage winding
2- High voltage winding
3- Low voltage terminal
4- High voltage terminal
5- Core
6- Off-load Tap Changer
7- Earthling Terminal
8- Oil Level Indicator
9- Oil drain valve
10- Thermometer pocket
11- Buchholz Relay
12- Lifting Lugs
13- Air Dryer including Silica Gel
14- Wheel
Eng/Alaa Hmam
230
2. Dry type transformer:
Eng/Alaa Hmam
231
Oil type Dry type
Low cost compared with dry type High cost compared with oil type
Eng/Alaa Hmam
232
Eng/Alaa Hmam
233
2. Dry type:
Eng/Alaa Hmam
234
Chapter 19
Diesel Generator
Standby diesel generator used to feed the important loads in case the Main supply is being cut
off. Selecting the generators that can produce the power required by a field unit is an important
function.
Eng/Alaa Hmam
235
Equipment (KVA) Generator (KVA)
1.5 3.8
1.7 4.3
5 12.5
6.3 15.8
12.5 31.3
25 62.5
37 93.8
45 112
62 156
75 187
77 192
108 270
Eng/Alaa Hmam
236
Eng/Alaa Hmam
237
Chapter 20
Uninterruptible Power Supply (UPS)
An UPS system is an alternate or backup source of power with the electric utility company
being the primary source. The UPS provides:
1. Protection of load against line frequency variations.
2. Elimination of power line noise and voltage transients.
3. Voltage regulation.
4. Uninterruptible power for critical loads during failures of normal utility source.
An UPS can be considered a source of standby power or emergency power depending on the
nature of the critical loads. The amount of power that the UPS must supply also depends on
these specific needs.
These needs can include
1. Emergency lighting for evacuation.
2. Emergency perimeter lighting for security.
3. Orderly shutdown of manufacturing or computer operations,
4. Continued operation of life support or critical medical equipment.
Eng/Alaa Hmam
238
20.1 Types of UPS:
1. ON-LINE UPS:
2. OFF-LINE U.P.S:
Eng/Alaa Hmam
239
3. ON LINE UPS WITN ISOLATING TRANSFORMER:
Eng/Alaa Hmam
240
Chapter 21
Automatic Transfer Switch (ATS)
21.1 Transfer switch definition:
A transfer switch is used to reconnects electric power source from its primary source to a
standby source.
Switches may be manually or automatically
An Automatic Transfer Switch (ATS) is often installed where a backup generator is
located.
Eng/Alaa Hmam
241
21.3 Types of transfer switch:
1. Open transition types:
Called a break before make transfer switch.
Total power interruption for a short period of time.
It prevents back feeding from an emergency generator back into the utility.
Eng/Alaa Hmam
242
2. Closed transition types:
Called a make before break transfer switch.
Eng/Alaa Hmam
243
Chapter 22
Ring Main Unit (RMU)
RMU is used to connect distribution transformers to medium voltage system with a capacity of
less than 5MVA.
Eng/Alaa Hmam
244
Eng/Alaa Hmam
245
Eng/Alaa Hmam
246
Description symbol
Load break switch Q1
Earth switch Q2
Load break switch with fuse Q3
Earth fault indictor EFI
hygrostat H1
heater H2
Voltage transformer T1
Current transformer T2
voltmeter P1
(Kwh+kvarh)meters P2
High Rupture Capacity Fuse F1
Voltmeter selector switch S1
Mechanical interlock X1
Mechanical interlock X2
Eng/Alaa Hmam
247
Eng/Alaa Hmam
248
Types of Ring Main Unit:
TYPE
Eng/Alaa Hmam
249
Eng/Alaa Hmam
250
Chapter 23
Distributors
Eng/Alaa Hmam
251
Eng/Alaa Hmam
252
Eng/Alaa Hmam
253
Eng/Alaa Hmam
254
Eng/Alaa Hmam
255
Eng/Alaa Hmam
256
Eng/Alaa Hmam
257
Eng/Alaa Hmam
258
Eng/Alaa Hmam
259
Chapter 24
Feeding System
Eng/Alaa Hmam
260
Eng/Alaa Hmam
261
Eng/Alaa Hmam
262
Eng/Alaa Hmam
263
Eng/Alaa Hmam
264
Eng/Alaa Hmam
265
Eng/Alaa Hmam
266
Eng/Alaa Hmam
267
Eng/Alaa Hmam
268
Eng/Alaa Hmam
269
Eng/Alaa Hmam
270
Eng/Alaa Hmam
271
Eng/Alaa Hmam
272
Eng/Alaa Hmam
273
Eng/Alaa Hmam
274
Eng/Alaa Hmam
275
Eng/Alaa Hmam
276
Eng/Alaa Hmam
277
Eng/Alaa Hmam
278
Eng/Alaa Hmam
279
Eng/Alaa Hmam
280
Eng/Alaa Hmam
281
Eng/Alaa Hmam
282
Eng/Alaa Hmam
283
Eng/Alaa Hmam
284
Eng/Alaa Hmam
285
Eng/Alaa Hmam
286
Eng/Alaa Hmam
287
Eng/Alaa Hmam
288
Chapter 25
قولعد توصيل لحتغريو لحكهسبيو حلونشمت لحسكنيو بمحقس يلحودى
Eng/Alaa Hmam
289
Eng/Alaa Hmam
290
Eng/Alaa Hmam
291
Eng/Alaa Hmam
292
Eng/Alaa Hmam
293
Eng/Alaa Hmam
294
Eng/Alaa Hmam
295
Eng/Alaa Hmam
296
Eng/Alaa Hmam
297
Chapter 26
Power Factor Correction
Eng/Alaa Hmam
298
Eng/Alaa Hmam
299
Eng/Alaa Hmam
300
Eng/Alaa Hmam
301
Eng/Alaa Hmam
302
Eng/Alaa Hmam
303
Eng/Alaa Hmam
304
Eng/Alaa Hmam
305
Eng/Alaa Hmam
306
Eng/Alaa Hmam
307
Eng/Alaa Hmam
308
Eng/Alaa Hmam
309
Eng/Alaa Hmam
310
Eng/Alaa Hmam
311
Eng/Alaa Hmam
312
Eng/Alaa Hmam
313
Chapter 27
Power System Representation Using ETAP
Steps of design using ETAP:
Eng/Alaa Hmam
314
Select symbol (power grid):
Eng/Alaa Hmam
315
Select symbol (cable)
Eng/Alaa Hmam
316
Select symbol (Bus)
Eng/Alaa Hmam
317
-select symbol (transformer)
Eng/Alaa Hmam
318
Eng/Alaa Hmam
319
Select short circuit analysis:
Eng/Alaa Hmam
320
Eng/Alaa Hmam
321
Chapter 28
Voltage Drop Calclation
Eng/Alaa Hmam
322
Eng/Alaa Hmam
323
ٚوزٌه يّىٓ اعحخذاَ تشٔاِح االيحاب
Eng/Alaa Hmam
324
Chapter 29
Short Circuit Calculation
Eng/Alaa Hmam
325
Eng/Alaa Hmam
326
ٚيّىٓ زغاتٗ ليّٗ جياس اٌمصش تاعحخذاَ تشٔاِح االيحاب (وّا عثك جٛظيسٗ).
Eng/Alaa Hmam
327
Chapter 36
Street Lighting
Eng/Alaa Hmam
328
Eng/Alaa Hmam
329
Eng/Alaa Hmam
330
Eng/Alaa Hmam
331
Eng/Alaa Hmam
332
Eng/Alaa Hmam
333
Eng/Alaa Hmam
334
Eng/Alaa Hmam
335
Eng/Alaa Hmam
336
Eng/Alaa Hmam
337
Eng/Alaa Hmam
338
Eng/Alaa Hmam
339
Eng/Alaa Hmam
340
Eng/Alaa Hmam
341
Eng/Alaa Hmam
342
Eng/Alaa Hmam
343
Eng/Alaa Hmam
344
Eng/Alaa Hmam
345
Eng/Alaa Hmam
346
Chapter 31
Coordination Study
Eng/Alaa Hmam
347
Medium & high voltage C.B:
In medium & high voltage C.B, the relay and the C.B are separate.
Eng/Alaa Hmam
348
Why Protective Relaying?
By minimizing damage when failures occur, protective relaying minimizes:
A. The cost of repairing the damage.
B. The likelihood that the trouble may spread and involve otherequipment.
C. The time that the equipment is out of service.
D. The loss in revenue and the strained public relations while the equipment is out
of service.
B. Frequency.
C. Phase angle.
D. Duration.
E. Rate of change.
Eng/Alaa Hmam
349
Types of relay's curves:
Eng/Alaa Hmam
350
M4 M5
Actual 720 1900
current(A)
Pick up current 864 (1900*1.05)=1995
(1.2 Iact)A
Trip unit Micro_logic Micro_logic
Power air C.B
C.B rating(A) 1000 2000
Breaking 50 50
capacity(KA)
Is.t.d(A) 1728 3990
ts.t.d(sec) 1 1.5
Iinst(5Iact)A 4320 (1995*7)=13965
tinst(msec) 10 25
Relay setting:
R1 R2 R3
Actual 66 217.5 1540
current(A)
Pick up 1.5*66=99 205.16*1.05=215.25 1540*1.05=1617
current(A)
C.T 100:5 250:5 1800:5
C.B rated 630 1250 2000
current
Breaking 25 31.5 60
capacity
C.B rated 12 12 12
voltage
Curve type Extremely Very inverse Very inverse
inverse
Iinst(A) 990 2152.5 16170
tinst(msec) 125 325 525
Eng/Alaa Hmam
351
MATLAB Program for Coordination:
clc
num=input('**Enter the number of C.Bs in Low Voltage
Side**=');
for i=1 : num
prompt={'The Actual Current','Over-Load Current(As a
ratio of the actual current)'};
name='General Inputs';
numlines=1;
def={'0','0'};
a=inputdlg(prompt,name,numlines,def);
b=char(a);
c=str2num(b);
d=c(1)*c(2);
if d>=400
clc
disp('The Trip_Unit For This C.B Will Be
MicrLogic')
prompt={'The Is.d as Ratio of The Pick-up
Current','The Time of Short Time Current =','The
Instantaneous Current as Ratio of The Pick-up
Current','The Time of Instantaneous Current','The
Symmetrical S.C Current'};
name='C/Cs of the Curve';
numlines=1;
def={'2','.5','7','.025','25000'};
a=inputdlg(prompt,name,numlines,def);
b=char(a);
c=str2num(b);
r=c(1);
t=c(2);
a1=c(3);
t1=c(4);
u=c(5);
u=u/d;
x=[ r a1 a1 u];
y=[ t t t1 t1];
Eng/Alaa Hmam
352
loglog(d*x,y)
hold on
grid on
x1=[r r r r r r];
y1=[t 2 4 6 8 11];
loglog(d*x1,y1,'.m')
f=d;
x2=[f f];
y2=[10000 3000];
loglog(x2,y2,'.m')
[j,h]=ginput(2);
x3=[j(1) j(2)];
y3=[h(1) h(2)];
loglog(x3,y3)
loglog([j(1) j(1)],[h(1),10000])
loglog([j(2) d*r], [h(2) t])
clear
else
clc
disp(' The Trip_Unit For This C.B Will Be
MicrLogic')
disp(' ')
prompt={'The Instantaneous_Current (As ratio of
the Pick-up Current)','The Time of
Instantaneous_Current','The Symmetrical
S.C_current'};
name='C/Cs of the Curve';
numlines=1;
def={'5','.01','20000'};
a=inputdlg(prompt,name,numlines,def);
b=char(a);
c=str2num(b);
r=c(1);
t=c(2);
u=c(3);
u=u/d;
x=[1.1 1.1 1.125 1.175 1.2 1.225 1.25 1.275 1.4
1.5 1.6 1.65 1.8 1.9 2 3 4 r r u];
y=[10000 3000 2000 900 700 600 500 400 200 130
100 90 60 50 43 15 7 4.4 t t];
Eng/Alaa Hmam
353
loglog(d*x,y)
hold on
grid on
clear
end
end
%****************************************************
*************
% This Program Designate The ANSI Point and The
INRUSH Point
clc
disp(' ***** The ANSI Point and The INRUSH Point
*****')
disp('
')
KVA=input('The Rating of The Transformer KVA = ');
KV=input('The Region Voltage KV = ');
Zpu=input('The Transformer Percentage Impedance = ');
Ifl=KVA/(sqrt(3)*KV);
if KVA>=1000
Iinrush=12*Ifl;
w=.1;
else
Iinrush=8*Ifl;
w=.1;
end
loglog(Iinrush,w,'o')
hold on
Iansi=Ifl*100/Zpu;
t=Zpu-2;
loglog(Iansi,t,'o')
hold on
clear
%****************************************************
**********************
% Relay Curves
clc
disp('***the Relay curve design***')
p=input('enter number of relay=');
for n=1:p
prompt={'The Bus Voltage','Alfa constant of
Eng/Alaa Hmam
354
time/current curve','beta constant of
time/current curve','time multiplier(k)','the current
of the
relay','over-load of current','the instantaneous
current as ratio of the Pick-up current','the time of
instantaneous current','the symmetrical S.C
current'};
name='C/Cs of the Curve';
numlines=1;
def={'10.5','1','13.5','.5','55','1.5','10','.325','2
5000'};
a=inputdlg(prompt,name,numlines,def);
b=char(a);
c=str2num(b);
v=c(1);
a1=c(2);
b1=c(3);
k=c(4);
q=c(5);
w=c(6);
r=c(7);
t=c(8);
u=c(9);
u=(v*u)/(w*q*.38);
c=0;
for i=w:.01:r
c=c+1;
I(c)=i;
T(c)=(k*b1)/((i^a1)-1);
end
e=q*w*v/.38;
loglog(e*I,T)
hold on
A=T(c);
B=I(c);
x=[B B u];
y=[A t t];
loglog(e*x,y)
hold on
aa=e*w;
plot([aa aa],[T(1) 10000])
hold on
End
Eng/Alaa Hmam
355
hold on
clear
%====================================================
======================
:البرايزوالباور
ٗاٌىّي اٌؼٕصش
1408 Duplex Socket
568 Single Socket
30 Power Socket
173 Socket Packet Ground
2 Distribution Board (30)
Line:3*4mm2,25A C.B
1 Distribution Board (24)
Line:3*4mm2,25A C.B
2 Distribution Board (36)
Line:3*4mm2,25A C.B
6 Distribution Board (42)
Line:3*4mm2,25A C.B
5 Distribution Board for Fans(30)
Line:3*4mm2,25A C.B
8m Cable 4*16+1*10, CU/PVC
24m Cable 3*50+25+1*16mm2,CU,PVC
32 Cable 3*35+25+1*16mm2,CU,PVC
6 Molded Case C.B 125A
2 Molded Case C.B 60A
8 Molded Case C.B 80A
:أزاس اٌسشيك
ٗاٌىّي اٌؼٕصش
45 ق جٕييٗ ٌٍسشيكٛت
50 خشط جٕثيٗ ٌٍسشيك
50 ي ٌٍسشيكٚأزاس يذ
730 ْشّؼٗ أزاس ٌٍذخا
15 ٓفاصً تيٓ ِٕطمحي
ارضي
ارضي
خامس
خامس
بدروم
بدروم
ثالث
ثالث
رابع
رابع
تاني
تاني
اول
اول
1 3 3 2 1 1 2 3 3 5 5 6 و3
1 1 8 و2
3 3 2 3 3 3 3 ق3
2 2 2 2 3 4 2 2 2 4 4 4 4 4 ع1
11 ع2
1 1 3 4 1 1 2 3 5 6 6 7 ش2
1 2 3 4 1 2 2 4 4 4 5 ش4
1 1 1 2 2 7 ش5
7 ص3
6 ص5
2 1 2 2 2 5 ط4
3 3 3 3 2 3 3 3 3 3 3 ل
8 ث1
9 ث4
8 ث5
11 ث7
االجمالي:
اعمال كهرباء داخلي اسقف اسم المقاول
64 128
3 9
مالحظات قيمة األعمال االجمالي الحالـى السابـق فئـو وحده بي ــان األعمــال م
المق ــاول
رئيس قطاع التنفيذ مهنـدس المشــروع